Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Similar documents
H81xx. H81xx Energy Meter. quick install POWER MONITORING INSTALLATION GUIDE. Installer s Specifications

H81xx Energy Meter. H81xx NOTICE DANGER INSTALLATION GUIDE QUICK INSTALL POWER MONITORING

Enclosure for AMP1 Series Energy Meters with Swing Panel Kit

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

AE012 Enclosure for E5x Series Energy Meters With Swing Panel Kit Product Overview

Models beginning with MO, MK, 7B, 6S, 6F or 5B. Product Description. Technical Specifications. Installation Instructions.

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

Quick Start Guide TS 910 & TS 920

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

WF-5110R True Sine Wave Inverter

Quick Start Guide TS 910

Technical Specificaions. kwh Energy Meter

A419ABG-3C Electronic Temperature Control

Mini Multimeter with Non-Contact Voltage Detector (NCV)

USERS MANUAL MCD REMOTE OPERATOR

WF-5110R True Sine Wave Inverter

User Manual. Solar Charge Controller 3KW

Powerware Vdc Extended Battery Cabinet User s Guide.

INSTALLATION AND OPERATING INSTRUCTIONS OF THE INTERNATIONAL ISOBOX SERIES ISOLATION TRANSFORMERS.

MODEL 422 Submersible Pump Controller

WF-5100 Series True Sine Wave Inverters

INSTALLATION AND OPERATING INSTRUCTIONS OF THE INTERNATIONAL ISOBOX SERIES ISOLATION TRANSFORMERS.

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

825-P Modular Protection System for motors Specification Guide

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

9200 Revenue Meter. Model Certification Current Inputs. Complies with the accuracy requirements of the ANSI C Revenue Metering Standard

- Wiring Brochure Zone Manager 335

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

Document: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger

USE AND CARE GUIDE DUALCHECK CIRCUIT TESTER

University of Houston Master Construction Specifications Insert Project Name

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

Mini Multimeter with Non-Contact Voltage Detector (NCV)

- Wiring Brochure Zone Manager 336

COUNTIS E22 Three-phase energy meter Direct - 80 A

User Manual Solar Charge Controller 3KW

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

PowerOhm Installation Manual for LG ATV Series Braking Modules

Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

SECTION MOTOR CONTROL

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

Operator Manual For use with WFCO ULTRA III Deckmount Converter WF-9800 Series (model number located on the cover of the unit)

199.9 µa to A *, mv (AC or DC) * Accessory Shunts Available For Higher Current Ranges.

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

User Manual Pocket Pro, Pro + ph

Aurora Wind Interface Box

Installation and Operating Manual

1.Safe testing IMPORTANT:

These devices meet the requirements of OSHA 29 CFR (b)(1)(ii) and OSHA 29 CFR (a) (2)(ii)(G). Airpax LEL series

I n s t a l l a t i o n M a n u a l. f o r T E D

D. Operation and Maintenance Data. In addition to items specified in Division 1 Section "Operation and Maintenance Data," include the following:

True RMS Autoranging Multimeter

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

Autoranging Multimeter

Autoranging Industrial Multimeter

TC26-B Vehicle Sensor

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

DIGITAL RCD(ELCB) TESTER

Galaxy VM. Battery Breaker Box Installation 09/

SOS SERIES SOS1 SOS2. Spares On Site Battery Cabinet Installation Guide rEV3

Bussmann series Quik-Spec Coordination Panelboard

Galaxy VM. Classic Battery Cabinet Installation GVMCBCWUE, GVMCBC2WUE, GVMCBC2WUF, GVMCBC3WUF 07/2017.

Asymmetrical Installation Instructions. Components: i2cove Asymmetrical LED Light Fixtures. 12 [305mm] [918mm] 48.

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

1329I Integrated Drive/Motor CE Filter Option Kit

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

PRM-4. Phase Sequence and Motor Rotation Tester. Users Manual. For detailed specifications and ordering info go to

VP-6124/VP-6124-E 24 VOLT DC SWITCHING POWER SUPPLY

Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount

RF Point Level Control with Sensor Monitor

Instruction Manual. Blink HQ Charger. Charge on. a CarCharging Company

USER MANUAL. Insulation Tester + DMM. Model MG320

R820 REV2 SERIES SCR POWER CONTROLS NOVEMBER 2017

Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P

Nature Power Inverters. True Sinewave Inverter Modified Sinewave Inverter. Owner s Manual

VP-4124/VP-4124-E 24/48 VOLT DC SWITCHING POWER SUPPLY

nual k Voltage Stabilizer N) manual New Brunswick Voltage Stabilizer Operating manual

Digital Scale. Revision 1.0 August 17, Contents subject to change without notice.

Installation Instructions

Adam Equipment QT SERIES. ADAM EQUIPMENT CO. LTD. pn Rev. D1, July 2002

BTB TYPE AUTOMATIC TRANSFER SWITCH (ATS)

CurrentGuard. CurrentGuard. CurrentGuard. Plus. Surge Protective Devices. Installation,Operation and Maintenance Manual PN

PREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J.

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual

Model (Circuit Tester) Model (GFCI Tester)

Transient Fault Location for Branch Circuit Breakers TFT Turquoise Circle Newbury Park, CA Toll Free:

INTECH Micro 2300-RTD6

USER MANUAL. 200A AC Mini Clamp Meter. Model MA130. Please visit for user manual translations

FIRE DOOR OPERATOR WARNING INSTALLATION LOGIC BOARD REPLACEMENT KIT K , K A-400 & K B-400 APPLICATION REMOVE AC AND DC POWER

RVS-DN Digital Reduced Voltage Motor Starter

CP-250E-60/72-208/240-MC4 Microinverter with Modular Trunk Cable

Optimizing Emergency Power Systems for Health Care Applications

Operating and Installation Instruction Manual

CTRC Series Flexible Rogowski Current Transformer - Installation Guide

Installing Power Components

Transcription:

AH06 (optional mounting bracket for small, medium, and large CTs) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes. This equipment must only be installed and serviced by qualified electrical personnel. Read, understand and follow the instructions before installing this product. Turn off all power supplying equipment before working on or inside the equipment. Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors. Failure to follow these instructions will result in death or serious injury. A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2011 Article 100 No responsibility is assumed by Veris Industries for any consequences arising out of the use of this material. NOTICE This product is not intended for life or safety applications. Do not install this product in hazardous or classified locations. The installer is responsible for conformance to all applicable codes. Mount this product inside a suitable fire and electrical enclosure. FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Modifications to this product without the express authorization of Veris Industries nullify this statement. Always observe all National and Local Codes during installation of this product. Provide a disconnect device to disconnect the from the supply source. Place this device in close proximity to the equipment and within easy reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the relevant requirements of IEC 60947-I and IEC 60947-3 and be suitable for the application. In the US and Canada, disconnecting fuse holders can be used. Provide overcurrent protection devices for supply conductors. Install per national or local regulations. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the device may be impaired. Product Overview Energy Meter The Series energy meter combines industrial-grade split-core current transformers and precision microprocessor-based metering electronics. It can detect phase reversal, eliminating load orientation concerns. The meter and current transformers are calibrated as a set, so the installer must match their serial numbers at the time of installation. The H8150 provides a control power voltage range of 90-132 VAC. The H8163 and H8167 provide an extended input control power voltage range (90-300 VAC). The H8163 and H8167 models also have a pulse output compatible with building control systems and a phase loss output to protect equipment. All models include a slot to install a Modbus, BACnet, or Metasys communication board (sold separately). When equipped with this board and connected to a data acquisition system, the H8163 and H8167 can report energy and power diagnostic variables, including kwh, kw, PF, kvar, Volts, and Amps. Product Identification 120 VAC - 240 VAC (nom.); 90-132 VAC L-N; Display Only Output Amps One CT Two CTs Three CTs 100 Micro H8150-0100-0-1 H8150-0100-0-2 H8150-0100-0-3 200 Mini H8150-0200-1-1 H8150-0200-1-2 H8150-0200-1-3 300 Small H8150-0300-2-1 H8150-0300-2-2 H8150-0300-2-3 400 Med H8150-0400-3-2 H8150-0400-3-3 800 Med H8150-0800-3-2 H8150-0800-3-3 800 Lg H8150-0800-4-3 1600 Lg H8150-1600-4-3 2400 Lg H8150-2400-4-3 120 VAC - 480 VAC (nom.); 90-300 VAC L-N; Pulse, Phase Loss, and Display Outputs Amps One CT Two CTs Three CTs 100 Micro H8163-0100-0-1 H8167-0100-0-1 H8163-0100-0-2 H8167-0100-0-2 H8163-0100-0-3 H8167-0100-0-3 200 Mini H8163-0200-1-1 H8167-0200-1-1 H8163-0200-1-2 H8167-0200-1-2 H8163-0200-1-3 H8167-0200-1-3 300 Small H8163-0300-2-1 H8167-0300-2-1 H8163-0300-2-2 H8167-0300-2-2 H8163-0300-2-3 H8167-0300-2-3 400 Med H8163-0400-3-2 H8167-0400-3-2 H8163-0400-3-3 H8167-0400-3-3 800 Med H8163-0800-3-2 H8167-0800-3-2 H8163-0800-3-3 H8167-0800-3-3 800 Lg H8163-0800-4-3 H8167-0800-4-3 1600 Lg H8163-1600-4-3 H8167-1600-4-3 2400 Lg H8163-2400-4-3 H8167-2400-4-3 Z205338-0F Page 1 of 10 2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09132

Product Identification (cont.) Optional Comm Board (sold separately) Model Description H8163-CB Modbus Communications Board for Series H8186-CB BACnet Communications Board for Series H8126-CB Metasys N2 Communications Board for Series (consult factory if ordering this item) Optional Accessory Model AH06 Description Mounting Bracket Kit (fits the Small, Medium, and Large CTs only) Specifications H8150 INPUTS 90 to 132VAC line-to-neutral H8163, H8167 90 to 300VAC line-to-neutral Frequency 50/60 Hz ACCURACY System Accuracy ±1% of reading from 2% to 100% of the CT current rating Sample Rate All Models H8163 and H8167 PULSE OUTPUT PULSE RATE PULSE WIDTH PHASE LOSS ALARM OUTPUT 1280 Hz Protection Class NEMA 1 Insulation Class 600 VAC Operating Temperature Range Storage Temperature Range Humidity Range Altitude of Operation H8150 OUTPUTS 1.2 x 3.8 (31 mm x 97 mm) viewing area, 160 segments, backlit LCD N.O., Opto-FET, 100mA@24VAC/DC 0.10, 0.25, 0.50, 1.00 kwh per pulse (jumper selectable) 200msec closed H8163: N.O. (opens on alarm, remains open while alarm persists); H8167: N.C. (closes on alarm, remains closed while alarm persists); Both H8163 and H8167: Opto-Fet, 100mA@24VAC/DC; Fixed threshold 25% below any other phase MECHANICAL OPERATING CONDITIONS 0 to 50 C (32 to 122 F) -40 C to 70 C (-40 to 158 F) 0-95% RH, non-condensing 0 to 2000 m ELECTRICAL SERVICES 120/240 VAC with neutral, 208Y/120 VAC line-to-neutral H8163, H8167 Any Wye service in which the phase L-N voltage is 300VAC and the phase-tophase voltage is 480 VAC nom. with neutral Agency Approvals UL 61010 COMPLIANCE INFORMATION Installation Category Cat III, pollution degree 2 Meters and current transformers are calibrated as a set. To achieve this accuracy, match the serial numbers on the current transformers and the meter at the time of installation (does not apply to 100 A CTs). Do not apply 600V class current transformers to circuits having a phase-to-phase voltage greater than 600V without adequate additional insulation between primary conductor and current transformers. Z205338-0F Page 2 of 10 2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09132

Dimensions 7.6" (193 mm) 3" (77 mm) 8.3" (211mm) 14.8" (375 mm) MICRO 100 Amp A = 1.6 (40 mm) B = 0.7 (16 mm) C = 0.7 (16 mm) D = 1.2 (29 mm) E = 2.1 (53 mm) D A B C E SMALL 300 Amp A = 3.8" (95 mm) B = 1.5" (38 mm) C = 1.3" (32 mm) D = 1.1" (29 mm) E = 4.2" (107 mm) F = 4.8" (121 mm) A B C D E F MINI 200 Amp A = 2.6" (66 mm) B = 1.1" (28 mm) C = 0.8" (19 mm) D = 1" (27 mm) E = 2.9" (74 mm) F = 3.5" (90 mm) D B A C E F MEDIUM 400/800 Amp A = 4.9" (124 mm) B = 2.9" (73 mm) C = 2.5" (62 mm) D = 1.1" (29 mm) E = 5.6" (141 mm) F = 5.9" (150 mm) A B C D E F LARGE 800/1600/2400 Amp A = 4.9" (124 mm) B = 5.5" (140 mm) C = 2.5" (62 mm) D = 1.1" (29 mm) E = 8.1" (207 mm) F = 5.9" (150 mm) A B C D E F Z205338-0F Page 3 of 10 2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09132

C US Installation Guide Product Diagram Series Cover H8163/H8167 Inside and Board Layout Comm Board Slot 1 8 7 Display Plain Full 10 5 6 2 9 Power Supply Board Slot U L + - + - + - 3 + A D + B D + C D 4 H8150 Inside and Board Layout Comm board is optional and sold as a separate product. Comm Board Slot 8 Display Plain Full 10 9 Power Supply + - + - + - 3 4 + A D + B D + C D 1. Display. Large digit backlit LCD for data and diagnostics. 2. Security hasp. 3. Current transformer input terminals. These ensure that voltage lead and current transformer are properly matched (e.g. red to red). 4. Voltage input terminals. These ensure that voltage lead and current transformer are properly matched (e.g. red to red). 5. Pulse output terminals. These provide easy integration to existing control/data acquisition systems. (H8163 and H8167) 6. Phase loss output alarm. Alarm trips to protect equipment if phase voltage drops 25%. (H8163 and H8167) 7. Pulse rate selection switch. Set the pulse output at 0.1, 0.25, 0.50, or 1 pulse/kwh to match resolution requirements. (H8163 and H8167) 8. kwh reset. To reset the kwh counter, push both buttons at the same time and hold for 10 seconds. To reset kw max, push both buttons and hold for 5 seconds. 9. Backlight enabling jumper. Remove this jumper to disable lighting. 10. Plain/full display data jumper. 20 or 90 second display cycle. Comm board is optional and sold as a separate product. Z205338-0F Page 4 of 10 2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09132

VERIS INDUSTRIES 1-800-354-8556 Installation Guide Installation Disconnect and lock out all power sources during installation and configuration. If making connections to the meter through more than one metallic conduit, use a bonding plate (Veris part number AH11 or equivalent) to prevent electric shock. 1. Verify that the serial number on the meter matches the serial numbers on the current transformers (CTs). These are calibrated as a set, and mixing transformers with non-matching meters may damage the device when power is applied. The meter s serial number is printed on the label affixed to the inside of the front cover, and the CT serial number is on the CT label. If using 100 A CTs, serial number matching does not apply. Match serial numbers between meters and CTs. Serial number matching does not apply if using 100 A CTs. 2. Mount the meter. 3. Attach the CTs to the conductors. Local code requirements may require a mounting bracket. For maximum accuracy, run the conductor through the center of the current transformer window. 4. Optional step, per NEC and local regulations: Attach external fuses (not included with the devices). Verify that the fuse rating is adequate for the applied voltage, with a current rating of ½ Amp (T) slow blow. Select fuses with a fault current rating that matches the power source rating. Shock Hazard! CONTROLLER Accessory bonding plate or equivalent required when more than one metallic conduit will be used. 1/2A (T) SLO-BLO Use fuses compatible with this meter: Single phase Veris AH02 Two phase Veris AH03 Three phase Veris AH04 ØA ØB ØC N Installer Supplied Fuses Bond multiple metallic conduit runs with available bonding plate (Veris AH11 or equivalent) Z205338-0F Page 5 of 10 2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09132

Installation (cont.) 5. Use color coding to attach current transformer (CT) leads to the input terminals (e.g. red labeled lead to red terminal). Polarity is indicated in the wiring diagrams, but the meter is not polarity sensitive. See the Wiring section. 6. Use color coding to connect voltage leads to phase conductors (e.g. red transformer lead to red terminal). The meter is powered from the monitored source, so connect the voltage leads to a circuit that is normally left on. See the Wiring section. 7. H8163 and H8167: Connect the output terminals to the control/data acquisition system. The Pulse Output is normally open. For the H8163, the Phase Loss Output is normally open, and for the H8167, it is normally closed. Both are rated for 24 VAC/VDC@100 ma maximum. Ensure that the installation method and insulation ratings conform to local and national electrical codes. Plain Display Full + - + - + - + A D + B D + C D Pulse Output Terminal Phase Loss Output Terminal 8. Set the backlight enabling jumper as desired. Remove the jumper to disable the backlight. Backlight Enable Jumper 9. Set the Display Data jumper for either Plain or Full settings. Plain mode cycles the display through five data elements (kw, max. kw since last reset, average PF, line-to-line voltage, and amps) for four seconds each. Full mode cycles through all of the data available in the meter. See the Information Reporting section for more details. 20 seconds per cycle kw max. kw PF Volts L-L Amps 90 seconds per cycle kw max. kw PF Volts L-L Amps kvar kw Phase A kw Phase B kw Phase C PF Phase A etc. Z205338-0F Page 6 of 10 2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09132

Installation (cont.) 10. H8163 and H8167: Set the Pulse Rate selection switch to the desired output rate (kwh per pulse). Note that 0.1 is not valid for 1600 A systems, and 0.1 and 0.25 are not valid for 2400 A systems. 1.0 0.5 0.25 0.1 Plain Display Full + - + - + - + A D + B D + C D 11. Secure the meter cover shut using a padlock, wire tie, or other locking device. 12. Apply power to the meter. 13. Check the display. At initial power-up, the meter checks each phase. If the phasing is correct, an OKAY message appears. If the phasing is incorrect, an error message indicates which color leads are not connected properly. Disconnect power before reconnecting leads. 14. Check the power reading. Expected power is estimated as follows: kw = Volts(L-L) Amps 1.732 PF 1000 kw = horsepower 0.746 15. To reset the kwh accumulator to zero, press and hold the two pushbuttons on the inside of the meter cover for 10 seconds. 16. To reset the kw max. register, press and hold the two pushbuttons on the inside of the meter cover for 5 seconds. Z205338-0F Page 7 of 10 2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09132

Wiring Connect the white wire to (-). Connect the red/black/yellow wire to (+). Typical 208/480VAC, 4-Wire, 3Ø Installation RED CT ØA BLACK CT ØB YELLOW CT ØC + A Ð + B Ð + C Ð White WHITE N RED CT ØA Typical 240/120 VAC, 3-Wire, 1Ø Installation BLACK CT ØB + A + B + C White WHITE N RED CT Ø A Typical 120 VAC, 2-Wire, 1Ø Installation WHITE N White + A + B + C External fuse provided by installer (optional, per NEC and local regulations). 480 VAC only applies to the H8163 and H8167. Z205338-0F Page 8 of 10 2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09132

Alarms The following messages remain on the lower display for the duration of an alarm condition: Message Phase loss Amps Over Volts Over Explanation The voltage on one phase is less than 75% of the voltage on any other phase. The displayed message indicates the problem phase. The measured current is greater than 110% of the transformer range. The display message indicates the problem phase. Volts A-C, B-C, or A-C is greater than 660VAC. The displayed message indicates the problem phase. The H8163 and H8167 are rated to 300 VAC L-N, and the H8150 is rated to 132 VAC L-N. Operation above these levels damages the device. Data Outputs The continually reports kwh or MWh, depending on the total accumulated energy. A secondary display cycles through other parameters. The meter has two modes of display operation, depending on the setting of the Display Data jumper (J8) on the main circuit board. In Full Display mode, the meter cycles through all parameters. In Plain Display mode, the meter cycles through only the first five parameters as listed below: kw Max. kw PF Volts Amps kvar kw, phase A kw, phase B kw, phase C PF, phase A PF, phase B PF, phase C Volts, A-B Volts, B-C Volts, A-C Volts, A-N Volts, B-N Volts, C-N Amps, A Amps, B Amps, C If the has a communication board installed, every 10th rotation of parameters displays an additional set of data values: Pulse Rate Address Baud Rate Parity 2/4 Wire For meters with 2 or 3 current transformers. For meters with 3 current transformers. H8163 and H8167 only. Z205338-0F Page 9 of 10 2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09132

Troubleshooting No display Problem Reported power too low Reported power inaccurate Accuracy not as specified No Pulse output (H8163 and H8167) Pulse output wrong, display OK (H8163 and H8167) No Phase Loss output (H8163 and H8167) bad appears in the display (H8163 and H8167) Accuracy not as specified Solution Check external fuses. Verify that the display cable has not been disconnected during installation. Verify voltage leads are properly connected. Verify CTs and terminals are color-matched. Check for phase loss. Check external fuses. Verify meter and CTs have matching serial numbers (serial number matching does not apply if using 100 A CTs). Verify CTs and terminals are color-matched. Verify that no stray conductive materials (wire clippings, etc.) have shorted between the terminals. Verify power is supplied in the range of 5-24 VAC/DC, with a max. load of 100 ma. The pulse output internal is 200 msec; verify the controller accepts this signal as input. Set the pulse rate switch and the controller to match kwh/pulse. Verify power is supplied in the range of 5-24 VAC/DC, with a max. load of 100 ma. Verify that the Pulse Rate slide switch is set to a valid value. 0.1 is not valid for 1600 A systems; 0.1 and 0.25 are not valid for 2400 A systems. Verify current transformers and terminals are color-matched. Z205338-0F Page 10 of 10 2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09132