low voltage GLOBAL CATALOGUE RANGE ACB Air Circuit Breakers

Similar documents
Comprehensive Catalogue. Super Solution. Air Circuit Breakers

Super Solution Air Circuit Breakers

Super Solution Meta Solution Marine Air Circuit Breakers

DMX 3 -I 2500 switch disconnectors

ACB l COMET AIR CIRCUIT BREAKER

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Memshield - ACB Ratings & Specifications

ACB l COMET AIR CIRCUIT BREAKER

5. OVERCURRENT RELEASE (OCR)


cor Long Run Experience

Low voltage. Masterpact NT and NW. LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type. Catalogue

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63

CONTENTS. Dimensions A1-57

DPX 1600 Electronic release

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE

DPX Electronic + earth leakage

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

Low Voltage Air Circuit Breakers 630AF~6300AF 15A

Contents. Compact ACB 1600A. Ratings 03 Ordering 04 Electrical diagram. 06 Accessories 08 Structure 09 Dimensions 10

Contents. Compact ACB 1600A. Ratings 03 Ordering 04 Electrical diagram. 06 Accessories 08 Structure 09 Dimensions 10

(p. 47) (p. 155) (p. 155)

MCCB Accessories to suit AF

DPX Electronic. Fiche technique : F01362EN/02 Mise à jour le : 15/12/2011 Créé le : 15/06/2011

DPX moulded case circuit breakers

ACB/ATS Air Circuit Breaker / Automatic Transfer Switch

DPX earth leakage DPX 3 -I earth leakage

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C2. General characteristics. C3. Fixed circuit breaker. C4. Withdrawable circuit breakers

(Example) In case of DC24 to 48V, it is operating time for DC24V.

Air Circuit Breakers DH series General information

LSIS UL MCCB & Accessory

DPX 630 Electronic release

Overview of Low voltage equipment - Moulded-case & Air circuit-breakers

Low voltage moulded case circuit breaker EB2

PROTECTION AND CONNECTION. ABB Compact ATS Compact without compromise

High Breaking Capacity

WORKSHOP SPECIFICATIONS

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

BREAKER. Molded Case Circuit Breaker/Earth Leakage Circuit Breaker

Moulded case circuit breakers

Protection and Connection Motorized and automatic transfer switches IEC Technical guide


Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

ME 07 Air Circuit Breakers. ME 07 - Air Circuit Breakers. Low Voltage. Low Voltage. Low Voltage

Selection and Application Guide usa.siemens.com/circuitbreakers

DRX 125 Circuit breaker (not adjustable)

Magnum IEC Low Voltage Air Circuit Breakers

Breaking and protection devices

Molded Case Circuit Breaker

Motor Protection Circuit Breakers

MODpower Air Circuit Breakers

DPX 160 Thermal magnetic and trip-free switches DPX-I 160

3 - Protection components Motor circuit-breakers

DPX Thermal magnetic and trip-free switches DPX 3 -I 630

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

Manual Motor Starters. Meta-MEC

DPX 630 Thermal magnetic and trip-free switches DPX-I 630

OSS - TN, TBN Type. Information to Order. Features. External View ATS(60~600A) OSS P- A B C D. Rated Current. D Operating Voltage

Thermal magnetic and trip-free switches

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers

SD Series Non-Fused Load Switches

B4 Load Break Switches

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker

22AF 40AF AF 150AF 225AF 400AF 800AF

Low voltage circuit breakers

UTS400 SELECTION GUIDE CATALOG NUMBERING [PRODUCT SELECTION] UTS400 NT ATU 400A 3P LL LSIS UL MCCB

Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter

01 Spectra Plus - Introduction

Section Contents. 1. Introduction 2-5. Salient features, internal & general appearance of Drawout ACB

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

GE Consumer & Industrial. M-PACT New Air Circuit Breaker A

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

Power protection solutions

Data Sheet Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M

Instantaneous tripping TYPE B, C, D TYPE B, C TYPE B, C, D TYPE B, C IEC RCCB TYPE C IEC61008 RCBO 25, 40, 63A. IEC61009 Isolating Switch

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

World Super Series WSS The extensive breaker series from Mitsubishi Electric

Meta Solution. Contactors and Overload relays

AF40... AF96 3-pole contactors Technical data

CDM1. Standard: IEC Technical data. current A 3P,4P Rated frequency Hz V. voltage Ui V. withstand voltage Uimp V.

Emax DC. Annex to the technical catalogue. Low voltage switch-disconnectors and automatic circuit-breakers for Direct Current Applications

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

3.1. Power Breakers, Contactors and Fuses. Contents. Series NRX Low Voltage Power Circuit Breakers. Power Circuit Breakers

DPX Magnetic only

Phase + Neutral, neutral on right side

Protection components

Emax DC. Annex to the technical catalogue. Low voltage switch-disconnectors and automatic circuit-breakers for Direct Current Applications

ACW. Molded-Case Circuit Breaker UL 489 Listed. ACW Catalog Number Sequence

DRX 250 B/N/H Circuit breaker (not adjustable)

Low voltage circuit breakers

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals

Product Line Overview. The Most Logically Designed Contact Assembly

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B,21B,22B,31B Overcurrent Protective Device)

atalog Welcome to ATO.com! Contact us... Tel: (Toll-free) Website:

Low voltage circuit breakers

Contents. We build a better future! MCC HCB

Transcription:

CATALOGUE GLOBAL RANGE 3. ACB Air Circuit Breakers

Inde 3. Air Circuit Breakers 3.1 ACB Product Overview Air Circuit Breakers 3.2-3.3 ACB Product Specifications 3.4 ACB Accessories Overview 3.5 ACB Accessory 3.6 OCR - Over Current Relay 3.7 ACB Protection 3.8-3.9 ACB Wiring Diagram 3.10-3.13 ACB Dimensions 3.14-3.18 Characteristic Curves 3.19-3.24 ACB Accessories

ACB Product Overview Product Line up Amp Circuit Breaker Fied Draw Out Disconnector 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A ACB 630 CM F/D ACB 800 CM F/D ACB 1000 CM F/D ACB 1250 CM F/D ACB 1600 CM F/D ACB 2000 CM F/D ACB 2500 CM F/D ACB 3200 CM F/D ACB 4000 CM F/D DIS 1600 CM F/D DIS 2000 CM F/D DIS 2500 CM F/D DIS 3200 CM F/D DIS 4000 CM F/D Fied Draw Out Accessories Standard Standard (pre-fitted) Motor Charge AC/DC Standard Shunt AC Standard Closing Coil AC Standard Au AC Standard Advanced Control Module AC Standard Counter Frame Door Cradle Lifting Hooks ACB Fied ACB Draw Out Isolator Fied 230 V 230 V 230 V 230 V 230 V 230 V 3a3b 3a3b AG5** AG5** Isolator Draw out AG5** C Overload protection C Short-circuit protection C Ground fault protection C Realization of protective coordination by ZSI C High-performance and high-speed MCU built-in C Fault recording C SBO (Select Before Operation) C 3 DO (Digital Output) C Communication Accessories Optional Motor Charge AC/DC Optional Shunt AC Optional UVT AC Optional Closing Coil AC Optional Au AC Optional Advanced Control Module AC Optional ACB Fied ACB Draw Out Isolator Fied 24-48 -110 V 24-48 -110 V 24-48 -110-230 V 24-48 -110-230 V 5a5b P/S 24-48 -110 V 24-48 -110 V 24-48 -110-230 V 24-48 -110-230 V 5a5b P/S Isolator Draw out Standard Optional * Contact CBI for availability Not available Page 3.1of 3.24

ACB Product Specifications Type Ampere frame (AF) ACB 630 CM F/D 630 A ACB 800 CM F/D ACB 1000 CM F/D ACB 1250 CM F/D ACB 1600 CM F/D 800 A 1000 A 1250 A 1600 A Rated Current (A) (In ma) at 40 630 A 800 A 1000 A 1250 A 1600 A Setting current (A) Control trip relay (... In ma) Rated Current of neutral pole (A) (0.4 ~ 1.0) In ma 630 A 800 A 1000 A 1000 1250 A 1250 1600 A Rated Insulation Voltage (V) (Ui) 4P%* 100% 100% 100% 100% 100% 1000 Rated Operating Voltage (V) (Ue) 690 Air Circuit Breakers Rated Impulse withstand voltage (Uimp) kv 12 Frequency (Hz) 50/60 Number of poles 3/4P* Rated breaking capacity (ka sym) 220V/230V/380V/415V 65 IEC60947-2 (Icu) 460V/480V/500V 65 AC 50/60 Hz 550V/600V/690V 50 Rated Service breaking capacity (ka) (Ics)...% Icu 100% Rated making capacity (ka peak) 220V/230V/380V/415V 143 IEC60947-2 (Icm) 460V/480V/500V 143 AC 50/60 Hz 550V/600V/690V 105 Rated short-time withstand current (ka) 1 sec 50 (Icw) 2 sec 42 3 sec 36 Operating time (ms) Maimum total breaking time 40 Maimum closing time 80 Life Cycle Mechanical 20 000 Electrical 5000 Connections Draw-out / Fied Horizontal connection Vertical connection Front connection Weight (kg) (3P) Mied connection Draw-out type Main body Motor charging type (with cradle) Manual charging type cradle only Fied type Motor charging type 63 61 29 34 Manual charging type Eternal dimensions (mm) Draw-out type 3P 430 334 375 (H W D) Fied type 3P 300 300 295 Trip Relay Certifications / Standards Standard Option * Contact CBI for availability 32 A type KS / KEMA / KERI / GOST / SANS Page 3.2 of 3.24

ACB Product Specifications Type ACB 2000 CM F/D ACB 2500 CM F/D ACB 3200 CM F/D ACB 4000 CM F/D Type DIS 2000 CM F/D** DIS 2500 CM F/D** DIS 3200 CM F/D** DIS 4000 CM F/D** Ampere frame (AF) 2000 A 2500 A 3200 A 4000 A Rated Current (A) (In ma) at 40 2000 A 2500 A 3200 A 4000 A Setting current (A) Control trip relay (... In ma) (0.4 ~ 1.0) In ma Rated Current of neutral pole (A) 2000 A 2500 A 3200 A 4000 A 1000 1250 1250 4P%* 100% 100% 100% 100% Rated Insulation Voltage (V) (Ui) 1000 Rated Operating Voltage (V) (Ue) 690 Rated Impulse withstand voltage (Uimp) kv 12 Frequency (Hz) 50/60 Number of poles 3/4P* Rated breaking capacity (ka sym) 220V/230V/380V/415V 85 IEC60947-2 (Icu) 460V/480V/500V 85 AC 50/60 Hz 550V/600V/690V 85 Rated Service breaking capacity (ka) (Ics)...% Icu 100% Rated making capacity (ka peak) 220V/230V/380V/415V 187 IEC60947-2 (Icm) 460V/480V/500V 187 AC 50/60 Hz 550V/600V/690V 187 Rated short-time withstand current (ka)** 1 sec 85 (Icw) 2 sec 75 3 sec 65 Operating time (ms) Maimum total breaking time 40 Maimum closing time 80 Life Cycle Mechanical 15 000 Electrical 5000 Air Circuit Breakers Connections Draw-out / Fied Horizontal connection Vertical connection Front connection Mied connection Weight (kg) Draw-out type Main body Motor charging type (3P) (with cradle) Manual charging type cradle only Fied type Motor charging type Manual charging type Eternal dimensions (mm) Draw-out type 3P (H W D) Fied type 3P Trip Relay Certifications / Standards Standard Option * Contact CBI for availability 87 104 85 102 44 58 44 63 42 61 430 412 375 300 378 295 A type (self powered/current display/comms) KS / KEMA / KERI / GOST / SANS Page 3.3 of 3.24

ACB Accessories Overview Mounting Accessories Standard Option Mounting Accessories Standard Option SHT1 Shunt Coil 230 V N N type SHT2 Double Shunt Coil 230 V A AG 5 CC Closing Coil Trip relay P P type M Motor 230 V S S type CS1 Charge Switch VM Voltage Module CS2 Charge Switch Communication ZCT ZCT for the earth leakage Internal UVT Under Voltage Trip Device AL Trip Alarm Contact SBC Shorting "b" Contact MI Mechanical Interlock MRB Manual Reset Button ST Safety Shutter (Draw out only) RES Remote Reset Switch STL Safety Shutter Lock RCS Ready to Close Switch MIP Miss Insertion Prevent Device C Counter MOC Mechanical Operated Cell Switch Air Circuit Breakers AUX Auiliary Switch 3a3b 5a5b CEL Cell Switch TM Temperature Alarm Cradle DI Door Interlock K1 Key Lock ZAS Zero Arc Space K2 Key Interlock Set SC Safety Control Cover K3 Double Key Lock BSP Body Supporter B On/Off Button lock RI Racking Interlock LH Lifting Hook PL Pad Lock/ Position Lock CTD Condenser Trip Device IB Insulation Barrier Eternal ATS Automatic Transfer Switch Controller UDC UVT Time Delay Controller ADP Compatible Adapter DC Dust Cover DF Door Frame Other VAD RCO Various Connection Type Remote I/O OT OCR Tester PC Profibus-DP comm. module Note: Available or supplied as standard Optional - Please contact CBI for availability Insulation Voltage Keep the isolation distance between ACB and panel as table below. Type A B Fied Draw out Page 3.4 of 3.24

ACB Accessory Standard AG 5 Optional P Type Optional S Type Measurement Class. Detailed element Unit Display range Accuracy element Line current Ia,Ib,Ic ±3% Current Normal current I1 A 80A~65,535A Reverse current I2 Line voltage Vab,Vbc,Vca ±1% Voltage Phase voltage Va,Vb,Vc ±1% V 60~690V Normal voltage V1 Reverse voltage V2 Line-to-line VabIa, VabIb, VabIc, ±1 Line-to-current VabVbc, VabVca Angle 0~360 Phase-to-phase VaVb, VaVc ±1 Phase-to-current VaIa, VbIb, VcIc ±1 Active power Pa(ab), Pb(bc), Pc(ca), P kw 1kW~99,999kW ±3% Power Reactive power Qa(ab), Qb(bc), Qc(ca), Q kvar 1kVar~99,999kVar ±3% Apparent power Sa(ab), Sb(bc), Sc(ca), S kva 1kVA~99,999kVA ±3% Active energy Energy Reactive energy WHa(ab), WHb(bc), kwh WHc(ca), WH MWh VARHa(ab), VARHb(bc), kvarh VARHc(ca), VARH Mvarh Reverse active rwha(ab), rwhb(bc), kwh energy rwhc(ca), rwh MWh 1kWh~9999.99MWh ±3% 1kVarh~9999.99MVarh ±3% 1kWh ~9999.99MWh ±3% Freq. Frequency F Hz 45~65Hz Power factor Power factor(pf) PFa(ab), PFb(bc), PFc(ca), PF +: Lead, -: Lag Unbalance Unbalance rate I unbalance, V unbalance % 0.0~100.0 Active power Demand demand Peak demand kw 1kW~99999kW Current demand Peak demand A 80A~65,535A Voltage 1st~63th harmonics of harmonics Va(ab),Vb(bc),Vc(ca) V 60~690V Harmonics Current harmonics 1st~63th harmonics of Ia,Ib,Ic A 80A~65,535A THD, TDD % 0.0~100.0 K-Factor - 0.0~100.0 Air Circuit Breakers Voltage module For P and S type Trip relay, s epera te voltage module is necessary to measure other element besides current (Seperate purchase is needed) - Voltage input range: AC 60~690V Vr Vs Vt Vn Vr Vs Vt 1 2 3 4 5 6 7 8 Voltage module 13 14 15 16 17 18 19 20 V1 V2 V3 Vn 1 2 3 4 5 6 7 8 Voltage module 13 14 15 16 17 18 19 20 V1 V2 V3 Vn 9 9 10 10 11 11 12 12 3P4W wiring 3P3W wiring Page 3.5 of 3.24

OCR: Over Current Relay A type: Over Current Relay Overload protection -Long-time delay -Thermal Short-circuit protection -Short-time delay / Instantaneous -I 2 t On/Off optional (for short-time delay) Ground fault protection -I 2 t On/Off optional Realization of protective coordination by ZSI (Zone Selective Interlocking) High-performance and high-speed MCU built-in -Accurate measurement with tolerance of 1.0% Fault recording -Records Ma. up to 10 fault information about fault type, fault phase, fault data, occurrence time of fault SBO (Select Before Operation) -High reliability for control and setting change method 3 DO(Digital Output) -Fied Communication -Modbus/RS485 -Profibus-DP 1 2 LCD: Indication of measurement and information LED: Indication of trip info. and overload state 1 Alarm SP Ir Isd Ii Ig Comm 2 Ig: LED indicating ground-fault Isd/Ii: LED indicating short-time or instantaneous tripping Ir: LED indicating long-time delay SP: Self-protection and battery test LED Alarm: LED indicating an overload (Turn on above 90%, Blink above 105%) 3 3 Key: Move to menu or reset Reset Esc 4 5 7 6 8 Reset/ESC: Fault reset or ESC from menu Enter: Enter into secondary menu or setting input Up/Down: Move the cursor up/down on screen or increase/decrease a setting value Right/Left: Move the cursor or setting right/left on screen (Rotation) Menu: Menu display Measurement display 4 5 6 7 8 Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting Isd: Short-time current setting, tsd: Short-time tripping delay setting Ii: Instantaneous current setting Ig: Ground fault current setting, tg: Ground fault tripping delay setting Test terminal: OCR test terminal (Connected with OCR tester) Page 3.6 of 3.24

ACB Protection Page 3.7 of 3.24

ACB Wiring Diagram This diagram is based on CONNECTED position of a circuit breaker and opening, Motor charging and releasing of locking should be normal condition. 6 Page 3.8 of 3.24

ACB Wiring Diagram Page 3.9 of 3.24

ACB Dimensions ACB 630-1600A CMF Fied ACB 630-1600A CMD Horizontal Type Draw out Page 3.10 of 3.24

ACB Dimensions ACB 2000 A CMF Vertical Fied ACB 2000 A CMD Vertical type Draw-out Page 3.11 of 3.24

ACB Dimensions ACB 2500-3200 A CMF Horizontal Fied ACB 2500-3200 A CMF Horizontal type Draw-out Page 3.12 of 3.24

ACB Dimensions ACB 4000 A CMF Horizontal Fied ACB 4000 A CMD Horizintal type Draw-out Page 3.13 of 3.24

ACB Characteristic Curves Page 3.14 of 3.24

ACB Characteristic Curves Page 3.15 of 3.24

ACB Characteristic Curves Page 3.16 of 3.24

ACB Characteristic Curves Page 3.17 of 3.24

ACB Characteristic Curves Page 3.18 of 3.24

ACB Accessories Shunt Coil [SHT1] Shunt coil 1 SHT1 is a control device which trips a circuit breaker from remote place, when applying voltage continuously or instantaneously over 200ms to coil terminals(c1, C2). SHT2, if using a secondary shunt, a UVT cannot be used. 1. Rated voltage and characteristics of Trip coil Opening order C1 SHT1 C2 Rated voltage [Vn] Power consumption (VA or W) DC [V] AC [V] Operating voltage range [V] Inrush Steady-state Trip time [ms] 24~30-0.6~1.1 Vn 48~60 48 0.6~1.1 Vn Less 100~130 100~130 0.56~1.1 Vn 200 5 than 200~250 200~250 0.56~1.1 Vn 40ms - 380~480 0.56~1.1 Vn Note) Operating voltage range is the min. rated voltage standard for each rated voltage(vn). * The 점선은 dotted User line 배선임 to be made by the customer Wiring Diagram Wiring Diagram 2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maimum wire length Wire type DC 24~30 [V] Rated voltage [Vn] DC/AC 48 [V] #14 AWG #16 AWG #14 AWG #16 AWG (2.5 2 ) (1.5mm 2 ) (2.5mm 2 ) (1.5mm 2 ) Operating 100% 95m 61m 457m 287 voltage 85% 625m 38m 291m 183 Page 3.19 of 3.24

ACB Accessories Closing Coil [CC] Closing coil The closing coil closes the Circuit Breaker when voltage is applied continuously or instantaneously over 200ms to the terminals (A1, A2). 1. Rated voltage and characteristics of Closing coil Closing order A1 CC A2 * The dotted line to be made by the customer Wiring Diagram Rated voltage [Vn] Power consumption (VA or W) DC [V] AC [V] Operating voltage range [V] 24~30-0.75~1.1 Vn Shunt time Inrush Steady-state [ms] 48~60 48 0.75~1.1 Vn Less 100~130 100~130 0.75~1.1 Vn 200 5 than 200~250* 200~250 0.75~1.1 Vn 80ms - 380~480 0.75~1.1 Vn Note) Operating voltage range is the min. rated standard for each rated voltage (Vh). * CBI Standard 2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maimum wire length Wire type DC 24~30 [V] Rated voltage [Vn] DC/AC 48 [V] #14 AWG #16 AWG #14 AWG #16 AWG (2.5mm 2 ) (1.5mm 2 ) (2.5mm 2 ) (1.5mm 2 ) Operating 100% 95m 61m 450m 285m voltage 85% 62m 40m 290m 180m Page 3.20 of 3.24

ACB Accessories Motor [M] Motor Main ais Gear Charge the closing spring mechanism of the circuit breaker by an eternal power source. Without the eternal power source, charge manually. Operating voltage range(iec 60947) 85%~110%Vn Fully charged contact CBI Standard Input voltage(v) DC 24~30V AC/DC 48~60V AC/DC 100~130V AC/DC 200~250V AC 380V AC 440~480V Load current(ma.) 5A 3A 1A 0.5A 0.3A 0.3A Starting current(ma.) 5 times of load current Load rpm(motor) 15000 ~ 19000 rpm Charge time Less than 5sec. Dielectric strength 2kV/min Using temperature range -20º ~ 60º Using humidity range Ma. RH 80% (No dew condensation) Endurance 15,000 cycle (Load connection, 2 times/min) Charge switch 10A at 250VAC Charge Switch [CS1] Charge Switch Communication [CS2] It is a built-in contact which sends the signal to the outside, when motor charging is completed. (2a) It has a 1a contact for communication and the other 1a contact for complete charging. When using an etra communication module (Remote I/O), the state of contacts can be displayed through the network. 10A at 250VAC Page 3.21 of 3.24

ACB Accessories UVT coil Shunt coil Closing coil If the voltage of the main or the control power is under voltage, UVT which is installed inside of the breaker trips the ACB automatically. Please connect with UVT time-delay device in order to present the timedelay function because UVT is technically instantaneous type. The closing of a circuit breaker is impossible mechanically or electrically if control power not supplied to UVT. To close the circuit breaker, 65~85% of rated voltage should be applied to both terminals of UVT coil (D1, D2). Air Circuit Breakers When using UVT coil, the double trip coil can not be used. Page 3.22 of 3.24

ACB Accessories Auiliary switch [AX] It is a contact used to monitor ON/OFF position of ACB remotely. Air Circuit Breakers Standard 2000, 5000AF 4000, 6300AF Classification Resistive load Inductive load Remark 490V 5A 2.5A AC 250V 10A 10A Contact 125V 10A 10A capacity 250V 3A 1.5A DC 125V 10A 6A 30V 10A 10A No. of Contact that can be used HX HC JC 5a5b (OFF charge) 5a5b (On charge) 6a6b (On charge) Rapid autoreclosing charging type Page 3.23 of 3.24

ACB Accessories Key Interlock Set [K2] Wiring ACB 1 ACB 2 3 circuit breakers can be arranged for the continuous power supply to the load side and be interlocked mutually by using Key Lock embedded in each circuit breaker. ACB-1 ACB-2 ACB-3 LOAD1 Status LOAD2 OFF OFF ON ON ON ON ON ON OFF OFF OFF ON ON OFF Air Circuit Breakers : Release : Lock ACB 3 Load 1 Load 2 Condenser Trip Device [CTD] Ratings A device for continuous tripping of the ACB after power interuptions Ratings Model Rated input voltage (V) Frequency ( Hz ) Rated charge voltage (V) Charging time Trip possible time Range of Input voltage (%) Condenser capacity Specification CTD-100 CTD-200 AC 100/110 AC 200/220 50/60 50/60 140/155 280/310 Within 5S Within 5S Over 3 MIN Over 2 MIN 85~110 85~111 400µF 160µF Eternal dimension Circuit diagram 15 131 118 7.5 AC input DC output Side view 108 75 75 Rear view Front view Page 3.24 of 3.24