MATERIAL SPECIFICATION ELECTRIC OPERATIONS ORGANIZATION. M3902 ****Supercedes BECo Standard E and ComElectric Spec ****

Similar documents
MATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

SECTION PADMOUNT TRANSFORMER - OIL FILLED

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115

C. System Design and Performance Requirements

GENERAL INFORMATION POLE MOUNT TRANSFORMER SINGLE PHASE PAD MOUNT TRANSFORMER SINGLE PHASE POLE MOUNT TRANSFORMER THREE PHASE 17

1500 kva Pad Mount Transformer GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled

TECHNICAL SPECIFICATIONS OIL FILLED PADMOUNTED THREE PHASE WYE-WYE TRANSFORMERS

SPECIFICATION FOR THREE PHASE PAD-MOUNT DISTRIBUTION TRANSFORMERS

1TSF /CD Attachment B. City and County of San Francisco Office of Contract Administration

DISTRIBUTION TRANSFORMERS SPECIFICATION #

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

Distribution Transformers

DISTRIBUTION TRANSFORMERS Single-Phase Pad-Mounted

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

Technical Specification for Pole Mounted Capacitor Rack

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

Single-Phase Step Voltage Regulator

Three-Phase Pole Mounted Recloser

Distribution Transformers

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS

500 kva Pad Mount Transformer V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled

SUBSTATION TYPE TRANSFORMER - MINERAL OIL FILLED THREE PHASE OISC 65 C RISE 60 HERTZ

Effective March 2015 Supersedes S August 2012

Underground Distribution Switchgear

35-kV Safefront 200 Amp Primary Metering Station Pad-Mounted Outdoor

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

Underground Distribution Switchgear

Single phase pole mounted. 11kV. Electrical Engineer KEU ID#:

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

Technical Specification For Outdoor Substation Harmonic Filter Banks

15-kV Live Terminal Primary Metering Station Pad-Mounted Outdoor

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

10 Commercial, Industrial, Agricultural Services

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

Power IT Liquid Filled Single Phase Padmounted Transformers kva

INSTRUCTION MANUAL #103

Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

15-kV Safefront 200 Amp Source Isolated Cable Switching Station Pad-Mounted Non-Fusible

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Single Phase Padmounted Transformers kva

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

TERMINATION ENCLOSURE OPTIONS

15-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 140 Amp (Max) Clip-Mounted Current-Limiting Fuses

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

UNDERGROUND SERVICES - SECONDARY

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

C1000 Series Automatic Cap Bank

CITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS. September 2018

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Generator Fire Safety: Generator assemblies should be located outside the building.

www. ElectricalPartManuals. com WeSTinghouse Secondary Unit Substation Transformers (Power Centers) Descriptive Bulletin Page 1

SECTION PANELBOARDS

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

Requirements for Secondary Voltage Revenue Metering (750 V and less)

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

STANDARD SPECIFICATION FOR PAD-MOUNTED CAPACITOR BANKS FOR 15kV or 25kV APPLICATIONS

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage

BUSWAY Low Voltage (Pow-R-Flex)

Switchgear Skid, C1192

SAFETY SOCKET BOX. Note 8 3" MIN. 3" Max. (200 A)

Figure 1. Single-phase pad-mounted voltage regulator. STANDARD FEATURES

MIRUS International Inc. TYPICAL SPECIFICATION ULLTRA & ULLTRA-H1E 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6

7. SERVICES OVER 600 VOLTS

M-Force three-phase switch

Product Specifications for Phase Over Phase GOABS(r)

NEW Solutions for Underground System Growth

Approved Meter Sockets and Cabinets

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

CABINET OPTIONS AND DESIGNATORS CODE LETTERS

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5

www. ElectricalPartManuals. com Westinghouse PLAZAPADTM Tamper-Resistant Transformers For Underground Power Distribution 750 Thru 2500 Kva

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE

NGR NGR NEUTRAL GROUNDING RESISTOR

Cleaning Flooded Gear

25-kV Safefront Mini-Switch Phase Isolated Pad-Mounted Switchgear 125 Amp (Max) Clip-Mounted Current-Limiting Fuses

Padmount. Small Power Transformers 2500 kva Through 20,000 kva 5 kv Through 46 kv Primary Voltage 120V Through 25 kv Secondary Voltage

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

Transcription:

Page 1 of 8 ****Supercedes BECo Standard E2.12-2.12 and ComElectric Spec 6-0895**** 1.0 General Requirements SINGLE PHASE PAD-MOUNTED DISTRIBUTION TRANSFORMERS 1.1 These specifications cover single-phase deadfront pad-mounted transformers that shall be mineral oil filled, Class OA, 60 Hertz, 65 C average winding temperature rise. 1.2 Transformers furnished under these specifications shall conform to the applicable portions of the latest version of ANSI Standard C57.12.25, except where otherwise specified herein. 1.3 Sound levels for transformers shall meet NEMA TR1, latest revision. 1.4 No changes shall be made in any way that would affect agreement with these specifications after transformer designs have been approved by NSTAR Electric (the Company). No transformer shall be furnished or accepted unless the details of such proposed changes have first been submitted in writing and approved by the Company. Failure to comply with these terms may result in complete or partial removal from the approved supplier list. 1.5 Any exceptions to these specifications shall be clearly indicated with price quotations. Approval drawings shall be submitted upon request. 1.6 Unless otherwise specified on purchase order, transformer warranty must be for a minimum period of one year from date of installation or 18 months from the date of receipt, whichever occurs first. Written warranty policy must be on file with NSTAR Electric s Purchasing Department. 1.7 All units shall have the following additional information on their nameplate: year of manufacture, total weight with oil and volume of oil (in gallons). 1.8 All units shall meet the minimum efficiencies in Table 2 of NEMA Publication TP-1, latest revision, or DOE s final ruling of 10/12/07 as called for on the purchase order. Transformer test reports shall be provided upon request. 1.9 NSTAR North and NSTAR South designs may be distinguished by voltage or characteristic code. The primary voltage for NSTAR North units is either 13800GY/7970 (code 281) or 13800GY/7970 x 4160GY/2400 (code 282). All other voltages and characteristic codes are NSTAR South units.

Page 2 of 8 2.0 Construction 2.1 NSTAR North units shall be Type 2 connector and terminal arrangement. NSTAR South units shall be Type 1 connector and terminal arrangement with 15.2 kv dimensions applying, regardless of primary voltage. 2.2 All high and low voltage bushings shall be field replaceable. 2.3 High Voltage Bushings: A. High voltage connectors shall be externally clamped bushing wells with replaceable stud. B. NSTAR North 15 kv class bushing well inserts shall be installed and properly torqued into each bushing well. NSTAR South Units with a primary voltage of 13200GY/7620, either straight or dual voltage, shall be provided with 15 kv class bushing well inserts, installed and properly torqued. C. Inserts shall have grounding tabs bonded to tank ground connector using #14 AWG solid copper wire. D. All NSTAR North units shall be arranged for loop feed. All NSTAR South units shall be either loop or radial feed arrangement as detailed in the ordering specifications on the purchase order. E. For NSTAR South units: All HV bushings, regardless of primary voltage, shall be spaced for 15.2 kv. 2.4 Low voltage terminals: A. Low voltage terminals shall consist of a stud in accordance with Figure 4c of C57.12.25. Each stud will have a jamb nut except the neutral shall have tank ground strap secured between two nuts. Each stud will have a minimum of 1 ½ of available thread beyond the jamb nut(s). B. Company approved quick disconnect bus bar connectors with clear insulating cover will be provided Utilco # PTF6-350CJNUP (thru 50 kva), Utilco # PTF6-500-CJNUP (above 50 kva) or approved equivalent. C. Low voltage neutral terminal shall be a fully insulated bushing. 2.5 Dimensional requirements for NSTAR North units: Dimension A in Figure 2a of C57.12.25 shall be a minimum of 16 and Dimension D in Figure 2a shall be a minimum of 4. The base dimensions, including sill, shall be restricted to the following ranges: 32-37 (side to side) and 34-42 (front to back). 2.6 The impedance, including manufacturing tolerance, shall be 1.6-2.6%.

Page 3 of 8 2.7 Enclosure integrity shall meet or exceed requirements of the most current ANSI C57.12.28. Transformer doors are to be equipped with stainless steel hinges and pins that are not externally removable. A captive, recessed ½ stainless steel penta-head bolt shall be supplied that can be secured with a padlock. Threaded bolthole or captive nut shall be stainless steel. 2.8 Sill shall be stainless steel. 2.9 Tamperproof knockouts shall be provided in the sill. Design of the knockout shall be such that the knockout hole can be resealed after use. 2.10 All bolts, nuts, clamps and other hardware not exposed to the weather must have corrosion resistant electroplating. 2.11 Lifting bolts shall be installed by the manufacturer into recessed, stainless steel nuts welded to the tank. 2.12 The paint color shall be Green (Munsell Notation 7GY3.29/1.5). Final finish shall exceed the requirements of ANSI C57.12.28 with a minimum dry film thickness of 4 mils on all surfaces and seams. All compartment and transformer surfaces in contact with the pad shall be treated to minimize corrosion. 2.13 Coastal Zone Design transformers shall have tanks, sills, hinges, clamps and all other hardware fabricated of Type 304L stainless steel. 3.0 Accessories 3.1 Transformer taps, if required, will be detailed in the ordering specifications on the purchase order. An externally operated tap changer shall be provided. 3.2 An externally operated, series multiple switch shall be provided on dual voltage units. 3.3 NSTAR North units shall have two parking stands. 3.4 Under oil type heavy duty arresters shall be provided on all units. Dual voltage units shall have arresters sized for the higher primary voltage. See table 1 for arrester ratings.

Page 4 of 8 Primary Voltage (Phase-Ground kv) Arrester Class (kv) 2.4 3 4.8 6 7.62 10 7.97 12 13.2 & 14.4 18 Table 1 Arrester Ratings 3.5 Single voltage unit fusing. See tables 2-6. A. For NSTAR North, fusing shall be provided on all units and consist of a hot stick operable Bay-O-Net dual element fuse in series with a partial range current limiting fuse. B. For NSTAR South, fusing, when specified, shall be detailed in the ordering specifications on the purchase order and consist of a hot stick operable Bay-O-Net fuse in series with either a partial range current limiting fuse or an isolating link. 3.6 Dual voltage unit fusing. See tables 2-6. A. For NSTAR North, fusing shall be provided on all units and consist of a hot stick operable Bay-O-Net fuse in series with a partial range current limiting fuse. The units shall be shipped fused for the higher voltage. For coordination purposes, Table 2 indicates Bay-O-Net fuse size that will be used at the lower voltage. B. For NSTAR South, fusing, when specified, shall be detailed in the ordering specifications on the purchase order and consist of a hot stick operable Bay-O-Net fuse in series with either a partial range current limiting fuse (voltages in tables 3&4) or an isolating link (voltages in table 5&6). Units shall not be shipped with fuse cartridge installed. Units shall be shipped with the fuse cartridges (not just the fuse links) for both voltage levels, secured in the primary compartment.

13,800 Grd Y/7,970 Volts or 4,160 GrdY/2,400 X 13,800 GrdY/7,970 Volts (NSTAR North) kva SIZE Phase-to-Grd Voltage BAY-O-NET LINK 25 6A (Cooper 108C04) 50 7970 15A (Cooper 108C07) 100 25A (Cooper 108C09) 50A (Cooper 108C12) 25 25A (Cooper 108C09) 50 2400 50A (Cooper 108C12) 100 65A (Cooper 353C14) 140A (Cooper 353C17) Table 2 Page 5 of 8 22,860 GrdY /13,200 or 24,940 GrdY /14,400 Volts (NSTAR South) kva Size Phase-to-Grd Voltage BAY-O-NET LINK 25 3A (Cooper 358C03) 50 8A (Cooper 358C05) 75 13,200V 12A (Cooper 108C07) 100 15A (Cooper 108C07) 25A (Cooper 108C09) Table 3 13,200 GrdY /7,620 Volts (NSTAR South) kva Size Phase-to-Grd Voltage BAY-O-NET LINK 25 8A (Cooper 358C05) 50 15A (Cooper 108C07) 75 7620 25A (Cooper 108C09) 100 25A (Cooper 108C09) 50A (Cooper 108C12) Table 4

3.0 Accessories, cont d Page 6 of 8 3740GrdY/2160 or 4,160GrdY/2400 or 7620GrdY/4400 or 8,320GrdY/4800 Volts (NSTAR South) kva Size Primary Voltage BAY-O-NET LINK 25 25A (Cooper 108C07) 50 50A (Cooper 108C09) 2160 or 2,400 Ph Grd 75 65A (Cooper 353C14) 100 65A (Cooper 353C14) 140A (Cooper 353C17) 25 12A (Cooper 108C06) 50 25A (Cooper 108C09) 4400 or 4,800 Ph Grd 75 50A (Cooper 108C12) 100 50A (Cooper 108C12) 65A (Cooper 353C14) Table 5 2,400 or 4,800 delta (NSTAR South) kva Size Primary Voltage BAY-O-NET LINK 25 15A (Cooper 108C07) 50 25A (Cooper 108C09) 75 50A (Cooper 108C12) 2400 Ph Ph 100 50A (Cooper 108C12) 65A (Cooper 353C14) 25 8A (Cooper 358C05) 50 15A (Cooper 108C07) 75 25A (Cooper 108C09) 4800 Ph Ph 100 25A (Cooper 108C09) 50A (Cooper 108C12) Table 6 3.7 An internal flapper valve shall be provided for all units with Bay-O-Net fuses. An external drip cup shall be provided to catch excess oil when fuses are removed. 3.8 All transformers must be supplied with two (2) case grounding lugs installed, Anderson #GTCS-34A or approved equivalent.

Page 7 of 8 3.9 All units will have an automatic pressure relief device with a minimum flow rate of 50 SCFM at 15-psi pressure. 3.10 Hold down cleats shall be provided for anchoring the transformer to a pad. 4.0 Labeling/Marking 4.1 A PCB information statement will be placed either on the transformer s nameplate or on a separate distinct and equally durable label. In addition, a separate company approved, durable, weatherproof, UV resistant,no-pcb label shall be affixed to the outside of the transformer on the right side of the tank. The label shall read No-PCB Less than 2PPM in large bold-type white lettering on a green background. 4.2 A permanent bar code label meeting the latest revision of ANSI C57.12.35 shall be provided. 4.3 Each transformer shall be stenciled with numbers that identify the KVA- CODE of the transformer. This is in lieu of the KVA only stencil. The KVA- CODE shall be designated on the purchase order. Flat black, UV light resistant paint shall be used. The lettering shall be approximately 2.5 high and will be located 3 from the top hinge, towards the handle, centered. Stenciling Examples: 25-223, 50-213 4.4 Two approved warning decals advising field personnel to vent transformer prior to operating bayonet fuses shall be installed and located on each unit as follows: A. Directly to the right of the bayonet fuse location. B. Inside the cover, below captive bolt/latching area. 4.5 The manufacturer shall install an external warning label (Electromark # BOS044-W-PT-A72) and an internal danger label (Electromark # BOS045-W- PT-112). Outer label shall be located on the door, above the lock. Inner label shall be located on the tank wall adjacent to the low voltage bushings. 4.6 Each transformer shall be marked with the cat id using durable, weather proof, UV resistant labels or painted stencils. The lettering shall consist of 1 inch high bold black characters. Cat id shall be located above the No PCB label.

5.0 Delivery Page 8 of 8 5.1 Unless otherwise specified on purchase order, all deliveries shall be made in an open top truck. Each unit shall be shipped on a wooden pallet. The stacking of transformers may be cause for rejecting an entire shipment, unless otherwise approved. 5.2 All transformers shall be secured to a wooden pallet for forklift unloading and shall be stored and shipped with the proper quantity of approved transformer oil. Paint finish shall be protected from damage due to any steel bands used for shipment. 5.3 Transformers are subject to inspection by the Company upon delivery. Approved by: Amin Jessa Director, Distribution Engineering