Bulk storage and handling of solvents and coalescents

Similar documents
Eastman plasticizers. Bulk storage guidelines. Storage equipment. Tank components and materials. Piping. Pumps. Valves. Gaskets

Bulk Storage and Handling of Isobutyronitrile and n-butyronitrile

Bulk storage and handling of Eastman acetaldehyde

Lower coatings costs. with Eastman Texanol ester alcohol or Eastman Optifilm enhancer 300. Data

Eastman TMPD Glycol and Purified Isophthalic Acid

THERMINOL LT. heat transfer fluid. Wide temperature range, liquid/vapor phase fluid to 315 C. (--103 to 600 F)

THERMINOL 68. heat transfer fluid. High-temperature, low-viscosity fluid. -26 to 360 C. ( 14 to 680 F)

THERMINOL 72. heat transfer fluid. High temperature, excellent stability at medium pressure. -14 to 380 C. (7 to 715 F)

THERMINOL RD. heat transfer fluid. Low-viscosity, medium-temperature fluid. -36 to 270 C. (--33 to 520 F)

THERMINOL 75. heat transfer fluid. Ultrahigh temperature at low pressure. 80 to 385 C. (175 to 725 F)

THERMINOL VP-3. heat transfer fluid. High-temperature, low-odor, vapor/liquid phase fluid. 2 to 330 C. (36 to 625 F)

Eastman specialty ketones Enabling low-voc refinish coatings

THERMINOL 55. heat transfer fluid. Efficient, reliable mediumtemperature-range. -28 to 290 C. (--18 to 550 F)

THERMINOL 62. heat transfer fluid. High performance under low-pressure applications. -23 to 325 C. (--9 to 620 F)

THERMINOL 54. heat transfer fluid. Efficient, reliable mediumtemperature-range. 28 to 280 C. (- 18 to 540 F)

THERMINOL 66. heat transfer fluid. Proven performance for high-temperature, low-pressure applications. -3 to 345 C. (27 to 650 F)

Polypropylene Piston Drum Pumps

PENBERTHY MODELS GL AND GH GAS OPERATED JET PUMPS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

The performance to compete. The versatility to comply.

FLEX-ING TM DISPENSER HOSES INSTALLATION GUIDE

RECYCOIL Used Oil Tank

Installation Instructions

Martin Tornado Retrofit Valve

Summaries for Gasoline Distribution Facilities and Gasoline Dispensing Facilities 40 CFR 63 subpart BBBBBB and 40 CFR 63 subpart CCCCCC

SPILL PREVENTION CONTROL AND COUNTERMEASURES PLAN (SPCCP) FOR FUELING AT STATION 63

RULE 448 GASOLINE TRANSFER INTO STATIONARY STORAGE CONTAINERS Adopted (Amended , , , , , ) INDEX

BIG BLASTER XHV Air Cannon Retrofit with MARTIN TORNADO Exhaust Valve

Crosby Style JQ Pressure Relief Device. Flow Control

ANSI Z50.1. Safety Standards

Code Requirements for ASTs at Motor Vehicle-Dispensing Stations

n-butyric Anhydride n-butanoic acid anhydride CAS no EC no

-5 F to 620 F. High Performance, Low-pressure Heat Transfer Fluid. Heat Transfer Fluid by Solutia. Technical Bulletin A +400 C +700 F +350 C

ANDERSON GREENWOOD. Flow Control. Anderson Greenwood Tank and Equipment Blanketing Systems. Pad Valves. De-Pad Valves. Total Flow Control Solutions

PROCEDURE FOR THE HANDLING OF FUEL ON CONSTRUCTION SITES. Civil Engineering Sector Labour-Management Health and Safety Committee

Fueltec Models 950AW & 955SS Mobile Fuel Tank Cleaning Systems

1) Activity Description: Management of Petroleum Storage Tanks and Containers

Fire & Rescue District

2-in-1 Air Operated Waste Oil Drainer

AQUATOR Commercial Oil Water Separator Operating, Installation & Maintenance Manual

ARALDITE AV 8574 Resin Hardener HV 8574

OPERATIONS MANUAL MODEL MT-500

UV PROCESS SUPPLY, INC. CON-TROL-CURE ½ DIAPHRAGM PUMP INSTRUCTION MANUAL PART # J

Crosby Style JQ pressure relief device

Defender Series. Overfill Prevention Valve. Automatic Shutoff for USTs. Installation, Operation and Maintenance Series

PEI/RP Recommended Practices for Installation of Bulk Storage Plants

MATERIAL SAFETY DATA SHEET

HURRICANE 300 INSPECTION/MAINTENANCE MANUAL. N7959 BIRCH ROAD IXONIA, WI FAX:

OWS OPERATIONS & MAINTENANCE

Solutions beyond products...

FLEX CONNECTOR HEAT SHRINK SLEEVE INSTALLATION GUIDE

Air Operated Diaphragm Pumps Operating and Maintenance Instructions

RIGID ENTRY BOOT INSTALLATION GUIDE

LOADING OF ORGANIC LIQUID CARGO VESSELS. (Adopted 10/13/1992, revised 1/18/2001)

APPLICATION for BUSINESS LICENSE Licensing & Permits City of Williston PO Box 1306, Williston, ND

Micro Motion F-Series Coriolis Flow and Density Sensors. Installation Manual , Rev CC December 2010

Cast Iron Rotary Drum Pump

Material Safety Data Sheet

Environmental Management System

INSTALLATION GUIDE FUELTEC- FUEL POLISHING SYSTEM

DIESEL EXHAUST FLUID PUMP MOTOR ASSEMBLY REPLACEMENT GUIDE

Code Requirements for ASTs at Motor Vehicle-Dispensing Stations

OWNER S MANUAL PRODUCT CODE: BOD1907

Installation and Maintenance Manual for the Lock Down Hatch for the Gauge Hatch Model L61T

Environmental Standard Operating Procedure (ESOP) Originating Office: Natural Resources and Environmental Affairs (NREA) Office

Installation, Operation and Maintenance Manual for Pressure/Vacuum Relief Valves

VARIFUEL MAINTENANCE AND REPAIR INSTRUCTIONS

WHY DO YOU NEED FOAM?

40 CFR 63, Subpart CCCCCC

1. All aircraft fueling equipment shall have a Filter/Separator or a Full-Flow Fuel Monitor.

Hydrogen Peroxide Horizontal Storage Tank

Installation Instructions

289 Series Relief Valves

ANTI-SYPHON VALVE INSTALLATION GUIDE

Earth-Rite MGV Mobile Grounding Verification. White Paper. Author Details: Page 1 of 5

MATERIAL SAFETY DATA SHEET MSDS009. Ultralife Batteries, Inc Technology Parkway Newark, NY

Types and 52.20, Specialized test procedure Milk receiving and milk pick-up metering systems

Installation and Maintenance Manual CEMLINE CORPORATION

Installation & Operation Manual. IMPORTANT: This manual contains important information. READ AND KEEP FOR REFERENCE.

AUTOGAS 150 SERIES PUMPS INSTALLATION GUIDELINES FOR UNDERGROUND TANK APPLICATIONS

Western Plant Health Association Anhydrous Ammonia Facility / Field Tank Safety Self Inspection Safety Checklist Form

VARIFUEL MAINTENANCE AND REPAIR INSTRUCTIONS

Powered Industrial Trucks

Product overview. Technical data

SECTION FUEL-OIL DISTRIBUTION (APPLIES TO FUEL TANKS FOR GENERATORS)

Material Safety Data Sheet

Installation and Maintenance Manual CEMLINE CORPORATION

S v S e r i e s F M f i r e e x t i n g u i s h i n g s y s t e m

C2000, Mirror Glaze Professional Detailing Clay (Mild) Meguiar's, Inc. Meguiar's. EMERGENCY PHONE: CHEMTREC (24 hours)

MERIDIAN, 2 or 3 PIECE, TRUNNION MOUNTED BALL VALVES

THERMINOL D-12. heat transfer fluid. Low-odor, FDA-grade, NSF-registered cooling/heating fluid. -94 to 230 C. (--137 to 450 F)

AQUATOR Commercial Oil Water Separator Operating, Installation & Maintenance Manual

SAFETY DATA SHEET. 1. Company Identification. 2. Product Information

Stainless Steel Rotary Drum Pump

LIQUEFIED GAS PUMP INSTALLATION

Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators

Air-Operated Waste Oil Drainer

ATD Gallon Pressurized Oil Drain Owner s Manual

Air-Operated Double-Diaphragm Pump

ENGINEERING STANDARD FOR MACHINERY PIPING

DIESEL EXHAUST FLUID PUMPING ACCESSORIES INSTALLATION GUIDE

Transcription:

Bulk storage and handling of solvents and coalescents Introduction This publication provides information for solvent storage, tank construction materials, and unloading tank cars and tank trucks containing Eastman solvents and coalescents. The discussion and drawings are given as information only and should be used solely as a guide in developing procedures and facilities for handling these materials. Customers must determine for themselves the appropriate procedures and facilities for their operations. The information in this publication, along with the data and information contained in Eastman s Safety Data Sheets (SDS), needs to be reviewed and understood to help ensure the safe storage and handling of Eastman solvents and coalescents. It is the customer s responsibility to direct and control the unloading of any chemical or material into or from bulk storage and handling facilities. Federal, state, and local regulations regarding the handling and storage of chemicals may vary widely in the United States. The Federal Occupational Safety and Health Administration (OSHA), Environmental Protection Agency (EPA), National Fire Protection Association (NFPA), and a user s insurance company also impose safety standards. In addition, the U.S. Department of Transportation (DOT) prescribes rules and regulations for unloading hazardous materials from tank cars and tank trucks (see 49 CFR 100-199). Knowledge of these and other appropriate federal and state laws and regulations as well as consultation with the proper authority should provide guidance for developing adequate handling procedures and constructing appropriate storage and drumming facilities. Neither Eastman Chemical Company nor its marketing affiliates shall be responsible for the use of this information, or of any product, method, or apparatus mentioned, and you must make your own determination of its suitability and completeness for your own use, for the protection of the environment, and for the health and safety of your employees and purchasers of your products. No warranty is made of the merchantability or fitness of any product, and nothing herein waives any of the Seller s conditions of sale. Storage equipment Tank construction and facilities for tank car and tank truck handling of Eastman solvents and coalescents are described and illustrated in this publication. The drawings and discussions are given as information only and should be used solely as a guide in storing and handling these products. Customers must determine for themselves the appropriate procedures and facilities for their storage and handling operations. Figure 1 is a schematic drawing of a typical storage tank. For the location, fabrication, installation, inspection, and testing of solvent storage tanks, the designer should refer to appropriate standards including the following: ASME Boiler Pressure Code, Sect. VIII, Div. 1 API Standard 510 American Petroleum Institute Inspection Codes API Standard 570 Inspection, Repair, Alteration, and Rerating of In-Service Piping API Standard 620 Rules for Design and Construction of Large, Welded, Low-Pressure Storage Tanks API Standard 650 Welded Steel Tanks for Oil Storage API Standard 653 Tank Inspection, Repair, Alteration, and Reconstruction API Standard 2000 Venting Atmospheric and Low- Pressure Storage Tanks 29 CFR 1910.106 Flammable and Combustible Liquids NFPA 30 Flammable and Combustible Liquids Code 1

Figure 1 Storage tank Nitrogen or inert gas blanketing system Emergency pressure/vacuum relief Measuring nozzle Vacuum Vent to atmosphere or vapor recovery device via open pipe, conservation vent or flame arrestor as appropriate Pressure To vapor recovery device 1 /2-in. (13-mm) antisiphon hole Fill and recirculate line Fill line 20-in. Manhole To process From tank car or tank trailer Liquid level gauge or level transmitter Tank hold-down lug Sloped bottom Ground cable Centrifugal pump Note: A leak detection system with provisions for secondary containment away from tanks or equipment is recommended. Bonding and grounding are important to prevent the accumulation of static electricity and provide for its safe discharge. Bonding and grounding are required for all equipment, piping, tank cars, tank trailers, and interconnections. Designers should refer to the appropriate standards including the following: API Standard RP 2003 Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents NFPA 77 Recommended Practice on Static Electricity For maintenance of storage tanks and relief devices, it is recommended that the customer establish a schedule for the inspection of the tanks, relief devices, and piping on a regular basis. Tank construction materials The basic construction material suggested for tank storage of Eastman solvents and coalescents is stainless or carbon steel. To reduce corrosion of the tank bottom exterior, a coating should be applied between the tank and foundation. Piping The lines used for transferring solvents and coalescents into and away from the tank may be stainless or carbon steel. Carbon steel lines may cause contamination from rust. The lines should have as few flanged connections as possible. Pumps For solvent transfer, stainless steel centrifugal or positivedisplacement pumps with mechanical seals instead of packing glands are suggested. Where suction lift is needed, a centrifugal pump should not be used unless specifically designed for that purpose. Valves Ball and plug valves with Teflon 1 plastic (or equivalent PTFE 2 ) seats, sleeves, and packing should be considered for solvent transfer lines. Gaskets CycleTite 3 or Teflon plastic (or equivalent PTFE) gaskets should be considered for use with solvents and coalescents. 1 DuPont 2 Poly(tetrafluoroethylene) 3 CycleTite 2

Vents If environmental laws and regulations of federal, state, and local agencies permit, tank vents may be open to the atmosphere. The vents should be angled at 45 from vertical and cut off vertically to prevent rain from entering. It is recommended that solvent storage tanks be provided with a blanket of inert gas or nitrogen and equipped with a pressure/vacuum conservation vent valve piped away to a safe location. Refer to 29 CFR 1910.106 for some federal requirements relative to flammable and combustible liquids. It is recommended that combustible solvents and coalescents handled at or above their flash points be treated as if they were flammable solvents and coalescents. Handling The method of unloading will depend on the customer s equipment. Figures 2, 3, and 4 show typical unloading facilities for transferring solvents and coalescents from tank car to storage tank. All tank trailers and tank cars should be vented or pressurized with inert gas when unloading. Figure 5 illustrates possible arrangements of equipment for tank trailer unloading. The contents may be unloaded by using a pump supplied by the customer Bulk unloading Tank fill line The tank fill line should extend to within 2 to 3 inches of the bottom of the tank to help inhibit the accumulation of static charges. Figure 2 Tank car top unloading fixed piping with swivel joints Vapor balance return or inert gas supply for flammable liquid or vent for combustible liquid Tank car Ground lines Flanged ball valves (on car) 3 in. (7 mm) and 2 in. (51 mm) for 20,000-gal. car, 2 in. (51 mm) and 1 in. (25 mm) for 10,000-gal. car Flexible metal hose Fixed well line in car Swivel joint Vacuum breaker valve Swivel joint To storage tank Wheel chocks Safety warning sign Self-priming centrifugal or positive-displacement pump 3

Figure 3 Tank car top unloading flexible hose with flanged elbow Ground lines Vapor balance return or inert gas supply for flammable liquid or vent for combustible liquid Vacuum breaker valve Swivel joint Tank car Safety warning sign Flanged ball valves (on car) 3 in. (76 mm) and 2 in. (51 mm) for 20,000-gal. car, 2 in. (51 mm) and 1 in. (25 mm) for 10,000-gal. car Fixed well line in car Swivel joint To storage tank Wheel chocks Flexible metal hose Self-priming centrifugal or positive-displacement pump Figure 4 Tank car top unloading removable well pipe with swivel joints Tank car Swivel joint Ground lines Safety warning sign Manhole, 18 or 20 in. (457 or 508 mm) Swivel joint Wheel chocks Removable well pipe To storage tank Self-priming centrifugal or positive-displacement pump 4

The following procedures for unloading tank cars and tank trailers are for information only. The comprehensive United States Department of Transportation (DOT) regulations should also be consulted and observed. It is the customer s responsibility to be aware of and comply with all laws and regulations governing the unloading of tank cars and tank trucks. Eastman solvents and coalescents are shipped in steel, aluminum, or stainless steel tank cars and/or stainless steel and aluminum tank trailers. The usual tank car sizes are 10,000, 20,000, and 30,000 gallons. Tank trailer sizes vary between 4,000 and 6,500 gallons. Compartmented tank trailers or tank cars are available for delivery of mixed loads. The unloading area should be provided with an emergency containment and drainage system to direct the contents of the delivery vehicle to a safe location other than the sanitary sewer or surface waters in the event of a spill. Also, a vapor return can be used to comply with Environmental Protection Agency (EPA) venting requirements. A properly designed system utilizing vapor return can be used to reduce vapor generation and increase recovery of solvents and coalescents. It is also recommended that a nitrogen or inert gas blanket be used during loading or unloading of materials at or above their flash points. Tank car unloading Unloading operations must be performed in accordance with 49 CFR 174.67. It is recommended that tank cars be unloaded from the top, making it easier to shut off the flow if a transfer line leaks or ruptures. This helps minimize the chance of an accidental discharge. Figures 2 through 4 show several unloading arrangements for tank cars. In Figures 2 and 3, the unloading lines are connected to the fixed well line in the car. This arrangement provides a more nearly closed system and minimizes personnel exposure. The unloading method shown in Figure 4 involves lowering a well pipe through the open manhole of the car. For top unloading, an approach platform is suggested. Typical unloading procedure for tank cars 1. Read storage tank liquid level gauge, record reading, convert inventory to gallons, and make certain that tank will accept contents of tank car. 2. Spot tank car at unloading station and set hand brake. Apply chocks to wheels to help prevent movement of car in either direction. Position warning sign on each side of car along rails and, if necessary, attach derailing device to rails or lock switch to spur track involved. 3. Attach a ground wire to tank car. 4. Read and record tank car number, numbers on metal tape seals located at various openings on car, and product identification tags on manhole and bottom outlet. If these do not agree with information in shipping papers, check with shipper before unloading. 5. Depending on type of unloading facilities, connect flexible stainless steel or chemical rubber hose to outlet valve on car, or lower well pipe through manhole. 6. Make certain car is vented. For top unloading through flexible well line, open smaller ball valve next to unloading line. For bottom unloading, prop open manhole cover on car a few inches. For flammable material, start inert gas purge. 7. Open all valves in transfer line between tank car and bulk storage tank. Start pump and immediately check transfer line for leaks. 8. Check liquid level gauge on storage tank to ensure liquid is being transferred. 9. When tank car is empty, stop pump and close valves on car. Close valves in transfer line. For flammable material, stop inert gas purge. 10. Disconnect flexible hose or raise well pipe. Walk all flexible hoses into proper catch containers, ensuring no product is lost onto the ground. Collect the drainings for proper waste disposal. Close up car to its original condition as required by DOT regulations. Remove chocks, warning signs, derails, and switch locks. 11. Read storage tank liquid level gauge and record reading. 5

Tank trailer unloading A cargo tank must be attended by a qualified person designated by the customer at all times during unloading in accordance with 49 CFR 177.834(2). Tank trailer unloading connections (Figure 5) show the liquid being unloaded through a stationary pump. Figure 5 Tank trailer unloading stationary pump Inert gas supply for flammable liquid or vent for combustible liquid Steel or aluminum tank trailer Chocks To storage tank Flexible hose (on trailer) Centrifugal pump 3-in. (76-mm) female quickconnect fitting on pump outlet Typical unloading procedure for tank trailers 1. Read storage tank liquid level gauge, record reading, convert inventory to gallons, and make certain that tank will accept contents of tank trailer. 2. Position tank trailer at unloading station and set hand brake. Apply chocks to trailer wheels to help prevent movement in either direction. 3. Attach a ground wire to tank truck. 4. Read and record tank trailer number, numbers on seals located on various openings on trailer, and product identification tags on manhole and bottom outlet. If these do not agree with information on shipping papers, check with shipper before unloading. 5. Connect flexible stainless steel or chemical rubber hose to tank trailer outlet and to quick-connect fitting on inlet of customer s pump (Figure 5). 6. Make certain flexible hose is connected correctly. Open valves in line between trailer and storage tank. Open dome lid or vent valve. For flammable liquids, start inert gas purge. Proceed with unloading. 7. Open trailer manual outlet valve and trailer hydraulic outlet valve. Advise that customer s pump may be started. 8. Check transfer lines for leaks. Check storage tank liquid level gauge to ensure liquid is being transferred. 9. When tank trailer is empty, close hydraulic outlet valve, stop pump and close trailer manual outlet valve. For flammable liquids, stop inert gas purge. Close dome lid or trailer vent valve. Close valves in transfer line. 10. Disconnect and walk all hoses into proper catch containers, ensuring no product is lost onto the ground. Collect the drainings for proper waste disposal. 11. Secure all manholes, valves, closures in closed position and verify no leaks. 12. Remove chocks from trailer wheels. 13. Read storage tank liquid level gauge and record reading. 6

Safety precautions Information A Safety Data Sheet (SDS) providing toxicity information, physical and chemical data, and spill and emergency response information is available for each Eastman solvent. The user should review this publication before undertaking to handle, store, or use any Eastman solvent. For copies, contact your Eastman representative. Protective clothing Protective clothing such as gloves, goggles, face shields, boots, and aprons appropriate for the chemical being handled should be readily available and should be worn by personnel involved in the handling operation. Consult the SDS for recommended practices. Technical assistance If you have questions concerning the handling of Eastman solvents and coalescents, contact your Eastman representative. The information in this publication, along with the data and information contained in Eastman s Safety Data Sheets, needs to be reviewed and understood to help ensure the safe handling of Eastman solvents and coalescents. It is the customer s obligation to direct and control unloading of any chemicals or materials into or from bulk storage and handling facilities. 7

Eastman Chemical Company Corporate Headquarters P.O. Box 431 Kingsport, TN 37662-5280 U.S.A. Telephone: U.S.A. and Canada, 800-EASTMAN (800-327-8626) Other Locations, (1) 423-229-2000 Fax: (1) 423-229-1193 Eastman Chemical Latin America 9155 South Dadeland Blvd. Suite 1116 Miami, FL 33156 U.S.A. Telephone: (1) 305-671-2800 Fax: (1) 305-671-2805 Eastman Chemical B.V. Fascinatio Boulevard 602-614 2909 VA Capelle aan den IJssel The Netherlands Telephone: (31) 10 2402 111 Fax: (31) 10 2402 100 Eastman (Shanghai) Chemical Commercial Company, Ltd. Jingan Branch 1206, CITIC Square No. 1168 Nanjing Road (W) Shanghai 200041, P.R. China Telephone: (86) 21 6120-8700 Fax: (86) 21 5213-5255 Eastman Chemical Japan Ltd. MetLife Aoyama Building 5F 2-11-16 Minami Aoyama Minato-ku, Tokyo 107-0062 Japan Telephone: (81) 3-3475-9510 Fax: (81) 3-3475-9515 Eastman Chemical Asia Pacific Pte. Ltd. #05-04 Winsland House 3 Killiney Road Singapore 239519 Telephone: (65) 6831-3100 Fax: (65) 6732-4930 www.eastman.com Although the information and recommendations set forth herein are presented in good faith, Eastman Chemical Company makes no representations or warranties as to the completeness or accuracy thereof. You must make your own determination of their suitability and completeness for your own use, for the protection of the environment, and for the health and safety of your employees and purchasers of your products. Nothing contained herein is to be construed as a recommendation to use any product, process, equipment, or formulation in conflict with any patent, and we make no representations or warranties, express or implied, that the use thereof will not infringe any patent. NO REPRESENTATIONS OR WARRANTIES, EITHER EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, OR OF ANY OTHER NATURE ARE MADE HEREUNDER WITH RESPECT TO INFORMATION OR THE PRODUCT TO WHICH INFORMATION REFERS AND NOTHING HEREIN WAIVES ANY OF THE SELLER S CONDITIONS OF SALE. Safety Data Sheets providing safety precautions that should be observed when handling and storing our products are available online or by request. You should obtain and review available material safety information before handling our products. If any materials mentioned are not our products, appropriate industrial hygiene and other safety precautions recommended by their manufacturers should be observed. 2013 Eastman Chemical Company. Eastman is a trademark of Eastman Chemical Company. All other brands are the property of their respective owners. M-190F 6/13