Case Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI

Similar documents
Summary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers

Breaker failure relay REB 010

Transformer Protection

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Unit Protection System for Pumped-Storage Power Stations

Improving Breaker Failure Protection for Generator Applications

KD LV Motor Protection Relay

Experiences in a Motor Protection Retrofit

Dual Power. Protection. Protection

Electronic Ballast EVG 2000-T

BREAKER FAILURE PROTECTION

2015 WDC Disturbance and Protection Standards Overview

Breaker-failure protection RAICA

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

UniSec Maintenance solutions

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

ISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Grounding Of Standby & Emergency Power Systems

Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any

EE 741 Over-voltage and Overcurrent. Spring 2014

TRIP OF HORSHAM-REDCLIFFS 220 KV TRANSMISSION LINE AND MURRAYLINK INTERCONNECTOR ON 12 NOVEMBER 2015

ADVISE DESIGN IMPLEMENT FOR ELECTROTECHNICAL EXCELLENCE

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010

Seabrook Substation Reliability Improvement Project

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals. Mike Schmaderer

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

8DJ. Maintenance-free for lifetime

RAPTOR DEFAULT TEST TEMPLATES

Breaker failure protection function block description

Zone Selective Interlock Module. For GE Circuit Breakers

5. OVERCURRENT RELEASE (OCR)

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

MESG 12 / 17.5 / 24 / 36 KV

LARSEN & TOUBRO LIMITED TYPICAL SCHEME FOR PROTECTION OF SYNCHRONOUS MOTORS

Safe, fast HV circuit breaker testing with DualGround technology

LA Motor Protection. A South African Company to be Proud of

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

POWER SYSTEM OPERATING INCIDENT REPORT TRIPS OF YALLOURN W POWER STATION UNITS W1 AND W3 ON 14 NOVEMBER 2012

DG SYNCHRONIZING &AMF PANEL

TS-E TURBO STEAM ELECTRIC COUNTERTOP CONVECTION STEAMER PARTS AND SERVICE MANUAL

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

Customer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

TIME REQUIREMENT GUIDE (TRG)

Functions provided by measuring relays in railway equipment

PROTECTION OF THREE PHASE INDUCTION MOTOR AGAINST VARIOUS ABNORMAL CONDITIONS

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

INTELLIGENT AIR CIRCUIT BREAKER

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

Table of Contents. For latest version, visit:

Reverse power relay and protection assemblies

34 th Hands-On Relay School

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

5. OVERCURRENT RELEASE (OCR)

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

BellMega BM-510. Operation Manual Ver: 1.0 Rev: 1

CHAPTER 4 PROTECTION REQUIREMENTS

Protection and control VIP30, VIP35. Relays technical manual

320 to 327 M Series Low and Medium Voltage Motor Protection Relays

Guide for Primary Injection Testing WL Circuit Breakers. Document No. : 11-C

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

Jemena Electricity Networks (Vic) Ltd

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

SF 6 gas insulated RMU SafePlus 24 kv. ABB SafePlus 24 kv SF6 gas insulated RMU 1

Recent Trades in Distribution System

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

POWER SESSION. DP3 Class Power System Solutions for Dynamically Positioned Vessels

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

NXPLUS C Single busbar. Maintenance-free for lifetime

24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)

SALES PRESENTATION FOR RELAYS, CONTACTORS & MOTOR STARTER TESTING EQUIPMENTS

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

RVS-DN Digital Reduced Voltage Motor Starter

Zone Selective Interlocking

CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK

DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES

ZX2 Gas-insulated medium voltage switchgear

A21M. Introduction: Functional Overview: Key Protection & Control Functions:

T5S4P3 Synchronous Condensers Application. Mr. Marco Schenone Mr. Sandro Tuscano Mr. Alessandro Oldrati

Switchgear and Distribution Systems for Engineers and Technicians

Publication No.: PSG

atalog Welcome to ATO.com! Contact us... Tel: (Toll-free) Website:

Electrical network protection VIP30, VIP35. User s manual 12/2008

Shippensburg University

DISTRIBUTION SOLUTIONS HA Breaker Retrofit. Medium Voltage Service Marketing and Sales

Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems

Combustion Turbine Outages For 2008

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Power systems Protection course

Transcription:

Case Study on On EHV Circuit Breaker Flashover

AUTHORS: B. K. SINGH (AGM-ELECT) S.C.SINGH (SUPDT-ELECT) MANOJ SHARMA (Dy SUPDT-ELECT) ANAND PANDEY (ENGR-ELECT)

BREAKER-FLASHOVER There has been a rising trend in the number of breaker-flashover failures world wide Existing protection schemes either fail to detect breaker-flashover conditions or operate too late to prevent extensive damage. Breakers can explode, damaging neighbouring equipment or placing substation personnel at risk Dedicated protection is required to prevent damage resulting from breaker flashover

Introduction Flashover may occur during synchronization across breaker terminals while the breaker is open due to - Internal or external contamination Low dielectric pressure Humidity Probability is higher on breakers used to synchronize two isolated power systems or on generator breakers.

Introduction contd Frequently, only one phase of the breaker flashes over during synchronizing procedures Power system suffers an undesirable out-of-step and single-phase synchronization Extensive damage to generators and step-up transformers No dedicated breaker flashover protection exists in our plant SSTPS also experienced one such incidence during synchronization on 15.09.2010 in 400 KV SF6 Breaker of Unit#5.

Incidence at SSTPS Following protection operated during the incidence resulting in BUS-II and Unit#3 trip GT back up earth fault (51NGT ) TYPE CDG11 PMS-0.2 TMS-0.45 Pole slip (98G) relay Type- ZTO11 During pole flashover Generator voltage sinks & Current shoots considerably in oscillatory manner leading to operation of pole slip relay

Incidence at SSTPS Current flow in Generator winding in case of Single Pole flashover

Incidence at SSTPS Power Flow as recorded in DAS system

Analysis of incidence In order to analyze simultaneous operation of B/U Earth fault of transformer and Generator pole slip protection during synchronization following components were checked- Generator Transformer 400 KV side CTs GT LAs Generator Breaker for any internal failure GT, 400 KV CTs & LAs were tested thoroughly and found OK.

Analysis of incidence IR of breaker across the contacts of Y-phase under open condition taken and found zero. Breaker was closed and CR was found to be1800 micro ohm against a value of 100 micro ohm. It is concluded some internal problem has occurred inside breaker. The failure of breaker lead to operation of above relays. SF6 gas sample of failed pole was found to be contaminated thereby confirming an internal flashover The unit was synchronized on TBC. Breaker was later on dismantled for investigation.

Generator circuit breaker flashover Guide Fig.01 Image of internal components of failed breaker at SSTPS

Generator circuit breaker flashover Moving contact Fig.02 Image of internal components of failed breaker at SSTPS

Generator circuit breaker flashover Fixed contact Fig.03 Image of internal components of failed breaker at SSTPS

Generator circuit breaker flashover Fixed contact Fig.04 Image of internal components of failed breaker at SSTPS

Generator circuit breaker flashover Ballast cylinder Fig.05 Image of internal components of failed breaker at SSTPS

Why do breaker flashover occur? During synchronization, the out-of-phase voltage angle between contacts changes from 0 to 360 degrees continuously Voltage between breaker contacts reaches its maximum instantaneous value when the angle difference between the voltages is 180 degrees For 400 KV system ΔV max may be 654 KV (aprox)

Voltage across breaker contacts before synchronization Line volatge= 400 KV Phase volatge= (400 / 3) = 231 KV Peak value of phase volatge = 2* 231 = 327 KV Similarly voltage also appearing on Bus side of breaker contact. During out of phase condition (180 deg ) Net voltage across breaker contacts = 327 - ( 327 ) = 327-(- 327) =654 KV Bus side 327 KV 327 KV Generator side 654 KV

Why Traditional Protection is not effective Flashover is a series fault and lead to power oscillation Residual current much lower than phase-to-ground fault Generator protection are not effective or effective with delay in this situation LBB Scheme is not effective at detecting flashover failure Relying on an external trip prolongs the failure until line, generator, or transformer protection trips

Generator V & I Due to oscillatory & pulsating voltage & currents relay fail to detect the flashover condition

Current & Voltage signals for Protection relays

Methods for Flashover Protection Following parameters can be used as inputs for breaker flashover protection scheme Phase currents Residual current Voltages from one or both sides of the breaker, Breaker position auxiliary contacts ( 52 a or 52b ) Close-signal monitoring or timers Once the flashover is detected, all the breakers in the bus must be tripped, as in a conventional breaker-failure scheme. Security considerations are very important to avoid maloperations.

Method-1 Breaker OFF Based on residual-current measurement and a breaker auxiliary contact (52a (NO) or 52b (NC)) supervision Flashover is detected and the bus cleared if there is residual current and the breaker is open Require timer to eliminate mismatching in time of simultaneous closing of three phases Limitation: The scheme may mal-operate in case breaker closed status is lost and there is any external fault.

Method-1 Contd..

Method- 2 Time Limits and Close-Signal Monitoring to Detect Flashover In order to operate, this logic requires

Method- 2 Continued Allows scheme operation only if latch conditions occur in the first five cycles after current flows in the breaker. No Mal-operation where a breaker auxiliary signal is lost during normal operation with the breaker closed and residual or phase currents present. Method I would trip for this condition in case of external fault Timer is used to confirm the flashover condition The timer resets once current falls set value or close signal appears or 52a indicates a closed indication

Preventive measures to avoid flashover Probability of breaker flashover is highest in SF6 type of breaker Measurement of Dew point of SF6 gas in breakers (should be nearly -50 deg C) Overhauling of breakers at definite intervals Site test of breaker during overhauling of Units Line isolators should be closed just prior to voltage build-up and when machine is ready for synchronization

Pole Slip relay may be used for two phases for conventional protection schemes

CONCLUSIONS A dedicated breaker-flashover scheme is a must for breakers used to synchronize systems or generators There are several methods for implementing breaker-flashover protection. Residual current and breaker auxiliary position method ( Method-I) has lower dependability and security than other methods Method II, based on phase currents, close monitoring, and coincidence timers, has a very good dependability and security Present technology allows us to use multifunction intelligent electronic devices as well as separate breaker flashover protection relays

Thank-you