Instructions for the FMLB, FKLB, FAMB, FAHB (P,R)-1-3 Centrifugal fans

Similar documents
LQLR Fan. Installation instruction. Outlet: Installation. Inlet:

EULR Fan. Fläkt Woods 8192 GB Specifications are subject to alteration without notice

EUL(B,F) FAN. Fläkt Woods 3178 GB Specifications are subject to alteration without notice

Jet Fans. Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY

Operation and Maintenance Manual. Series BI Centrifugal Blowers

HOOD EXHAUST OR SUPPLY PROPELLER FAN

MARLEY ENGINEERED PRODUCTS OPERATING INSTRUCTIONS AND PARTS LIST

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting


INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN

SAI GM Series Piston Hydraulic Motor Crankshaft Design Radial Piston Motors

CENTRIFUGAL FANS INSTALLATION AND MAINTENANCE INSTRUCTIONS EQLR CENTRIFUGAL FAN

Commissioning & Maintenance Instructions. for. COBRA linear stepping motors

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS

Heavy duty slurry pumps

Maximum operating temperature for standard motors = 110 C. Shut down temperature in case of a malfunction = 115 C.

PACKING, HANDLING, TRANSPORTING AND STORING MOTORS

aintenance and hapter troubleshooting Table of ConTenTs

DPL/DPL-AF SERIES PLENUM FANS OPERATION INSTRUCTIONS AND PARTS MANUAL MODELS: DPL/DPL-AF-12, 13, 15, 16, 18, 20, 22, 24, 27, 30, 33, 36 GENERAL SAFETY

Sisu S-Cam Drum Brakes

Installation Vertical Pump: Installation 'CM' and 'CDM' Style: Operation:

IMPORTANT! READ BEFORE PROCEEDING! PHR Axial Flow Hooded Roof Ventilators

IMPORTANT! READ BEFORE PROCEEDING! PAF Axial Propeller Fans

Tubular Centrifugal Inline Fans TCN

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Upblast Exhaust Fan (Standard & High Pressure Exhaust) Belt Driven for Roof & Wall Mounting

The ELM Series Slurry Pump Installation and Operating Manual

Series Base mounted pump. Installation and operating instructions

READ AND SAVE THESE INSTRUCTIONS. High Velocity Restaurant-Duty Utility Set Belt Driven for Roof Mounting

2.- HANDLING OF VALVES BEFORE ASSEMBLY 3.- FITTING THE VALVE TO THE REST OF THE ASSEMBLY 5.- PERIODICAL INSPECTION OF THE VALVE AND MAINTENANCE

Profi le rail guides LLR

READ AND SAVE THESE INSTRUCTIONS

Installation, Maintenance and Operation manual 4 Submersible sand fighter pump. Type: SSFP - Series

Centrimaster, GX Installation and Maintenance Instructions

Automotive manufacturing accelerometer applications

D-Series Blowers and Exhausters

ROSTA MOTORBASES ROSTA. Self-Tensioning Motor Mount for Belt Drives. without slippage self-adjusting maintenance-free

AVK SERIES 854 BALL FLOAT VALVE FIELD MAINTENANCE AND INSTRUCTION MANUAL FOR BALL FLOAT VALVES

ROSTA Tensioning Motorbases Type MB. self-adjusting maintenance-free overload-proof non-slip dampen harmful vibrations extend belt drive

COOLING SYSTEM. Return to Main Table of Contents

Automotive manufacturing accelerometer applications

ROSTA Tensioning Motorbases Type MB. self-adjusting maintenance-free overload-proof non-slip dampen harmful vibrations extend belt drive

User s Manual D-Series Blowers and Exhausters

Table of contents. Table of contents Repair manual

Maintenance Instructions

Troubleshooting:Passenger Car


VEM motors Thurm GmbH

INSTALLATION VARIABLE FREQUENCY DRIVE THREE PHASE ALX SERIES SPUN ALUMINUM EXHAUSTERS

SECTION AIR INTAKE SYSTEM

SECTION CENTRIFUGAL HVAC FANS

PowerLink GW series Eddy Current Dynamometer User Manual

BLISS PELLET MILL 200

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL CNW DHK PVK

Emergency Smoke Control Centrifugal Roof Exhaust Fans

FRP Ball Valves INSTALLATION & MAINTENANCE MANUAL

Operating Instruction

Operating Instructions

IMPORTANT INSTRUCTIONS FOR OPERATION & MAINTENANCE OF

Electric motor testing

Installation, operation and maintenance manual

Heavy duty slurry pumps

Instructions for Fitting, Operating and Maintenance Canopy Door RE / (St.: )

Ball Rail Systems RE / The Drive & Control Company

PROMAG SR SERIES SEAL-LESS CENTRIFUGAL PUMPS

1 Mounting V-belt drive (motor pulley, fly wheel, V-belts and guard)

Installation and Operational Instructions for EAS -Compact overload clutch, Type 49_. 4._ Sizes 4 and 5

HYDRAULIC PALLET TRUCK MODEL NO: PT540M/BM/CM & PT685BM/CM PART NO: , , , ,

Instructions for Fitting, Operating and Maintenance

INSTALLATION, OPERATION & MAINTENANCE MANUAL AXIAL UPBLAST FANS RTA, RWTA, RHTA, RB, RD, RTA SH

Installation and Operating Instructions for EAS -NC clutch Type 45_. _. _ Sizes 02 and 03

USER S MANUAL FOR F & Q. Submersible Sewage Pumps

KLINGER Piston Valves KVN DN PN 16 I/III with valve ring KX-GT Modul

TSL and QSL Inline Centrifugal and Mixed Flow Fans

SERIES PC INSTRUCTION AND OPERATION MANUAL

7. Oil Pump OIL PUMP PS-46. 7) Place the oil pump bracket in a vise, remove the two bolts from front side of oil pump. CAUTION:

Power Transmission Belt Drive System Installation, Maintenance and Troubleshooting Guide

Portable Oil Free Silent Series Compressor Operating Instructions

S3 General Installation

EU DECLARATION CONFORMANCE

Before you go through this booklet, we request you to go through the following general instruction before commissioning your hydraulic systems.

Q&A Session for Advanced Linear Bearings and Guides 201 : Troubleshooting for Design Engineers

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS. Frames 143T - 449T

THREE PHASE AND SINGLE PHASE ASYNCHRONOUS ELECTRIC MOTORS OPERATION AND MAINTENANCE BOOKLET Rev

NSGV Direct Drive Pressure Blower (AF) Aluminum Housing & Wheel

Positive Displacement Pump

VBK 2596/12E/RSF. Thickness and Width Gauge for Strip and Profile. Operating- & Service Instructions. (with lateral guide rollers)

Maintenance and Repair

Timing Belt Installation

MODEL VBO-HV & VBO UPBLAST PROPELLER ROOF FANS

Assembly and Maintenance Instructions. Pad Thrust Bearings

Installation, Operation and Maintenance Manual

Installation, Operating and Maintenance Instructions. Rotating Machine Screw Actuators. With Parts List Publication Part No.

INTRODUCTION GENERAL GUIDELINES ATTACHING THE DRIVE PARTS

Assembly Instructions and Handling Regulations for KLINGER. Piston Valves KVN DN VI,VIII and Regulating Piston KVRLN DN , PN 40 VI, VIII

WELDING FUME EXHAUSTERS & ARMS

ISO 9001 CERTIFIED COMPANY INDUSTRIAL PUMPS. Installation & Operational Manual For BACK-PULL-OUT PUMP

Routine Compressor Maintenance

USER S MANUAL FOR F & Q. Submersible Sewage Pumps

Transcription:

Instructions for the FMLB, FKLB, FAMB, FAHB (P,R)-1-3 Centrifugal fans 1. GENERAL These instructions, wherever relevant, are applicable to the entire range of Swegon centrifugal fans. The instructions must be read and understood by all personnel concerned before any work with the product is begun. The direction of rotation of the fan is indicated by an arrow on the fan casing. The type designation of the fan is specified on an identification plate on the fan. The fan designation begins with a four-letter combination such as: FMLB. F denotes a fan, M is a code letter for in-house use and L denotes that the fan is of low-pressure type (M = intermediate pressure or H = high-pressure may instead be specified). The last letter, B, denotes backward-curved impeller blades (can also be P for flat, backward-curved blades or R for straight,radial blades). The digits after the four-letter combination indicate the size, variant and other particulars. Whenever you get in touch with Swegon, it is important that you state the correct fan designation and design. If the identification plate of the fan is missing, the illustrations below may be of help. FMLB, FKLB FAMB, FAHB Variants for various directions of discharge H1 H2 H3 H4 V1 V2 V3 V4 Impeller Blade Design Backward-curved blades For transporting air and pure gases. Flat, backward-curved blades For transporting pure gases or gases with low dust content Straight, radial blades For transporting gas containing dust Also suitable for gas containing coarse particles Specifications are subject to alteration without notice. www.swegon.se 1

2. INSTALLATION 2.1 Installation and anchoring The rotating parts in the centrifugal fans have been both statically and dynamically balanced. All the fans are thoroughly tested and test-run prior to delivery. The fans are normally delivered mounted on a steel base. If the fan is mounted on a concrete foundation, it is advisable to secure it by means of expansion-shell bolts. 2.2 Connection to the ducting The dead weight of the connected ducting must not apply a load on the fan casing. Otherwise, the casing may be deformed and come in contact with the impeller. Fans that are mounted on anti-vibration mountings or on an anti-vibration insulated base, should be connected to the ducting across a flexible duct. 2.4 Safety guards In accordance with the Labour Welfare Act and the directives of the National Board of Occupational Safety and Health, adequate protection is required for rotating machine parts. If the fan will be situated 2 metres or lower from the floor, a platform or similar, then safety guards most be reguired at both the impeller and at the belt drive. This also applies if greasing or other necessary inspection must be carried out when the machinery is running. The belt guard is normally included in the supply. Protective screens for the fan inlet or outlet are available to special order. Shaft guard 2.5 V-belt drives 2.5.1 Alignment Make sure that the shafts are parallel and that the belt pulleys do not pitch while you align them. Check the alignment by placing a straight edge or the like against both the drive pulley and the driven pulley, in full contact with the sides of the pulleys. Use a straight edge or the like to check the alignment of the belt pulleys Correct Wrong Wrong Wrong The maximum angular error of the pulleys (A in the figure below) must not exceed 2 mm per metre distance between the shaft centres. If the distance between the centres is less than 500 mm, a max. angular error of 1.0 mm is permissible. Place the straight-edge B with both its edges against pulley C. Turn pulleys C and D to provide the greatest distance at A occurs. B Belt guard C D A Protective screen at fan inlet A = max. 2 mm per metre distance between the shaft centres; 1.0 mm if the distance between the centres is less than 500 mm. 2 www.swegon.se Specifications are subject to alteration without notice.

2.5.2 Belt replacement If any of the drive belts should become worn, the complete set should be replaced. If only some of the belts are replaced, these will carry a higher load, since they are shorter than worn, stretched belts. Adjust the distance between the centres to enable the belts to be slipped on the pulleys by hand. Under no circumstances should the belts ever be forced into the grooves by means of a lever, screwdriver or the like. CAUTION! Do not apply belt dressing to the belts. 2.5.3 Belt tension If drive belts are insufficiently tensioned, they are likely to slip, and if they are excessively tensioned, the motor and fan bearings may be overloaded. If the belts are tapped, they should give slightly and give the impression of elasticity. They should not feel slack or lifeless. The belt tension should be rechecked after 50 hours of operation. Belt elongation mostly arises during the initial hours of operation. The belt tension must always be checked whenever a new fan is commissioned, whenever new belts have been fitted and if the fan has not been in use for a longer period. In other cases, the belt tension should be checked at least once every six months. The belt tension should be checked for correctness as follows: 1. Measure the distance between the shaft centres. 2. Measure the force P required for deflecting the belt 16 mm per metre distance between the centres, perpendicular to the direction of belt movement and about halfway between the pulleys. The use of a Trelleborg tensiometer or a small (fish) scale is recommended for this measurement. Use calibrated measuring instruments only. 3. Increase the belt tension if the force is less than P in the adjacent table and vice versa. 4. The recommended belt tension is 0.8 x P max. New belts must be tensioned so that the necessary deflection and force will be as equivalent as possible to the higher P value in the table. Use drive belts having the same nominal length in each belt drive. Make sure that the pulleys are aligned with one another. Regular inspections of the belt tension will give the belts a long useful service life. Force P for 16 mm deflection/m distance between the shaft centres Dia, of small pulley Belt profile d d (mm) P in Newton (N) SPZ 67 95 10 15 100 140 15 20 SPB 160 224 35 50 236 315 50 65 2.6 Fitting V-belt drive pulleys Fitting Axelavstånd Distance between shaft centres P 16 mm 16 mm per per metre distance meter axelavstånd between shaft centres Clean and degrease all machined surfaces. Fit the belt pulley and bush together, arranging them with the half-threaded holes (2-3 holes) aligned with one another and insert the screws but do not tighten them. Fit the pulley/bush onto the shaft as one unit, position them and tighten the screws with uniform torque. Dismantling Remove the screws, insert one of them in the extractor hole, i.e. the hole with half threads in the bush, and tighten it. This will loosen the bush. The loose pulley should then be withdrawn by hand without the aid of any hammer blows. Specifications are subject to alteration without notice. www.swegon.se 3

3. COMMISSIONING 3.1 Before starting the fan Before starting the fan, check the following: 1) That the electric motor is wired for the correct mains voltage and that all phases are connected (fuses are intact). 2) That the fan motor and belt drive have been aligned and are securely anchored. 3) That the V-belts are correctly tensioned. 4) That the ducting is properly secured and is tight against the fan without applying any load on the casing. 5) That the flexible ducts are correctly fitted. 6) That no tools or other objects have been left inside the fan. 3.2 After the fan has been started After the fan has been started, check the following: 1) That the impeller is rotating in the right direction. 2) That there are no abnormal vibrations or noise. 3) That the bearing temperature is normal. 4) That the motor doesn t exceed the rated current, and that there is equal amperage in all the phases. 4. MAINTENANCE 4.1 Fan The following items must be checked at least once every 12 months: 1. Check the fan balance. Feel the fan casing and ascertain that there are no abnormal vibrations. 2. If the fan has a drain connection, make sure that it isn t clogged. 3. Check that the connected flexible ducts are intact. 4. Fans that are used for transporting material should be inspected from the inspection cover. Clean the fan casing, if needed. 5. Check that the motor doesn t exceed the rated current, and that there is equal amperage in all the phases. 4.2 Electric motor Inspect at least once every 12 months: Listen to the bearings. A normal bearing emits a slight humming sound. A whistling sound indicates that the bearing has run dry. A scraping or thumping sound indicates that bearing balls or ball races are damaged. Any damaged bearings ought to be replaced. Also check that the motor mounts are intact and that the mounting bolts are properly tightened. Clean at least once every 12 months: The interior of the motor should be kept free of dust, grime and oil. In particular, clean the motor cooling fan and the grille below. Clean with a dry cloth. If the motor is especially dirty, noncaustic cleaning agent will be used. The motor is likely to overheat if layers of dirt obstruct the flow of air that cools the stator. Lubricating rolling bearings: Under normal operating conditions, bearing lubrication will last about 3 years in the size 200 and smaller motors. When a grease change is necessary, the bearing casing must be opened and thoroughly cleaned. All old grease and any remaining degreasing agent must be removed before new grease is applied. The size 225 355 motors have grease nipples as standard. Lubrication instructions are specified on a special label. 4.3 BEARINGS 4.3.1 Inspection The bearings in machines where a stoppage would give rise to serious consequences, should be regularly inspected. Bearings at less critical locations where the operating conditions are not particularly demanding, need in most cases only be lubricated. Check that grease is not leaking out through defective seals or insufficiently tightened plugs. Impurities usually discolour the grease and make it darker. Also check the seal arrangments in the vicinity of the bearing. They should be intact so that hot or corrosive liquids cannot penetrate the seal and reach the bearing. Check that the automatic lubricator, if fitted, is lubricating properly. Listen to the bearing by holding a stick of wood, a screwdriver or the like against the bearing casing. Press your ear against the tool and listen. A correct bearing emits a soft purring sound whereas a damaged bearing emits a harsh, often irregular and rumbling noise. Check the bearing temperature with a thermometer, heatsensitive crayon or by feeling the bearing casing with your hand. If the bearing temperature seems abnormally high or suddenly changes, this is a sign that bearing function is impaired. This may be due to insufficient grease, excessive grease, impurities, overloading, bearing damage, insufficient bearing clearance, excessive friction in seals or heat absorbed from the surroundings. However, keep in mind that a natural rise in bearing temperature often occurs after topping up with grease. This condition may last for 1 2 days Listen! Check the temperature! Inspect! 4 www.swegon.se Specifications are subject to alteration without notice.

4.3.2 Quantity of grease necessary for lubrication It is vitally important to lubricate parts with the correct type of grease and that the quantity of grease used on each occasion follows our recommendation. Overfilling in the bearing housing may cause a sharp rise in the bearing temperature and subsequently degrade the lubricant. Suitable lubricant is SKF LGEP 2 Lubricant. The correct quantity of grease for re-lubrication is tabulated below. 4.3.3 Lubrication interval The type FML(B,P,R)-3 fans have permanently lubricated bearings. The bearings of the other fans must be re-lubricated after the fan has operated for given number of hours depending on size and speed of rotation according to the Tables on this page. The permissible length of the lubrication interval may substantially vary for various qualities of grease, even if they appear to be the same. Fan type and size Recommended lubrication interval in hours in operation for various speeds* Quantity of grease FKL(B,P,R) 5000 hrs 3000 hrs gram 90 <800 800-1450 10 100 <750 750-1300 10 112 <700 700-1150 10 125 <650 650-1050 15 140 <600 600-900 rpm 20 * The lubrication interval for this type of fan applies to bearings on the drive side. Bearings when purchased are permanently lubricated. The tables specify suitable lubricating intervals, expressed in hours in operation, for non-ageing grease of average quality. The tables are applicable to bearings under normal load conditions and for a bearing temperature of +70 C. For bearing temperatures exceeding +70 C, the lubrication interval must be reduced to half for each 15 C increase in temperature.for operating temperatures lower than +70 C, the lubrication interval can be lengthened even doubled if the operating temperature is below +50 C. Fan type and size Recommended lubrication interval in hours in operation for various speeds* Quantity of grease FAM(B,P,R) FAH(B,P,R) 3000 hrs 2000 hrs 1500 hrs 1000 hrs 500 hrs 350 hrs gram 012-016 <5000 5000-6000 6000-7500 10 020-025 010-012 <2700 2700-3500 3500-5500 5500-6500 10 031 025 <1800 1800-2000 2000-2500 2500-4000 4000-4800 10 040 031 <1500 1500-1800 1800-2200 2200-3200 3200-3800 15 050-071 040 <1400 1400-1700 1700-2000 2000-2700 2700-3000 20 080-090 050-071 <1300 1300-1400 1400-1700 1700-2400 20 100-112 <1100 1100-1300 rpm 30 Specifications are subject to alteration without notice. www.swegon.se 5

4.3.4 Fault tracing the bearings Symptom Possible cause Action noise Abnormal load. Faulty assembly. Lack of lubrication or dirt inside the bearing. Alter the fit, play or pretension. Check the assembly and alignment. Lubricate or change the lubricant. Loud metallic Wrong type of bearing used. Change to silent-running bearings or bearings with less play. Skidding rollers. with less play or softer grease. Contact with rotating parts. Correct the pretension, select bearings Adjust the labyrinth seal. Abnormal Impeller comes in contact with the inlet cone. If possible: Balance impeller and shaft. noise Regular loud Rust or scratches on races. Replace the bearing,improve seals, noise use clean lubricant. Indentations on rollers. Peeling in the races. Too much play. Alter the fit, play, pretension. Irregular Embossing by foreign particles. Replace the bearing, clean, improve the noise Interior damage. seals, use clean lubricant. Scratches or roller damage. Excessive lubricant. grease. Reduce the volume of grease, use softer Insufficient lubricant, Top up or change the grease. Abnormal temperature or dirt inside bearing. Inspect the bearing. rise Abnormal load. Check the fit, play, pretension. Faulty assembly. Slipping between fitted surfaces, excessive seal friction. Indentations in rollers. Peeling in the races. Check the assembly and alignment. Check the seals, replace the bearing alter the fit. Vibrations Faulty assembly. Imbalance. Check for angular deviation of the shaft/ bearing casing and the contact surfaces of the spacer rings. Check the balance. Penetration by foreign particles. Replace bearing, clean. Improve seals. Loss of lubricant or Excessive lubricant, penetration Reduce the volume of grease, use firmer discoloured by foreign particles, grease, replace bearing casing and lubricant wear. connection fittings. 6 www.swegon.se Specifications are subject to alteration without notice.