SECTION AIR TERMINAL UNITS

Similar documents
University of Delaware

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SINGLE DUCT TERMINAL UNITS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

FAN POWERED TERMINAL UNITS

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499]

Variable Air Volume (VAV) Pressure Independent Control

SECTION HVAC AIR CLEANING DEVICES

SDL Single-Duct, Low-Height, VAV Terminals

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

Variable Air Volume Dampers

FAN POWERED TERMINAL UNITS

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes:

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

Product Data. Features/Benefits. 45J,M,K,N,Q,R Standard, Quiet, and Low Profile Fan Powered Variable Air Volume Terminals

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

SINGLE DUCT AIR TERMINAL UNITS

Climas y Proyectos Leyco, S.A. de C.V.

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

TSS Single-Duct VAV Terminals

HOW TO SPECIFY SDV UNITS

catalog SDL Single-Duct, Low-Height, VAV Terminals

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

Application Guide TABLE OF CONTENTS: I. Introduction II. LHK Description III. Applications IV. Suggested Specification

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design

I Fan Powered Terminal Unit

catalog SDL Single-Duct, Low-Height, VAV Terminals

UNIVERSITY OF NORTH FLORIDA Arena HVAC Replacement SECTION MODULAR INDOOR CENTRAL-STATION AIR-HANDLING UNITS

SINGLE DUCT AIR TERMINAL UNITS

Product Data. Features/Benefits. 45J,M,K,N,Q,R Standard, Quiet, and Low Profile Fan Powered Variable Air Volume Terminals.

RETROFIT TERMINAL UNITS

Technical information

D2-2. Table of Contents RETROFIT/BYPASS TERMINAL UNITS

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

IAQ. Model AVC. SINGLE DUCT VAV Model AVC

FS Fan-Coil Units Hi-Rise, Vertical

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL

VAV RETROFIT/BYPASS TERMINAL UNITS TABLE OF CONTENTS RETROFIT/BYPASS TERMINAL UNITS. E-2 Excellence in Air Distribution MODEL RVE MODEL KLB MODEL SVE

SECTION AXIAL HVAC FANS

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101)

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

PH SERIES SINGLE DUCT ATU PERFORMANCE DATA

HBC SERIES-PSC MOTOR HBCX SERIES-ECM MOTOR

Fan - Powered Terminal Unit Series Flow

TVS/R FAN COIL UNITS HI-RISE, VERTICAL

500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT FORM EG3 (404)

RAV Sales Guide FAN COIL UNITS HI-RISE, VERTICAL

WATER SOURCE HEAT PUMPS

Direct Gas-Fired Heating

PNEUMATIC CONTROL SYSTEMS DESIGN AND CONSTRUCTION STANDARD PART 1 - GENERAL. A. Codes and Standards that are Standard at the University:

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume

Catalog Air Terminal Units. Models MQTH, MQFCI and MQFVI. Model MQTH. Model MQFCI. Model MQFVI

Submittal 30 [762] 36 [914] 40 [1016] 50 [1270] 60 [1524] 70 [1778]

GUIDE SPECIFICATIONS. ES Series R-410A

STR Circular VAV Terminal Units

Filtered Kitchen Supply Packaged Ventilator

500-YCI SERIES FAN-POWERED AIR TERMINAL UNIT FORM EG2 (404)

Product Data. AXIS 45X, 45U, 42K, 35BF Access Floor Terminal Units for Variable Air Volume Systems

Centrifugal Cabinet Fans Model BDF. Belt Drive Duct Fan

ELITE SERIES R-410A Ready - Multi-Position

Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS

Product Data. Features/Benefits. 35E Single Duct Terminal Units for Variable Air Volume Systems. Nominal 45 to 7100 cfm

Dual Duct Terminal Units DPS, DDS Series, DPQ, DDQ Series, DPV, DDV Series, DPM, DDM Series, DPUQ, DDUQ Series

Laboratory Room Single Duct Supply Air Terminal

Complete HVAC Capability

NV series. Induction VAV air volume control terminals

forward curved inline duct blowers

Dual Duct Variable Air Volume Terminal (Model TDS)

engineering guide TCS Series Fan-Powered, VAV Terminals

Air Handling Unit Construction Checklist

SECTION (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES


C2-2. Table of Contents DUAL DUCT TERMINAL UNITS

catalog SDR Single-Duct VAV Terminals

Terms. Direct Acting (DA) The action of a controller that increases its branch line pressure as the controlled variable increases

GUIDE SPECIFICATIONS CE Series Two Stage R-410A

Centrifugal Inline Fans Models SQ-M and BSQ-M. Direct and Belt Drive

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

IAQ. ROUND DUCT RETROFIT Model ARR

Products for Indoor Air Quality and Control

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

Inline Fans [ 14 ] * UL is optional and must be specified.

SECTION GENERAL-SERVICE AIR COMPRESSOR PART 1 - GENERAL

Submittal. Front View Side View

The Premium Quality Fan Coil Units for Horizontal Application Hydronic or Electric Heat

FCVC Series VERTICAL FAN COILS

catalog VFR Parallel Flow, Fan-Powered, 50/60 Hz VAV Terminals

IAQ. Model AVW. SINGLE DUCT w/hot WATER HEAT Model AVW

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

A. Product Data: For each type of product. TLC ENGINEERING FOR ARCHITECTURE - PROJECT NO AIR DUCT ACCESSORIES

SECTION DUST COLLECTOR

SECTION CENTRIFUGAL HVAC FANS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

SECTION COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

Fan Powered Low Profile Variable Volume Terminal Units

Transcription:

SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units, variable volume regulators, integral sound attenuation, integral heating coils, integral damper motor operators, integral controls. 1.2 REFERENCES A. NFPA 90A (National Fire Protection Association) - Installation of Air Conditioning and Ventilation Systems. B. UL 181 (Underwriters Laboratories, Inc.) - Factory-Made Air Ducts and Connectors. 1.3 SUBMITTALS A. Section 01 33 00 - Submittal Procedures: Submittal procedures. B. Product Data: Submit data indicating configuration, general assembly, and materials used in fabrication. Include catalog performance ratings that indicate airflow, static pressure, and NC designation. Include electrical characteristics and connection requirements. Include schedules listing discharge and radiated sound power level for each of second through sixth octave bands at inlet static pressures of 1 inch to 4 inches wg. C. Manufacturer's Installation Instructions: Submit support and hanging details, and service clearances required. D. Manufacturer's Certificate: Certify that products meet or exceed specified requirements. 1.4 CLOSEOUT SUBMITTALS A. Section 01 77 00 Closeout Procedures: Closeout procedures. B. Project Record Documents: Record actual locations of units, controls components and send a copy to Stanford Maps and Records. February 2018 Page 1 of 13 2018 FDG Section 23 36 00

C. Operation and Maintenance Data: Submit manufacturer's descriptive literature, operating instructions, maintenance and repair data, and parts lists. Include directions for resetting constant volume regulators. 1.5 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years documented experience. B. Installer: Company specializing in performing work of this section with minimum three years documented experience. 1.6 FIELD MEASUREMENTS A. Verify field measurements prior to fabrication. 1.7 WARRANTY A. Section 01 77 00 Closeout Procedures: Product warranties and product bonds. B. Provide 5 year manufacturer warranty for air terminal units. 1.8 EXTRA MATERIALS A. Section 01 77 00 Closeout Procedures. PART 2 - PRODUCTS 2.1 AIR TERMINAL UNITS A. Ceiling mounted variable air volume, constant volume, or fan powered supply air control terminals for connection to single or dual duct, central air systems, with pneumatic, electric, system powered, or electronic variable volume control, pneumatic or mechanical system powered constant volume control, hot water heating coils. B. Identify each terminal unit with clearly marked identification label and airflow indicator. Include unit nominal airflow, maximum factory-set airflow and minimum factory-set airflow and coil type. 2.2 SINGLE DUCT VARIABLE VOLUME UNITS A. Use Titus air terminals, VAV boxes, or equal, unless specified otherwise. B. Basic Assembly 1. Casings: Minimum 22 gage galvanized steel. February 2018 Page 2 of 13 2018 FDG Section 23 36 00

2. Lining: Minimum 1 inch thick neoprene or vinyl coated fibrous glass insulation, 1/5 lb./cu ft density, meeting NFPA 90A requirements and UL 181 erosion requirements. Face lining with 4 mil Mylar or Tedlar film. 3. Plenum Air Inlets: Round stub connections or S slip and drive connections for duct attachment. 4. Plenum Air Outlets: S slip-and-drive connections. C. Basic Unit: 1. Configuration: Air volume damper assembly inside unit casing. Locate control components inside protective metal shroud. 2. Volume Damper: Construct of galvanized steel with peripheral gasket and selflubricating bearings; maximum damper leakage: 2 percent of design air flow at 3 inches rated inlet static pressure. 3. Mount damper operator to position damper as indicated per design. D. Attenuation Section: Line attenuation sections with 2 inch thick insulation. E. Multi Outlet Attenuation Section: With 8 inch or less if design indicates diameter collars, each with butterfly balancing damper with lock. F. Round Outlet: Discharge collar matching inlet size. G. Hot Water Heating Coil: 1. Construction: ½ inch copper tube mechanically expanded into aluminum plate fins, leak tested under water to 200 psig pressure, factory installed. No spiral wound coils. 2. Capacity: Based on equal or less than 140 degree F entering water, equal or less 105 degree F leaving water. 3. Hydrostatic test with pressure gage positively pressurized for delivery. H. Electric Heating Coil: * Note: Allowed only where no other heat source is available and approved by Stanford University in writing. 1. Construction: UL listed, slip-in type, open coil design, integral control box factory wired and installed, with: a. Primary and secondary over-temperature protection. b. Minimum airflow switch. c. Pneumatic/electric switches and relays or Magnetic contactor for each step of control. February 2018 Page 3 of 13 2018 FDG Section 23 36 00

I. Automatic Damper Operator: Damper operators are Belimo for electric and Johnson Control or Honeywell for Pneumatic unless approved otherwise in writing by Stanford Engineer. 1. Electric Actuator: 24 volt with high limit with remote temperature read and reset capability. 2. Pneumatic Damper Operator: 8-13 or 3-13 spring range depending on design with pilot positioner. 3. Maximum Volume Controller and Probe: Pneumatic, with calibration pressure taps for high flow limited proportional variable-air-volume control. 4. Velocity Reset Controller and Probe: a. Pneumatic. b. Calibration pressure taps for pressure independent control to compensate for varying inlet static pressure. c. Minimum and maximum limits set at reset device. d. Maintain airflow to within 5 percent of set point with inlet static pressure variations up to 2 inches. e. Reset span, fixed at 5 psi or adjustable3 to 8 psi shall remain constant regardless of minimum or maximum setting. Reset start point shall be adjustable from 3-10 psi. J. Thermostat: Wall-mounted pneumatic Honeywell two-pipe, Wall-mounted electric or Electronic type with appropriate mounting hardware. K. Four Pipes VAV Drain Pan 1. Sealed double wall insulated drain pans constructed of minimum 18 gauge; cross break interior pans and pitch toward drain connections to ensure complete condensate drainage. Units with cooling coils shall have drain pans under complete galvanized steel exterior pans and 304 stainless steel interior pans. Encase manufacturer's standard insulation between exterior and interior walls. Drain pans shall be sloped in cooling coil section. All drain pan connections will be to the side of the unit to enable proper trapping. 2. Secondary drain pan with overflow pipe. 2.3 DUAL DUCT VARIABLE VOLUME UNITS A. Use suitable Titus model, or equal, unless otherwise approved in writing by Stanford engineer. B. Basic Assembly: February 2018 Page 4 of 13 2018 FDG Section 23 36 00

1. Casings: Minimum 22 gage galvanized steel. 2. Lining: Minimum 1 inch thick neoprene or vinyl coated fibrous glass insulation, 1.5lb/cu ft density, meeting NFPA 90A requirements and UL 181 erosion requirements. Face lining with 4 mil Mylar or Tedlar film. 3. Plenum Air Inlets: Round stub connections or S slip and drive connections for duct attachment. 4. Plenum Air Outlets: S-slip and drive connections. C. Basic Unit: 1. Configuration: Two air volume dampers inside unit casing with mixing attenuation section as required by design. Locate control components inside protective metal shrouds. 2. Volume Dampers: Construct of galvanized steel with peripheral gasket and selflubricating bearings; maximum damper leakage: 2 percent of design air flow at 3 inches rated inlet static pressure. 3. Mount damper operators to position dampers normally open or normally closed as indicated by design. D. Automatic Damper Operator: Belimo, Honeywell, or Johnson Controls unless otherwise approved 1. Electric Actuator: 24 volt with high limit and with remote temperature read and reset capability. 2. Pneumatic Damper Operator: 8-13 or 3-13 psig spring range as design dictates. 3. Velocity Reset Controller and Probe: a. Pneumatic. b. Calibration pressure taps for pressure independent control to compensate for varying inlet static pressure. c. Minimum and maximum limits set at reset device. d. Maintain airflow to within 5 percent of set point with inlet static pressure variations up to 2 inches. e. Reset span, fixed at 5 psi or adjustable 3 to 8 psi shall remain constant regardless of minimum or maximum setting per design. Reset start point shall be adjustable from 3-10 psi. E. Thermostat: Wall-mounted pneumatic, Wall-mounted electric or Electronic type with appropriate mounting hardware. F. Control Sequence: February 2018 Page 5 of 13 2018 FDG Section 23 36 00

1. Cooling damper to be normally open or closed based on application. 2. Modulate cold damper closed as warm damper opens. Provide for dual-duct constant volume operation. 3. Sequence so warm damper actuator may be field adjusted to start opening simultaneous with closing of cold damper or delayed until up to 10 degrees F change in room temperature after cold damper has closed. 4. Sequence pneumatic operators with spring ranges selected so warm damper begins to open after cooling damper has fully closed. 5. Provide pneumatic pressure independent controls or high limit controls for control of both warm and cold damper, factory calibrated for maximum airflow. 2.4 FAN POWERED VARIABLE VOLUME UNITS A. Basic Assembly: 1. Casings: Minimum 22 gage galvanized steel. 2. Lining: Minimum 1 inch thick neoprene or vinyl coated fibrous glass insulation, 1/5 lb./cu ft density, meeting NFPA 90A requirements and UL 181 erosion requirements. Face lining with 4 mil Mylar or Tedlar film. 3. Plenum Air Inlets: Round stub connections and S slip and drive connections for duct attachment. 4. Plenum Air Outlets: S-slip and drive connections. B. Basic Unit: 1. Configuration: Air volume damper assembly and fan in series or parallel arrangement inside unit casing per design. Locate control components inside protective metal shroud. 2. Volume Damper: Construct of galvanized steel with peripheral gasket and selflubricating bearings; maximum damper leakage: 2 percent of design air flow at 3 inches rated inlet static pressure. 3. Mount damper operator to position damper normally open or normally closed as indicated by design. C. Automatic Damper Operator: 1. Electric Actuator: 24 volt with high limit with remote temperature read and reset capability. 2. Pneumatic Damper Operator: 8-13 or 3-13 psig spring range per design. 3. Maximum Volume Controller and Probe: Pneumatic, with calibration pressure taps for high flow limited proportional variable-air volume control. 4. Velocity Reset Controller and Probe: February 2018 Page 6 of 13 2018 FDG Section 23 36 00

D. Fan Assembly Stanford University Facilities Design Guidelines a. Pneumatic. b. Calibration pressure taps for pressure independent control to compensate for varying inlet static pressure. c. Minimum and maximum limits set at reset device. d. Maintain airflow to within 5 percent of set point with inlet static pressure variations up to 2 inches. e. Reset span, fixed at 5 psi or adjustable 3 to 8 psi shall remain constant regardless of minimum or maximum setting. Reset start point shall be adjustable from 3-10 psi. 1. Fan: Forward curved centrifugal type with direct drive permanent-splitcapacitor type, thermally protected motor. 2. Speed Control: Infinitely adjustable with electric/pneumatic and electronic controls. 3. Isolation: Fan/motor assembly on rubber isolators. E. Attenuation Section: Line attenuation sections with 2 inch thick insulation. F. Hot Water Heating Coil: 1. Construction: ½ inch copper tube mechanically expanded into aluminum plate fins, leak tested under water to 200 psig pressure, factory installed. No spiral wound coils allowed. 2. Capacity: Based on 140 degree F entering water, equal or less 105 degree F leaving water.. G. Electric Heating Coil: 1. Construction: UL listed, slip-in type, open coil design, integral control box factory wired and installed, with: a. Primary and secondary over-temperature protection. b. Minimum airflow switch. c. Pneumatic/electric switches and relays or Magnetic contactor for each step of control. d. Electric heating coils only allowed in no other source of heating is available. February 2018 Page 7 of 13 2018 FDG Section 23 36 00

H. Wiring 1. Factory mounted and wire controls. Mount electrical components in control box with removable cover. Incorporate single point electrical connection to power source. 2. Factory mounted transformer for control voltage on electric and electronic control units. Provide terminal strip in control box for field wiring of thermostat and power source. 3. Wiring Terminations: Wire fan and controls to terminal strip. Provide terminal lugs to match branch-circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box. 4. Disconnect Switch: Factory mount fused disconnect switch in control panel or on equipment. I. Controls: 1. Pneumatic, Electric or Electronic Controls: Contain in NEMA-1 enclosure with access panel sealed from airflow and mounted on side of unit. Factory mounted controls and thermostat to accomplish the following specified sequence of operation. 2. Electronic Control, Central System Fan "On" - Occupied Mode: a. When duct pressure is sensed indicating primary air system operating, thermostat and primary variable volume damper proportions air flow from central system. b. As thermostat senses reduced cooling demand, volume damper closes. At field adjustable point, unit fan is energized. c. If central duct system pressure varies, volume damper maintains constant primary airflow. d. As thermostat senses no cooling requirement, control system closes volume damper. Before heating is initiated, control enters field adjustable no load band. On sensing need for heat, heating coil is energized proportionally. 3. Electronic Control, Central System Fan "Off" - Unoccupied Mode: a. Provide field adjustable temperature setback. On need for heat, terminal unit fan and heating coil are energized. b. Hold volume damper closed. 4. Pneumatic/Electric Control, Central System Fan "On" -Occupied Mode: February 2018 Page 8 of 13 2018 FDG Section 23 36 00

a. As thermostat senses cooling, volume damper proportions airflow from central system. b. As thermostat senses less cooling and damper closes, pneumatic/electric or damper position switch energizes fan per design. c. Electronic fan speed control manually adjusts maximum fan speed to match downstream resistance. d. Velocity reset primary air control (pressure independent) with maximum and minimum limits. e. Hi-limit device, factory set, limits maximum primary airflow. f. As thermostat senses no cooling, control system closes volume damper to stop flow from central-system primary air duct before heating is initiated. On sensing further need for heat, heating coil is energized. 5. Pneumatic/Electric Control, Central System Fan "Off" - Unoccupied Mode: a. Thermostat cycles fan. b. Day/night thermostat cycles fan and controls at reduced temperature. J. Thermostat: Wall-mounted pneumatic, Wall-mounted electric or Electronic type with appropriate mounting hardware. K. Four Pipes VAV Drain Pan 1. Sealed double wall insulated drain pans constructed of minimum 18 gauge; cross break interior pans and pitch toward drain connections to ensure complete condensate drainage. Units with cooling coils shall have drain pans under complete galvanized steel exterior pans and 304 stainless steel interior pans. Encase manufacturer's standard insulation between exterior and interior walls. Drain pans shall be sloped in cooling coil section. All drain pan connections will be to the side of the unit to enable proper trapping. 2. Secondary drain pan with overflow pipe. 2.5 MECHANICAL TYPE VARIABLE VOLUME UNITS A. Basic Assembly: 1. Casings: Minimum 22 gage galvanized steel; maximum casing leakage: 3 percent of design air flow at 6 inches minimum inlet static pressure. February 2018 Page 9 of 13 2018 FDG Section 23 36 00

2. Lining: Minimum 1 inch thick neoprene or vinyl coated fibrous glass insulation, 1.5lb./cu ft density, meeting NFPA 90A requirements and UL 181 erosion requirements. Face lining with 4 mil Mylar or Tedlar film. 3. Plenum Air Inlets: Round/oval stub connections or S slip and drive connections for duct attachment. 4. Plenum Air Outlets: S-slip and drive connections. B. Basic Unit: 1. Configuration: Air volume damper assembly and control components inside unit casing. 2. Volume Damper: Construct of galvanized steel with peripheral gasket and selflubricating bearings; maximum damper leakage: 2 percent of design air flow at 3 inches rated inlet static pressure. 3. Mount damper operator to position damper normally open or normally closed as indicated. C. Regulator: 1. Location: Air volume damper and automatic flow control assembly inside unit casing. 2. Construction: Extruded aluminum or 20 gage galvanized steel components; key damper blades into shaft with nylon fitted pivot points. 3. Automatic flow control assembly: Combine spring rates matched for each volume regulator size with machined dashpot for stable operation. 4. Air volume control damper shall be factory- calibrated assembly consisting of damper and damper shaft extension for connection to externally mounted control actuator. 5. Internally mounted pneumatic or electric actuator with pilot positioner: Position damper normally open or normally closed as indicated. D. Multi Outlet Adapter Section: With 8 inch diameter collars, each with butterfly balancing damper with lock. E. Hot Water Heating Coil: 1. Construction: ½ inch copper tube mechanically expanded into aluminum plate fins, leak tested under water to 200 psig pressure, factory installed. No spiral wound coils allowed. 2. Capacity: Based on 140 degree F entering water, equal or less 105 degree F leaving water. F. Electric Heating Coil: February 2018 Page 10 of 13 2018 FDG Section 23 36 00

1. Construction: UL listed, slip-in type, open coil design, integral control box factory wired and installed, with: a. Primary and secondary over-temperature protection. b. Minimum airflow switch. c. Pneumatic/electric switches and relays or Magnetic contactor for each step of control. G. Automatic Damper Operator: 1. Electric Actuator: 24 volt with high limit with remote temperature read and reset capability. 2. Pneumatic Damper Operator: 8-13 or 3-13 psig spring range per design. H. Thermostat: Wall-mounted pneumatic, Wall-mounted electric or Electronic type with appropriate mounting hardware. 2.6 SYSTEM POWERED VARIABLE VOLUME UNITS A. Basic Assembly: 1. Casings: Galvanized steel. 2. Lining: Minimum ½ inch thick neoprene or vinyl coated fibrous glass insulation, 1.5 lb/cu ft density, meeting NFPA 90A requirements and UL 181 erosion requirements. Face lining with 4 mil Mylar or Tedlar film. 3. Plenum Air Inlets: Round/oval stub connections. 4. Plenum Air Outlets: S-slip and drive connections. B. Basic Unit: 1. Configuration: Air volume damper and automatic flow control assemblies inside unit casing. 2. Volume Damper: Construct of galvanized steel with peripheral gasket and selflubricating bearings. C. Regulator Assembly: System-air powered bellows section incorporating polypropylene bellows for volume regulation and thermostatic control. Polypropylene material shall perform at temperatures of 0 to 140 degrees F and be impervious to moisture and fungus. Design bellows for 10 inches static pressure and factory check for leaks. D. Multi Outlet Attenuation Section: With 8 inch diameter collars, each with butterfly balancing damper with lock. E. Hot Water Heating Coil: February 2018 Page 11 of 13 2018 FDG Section 23 36 00

1. Construction: ½ inch copper tube mechanically expanded into aluminum plate fins, leak tested under water to 200 psig pressure, factory installed. No spiral wound coil allowed. 2. Capacity: Based on 140 degree F entering water, equal or less 105 degree F leaving water. F. Electric Heating Coil: 1. Construction: UL listed, slip-in type, open coil design, integral control box factory wired and installed, with: G. Controls: a. Primary and secondary over-temperature protection. b. Minimum airflow switch. c. Pneumatic/electric switches and relays or Magnetic contactor for each step of control. 1. Suitable for operation with duct pressures between 0.25 and 3.0 inches (60 and 750 Pa) static pressure. 2. Mount controls in sheet metal enclosure on unit. 3. Factory mounted and piped 5-micron filter, velocity resetting adjustable high limit control and amplifying relay. 4. System powered aspirating diffuser or wall mounted thermostat. 5. Limit switch shall activate heating system. 6. Provide morning warm up control to sense duct temperature and control unit at maximum airflow during heating mode. PART 3 - EXECUTION 3.1 EXAMINATION A. Verify ductwork is ready to receive work. 3.2 INSTALLATION A. Provide ceiling access doors or locate units above easily removable ceiling components. B. Support units individually from structure. Do not support from adjacent ductwork. C. Provide minimum of 5 ft of 2 inch thick lined ductwork downstream of units. February 2018 Page 12 of 13 2018 FDG Section 23 36 00

3.3 ADJUSTING A. Section 01 77 00 Closeout Procedures: Testing, adjusting, and balancing. B. Reset volume with damper operator attached to assembly allowing flow range modulation from 100 percent of design flow to 0 percent full flow. Set units with heating coils for minimum 0 percent full flow. END OF SECTION February 2018 Page 13 of 13 2018 FDG Section 23 36 00