B100S - Super Swing. Instruction Manual. Document number: B100S-C Release: V4.0 Date: May 08,2009

Similar documents
B-PC20 Power Close Module

Senior Swing Control Box. Table of Contents

Electro-Mechanical Swing Operator. Table of Contents

ASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY

Dor-O-Matic. Series Slide Control. Installation Instructions

USERS GUIDE LO-21U LOCKOUT RELAY

Setup and Programming Manual

ASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY

LCN AUTOMATIC OPERATORS

GLM SERIES CONTROL Users Manual Rev:

5600 Series Power Operator Installation and Instruction Manual

*70954* 240V Senior Swing Control Box Installation Instructions CAUTION WARNINGS. Table of Contents

SW10 (Full Power) & SW19 (Low Energy)

Requirements LEO Power Operator Installation Instructions Patents: 5,881,497; 7,316,096; 7,484,333 CAUTION CAUTION WARNING

Requirements LEO Power Operator Installation Instructions Patents: 5,881,497; 7,316,096; 7,484,333 CAUTION CAUTION WARNING

TEL: G&C Electronics CC E. T.

What s on your truck? MOTIONACCESS, LLC. Installation & Operation Manual

CB CONTROL BOARD INSTRUCTION MANUAL VERSION 1.03 DATE 30/10/2000

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Application Engineering

Sliding Gate Operator User's Manual

Instruction Manual for the. E-SL 450 Series

Sliding Gate Operator User's Manual

Dor-O-Matic. Astro-Fold Universal Control Box Instruction Manual Universal Control Box DOR - O - MATIC

Visit our web site at AMR LS-3000, LS-3010 & LS-3020 BELT SLIP/SEQUENCE CONTROL INSTALLATION AND SETUP INSTRUCTIONS

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

Te 803 Electronic Controller. Service, Operation & Technical Information Manual

Thru-Beam Photo Eye Monitored / Non-Monitored Battery Powered Emitter

Hunter Automatics HA-8. Installation Manual

ECONOMISER SERIES E2T USER MANUAL

Application Engineering

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

CD100 Series. Operators Manual SINGLE COLUMN CARD DISPENSER

ECU. Speed Switch Manual. Contents. ECU is a registered trademark of Engineering Concepts Unlimited Inc.

Triple Output Power Supply

SKC400U SLIDING GATE OPENER OWNER S MANUAL

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

Boston Gear Ratiotrol DC Motor Speed Control

Variable Regulated Voltage Power Supply Instruction Manual Model XP-605 / XP-752A

Flight Systems. Replacement for KASSEC DESCRIPTION

Roll Up Door Operator

3200NT Timer Service Manual

Installing the gate post bracket with the cardboard arm template

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start)

Allegion LCN Benchmark AU9100 Series

CONTROLLER DIAGNOSTIC GUIDE

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

Installing the gate post bracket with the cardboard arm template

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

RVS-DN Digital Reduced Voltage Motor Starter

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

M9216 Series Electric Spring Return Actuators

STEPPER-BLOCKplus. Manual. Version: 2.0 As of: 06/2002 Author: Edmund Burger &RPSDFW6WHSSHU'ULYHU IRU3KDVH6WHSSLQJ0RWRUV. Main. Status-LED.

EE30181A DC Electronic Load 300 Watt

PowerCommand 3300 Control Panel. Our Energy Is Working For You.

1. AC VOLTS: Displays generator output in voltage. 2. AC FREQUENCY: Displays the speed of the generator set in Hertz.

CONTROL UNIT BIOS2. Manual for installation. Programmable Control board for wings gates.

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

Model 1672, 1673 Triple Output Power Supply

INSTALLATION GUIDE For Surface Mounted Applications (Purchased after 08/01/2018)

Product Instruction. Door Control Board: Board 1Ø4 for PM/SSC (R3)

ELECTRO-MECH SCOREBOARD CO.

T57 SERIES LOW ENERGY OPERATOR INTRODUCTION FEATURES BENEFITS PATENTS TABLE OF CONTENTS

DORMA Automatics, Inc. 924 Sherwood Drive Lake Bluff, Illinois U.S.A. Toll Free: Fax:

231.V1 GUIDE VSD. CONTROL SYSTEM & INTERFACE GUIDE C/W TDP (Total Door Protection) Dual Light Curtains

ADJUSTABLE FREQUENCY CRANE CONTROLS

RVS-DX Digital Reduced Voltage Motor Starter

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

User Instructions for WRC1021D. Doc

ANALOG CONTROL PANEL

Automatic Sliding Door Retrofit Drive Assembly. Installation Manual DoorControlsUSA.com

DC4000 Series LE Operator

Dor-O-Matic. Series Slide Control. Installation Instructions

DKG-705 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT WITH PARALLEL TO MAINS AND DUAL GENSET PARALLEL FEATURES

Owner and Installation Manual For: EZ-7000 LOW ENERGY AUTOMATIC SWING DOOR OPERATOR

PowerOhm Installation Manual for BM R Series Braking Modules

DTC B153A 08: Liftgate Latch Switch Signal Circuit Signal Invalid. Short to Ground B396A 02, B153A 08. Open/High Resistance B396A 02,

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

Cruise Control Diagnosis

EQUIPMENT - MAIN BODY 7-1 SECTION 7 EQUIPMENT CONTENTS

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

ELECTRIC SCHEMATICS LS1 LS2. "1532ES / 1932ES" Service & Parts Manual - ANSI Specifications March 2008 Page 5-9 ART_2236 ART_2243

SWING GATE OPENERS 24V DC GEAR MOTOR

Button 1 Button 2. Button 3 Button 4. Programmed Remote Transmitter. Button Function Condition

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

5001TCP SPEED CONTROLLER

PCS 100 SYSTEM INSTALLATION INSTRUCTIONS

5001TCP SPEED CONTROLLER

2904 Power Supply Installation Instructions I-EA00041

POWER SUPPLY aps-412_en 06/16

MEGA 462 REMOTE CONTROL AUTO ALARM SYSTEM INSTALLATION & OPERATION INSTRUCTIONS WIRING DIAGRAM. White. H1 5 Pin White. H6 2 Pin White.

DKG-317 MANUAL AND REMOTE START UNIT

POWERLINE 2000 Energy Management System TM

1.0 Features and Description

Red #22 Power. Red #14. Brown #18. Ign/Acc/Start. White#14. Tachometer Foot-Brake Door Pin Pos Trunk/Hatch (open) (-) while running Lock Arm

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

GUIDE 200.V2 VSD VERTICALLY CONTROL SYSTEM & INTERFACE GUIDE. 202 Standard Operation 202 Slave Mode 201 Sequence of Operations

Transcription:

B00S - Super Swing Instruction Manual Document number: B00S-C Release: V4.0 Date: May 08,009

! WARNING This control must be adjusted/serviced by a qualified person. The service technician must be familiar with the latest ANSI A59.0/9 standards. NEVER sacrifice the safe operation of the automatic door for an incomplete solution. Call the factory for technical support. Permanent wiring shall be employed if required by local codes. Refer to connector J3 section for wiring references.

B00S Module Description/Connector Pinouts 0VAC Connector J3 Motor Connector J4 GROUND NEUTRAL LINE AC Ground Motor NEG Motor POS 3 T USED 4 Check SW 5 Open Check SW 6 Hold SW 7 Logic Ground 8 3 B00S - Super Swing TEST Current Limit Acceleration Latch Open Backcheck Hold Safety SPEEDS Push&Go Activation Delayed Activation TIMERS POWER SERIAL NUMBER OPTIONS SIGNALS ON OFF 3 4 5 6 7 8 ISP Safety Activate Activate A Delayed Module Safety Activation ON B 6 Electric Lock NC 5 Electric Lock 4 Electric Lock C 3 4VAC 4VAC +4VDC 0 Logic Ground / Data - 9 Data + Output 8 Low Voltage ON/OFF 7 Hold Open 6 Delayed Activation 5 Safety B 4 Safety A 3 Activation Activation Logic Ground Signal Connector J ISP/Synchronization Connector J ISP/Synchronization Connector J ISP (In System Programmer) FACTORY USE ONLY Synchronization This connector is used to synchronize two modules together (For Dual door operator). Synchronization cable part number is B00S-SYNC. When the synchronization cable is used, the activation switch(es)/sensor(s) can be wired to only one module. All signals, except for the Delayed Activation, are shared between the two modules via the synchronization cable. When the Delayed Activation Timer expires, an activation signal is sent to the mate control. Note: Using the synchronization cable will not synchronize the door speeds. The speeds are kept separately.

Signal and Sensor Connector J PIN Signal J. Logic ground J. Activation J.3 Activation J.4 Safety A J.5 Safety B J.6 Delayed Activation Ground reference for signals and power Definition This signal to ground will activate the operator, If the module is in the ON mode (Low voltage ON/OFF must be to ground) and no current fault is present. This signal is active when the door is in motion, If the module is in the ON mode (Low voltage ON/OFF must be to ground) and no current fault is present. Note: Manual use of the door will not enable this input. When the door is fully closed, this signal to ground will prevent an activation. When the door is fully opened, this signal to ground will prevent the door from entering the closing cycle. When the door is fully closed, this signal to ground will prevent an activation. During the opening clycle, the door will go to safety speed when this siganl is to ground. During the closing cycle, the door will go to a very slow speed when this signal is to ground. When the door is fully opened, this signal to ground will prevent the door from entering the closing cycle, unless option # is set to "ON" (Disable Safety B at backcheck). Delayed Activation This signal to ground will start the delayed activation timer. W hen the timer expires, an activation is generated. This signal is used to do door sequencing. J.7 Hold open J.8 Low voltage ON/OFF J.9 Data + J.0 Logic ground / Data - J. (+4VDC) DC power for sensors J. (4VAC) J.3 (4VAC) J.4 J.5 J.6 Electric lock switch (Common) Electric lock switch (Normally open) Electric lock switch (Normally close) This signal to ground will hold the door opened, If the module is in the ON mode (Low voltage ON/OFF must be to ground) and no current fault is present. This signal to ground enables the module. The module is disable if this signal is not to ground This is a signal output for sensor which requires door status information. When door is closed, Data output is 0V When door is in the opening cycle, Data output is V When door is closing (In motion), Data output is 8V Ground reference for signals and power AC power for sensor (300mA max.) This connection is the common to drive an electric lock (Active when electric lock option is set to ON) This connection is the normally open () to drive an electric lock (Active when electric lock option is set to ON) This connection is the normally close (NC) to drive an electric lock (Active when electric lock option is set to ON) Source (0VAC input connector) - J3 P IN S ig n a l D e fin itio n J 3. A C G ro u n d 3 J 3. A C N e u tra l J 3.3 A C L in e required is 0 VAC 60Hz 60W Max.

Motor Connector - J4 PIN Signal Definition J4. Motor AC Ground This connection is used to ground the motor body when applicable J4. Motor NEG This connection goes to the negative of the motor J4.3 Motor POS This connection goes to the positive of the motor J4.4 Polarizing key (NC) This is used to polarized the connector J4.5 During the closing cycle, the operator is on latch check switch speed when this signal is to ground J4.6 During the opening cycle, the operator is on Open check switch backcheck speed when this signal is to ground J4.7 Hold switch During the opening cycle, the operator is force to hold speed when this signal is to ground J4.8 Logic ground Ground reference for signals Option Switches Switch 3 4 5 6 7 Definition Push & Go - For operator without a clutch (Use for handipcap operator ONLY) If this switch is set to ON, the operator is activated when door is manually pushed. Disable Safety B at backcheck If this switch is set to ON, Safety B is disable at backcheck Electric Lock If this switch is set to ON, a small delay is added prior to the door opening to allow to unlock the electric lock. If this switch is set to ON, a reverse power is applied when the door stalls at the latch position. Reverse on obstruction If this switch is set to ON, during a closing cycle, if the door stalls before the latch position, a reactivation is generated. Push & Go - For operator with a clutch (Use for handipcap operator ONLY) If this switch is set to ON, the operator is activated when door is manually pushed outside the latch zone. Door Seal ( option must be set to ON) If this switch is set to ON, the operator will create a small resistance to prevent the door to open. 8 T USED Note: Safety A has a permanent lockout during the opening and closing of the door. Safety A is active when the door is fully closed or fully opened.

Setup procedures Before applying power to the operator, make all necessary connections (Refer to the wiring diagrams at the end on the document). Installation Check Start here With door closed, apply power to the operator The operator arm is not setup properly. Remove power, then load operator arm. Check lights on module. Is the light on? Remove power from operator, check the fuse, if burned, replace fuse with same type and size. If fuse is OK. Check J3 wiring and that power is available for the operator YES YES Does the operator has a close check (latch) switch? Check lights on module. Is the Latch light on? YES Check lights on module. Is the MODULE ON light on? Turn low voltage ON/OFF switch to the ON position. If the operator does not have a low voltage ON/OFF switch, a wire must be added to J between pin and 8. YES Operator is ready for module adjustment Module Adjustment All trimmers are at minimum values when turned fully counter clock wise and are at maximum values when turned fully clockwise. A speed or timer trimmer is active when the corresponding light (LED) is lit. Current Limit Trimmer/Light Obstruction Fault on opening During an opening cycle, if the motor exceeds the allowed current limit defined by the current limit trimmer, a red light (LED) will lit, the opening cycle is cancelled and the operator is disabled for ten seconds. Before beginning the adjustments, set the following: - Activation timer trimmer to ¼ turn from the minimum - Current Limit trimmer to the maximum (Fully clock wise) 3- and Latch Speed trimmers to minimum (Fully counter clock wise) 4- Set all option switches to the OFF position. If an electric lock is used, set option #3 to the ON position

. Basic Adjustments Activate the operator by pushing the test button (using a small screwdriver).. Adjust OPEN speed trimmer so that the door arrives at back-check in no greater that 3 seconds for Handicap applications.. Adjust BACK-CHECK speed trimmer so that door creeps to final open in no less than seconds for Handicap applications. 3. Adjust HOLD force trimmer so that the power is just enough to hold door at full open without drifting closed. 4. Adjust ACTIVATION so that the door remains in the full open position for no less than 5 seconds for Handicap applications. 5. Adjust CURRENT LIMIT so that the door stops when it meets an obstruction during the opening cycle. Cycle test several times. 6. Adjust ACCELERATION so that upon activation during close cycle the door reverses smoothly. (T SUPPORTED AT THIS TIME) 7. Adjust CLOSE speed so that door closes no faster that 4 seconds to latch-check. 8. Adjust LATCH so that door closes the final 0 degrees without slamming.. Other Adjustments and Options.. Safety Speed Trimmer If a safety sensor is used, follow these steps to adjust the safety speed. - Push the test button to generate an open cycle. - During the open speed (Before backcheck) generate a safety signal 3- With the safety signal present, adjust the safety speed trimmer to achieve a creep or a stall motion of the door. TE: If the safety sensor is a header mount type (Sensor will detect the door when the door swings in front of it), Safety A input must be used for that sensor and the lockout option must be set to the ON position (Option switch #)... Push & Go Timer Trimmer If Push & Go is needed set the option to the ON position. The B00S has two types of Push & Go, - Option # Push & Go for operators without a clutch - Option #6 Push & Go for operators with a clutch (Operator must have a close check (latch) switch to use this option) After the proper Push & Go option has been selected, manually push the door open. The controller will detect the door movement and will generate an open cycle. Adjust the Push & Go timer trimmer for the desired opening time for a Push & Go activity.

..3 Timer and Speed Trimmers If power close is needed, set the option #4 to the ON position. Follow these steps to adjust the length and strength of power close. - With option #4 set to the ON position, push the test button to generate an opening cycle. - When the door enters the closing cycle and reaches the latch area, stall the door open. When power close activates, adjust the power close speed trimmer for the desired strength. 3- Generate another opening cycle, when power close activates, set the length of the power close buy adjusting the power close timer trimmer. ( - 6 seconds) Note: The operator must have a close check (Latch) switch to use this feature...4 Door Seal If a positive pressure causes the door to slightly open, the door seal option #7 can be used. For option #7 Door Seal to work, option #4 must be set to ON. If power close is not needed, then set the power close speed and timer trimmers to the minimum (Fully counter clock wise)...5 Reverse on Obstruction Set option #5 to the ON position to activate the reverse on obstruction option. When the door stalls between the backcheck and latch position, the controller will generate a re-opening cycle. Note: The operator must have a close check (Latch) switch to use this feature...6 Delayed Activation Timer The activation signal of another operator can be connected to the delayed activation input to create door sequence operation. When used, adjust the delayed activation timer trimmer to create the proper delay. For further information contact technical support.

4VAC Strike M 0VAC LINE NEUTRAL GROUND AC Ground Motor NEG Motor POS 3 T USED 4 Check SW 5 Open Check SW 6 Hold SW 7 Logic Ground 8 6 Electric Lock NC 5 Electric Lock 4 Electric Lock C 3 4VAC 4VAC +4VDC 0 Logic Ground / Data - 9 Data + 8 Low Voltage ON/OFF 7 Hold Open 6 Delayed Activation 5 Safety B 4 Safety A 3 Activation Activation Logic Ground check switch NC COM Open check switch COM NC Handicap activation push button Hold switch (Optional) COM NC (For fully automatic doors) Activation Sensor N.O. Common Ground +4VDC (For fully automatic doors) DATA + DATA - Safety Presence Sensor (DATA input - Optional) N.O. Common Ground +4VDC Note: If ON/OFF switch is not used, add a jumper between pin 8 and 0 of terminal block ON/OFF switch C C (Optional) Hold open switch ON/OFF & Hold open switch C Safety beam Transmitter Safety beam Receiver 3 Wiring diagram (Example) Note: Maximum load on power supply (4VDC and 4VAC) is 300mA

B A For dual door operator, plug the B00S-SYNC REV0 cable as shown below. When using the SYNC cable, only one control maybe wired to the sensors/switches. All signals are shared between the two controls using the sync cable, except for the Delayed Activation input. When the Delayed Activation Timer expires, an activation signal is sent to the mate control. Sensor power can be supplied by both controls for a total of 600mA. Latch Open Backcheck Hold Safety SPEEDS Push&Go B Activation Delayed Activation A Dual Door Operator Sync Cable B00S - Super Swing TEST Current Limit Acceleration TIMERS POWER SERIAL NUMBER OPTIONS SIGNALS ON OFF 3 4 5 6 7 8 ISP Module Safety Safety Activate Activate ON Delayed Activation 6 Electric Lock NC 5 Electric Lock 4 Electric Lock C 3 4VAC 4VAC +4VDC 0 Logic Ground / Data - 9 Data + 8 Low Voltage ON/OFF 7 Hold Open 6 Delayed Activation 5 Safety B 4 Safety A 3 Activation Activation Logic Ground Master Controller In dual/twin mode, set the Activation timer and Push&Go timer trimmers to the value needed. B00S - Super Swing TEST Current Limit Acceleration Latch Open Backcheck Hold Safety SPEEDS Push&Go Activation Delayed Activation TIMERS POWER SERIAL NUMBER OPTIONS SIGNALS ON OFF 3 4 5 6 7 8 ISP Module Safety Safety Activate Activate ON Delayed Activation 6 Electric Lock NC 5 Electric Lock 4 Electric Lock C 3 4VAC 4VAC +4VDC 0 Logic Ground / Data - 9 Data + 8 Low Voltage ON/OFF 7 Hold Open 6 Delayed Activation 5 Safety B 4 Safety A 3 Activation Activation Logic Ground Slave Controller Note: The B00S-SYNC (REV0) cable has two wires switched at one end of the cable Important: In dual/twin mode, set the Activation timer and Push&Go timer trimmers to the maximum value (Fully clockwise) for the slave controller. Electric lock for twin doors For one controller to control the electric lock(s), wire the electric lock(s) to one controller. Set the option #3 to ON for that controller only. Wire the activation signal(s) to the controller that is wired to the electric lock. For two controllers to control the electric locks (to keep the electric locks independent), wire the first electric lock to the first controller, the second electric lock to the second controller. Set the option #3 to ON on both controllers. Wire J pin (Activation ) of the first controller to J pin (Activation ) of the second controller.