Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION

Similar documents
VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

VQ400M SERIES CLASS A COMBINATION VALVES INSTRUCTION SHEET APPLICATION

VE4000 & VE5000 SERIES

VE Series. Class "A" Gas Valves. Product handbook APPLICATION CONTENTS. General. Technical. Installation and operation. Various

VR400/VR800 series UNIVERSAL GAS VALVES CLASS A SERVO REGULATED COMBINATION VALVES APPLICATION. Contents PRODUCT HANDBOOK. General

S4562C 1085 COMBI BOARD APPLICATION. Contents PRODUCT HANDBOOK. General

/

Solenoid Valve DF-SA-series

SERIES 2000 GAS SAFETY SHUT OFF VALVE

VKF41...C. Butterfly Valves. Building Technologies Division Industry Sector

822 NOVAMIX GAS FLOW RATE ADJUSTMENT AS A FUNCTION OF THE AIR FLOW GAS/AIR RATIO 1:1 DOUBLE AUTOMATIC SOLENOID SHUT-OFF VALVE

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

AS-Interface Installation Manual. ASAHI / AMERICA, Inc. Thermoplastic Valves and Piping Systems

VML. elektrogas.com. Safety solenoid valves for gas Slow opening and fast closing type DN10 DN80 EE

BSW , -493, -494 Mechanical Rotary Cam Switches. User's Guide. Mechanical Rotary Cam Switches BSW BSW BSW

aero 2 -IOM aero 2 ACTUATOR - INSTALLATION, OPERATION & MAINTENANCE MANUAL

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

Solenoid Valve DF-SB-series

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

B21 Series BASOTROL Gas Valve

Product bulletin for: ST2 Ball valves with two-way and three-way BSPP threaded fittings

BALL VALVE - 10 SERIES Electric actuator - El-O-Matic

LKS 160 FOR AIR DAMPERS ON MULTI-STAGE AND MODULATING BURNERS

Motorized Butterfly Valve

CHALLENGER Propane to Natural Gas Instructions

S10010 / S SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS 10/20 Nm (88/177 lb-in) FOR MODULATING AND FLOATING CONTROL SPECIFICATIONS GENERAL

MBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N

ELECTRIC ACTUATOR MOD. VB015 MAINTENANCE AND INSTALLATION INSTRUCTIONS OF VALBIA ELECTRIC ACTUATORS

Double Acting & Spring Return. SERIES 92/93 Rack & Pinion PNEUMATIC ACTUATOR. The High Performance Company

A408 GB. Pneumatic oil and diesel pumps 1:1

Safety. Operating instructions Solenoid valve VGP DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 10.

Manually operated safety shut-off valve HSAV HSAV/5

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function Integrated bypass valve MB-D(LE) B07

AQUASTATS THERMOSTAT APPLICATION

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

Electromotoric actuators

DIAMOND POINT VIBRATING PROBES

Type N550 Snappy Joe Emergency Shutoff Valves

Double solenoid valve Rp 3/8 - Rp 2 nominal diameters DMV-D/11 DMV-DLE/11

Solenoid Valve ST-IA-series

Mounting and Operating Instructions EB 3913 EN. Electropneumatic Converters i/p Converter Type

CVR-625. Compact Vibrating Rod Instruction Manual

BGD258 Series BASOTROL CE Approved Class A Gas Valve

Center Center Exhaust Pressurized PS-32AS PS-32BS PS-32AD PS-32BD PS-520S PS-520D PS-53CD PS-53ED PS-53PD. Series PS. Function

Type 6213 EV, 6281 EV

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function Integrated bypass valve MB-D(LE) B07

Electromotoric Actuators

Section 21 Actuators. (Electric and Pneumatic) Edition 2

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Proportional controlling element

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

Motorized Butterfly Valve Actuated Wafer type butterfly valves

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 057 D01

HV Gate Valve with pneumatic actuator

Solenoid valves VZWM-L

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

Electromotoric Actuators

BGD278 Series BASOTROL CE Approved Gas Valve

BALL VALVE SERIES Electric actuator - El-O-matic

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

VLF45... Hot Air Valves. Siemens Building Technologies HVAC Products

Mounting and Operating Instructions EB 8227 EN. Pneumatic Control Valve Type 3331/BR 31a Special version Type 3331/3278. Type 3331 Butterfly Valve

MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 Fast-Acting, Two-Position Actuators

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

Holtumsweg 13, D Weeze, Tel /9134-0, Fax /1444

BC 4.3. Gas Tight Dampers GTD-GB40-B-E LISTED

Black Teknigas. Powerseat Eco Gas Safety Shut-Off Valve. Technical, Installation and Maintenance Details. WattsIndustries.co.uk

Old documentation - Only for your information! Product is not available any more!

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

PNEUMATIC QUARTER TURN RACK & PINION ACTUATOR MODEL - HP

Gas Pressure Governors

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 07.15

Solenoid Valve ST-SA-series

S1024-2POS / S POS S2024-2POS / S POS

Mounting and Operating Instructions EB 8111/8112 EN. Series V2001 Valves Type 3321 Globe Valve

CBU144. Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717. Product specification sheet

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

Installation & Operation Manual

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

TZIM. Electropneumatic Analog Positioner 10/ EN

Electro- Hydraulic Actuator Gas Valves GH-5000

IMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE

On/Off- Solenoid to RL 94/9/EG (ATEX 95) G HP E

Directional Seat Valve Series D4S (Denison)

Cylindrical Valves SCP Series

VALV-POWR SERIES VPVL MODEL D DOUBLE-ACTING AND SPRING-RETURN RACK- AND-PINION COMPACT PNEUMATIC ACTUATORS

Pilot-Operated Directional Control Valves Series D3 - D11

EW447-EW452 Series Mechanical Heat Meters FOR HEATING AND COOLING APPLICATIONS

Solenoid valves VZWM-L, NPT

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies

Mounting and Operating Instructions EB 8039 EN. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve

Motorized Butterfly Valve

CVS Rack and Pinion Pneumatic Actuator

HBSO1 Oil switch. Instruction manual. For detecting oil in refrigeration systems WE INCREASE UPTIME AND EFFICIENCY IN THE REFRIGERATION INDUSTRY

V4043 and V4044 Motorized Valves

Installation and Operating Instructions DDM-DS11 DDM-DS11-MS1 DDM-DS11-MS2

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 403 B01

Butterfly valves PN 16

Transcription:

Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION The VV Series class A vent valves are intended to be used in combination with the VQ400M series combination valve. The valves are supplied as a kit which enables the field mounting of the vent valve onto the VQ400M possible. The VP Series class A pilot valves are intended to be used in combination with the VQ400M series combination valve. The valves are supplied as a kit which enables the field mounting of the pilot valve onto the VQ400M possible. Figure 1: Vent Valve right Figure 2: Vent Valve left The valves are available in two different basic versions: 1: DN20 (3/4 ) Fast Opening 2: DN 20 (3/4 ) Slow Open version The VB Series class A by pass valves are intended to be used in combination with the VQ400M series combination valve. The valves are supplied as a kit which enables the field mounting of the by pass valve onto the VQ400M possible. The valves are available in two different basic versions: 1: DN20 (3/4 ) Fast Opening 2: DN 20 (3/4 ) Slow Open version Figure 3: Pilot Valve Figure 4: By Pass Valve The MS Series CPI switches are intended to be used in combination with the VQ400M series combination valve. The switches are supplied as a kit which enables the field mounting of the CPI switch onto the VQ400M possible Figure 5: CPI switch 1

SPECIFICATIONS The Vent Valves are supplied with kit KTVQM002 containing: - Valve Q.ty: 1 - Mounting screws M5 x 14 Q.ty: 4 - Mounting gasket Q.ty: 1 The Pilot Valves are supplied with kit KTVQM002 containing: - Valve Q.ty: 1 - Mounting screws M5 x 14 Q.ty: 4 - Mounting gasket Q.ty: 1 The Pilot Valves are supplied with kit KTVQM001 containing: - Valve Q.ty: 1 - Mounting screws M5 x 14 Q.ty: 4 - Mounting gasket Q.ty: 1 The CPI switches are supplied in ready to fit and use state Models See for model overview: survey 50040301. Available through Honeywell sales representative. Dimension VV420: See drawing: INST0176 VP420: See drawing: INST0175 VB420: See drawing: INST0174 MS06: See drawing: INST0181 Available through Honeywell sales representative Opening time: VV series: VB & VP series fast open: VB & VP series slow open: Closing time: N.A. < 1 sec Vent valve: <1 sec after energization VP & VB series: <1 sec Electrical connections Plug connection according to PG11 Adjust.: 1 30 sec Three pin plug connector according to DIN EN 175301-803 or ISO 4400, see page 10 Supply Voltages VV, VB & VP: Line voltage: 230V 50/60 Hz 115V 50/60 Hz 120V 50/60 Hz Coils for rectified AC with rectifier in connection box Maximum operating parameters MS: Voltage: Current: Operational Voltage range 250 V 3 A Valves will function between 85% and 110% of the rated voltage. Enclosure VV, VB & VP: IP54 in combination with PG11 connection IP65 in combination with DIN-plug connection Ambient temperature range -15 60 degrees C. Enclosure MS: IP65 Maximum operating pressure : 360 mbar Coil Insulation solenoid valves Insulation material specified according Class F Body material VV, VB & VP: Aluminum alloy die cast body MS: Nylon 2

Maximum working frequency VV420: VP & VB420 Fast Open: 30 cycles/min VP & VB420 Slow Open: 1 cycle/min MS: 30 cycles/min Closing spring AISI 302 steel SPECIFICATIONS cont. Seals and gaskets Hydro carbon resistant NBR rubber Hydro carbon resistant Cork-Nitril rubber Viton rubber Duty cycle Valves suitable for permanent energizing Designed life time 500000 cycles Power consumption Gas Voltage Power Current Coil nr valve [V] [W] [ma] BB020046 115 16,3 156 VV420 BB020046 120 17,8 160 BB020041 230 18,8 92 BB020046 115 16,3 156 VP420 BB020046 120 17,8 160 BB020100 230 14,8 72 BB020046 115 16,3 156 VB420 BB020046 120 17,8 160 BB020100 230 14,8 72 Table 1: Power consumption Capacity: (m3/h air at dp=2.5mbar) VV420 on VQ400 series: Not applicable VP420 on VQ420/425: 5.1 See figure 6 VP420 on VQ440/450: 6.8 See figure 7 VB420 on VQ420/425: 4.2 See figure 6 VB420 on VQ440/450 6.1 See figure 7 3

100 1000 Pilot valve capacity curves 300 200 10 100 80 60 Pressure drop 50 40 30 20 1 10 8 6 5 4 3 Air [kpa] [mbar] 0.1 (dv=1) 2 VQ420M/425M VQ440M/450M 1 1 2 3 4 5 6 8 10 20 30 40 60 80 100 200 300 500 1000 Methane (dv=0.64) 5 50 500 100 Flow [m 3 /h] 1000 Honeywell Figure 6: Capacity curve for Pilot valve mounted on main valve 4

100 1000 By-pass valve capacity curves 300 200 10 100 80 60 Pressure drop 50 40 30 20 1 10 8 6 5 4 3 Air [kpa] [mbar] 0.1 (dv=1) 2 VQ420M/425M VQ440M/450M 1 1 2 3 4 5 6 8 10 20 30 40 60 80 100 200 300 500 1000 Methane (dv=0.64) 5 50 500 100 Flow [m 3 /h] 1000 Honeywell Figure 7: Capacity curve for Bypass valve mounted on main valve 5

MOUNTING INSTRUCTIONS VV420 on to VQ420/425M Guideline for how to mount VV420 Vent valve: See figure 8 9 & 10 Figure 8: VQ420/425M (vent valve mounted on right side) 1: Choose side of VQ400 where to mount valve 2: By looking in direction of gas flow a choice concerning left or right handed models can be made. 3: Remove plug P1 4: Put gasket 2 in place. Mounting holes in gasket match hole pattern on valve body. 5: Put valve in place. 6: Mount screws and fix VV420 to VQ400M by tightening screws clockwise with 5 Nm. Tool bit to be used: TX25 7: Leak test to be carried out to ensure leak tight connection. WARNING Its not allowed to remove and re-direct orientation of outlet flange of VV420. Figure 9: VQ420/425M (vent valve mounted on left side) VV420 on to VQ440/450M Figure 10: VQ440/450M 6

MOUNTING INSTRUC. CONT. VP420 on to VQ420/425M Guideline for how to mount VP420 Vent valve: Figure 11: VQ420/425M VP420 on to VQ440/450M See figure 11 & 12 1: Choose side of VQ400 where to mount valve 2: Remove plug P1 3: Put gasket 2 in place. Mounting holes in gasket match hole pattern on valve body. 4: Put valve in place. 5: Mount screws and fix VP420 to VQ400M by tightening screws clockwise with 5 Nm. Tool bit to be used: TX25 6: If required, orientation of angled flange at bottom can be changed to required position. Fastening torque for flange screws after changing orientation flange: 5 Nm. Tool bit to be used: Cross hatched screw driver. 7: Leak test to be carried out to ensure leak tight connections. Figure 12: VQ440/450M 7

MOUNTING INSTRUC. CONT. VB420 on to VQ420/425M Guideline for how to mount VB420 Vent valve: Figure 13: VQ420/425M See figure 13 & 14 1: Choose side of VQ400 where to mount valve 2: Remove plug P1 and P2 3: Put gasket 2 in place. Mounting holes in gasket match hole pattern on valve body. 4: Put valve in place. 5: Mount screws and fix VB420 to VQ400M by tightening screws clockwise with 5 Nm. Tool bit to be used: TX25 6: Leak test to be carried out to ensure leak tight connections. VB420 on to VQ440/450M Figure 14: VQ440/450M 8

MS062001/2501 on to VQ420/425M Guideline for how to mount MS06 CPI switch: See figure 15,16 & 17 1: Choose valve to be detected 2: Remove plug P1 for first valve or P2 for second valve 3: Screw CPI switch to VQ400M clockwise tighten by 2,5 Nm. Be sure that terminals 1 and 2 in closed position. Tool to be used wrench 17 4: If sensing head tight can be turned CPI box to final position. 5: Leak test to be carried out to ensure leak tight connections. Figure 15: VQ420/425M (CPI mounted to detect V1 position) MS064001/5001 on to VQ420/425M Figure 16: VQ440/450M(CPI mounted to detect V2 position) Figure 17: VQ440/450M - detail 9

INSTALLATION IMPORTANT 1. Read these instructions carefully. Failure to follow the instructions could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. The installation has to be carried out by qualified personnel only. 4. Carry out a thorough checkout when installation is completed. Disconnect power supply to the valve actuator before beginning the installation to prevent electrical shock and damage to the equipment. Do not remove the seals and plugs from valves until ready for mounting. Take care that dirt does not enter the gas valves during assembly/handling Complete the electrical connections as instructed in the electrical connection section. Maintenance and service The designed lifetime* of this product is 10 years, based on date code, according to: a) the standard EN 126 b) the table on designed lifetime as stated on the Afecor website http://www.afecor.org/ We cannot assume that the product can be safely used beyond the mentioned designed lifetime. This lifetime is based on use of the control according manufacturer s instructions. Regular inspection of the control by authorized personnel in accordance with guidelines of the appliance manufacturer is required. After reaching the designed lifetime the product has to be replaced by authorized personnel. Note: * Warranty as opposed to designed lifetime is described in the delivery terms. Mounting position The gas valves and CPI switches can only be mounted as shown in figures 8 to 17. WARNING Tightness test after installation Spray all pipe connections and gaskets with a good quality gas leak detection spray. Start the appliance and check for bubbles. If a leak is found in a pipe connection, remake the joint. A gasket leak can usually be stopped by tightening the mounting screws, otherwise, replace the gas valve. Electrical connection WARNING Switch off power supply before making electrical connections. All wiring must comply with local codes, ordinances and regulations. Use lead wire which can withstand 105 C ambient. The electric ON/OFF operator is provided with a terminal block for electrical connections. Wiring PG11- VV, VB & VP Remove screws (A) Take off protective cover lids and gaskets (B) Take off plug Pg11 from hole which used for connection. Un-tighten cable support screw (C). Prepare cable Remove plastic outside insulation for about 50 75 mm. Strip wires from plastic insulation for about 5 7 mm. Place cable in cable support screw (C), steel ring (D), rubber ring (E) and guide wires through the hole in the cover to the connection block (DF). Connect wires between plates by tightening the particular screws (D1F1, D2F2, D3F3). Left: Phase Middle: Earth connection Right: Neutral Tighten cable support screw (C). Place gasket and cover lid in position (B) 10

Place screws (A) and tighten screws. Wiring DIN plug - MS Follow the instructions supplied by the appliance manufacturer as shown in the figures below. Figure 20: CPI inside wiring (closed valve position) Figure 21: Connection base for four pins plug connector (according to ISO 4400 / DIN EN 175301-803) ADJUSTMENTS AND FINAL CHECKOUT Figure 18: Connection through PG11 bushing Wiring DIN plug Follow the instructions supplied by the appliance manufacturer as shown in the figures below. The procedures described in this chapter are related to the adjustments on the main gas valve, pilot valve and by-pass valve. For adjustments on the other additional functionalities (e.g. pressure switch), refer to the included instruction sheet of the product in question in the package. CAUTION Adjustments must be made by qualified personnel only. To ensure a safe closing of the valves, it is essential that voltage over the terminals of operators is reduced to 0 Volts. Figure 19: Three pin electrical plug connector (according to ISO 4400 / DIN EN 175301-803). 11

VP & VB valves fast opening 1. Remove the cap from top of the coil by loosening both screws. 2. Place a wrench on the adjustment hexagon nut. 3. Turn wrench counter-clockwise to increase or clockwise to decrease the flow rate. 4. Replace cap on top of the coil. Figure 22: Adjusting flow rate. Flow rate adjustment (see Fig. 22.) 1. Remove the cap screw from top of the coil. 2. Place a socket head wrench into the adjustment nut. 3. Turn wrench counter-clockwise to increase or clockwise to decrease flow rate. 4. Replace cap screw. VP & VB valves slow opening The following characteristics can be adjusted: flow rate step pressure opening speed Figure 24: Adjusting flow rate. Step pressure adjustment (see fig. 25.) 1. Remove the cap from top of the coil by loosening both screws. 2. Place a screw driver in the slot of adjustment screw which is situated in center of the valve. 3. Turn screw driver counter-clockwise to increase or clockwise to decrease step pressure. 4. Replace cap on top of the coil. Figure 23: Characterized opening. IMPORTANT To ensure a satisfactory setting of the valve the pressure drop over the valve should be at least 10% of the supply pressure or 2.5 mbar which ever is the greatest. Flow rate adjustment Figure 25: Adjusting step pressure. Opening speed adjustment 1. Remove the cap from top of the coil by loosening both screws. 2. Place screw driver in the slot of adjustment screw which is of center line. 3. Turn screw driver counter-clockwise to increase the opening speed and therefore the time till full opening will decrease. 12

4. Turn screw driver clockwise to decrease the opening speed and therefore the time till full opening will increase. 5. Replace cap on top of the coil. Figure 26: Adjusting opening speed. CPI switch adjustment 1. Ensure that valve is in closed position (no coil energized) 2. Place a socket head wrench into the adjustment nut. 3. Turn adjustment screw clockwise till terminals 1 and 3 in closed position. 4. Turn the adjustment screw an additional half turn clockwise to achieve some over travel at the switch. 5. Operate valve several times to ensure proper functioning of the switch Final checkout of the installation Set the appliance in operation after any adjustment and observe several complete cycles to ensure that all burner components function correctly. APPROVALS The gas valve series VV, VP & VB and CPI switch series MS, to be used with VQ series of gas valves, have been designed to meet the European standards: EN 161 Automatic shut-off valves EN 126 Multifunctional controls DECLARATION OF CONFORMITY Honeywell Technologies Sàrl. Rolle, Switzerland, declares under it s sole responsibility that in combination with the VQ Modular Valve product family, the following valves: Figure 24: CPI switch adjustment pilot valves VP, bypass valves VB, and vent valves VV to which this statement relates, are: 13

in conformity with the essential requirements of the Gas Appliance Directive 90/396/EEC based on EN 126:2004 in conformity with the essential requirements of the Low Voltage Directive 2006/95/EC based on EN 60730-1:2000 in conformity with the essential requirements of the EMC Directive2004/108/EC for immunity based on the standard: EN55014-2: 1997 (Immunity, Product Family Standard) for emission based on the standard: EN55014-1: 2006 (Emission, Product family standard) 14

CONSTRUCTION AND WORKING PRINCIPLES The VP and VB420 series gas valves are class A fail safe shut-off valves. The valve is opened by energizing the direct ON / OFF operator. The direct ON / OFF operator consists of a coil and stop sleeve assembly. Inside the top sleeve assembly a plunger is placed which is able to move up and down and thus opening or closing the valve. The plunger is gliding on two anti-friction bearings. Flow regulation is done by adjustable plunger stroke. Valve closing springs are made out of steel AISI 302. Seals and gaskets are manufactured out of hydrocarbon resistant NBR according to DIN 3535 and EN291 or made out of Viton The VV420 series gas valves are class A fail safe vent valves. The valve is closed by energizing the direct ON / OFF operator. The direct ON / OFF operator consists of a coil and stop sleeve assembly. Inside the top sleeve assembly a plunger is placed which is able to move up and down and thus opening or closing the valve. The plunger is gliding on two anti-friction bearings. Valve closing springs are made out of steel AISI 302. Seals and gaskets are manufactured out of hydrocarbon resistant NBR according to DIN 3535 and EN291 or made out of Viton The MS06 series CPI switches contain micro switches indicating the position of the valve. Closed position is detected by mechanical contact between valve and extension of the switch. If valve opens, the shaft is moved by spring and switch can change over. ORDERING INFORMATION Basic OS number structure for valves: VY420X1xxx VY= VV: Vent Valve VP: Pilot valve VB: Bypass valve 420: DN20 X: A: fast closing. Only for Vent valve series B: Fast Opening with throttle C: Slow open Basic OS number structure for CPI switches: MS06xx001 xx: 20: CPI switch suitable for VQ420M series 25: CPI switch suitable for VQ425M series 40: CPI switch suitable for VQ440M series 50: CPI switch suitable for VQ450M series Honeywell Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce 16, 1180 Rolle, Switzerland or its Authorized Representative: Automation and Control Solutions Combustion Controls Europe Honeywell BV Phileas Foggstraat 7 7821 AJ Emmen The Netherlands Tel.: +31 (-)591 695911 Fax: +31 (-) 591 695200 http://ecc.emea.honeywell.com/default.htm 15