Dynamic & Static Rated Fire Dampers, Ceiling Radiation Dampers. UL Classified High Free Area Minimal Pressure Drop

Similar documents
Dynamic & Static Rated Fire Dampers, Ceiling Radiation Dampers. UL Classified High Free Area Minimal Pressure Drop

Life Safety Dampers. Fire Combination Fire Smoke Smoke Ceiling Radiation

Model DFD-230 Multi-Blade Fire Damper Steel 3V Blades UL555 3 Hour Fire Resistance Rating

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I

Life Safety Dampers - International. Fire Combination Fire Smoke Smoke Ceiling Radiation

Model SMD-302M. Modulating Smoke Damper. Application. Steel Airfoil Blades UL 555S Leakage Class II. Ratings. Size Limitations.

Model DFD-150. Dynamic Rated Fire Damper 11/2 Hour Fire Resistance Rating. Application. Ratings. Optional Features

Model DFD-150. Dynamic Rated Fire Damper 11/2 Hour Fire Resistance Rating. Application. Ratings. Optional Features

Model FSD-211. Application. Combination Fire Smoke Damper Steel 3V Blades UL 555S Leakage Class I UL /2 Hour Fire Resistance Rating.

SMD-201M. Application. Modulating Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

Model FSD-331 Combination Fire Smoke Dampers

Model FSD-331. Combination Fire Smoke Dampers. Application. Ratings. Features

Model DFD-350. Dynamic Rated Fire Damper 3 Hour Fire Resistance Rating. Application. Ratings. Optional Features

Model FSD-212. Combination FIRE SMOKE DAMPERS

Model SSFSD-211. Combination Fire Smoke Damper 304 Stainless Steel 3V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating

Model SMD-301. Smoke Damper Steel Airfoil Blades UL 555S Leakage Class I. Application. Ratings. Size Limitations. Features

SMD-201. Application. Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

Model FD-350. Static Rated Fire Dampers 3 Hour Fire Resistance Rating. Application. Ratings. Construction Standard Optional.

Model FSD-211. Combination FIRE SMOKE DAMPERS Steel 3-V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating

Insulated Control Damper. 12 x 7 (305 x 178) 8 x 7 (203 x 178)

Fusible Link (replaceable) Horizontal Mount

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x in. W x 120 in. H (3658mm x 3048mm) 5 in.

Fire Dampers Catalogue

Thermal Isolation Break. Frame Type Channel Quick Connect Single or Reverse Flange Blade Action Parallel Opposed Parallel Opposed Parallel Opposed

Fusible Link (replaceable) Horizontal Mount

FSD60, FSD60LP CoMBINAtIoN FIRe AND SMoKe DAMPeR

Model VCD-18. Ratings. Blade Operation. Size Limitations. Features & Options

FSD36, FSD36LP COMBINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 2

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

Model VCD-20 3V CONTROL DAMPER

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Qualified for installation in wood joist ceiling construction. CRD-1WT. Fire Dampers. Model

Baked Enamel, Epoxy, Hi Pro Polyester, Industrial Epoxy, Kynar/Hylar (70%) Permatector. Single or Reverse Flange 8 x 6 (203 x 178)

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x 305) 5 in. (127mm) Parallel

Model VCD-20. Control Damper. Application. 3V Blade. Ratings. Flange Options. Size Limitations. Blade Operation. Features and Options

HVAC Control Damper Models VCD and MBD. Selection Construction Performance

Thermal Isolation. Break

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BDF. Belt Drive Duct Fan

VCD-23 Low Leakage CONTROL DAMPER

HCD-230 Industrial Control Damper

Model VCD-40. Extruded Airfoil Blade Control Damper Narrowline Frame Construction. Application. Ratings. Flange Options.

VCD-23. Flange Options. Size Limitations

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options

AMD-33 Air Measuring Station with VCD-33 Control Damper

Air Measuring Products. AMS Thermal Dispersion Pressure Differential

HVAC Control & Balancing Dampers

Model VCD-43 Extruded Airfoil Blade Control Damper

Model VCD-20V. 3V Vertical Control Damper. Application and Design. Ratings (See page 4 for specific limitations) Flange Options.

VCD-23. Low Leakage CONTROL DAMPER

WD-300 Series. Backdraft Damper Vertical Mount - Horizontal Airflow. Application and Design. Ratings. Frame Styles. Size Limitations.

Model VCD-34. Low Leakage Insulated Airfoil CONTROL DAMPER. Ratings (See page 3 for specific limitations) Flange Options.

Model SEVCD-33. Low Leakage Airfoil Control Damper. Application and Design. Ratings (See page 3 for specific limitations) Blade Operation

Part # Installation,Operation and Maintenance Instructions

RECEIVING AND HANDLING INSTALLATION SUPPLEMENTS WARRANTY SAFETY WARNING:

WD-200 Series. Model WD-220 Flange Opposite Motor. Model WD-210 Flange on Motor Side. Model WD-200 No Flange. Motorized Backdraft Damper.

AMD-42V Air Measuring Station with VCD-42V Control Damper

AMD-42 Air Measuring Station with VCD-42 Control Damper

FBV-43. Vertical Face & Bypass Control Damper Ultra Low Leakage Aluminum Frame Construction. Application and Design. Size Limitations.

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options

Control Dampers and Fire Dampers. Volume 1 - March Insulated Control Dampers. Non-Insulated Control Dampers. Framing. Accessories.

table of contents PRODUCT SUMMARY 2

First Inline fan in the industry to be UL/cUL Listed Power Ventilator for Smoke Control Systems

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application. Ratings. Features and Options

Fire, Smoke, and Combination Fire Smoke Dampers

Installation, Operation and Maintenance Instructions

Model VCD-33. Low Leakage Airfoil CONTROL DAMPER. Flange Options. Blade Operation. Size Limitations

SD-1250 and SD-1600 Series Smoke Dampers

High Performance Axial Fans

Sidewall Propeller Fans Direct Drive. Exhaust / Supply

Installation, Operation and Maintenance Manual

High Performance Axial Fans

VCD-43V. Vertical Airfoil Blade Control Damper. Application and Design. Ratings. Size Limitations. Features and Options: Pressure:

CEILING DAMPERS GENERAL PRODUCT OVERVIEW CEILING DAMPERS MODELS 0716, , 0714 & 0722 FOR SQUARE, RECTANGULAR OR ROUND DUCTS

MULTI-BLADE FIRE DAMPERS

Air Measuring Products AMD AMS IAQ

CURTAIN TYPE FIRE DAMPER

Positive Seal Damper Blades with Vinyl Gaskets 2.5" SERIES 3000 SIDE MOUNT - NO FLANGE ORDERING METHOD FOR BACKDRAFT & MOTORIZED BACKDRAFT DAMPERS

We make dampers easy for you!

SMOKE DAMPER - CLASS F MODEL BMSD

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

HVAC Control & Balancing Dampers

FSD60, FSD60LP COMBINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 1

Nobody delivers dampers and louvers faster!

FSD36, FSD36LP COMBINATION FIRE AND SMOKE DAMPER

COMBINATION FIRE/SMOKE DAMPER - CLASS F MODEL BMFSD (3 HR) / MODEL BEMFSD (1½ HR)

Propeller Hooded Roof Fans

Centrifugal Exhaust Fans Series C. Roof Upblast and Sidewall

CFSD Series. Product Description

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

Model ABV Pressure Independent Automatic Balancing Valve. Application: Standard Construction: Performance: Configurations Available:

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

Motorized Fire Dampers

Mancoolers Models MCY, MCB, MCP

BC 03. Fire Dampers FD-GB-30-AS LISTED

Installation, Operation and Maintenance Manual

DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING

CONTROL DAMPERS. Model Model 1370CB. Model 1380CB. Model 1390CB B7

A Complete Line of Quality Products for Marine Applications

Transcription:

Dynamic & Static Rated Fire Dampers, Ceiling Radiation Dampers UL Classified High Free Area Minimal Pressure Drop June 2008

Fire Dampers, Ceiling Radiation Dampers The Greenheck Difference What makes Greenheck different from other damper manufacturers? Perhaps it s having the most UL certified dampers, the industryleading testing capabilities. Most Greenheck dampers meet Califnia State Fire Marshal and NY MEA requirements. Aggressive research and development also keeps Greenheck a maj player in the damper industry. Unparalleled In-house Testing Capabilities Internal testing capabilities are directly related to product quality and the ability to meet stringent code requirements. With industry-leading testing abilities, Greenheck can introduce new products faster, and can quickly develop qualified products f your unique applications. ur dampers qualify to UL555, UL555C and AMCA 500-D test standards. Quick Build and Delivery Greenheck s Quick Build (QB) program, along with strategic manufacturing locations, ensures rapid response time. Products are manufactured the next day, in three, five ten days, then efficiently shipped to your job site. n Greenheck's Quick Delivery (QD) program, we have stock sizes of DFD's & CRD's available to ship the same day as dered. Leading Edge Technical Suppt All Greenheck products are suppted by the industry s best product literature, electronic media, and Computer Aided Product Selection program (CAPS). You ll also find extensive infmation on the internet. You can always count on the personal service and expertise of our national and international representative ganizations. To locate your nearest Greenheck representative, call 715-359-6171, visit our website at A Global Presence Greenheck operates four damper manufacturing locations, seven national distribution centers, and two international distribution centers: Manufacturing Rocklin, CA Schofield, WI Frankft, KY Kunshan, China National Distribution Schofield, WI Rocklin, CA Dallas, T Miami, FL Greensbo, NC Union, NJ Columbus, H International Distribution Dubai Mexico 2

Design and Construction Features Multi-blade DFD s Reinfced Cner Design Tog-L-Loc, Greenheck s reinfced cner design, is incpated into every Greenheck multi-blade fire damper frame. It provides higher structural rigidity than many competits welded frames. The design also ensures that every frame has square cners, helping prevent blades from binding on the frame and making damper operation much smoother due to less friction. Maximized Free Area and Minimized Pressure Drop Greenheck s ariable Symmetrical Blade Design (SB), available on multiblade models, uses a combination of four symmetrical blade sizes 4, 5, 6, and 7 inch (102, 127, 152, and 178 mm) to maximize the free area at any given height and minimize pressure drop. The SB design also allows f consistent operating characteristics regardless of airflow direction. Traditional damper designs utilize only one blade width usually 6 7 inch (152 178 mm) which reduces manufacturing costs, but compromises the dampers perfmance capabilities by having cutoff extended blades and perfmance robbing oversized closure strips. Low Profile Frame Low profile top and bottom frames, standard on all dampers 17 in. (432 mm) high less, optimize free area on smaller dampers and reduce pressure loss. Airflow wks against actuat Transitions When a rectangular multi-blade fire damper is being used in conjunction with round oval ductwk, they can be supplied in a facty sleeve with round oval transitions on both ends of the sleeve. Dampers should be dered to the duct dimensions. Actuat Tque Unbalanced Blade Requires Higher Tque Airflow wks against actuat Airflow wks with actuat Free Area Competit Actuat Tque Balanced Blade Requires Less Tque Free Area Greenheck TYPE R TYPE TYPE C ptions pen Close Indicat (CI) - The CI option provides two switches, one set of contacts to close when the damper blades are at their open position, and the other set to close when the damper blades are at their closed position. The switches are physically linked to a damper blade and therefe give a true representation of the damper s position. Sleeve Facty Sleeve - Fire Dampers are available in facty furnished sleeves. Sleeves are galvanized steel and are available in 10 through 20 ga. (3 mm through 1 mm) thicknesses and lengths up to 48 in. (1219 mm). Damper D* A Damper Location CL Damper Frame L D* + 2 in. sq. 3

Design and Construction Features Curtain FD s & DFD s Mounting Most fire dampers are available f mounting either vertically hizontally (at left below). Greenheck also offers fire dampers f out-of-the-wall installation (below right). Fire Rated Partition W* Stainless Steel Closur e Spring Fusible Link (replaceable) 165 Standard (212 available) Facty Supplied Thermal Blanket H* K Side Grille (Supplied by others) FD/DFD series HRIZNTAL MUNT 3 11 / 16" ER TICAL MUNT * These dimensions are furnished approximately 1/4" (6 mm) undersize. (Add sleeve thickness f overall sleeved damper dimension) Integral Sleeve (-series) -series dampers in the FD and DFD model lines have the sleeve fmed with the fire damper frame as one piece, giving the most economical sleeved fire damper. The frame with integral sleeve is constructed of galvanized steel. Facty Sleeve ption Fire Dampers are available in facty furnished sleeves. Sleeves are galvanized steel and are available in 10 through 20 ga. (3 mm through 1 mm) thicknesses and lengths up to 48 in. (1219 mm). K dimension specifies location of damper within the sleeve. Minimum is 2 in. (51mm), maximum is L less 4 in. (102 mm), which allows f mounting angle installation and duct connection at each end of sleeve. If K dimension is not specified, it will be provided as one half of L dimension (damper centered in sleeve). Hizontal dampers must be installed with the K dimension on the top. 7 1/2 in. max. Fire Damper Transitions When a rectangular fire damper is being used in conjunction with round oval ductwk, they can be supplied in a facty sleeve with round oval transitions on both ends of sleeve. Dampers should be dered to the duct dimensions. Sleeve Fusible Link (replaceable) (165º F Std., 212º F available) Damper K Damper CL Damper Frame Location W * verall Sleeve Length 10 in. = DFD-15010 12 in. = DFD-15012 14 in. = DFD-15014 16 in. = DFD-15016 H * A-A Type A Type B/B2 Type C Steel Stud Frame Steel Stud Wall Steel Stud Connection (SSC) ption The Steel Stud Connection (SSC) ption allows fastening of the damper sleeve, up to 36 in x 36 in (914 mm x 914 mm), directly to the wall's steel stud framing. This option replaces the angles that were previously required f wall installations. See drawing at right. Type C Type CR Type R Steel Stud Frame Retaining Bar Cross-Section A-A Wallboard Damper Sleeve 4

ptions and Accessies f FD s & DFD s Helpful Installation Decals Greenheck dampers come complete with decals highlighting damper areas that are imptant f an accurate installation. ur decals point out critical damper areas and include messages like Do not install screws here. We are the only damper manufacturer to offer these simple yet very helpful tips right on the damper. Single Side Retaining Angles and Plates Rectangular dampers and sleeve assemblies up to a maximum size (W x H, in., W x H, mm) of 80 x 50 (2032 x 1270), 50 x 80 (1270 x 2032), 40 x 100 (1016 x 2540) require retaining angles on one side of the partition only f 1 1/2 hour dampers. Round dampers and sleeve assemblies up to a maximum diameter of 24 in. (610 mm) require retaining plates on one side only. Damper assemblies exceeding these maximum sizes must be secured with retaining angles plates on both sides of the partition. Retaining Angles Save time by letting Greenheck install retaining angles f you. You can der your retaining angles four different ways: Single Fastened - one retaining angle mounted in the location you want Single Wrapped - one retaining angle wrapped around the damper sleeve and wire tied Double Wrapped - the same feature as single wrapped but, with 2 sets of retaining angles Fastened & Wrapped - one retaining angle fastened and one angle wrapped around the damper Breakaway Connections Greenheck was the first manufacturer to successfully UL qualify a universal breakaway duct connection that is compatible with TDC, TDF, Ductmate, Nexus Ward flange systems. You now have the option to choose the universal breakaway connection on fire dampers, smoke, and combination fire smoke dampers. You can der your dampers with breakaway connection three different ways: Universal flange attached to one end of the sleeve Universal flange attached to both ends of the sleeve ne end attached and one shipped loose S & Drive connection uses drive slip connection on the side of the hemmed sleeve and S-slip joints are used on top and bottom. Access Dos Accding to NFPA 80 (2007 edition) & NFPA 90A (2002 edition), an access do needs to be provided in air ducts adjacent to each fire damper, smoke damper, combination fire smoke damper f maintenance and inspection. Save time and money by letting Greenheck install the access do in the sleeve to save on lab cost in the field. Security Bars When a specification requires security bars to be installed with the damper, they can be shipped assembled. Installation of security bars into dampers reduces security risks and reinfces the equipment. Security bars maintain the UL classification f all products. The standard product is welded into the sleeve. The minimum size is 8 in. x 6 in. (203 mm x 152 mm), and the maximum size is limited to maximum size of damper. Grille Tabs The Grille Tab option provides mounting flanges on the sleeve to ease installation of grilles in the field. The flanges are concealed when the grille is installed. 3.250 2.875 0.375 LINE F WALL D NT INSTALL SCREWS BETWEEN THESE LINES ARUND ENTIRE DAMPER (2).375 DIA. HLES 5.500 458549 5

Design and Construction Features DFDR s & FDR s Mounting Round fire dampers are available f mounting either vertically hizontally. nly one retainer plate is required f mounting of damper. Dampers are supplied with sleeves from the facty and can be installed without the need f additional field installed sleeves. Retainer Plate Duct Connection Area 2 in. Clearance f expansion Retainer plate Blade latch Access do to be on same side as blade latch AIRFLW 2 in. Duct connection Area Wall Thickness in. (mm) Sleeve Length in. (mm) Up to 6.5 (165) 13.625 (3) Do not place retainer plate in this groove Up to 8.5 (216) 15.625 (397) Up to 10.5 (267) 17.625 (448) 6 in. max. TW 6 in. max. ver 10.5 (267) Consult Greenheck Sleeve Length DFDR- Blade rientation Axle Axle Axle ff Hizontal () ff Hizontal () Nmal Retaining Plates Round one-piece retaining plates easily wrap around the sleeve of the damper and tighten with the clamping screw f simplified installation. They are designed to mount flush to the wall/flo and hold the damper in the opening. ne retaining plate is provided with the damper. NUT RETAINING PLATE ASSEMBLY CLAMPING SCREW 6

Design and Construction Features CRD s Mounting Greenheck s CRD models have been tested and labeled f protection of ceiling openings in fire rated flo/ceiling assemblies with fire resistance ratings of three hours less. They can also be applied to steel lay-in style ceiling diffusers up to 24 in. x 24 in. (610 mm x 610 mm) maximum size when installed with an approved thermal blanket. Models CRD-1 and CRD-2 are Warnock Hersey listed f wood construction barriers. CRD-1 butterfly CRD-1LP low profile butterfly CRD-2 round butterfly CRD-60 curtain blade style CRD-60 curtain blade style with skirt Butterfly Style Model and Size Limitations Model CRD-1 LW PRFILE CRD-1LP Minimum Size in. (mm) 4 x 6 (102 x 152) 4 x 12 (102 x 5) Size in. (mm) ptions olume Controller ption - A volume controller gives you the ability to regulate the airflow thru the damper by manually setting the blades at a given angle. Adjusting the screw will open and close the blades. Curtain Style CRD-60 B-TYPE CRD-60B CRD-60 6 x 4 (152 x 102) 6 x 4 (152 x 102) 6 x 4 (152 x 102) Round CRD-2 5 (127) 24 (610) Note: Damper is shown upside down to illustrate volume controller. 7

Damper Perfmance Testing Criteria Pressure loss through an open damper (change in pressure) is a perfmance criteria required to appropriately select and apply a fire life safety damper in an HAC system. Any damper s pressure loss depends on where and how the damper is installed in the HAC system. AMCA Standard 500-D defines several configurations to be used f testing damper pressure drop. Greenheck has tested its dampers f pressure loss in the three test figures shown and provides data f each. Actual pressure loss found in any HAC system is a combination of many facts. This pressure loss infmation, along with an analysis of other system influences, should be used to estimate actual pressure losses f a damper installed in a given HAC system. Fig. 5.3 5D 5D 6D Pressure Loss Pressure Loss testing was conducted in accdance with AMCA Standard 500-D. All data has been crected to represent standard air at a density of 0.075 lb/ft 3 (1.2 kg/m 3 ). Dimension (in.) 12 x 12 36 x 36 12 x 48 48 x 12 (mm) 5 x 5 610 x 610 914 x 914 5 x 1219 1219 x 5 elocity (fpm) DFD-210, 2, DFDTF-210, SEDFD-210, & SSDFD-210 AMCA Figure 5.2 Pressure Drop Pressure Drop - in. wg 500.04.02.01.01.03 1000.14.07.04.06.10 1500.32.15.09.13.23 2000.56.27.16.23.41 2500.88..25.36.63 00 1.26.61.36.52.91 3500 1.72.83.49.70 1.24 4000 2.24 1.08.64.92 1.62 DFD-210, 2, DFDTF-210, SEDFD-210, & SSDFD-210 AMCA Figure 5.3 Pressure Drop Fig. 5.2 Fig. 5.5 Figure 5.3 illustrates a fully ducted damper. Figure 5.2 illustrates a ducted damper exhausting air into an open area. Figure 5.5 illustrates a plenum mounted damper. D=Duct length W=Damper width H=Damper height D 4 (W) (H) 3.14 Dimension (in.) 12 x 12 36 x 36 12 x 48 48 x 12 (mm) 5 x 5 610 x 610 914 x 914 5 x 1219 1219 x 5 elocity (fpm) Pressure Drop - in. wg 500.02.01.01.01.02 1000.09.04.03.04.07 1500.20.09.06.10.16 2000.36.16.11.17.29 2500.56.25.17.27.45 00.81.35.24.39.64 3500 1.10.48.33.53.88 4000 1.44.63..70 1.14 DFD-210, 2, DFDTF-210, SEDFD-210, & SSDFD-210 AMCA Figure 5.5 Pressure Drop 8 Greenheck Fan Cp. certifies that the models DFD-210, DFD-2, DFDTF-210, SEDFD-210, and SSDFD-210 shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures perfmed in accdance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air perfmance ratings only. Note: Curtain style fire damper pressure drop data is available on www.greenheck.com Dimension (in.) 12 x 12 36 x 36 12 x 48 48 x 12 (mm) 5 x 5 610 x 610 914 x 914 5 x 1219 1219 x 5 elocity (fpm) Pressure Drop - in. wg 500.06.03.03.03.04 1000.22.14.12.13.17 1500.50.31.26..38 2000.89.55..53.67 2500 1.39.86.73.83 1.04 00 2.00 1.24 1.05 1.19 1.50 3500 2.73 1.69 1. 1.62 2.05 4000 3.56 2.20 1.86 2.11 2.67

Model Number Codes FIRE DAMPER MDEL NUMBER CDE The fire damper model number consists of 5 individual components that make up a specific fire damper's construction. The model number breakdown and cresponding explanation of each component help insure the crect fire damper selection f your application. 1 2 1 CLSURE RATING DFD (dynamic) F use in HAC systems that are operational in the event of fire. DFD ut of wall dynamic rated FD (static) F use in HAC systems that are automatically shut down in the event of fire. FD ut of wall static rated FIRE RESISTANCE RATING 1 (1 1 2 hour) F use in walls, flos, and partitions with fire resistance ratings of less than 3 hours. 3 (3 hour) F use in walls, flos and partitions with fire resistance ratings of 3 hours me. CLSURE RATING DFD (dynamic) F use in HAC systems that are operational in the event of fire. SEDFD 316 stainless steel dynamic rated SSDFD 4 stainless steel dynamic rated DFDTF Thin frame dynamic rated DFDAF Airfoil blade dynamic rated DFD -15012 1 2 3 4 5 3 DFD -210 4 5 1 2 3 4 3 FRAME STYLE (depth) 0 = Ultrathin - 1 1 2 in. (38 mm) 1 = Narrowline - 2 3 16 in. (56 mm) 5 = Standard - 3 11 16 in. (94 mm) PRESSURE RATING 0 = Low to Medium Pressure Classes up to 2 in. wg (.5 kpa) 5 = High Pressure Classes up to 3 in. wg (.75 kpa) higher and Seal Classes A B DAMPER WITH INTEGRAL 20 GA. SLEEE (Economical facty assembled damper with sleeve) 10 = 10 in. long (254 mm) 12 = 12 in. long (4 mm) 14 = 14 in. long (355 mm) 16 = 16 in. long (406 mm) FIRE RESISTANCE RATING 1 (1 1 2 hour) F use in walls, flos and partitions with fire resistance ratings of less than 3 hours. 3 (3 hour) F use in walls, flos and partitions with fire resistance ratings of 3 hours me. 2 1 2 BLADE STYLE 2 Fabricated Steel with Triple ee Reinfcements (3) 3 Fabricated Steel Airfoil Style Blade CLSURE RATING CRD (ceiling radiation) F use in ceiling openings with fire resistance ratings of 3 hours less. BLADE STYLE 1 Rectangular 2 Round 60 Curtain type CRD -1LP 4 1 2 3 3 PRESSURE RATING 0 =Pressure rating up to 4 in wg (1 kpa) SPECIAL FEATURES LP Low profile Insulation skirt B B style 9

Quick Reference Guide Construction Material Blade Profile Fire Rating Closure Temperature Accessies = Standard = ptional Round frame (20 ga.)(1mm) Ultrathin frame (1 1/2 in.)(38mm) Narrowline frame (2 3/16 in.)(56mm) Integral 20 ga. (1mm) sleeve 10, 12, 14, 16 in. length (254, 5, 356, 406mm) High pressure standard frame (3 11/6 in.)(94mm) Standard frame (3 11/16 in.)(94mm) 5 in. x 1 in. 16 ga. (127 x 25 x 1.5mm) Hat channel frame Galvanized Steel 4 stainless steel 316 stainless steel Curtain Air foil 3 Round 1.5 hour 3 hour 165 F (74 C) 212 F (100 C) 286 F (141 C) 350 F (177 C) Retaining Angles Retaining Plates DFD-110 DFD-150 SSDFD-150 DFD-150 series DFD-155 DFD-150 SSDFD-155 DFD-210 DFD-2 DFDAF-310 DFDTF-210 SEDFD-210 SSDFD-210 DFD-310 DFD-350 SSDFD-350 DFD-355 SSDFD-355 DFDR-510 SSDFDR-510 SEDFDR-510 FD-100 FD-110 FD-150 SSFD-150 FD-150 series FD-155 SSFD-155 FD-150 FD-0 FD-310 FD-350 SSFD-350 FD-355 SSFD-355 FDR-510 SSFDR-510 10

Model and Size Limitations Static Fire Dampers Model 1.5 Hour 3 hour FD-100 FD-110 FD-150 FD-15010 FD-15012 FD-15014 FD-15016 SSFD-150 FD-155 SSFD-155 FD-150 Mounting Hizontal ertical (H ) H H H H H H H No Transitions A style 36 x 36 (914 x 914) Single Section Size W H, in. (mm) B/B2 C & C CR 48 x 40 (1219 x 1016) 48 x 43 (1219 x 1092) 48 x 43 (1219 x 1092) 48 x 43 (1219 x 1092) 48 x 43 (1219 x 1092) 36 x 32 (914 x 813) 48 x 43 (1219 x 1092) 0 in. R 1 in. 2 in. Multi Section W x H, in. (mm) x x x 34 x 31 (864 x 787) x x x (1168 1067) 34 x 31 (864 x 787) x 36 x 36 (914 x 914) 31 (787) 31 (787) 73 (1854) 35 73 (1854) 35 72 (1829) 34 72 (1829) 34 (964) A B C & C CR 96 x 48 120 x 40 (2438 x 1219) (48 x 1016) 74 x 74 (1880 x 1880) 96 x 48 120 x 40 (2438 x 1219) (48 x 1016) 96 x 48 120 x 40 (2438 1219) (48 x 1016) 96 x 43 120 x 35 (2438 x 1092) (48 x 889) 74 x 69 (1880 x 1753) 96 x 43 120 x 35 (2438 x 1092) (48 x 889) 96 x 43 120 x 35 (2438 x 1092) (48 x 889) 94 x 118 x 34 (2438 x 1067) (2997 x 864) 72 x 68 (1829 x 1727) 68 (1727 68 (1727) 94 x 118 x 34 (2438 x 1067) (2997 x 864) 96 x 118 x 34 (2438 x 1067) (2997 x 864) 72 x 68 (1829 x 1727) 68 (1727) 68 (1727) 96 x 118 x 34 (2438 x 1067) (2997 x 864) FDR-510 H 24 (610) SSFDR-510 H 24 (610) FD-0 FD-310 FD-350 FD-355 SSFD-350 SSFD-355 H H (121 9 x 1219) 40 x 40 (1016 x 1016) 48 x 40 (1219 x 1016) 48 x 43 (1219 x 1092) 40 x 35 (1016 x 889) 48 x 43 (1219 x 1092) 38 x 34 (965 x 864) x 38 x 34 (965 x 864) x 48 x 43 (1219 x 1092) x x 34 34 39 (991) 39 (991) 38 (965) 38 (965) 80 x 40 (2032 x 1016) 80 x 35 (2032 x 889) 78 x 34 (1981 x 864) 78 x 34 (1981 x 864) 11

Model and Size Limitations Model DFD-110 DFD-150 DFD-155 DFD-15010 DFD-15012 DFD-15014 DFD-15016 DFD-150 Temperature F/ C 165 /74 212 /100 286 /141 165 /74 212 /100 286 /141 165 /74 212 /100 286 /141 165 /74 212 /100 286 /141 212 /100 286 /141 SSDFD-150 212 /100 SSDFD-155 212 /100 No Transitions A style Single Section 36 x 36 () x (H) (914 x 914) 36 x 36 () x (H) (914 x 914) 36 x 36 () x (H) (914 x 914) 36 x 36 () x (H) (914 x 914) 36 x 36 () x (H) (914 x 914) 36 x 36 () x (H) (914 x 914) 36 x 36 () x (H) (914 x 914) 36 x 36 () x (H) (914 x 914) 36 x 36 () x (H) (914 x 914) x () x () Multi Section 72 x 48 60 x 60 () ; 48 x 36 (H) (1829 x 1219) (1524 x 1524); (1219 x 914) 48 x 36 (1219 x 914) Dynamic Fire Dampers Size W H, in. (mm) B/B2 C & C CR 36 x 32 () x 26 (H) (914 x 813) (762 x 660) 36 x 32 () x 26 (H) (914 x 813) (762 x 660) 24 x 21 (610 x 533) 72 x 45 60 x 56 (); 48 x 32 (H) (1829 x 1143) (1524 x 12); (1219 x 813) 48 x 32 (1219 x 813) 24 x 21 (610 x 533) 72 x 48 60 x 60 () ; 48 x 36 (H) (1829 x 1219) (1524 x 1524); (1219 x 914) 48 x 36 (1219 914) 36 x 36 (H) (914 x 914) 72 x 45 60 x 56 (); 48 x 32 (H) (1829 x 1143) (1524 x 12); (1219 x 813) 48 x 32 (1219 x 813) 24 x 21 (610 x 533) 0 in. R 1 in. 70 x 44 58 x 55 (); x 31 (H) (1778 x 1118) (13 x 1397); (1168 x 787) x 31 (1168 x 787) 22 x 20 (559 x 508) 70 x 44 58 x 55 (); x 31 (H) (1778 x 1118) (13 x 1397); (1168 x 787) x 31 (1168 x 787) 22 x 20 (559 x 508) 34 x 31 () (864 x 787) 28 x 25 (H) (711 x 635) 34 x 31 () (864 x 787) 28 x 25 (H0 (711 x 635) 22 x 20 (559 x 508) 55 ()) 31 (H) (1397) (787) 31 (787) 20 (508) 55 (H) 31 () (1397) (787) 31 (787) 20 (508) 31 () 25 (H) (787 635) 31 () 25 (H) (787 635) 20 (508) 24 (610) 24 (610) 59 () 35 (H) (1499) 35 23 (584) 59 () 35 (H) (1499) 35 23 (584) 35 () 29 (H) (737) 35 () 29 (H) (737) 23 (584) x 26 () (762 x 660) 28 x 25 () (711 x 635) 28 x 25 () (711 x 635) 25 () (635) 25 () (635) () () 29 () (737) 29 () (737) 2 in. 58 () 34 (H) (13) 34 22 (559) 58 () 34 (H) (13) 34 22 (559) 34 () 28 (H) (711) 34 () 29 (H) (737) 22 (559) 28() (711) 28 () (711) elocity fpm (m/s) 2000 (10), 4000 (20) up to, 165 F (74 C) only 2000 (10), 4000 (20) up to, 165 F (74 C) only 2000 (10), 4000 (20) up to, 165 F (74 C) only 2000 (10), 4000 (20) up to, 165 F (74 C) only 2000 (10) 4000 (20) up to 24 x24, 165 F (74 C) only 2000 (10) Pressure in. wg (kpa) 4(1) 2000 (10) 4(1) DFDR-510 286 /141 24 (610) 2000 (10) SEDFDR-510 286 /141 24 (610) 2000 (10) 4(1) SSDFDR-510 286 /141 24 (610) 2000 (10) 12

Model and Size Limitations Model DFD-310 DFD-350 DFD-355 Model Temperature F/ C 165 /74 212 /100 286 /141 165 /74 212 /100 286 /141 165 /74 212 /100 286 /141 SSDFD-350 212 /100 SSDFD-355 212 /100 No Transitions A style Single Section 36 x 36 () (914 x 914) x () () 36 x 36 () x (H) (914 x 914) 36 x 36 () x (H) (914 x 914) 36 x 36 () x (H) (914 x 914) x x () x () Dynamic Fire Dampers continued Multi Section () 48 x 36 (H) (1219 x 914) 48 x 36 (1219 x 914) () 48 x 36 (H) (1219 x 914) 48 x 36 (1219 x 914) Size W H, in. (mm) B/B2 C & C CR 36 x 32 () (914 x 813 26 () (762 x 660) 24 x 21 () (610 x 533) 48 x 45 () 48 x 32 (H) (1219 x 1143) (1219 x 813) 48 x 32 (1219 x 813) 24 x 21 (610 x 533) 48 x 45 () 48 x 32 (H) (1219 x 1143) (1219 x 813) 48 x 32 (1219 x 813) 24 x 21 (610 x 533) x 26 () (762 x 660) Multi-blade Dynamic Fire Dampers Sizes H Installation inches (mm) 0 in. No Transitions R C & Single Section Size Multi Section 0 in. 1 in. 2 in. R 1 in. x 44 () x 31 (H) (1168 x 1118) (1168 x 787) x 31 (1168 x 787) 22 x 20 (559 x 508) x 44 () x 31 (H) (1168 x 1118) (1168 x 787) x 31 (1168 x 787) 22 x 20 (559 x 508) 28 x 25 () (711 x 635) 28 x 25 () (711 x 635) 44 () 31 (H) (1118 787) 31 (787) 20 (508) 44 () 31 (H) (1118 787) 31 (787) 20 (508) 25 () (635) 25 () (635) 24 (610) 24 (610) () () () 35 (H) 35 23 (584) () 35 (H) 35 23 (584) 29 () (737) 29 () (737) 2 in. () 34 (H) 34 22 (559) () 34 (H) 34 22 (559) 28 () (711) 28 () (711) elocity fpm (m/s) elocity fpm (m/s) 2000 (10), 4000 (20) up to, 165 F (74 C) only 2000 (10), 4000 (20) up to, 165 F (74 C) only 2000 (10), 4000 (20) up to, 165 (74 ) only Pressure in. wg (kpa) Pressure in. wg (kpa) 2000 (10) 2000 (10) DFD-210 DFDTF-210 36 36 up to 350 F (914 914) 32 50 up to 212 F (813 1270) 32 x 48 (H) (813 x 1219) 32 x 50 () (813 x 1219) SSDFD-210 24 (610 762) SEDFD-210 24 (610 762) DFDAF-310 DFD-2 32 50 (813 1219) 36 36 (914 914) 32 48 (813 1219) 64 50 up to 212 F (1626 1270) 96 72 (2438 1829) 32 x 96 (H) (813 x 2438) 64 50 () (1626 1270) 64 48 (H) (1626 1219) 48 (1219 762) 48 (1219 762) 96 50 (2438 1219) 64 48 (1626 1219) 62 48 up to 212 F (1575 1219) 94 70 (2388 1778) 62 48 () (1575 1219) 62 (H) (1575 1168) 28 (1168 711) 28 (1168 711) 62 48 (1575 1219) 48 (762 1219) 62 (1575 1168) 48 (1219) 48 (1219) 2000 up to 64 x 50 (10 up to 1626 1270) 4000 up to 32 x 50 (20 up to 813 1270) 10 (2.5) 71 (1803) 70 (1778) 2000 (10) ( 45 (H) (1143) () 44 (H) (1118) 29 (737) 28 (711) 2000 (10) 29 (737) 28 (711) 2000 (10) 48 (1219) 48 (1219) 2000 (10) 48 (1219) 48 (1219) 4000 (20) 4000 (20) 8 (2) 2000 (10) (762 x 1168) 31 (787) 4000 (10) 10 (2.5) 13

Codes/Listings/Approvals UL Categy EMME R13317 CABS R134 Listings/Approvals Califnia State Fire Marshal DFD-2xx 3225-0981:103 All DFD/FD ( 1 1/2 3225-0981:102 hour) All DFD/FD (3 hour) 3225-0981:107 CRD-1/CRD-2 3226-0987:101 CRD-60 3226-0981:111 New Yk City MEA (all models) 260-91-M Test Standards & Certifications UL555 This standard governs fire dampers which are intended f use where air ducts penetrate terminate at openings in walls partitions, in air transfer openings in partitions, and where air ducts extend through flos as specified in the Standard f Installation of Air-Conditioning and entilating Systems, NFPA 90A. In a fire emergency the fire damper is designed to close and prevent the spread of fire from one side of the wall partition to the other. Testing includes cycling, salt spray, dust loading, dynamic closure, fire endurance, and hose stream. UL555C This standard governs ceiling dampers which are intended f use in air handling duct outlets which penetrate membrane ceilings of hourly fire rated resistive assemblies, f installation in the ceiling membrane of such assemblies which utilize the plenum space f return air. AMCA The AMCA Certified Rating Program seal assures you that a product line has been tested to the appropriate AMCA standards in accdance with a legal license agreement and that the manufacturer's catalogued certified ratings have been submitted to the AMCA staff f approval pri to publication. Warnock Hersey The Warnock Hersey is among the most well-recognized and respected Nth American marks of compliance f building codes, association criteria, and product safety and perfmance standards. Warnock Hersey, like UL, is an independent agency which evaluates and tests products to recognized standards including those dictated by UL, NFPA, and ASTM. Codes In addition to the UL, AMCA, Califnia State Fire Marshal and New Yk MEA, Greenheck fire and ceiling radiation products meet requirements established by: National Fire Protection Association (NFPA Standards 80, 90A, 92A, 92B, 101, and 105) Note: F maintenance, NFPA 80 states Each damper shall be tested and inspected at start up1 year after installation then every 4 years after except in hospitals which are 6 years. All maintenance shall be documented. IBC International Building Codes ICB Unifm Building Codes ICC International Code Council 14

Specification Checklist Static Fire Damper Specification Checklist UL Standard UL555 Classified Fire Resistance NFPA 80, 90A, & 101 required 1 1 2 hour (less than 3 hours) 3 hours (3 hours me) Fire Closure Temperature 165º F (73º C), 212º F (100º C), 286º F (141º C) available Damper Construction Frame, Blades Sleeves Single assembly with an integral facty sleeve of desired lengths and thickness. Retaining Angles Plates UL listed angles (rectangular dampers) plates (round dampers) Mounting ertical hizontal mount. Accessies Security Bar Dynamic Fire Damper Specification Checklist UL Standard UL555 Classified Fire Resistance NFPA 80, 90A, & 101 required 1 1 2 hour (less than 3 hours) 3 hours (3 hours me) Fire Closure Temperature 165º F (74º C), 212º F (100º C), 286º F (141º C) available. F multi-blade DFD s 350º F (177º C) is also available Differential Pressure pressure across closed damper (4, 6, 8, 10 in. wg [1 kpa, 1.5 kpa, 2 kpa, 2.5 kpa]) elocity airflow rate through the open damper (up to 4000 fpm [20 m/s]) Damper Construction Frame, Blades, Blade Stops, Jamb Seal only, Linkage, Axles Sleeves Single assembly with an integral facty sleeve of desired lengths and thickness. Retaining Angles Plates UL listed angles (rectangular dampers) plates (round dampers) Mounting ertical hizontal mount Accessies Security Bars Ceiling Radiation Damper Specification Checklist UL Standard UL555C Classified Fire Resistance NFPA 90A & 101 required 1 1 2 hour (less than 3 hours) Damper Construction Frame, Blades Frame options Standard, Bottom Extension, Top Extension, Bottom & Top extension Accessies olume Controller Please visit our website at www.greenheck.com/products/dampers/index f complete specifications. 15

The Greenheck Difference Greenheck has a complete line of Dampers f your needs! Commercial Control Industrial Control Fire, Smoke, & Combination Fire Smoke Ceiling Radiation Backdraft Pressure Relief Dampers Manual Balancing Access Dos Marine Severe Environment Industrial Smoke Insulated Thermally Broken Air Measuring Pressure Relief Access Dos Barometric Relief Industrial Backdraft Tunnel Transit Bubble Tight F over 50 years, the Greenheck name has been synonymous with innovation, product quality and customer service. We know our dampers are: Number one in product quality and reliability Number one in combined reputation and after-sale service and suppt Put into service over 150 times a day From the Petronas Twin Towers in Kuala Lumpur to well-known Las egas casinos and wld-renowned hospitals, Greenheck dampers meet the safety needs of the most complex applications. ur Warranty Greenheck warrants this equipment to be free from defects in material and wkmanship f a period of one year from the purchase date. Any units parts which prove defective during the warranty period will be replaced at our option when returned to our facty, transptation prepaid. Mots are warranted by the mot manufacturer f a period of one year. Should mots furnished by Greenheck prove defective during this period, they should be returned to the nearest authized mot service station. Greenheck will not be responsible f any removal installation costs. As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. P.. Box 410 Schofield, WI 546-0410 Phone (715) 359-6171 greenheck.com DFD FD CRD Rev. 3 June 2008 Copyright 2008 Greenheck Fan Cpation