Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel. Model Installation Guide

Similar documents
Dual 100A 4/4-KLM & 4/4-GMT Fuse Panel. Model N Installation Guide

50A Dual-Feed 5/5 GMT Total Front Access Fuse Panel

100A Universal Voltage Dual-Feed GMT Fuse Panels Power :: HPGMT10xx and HPGMT15 Installation Guide

Demarcation Fuse/Circuit Breaker Alarm Panel 125DM08. Installation Guide

Dual-Feed 600A Load Center Frame Power :: 600CB10 and 600CB12 User Manual

Demarcation Fuse Alarm Panel

Dual-Feed 600A Load Center Frame

Low-Current 20/20 GMT Series Fuse Panels Models & Installation Guide

100A/60A Universal Voltage GMT Fuse Panels With Enhanced Power/Fuse & Bay Alarms Power :: HPGMTXX & GMTXX Installation Guide

Dual-Feed 600A 8-Circuit Breaker/TPC/TFD Load Center With 5 GMTs

FUSE PANEL. Technical Practice N N-L33 10/10 GMT Front Access NEBS Level 3 Certified

PowerWorx GMT Series Power Distribution Panel Uninterrupted (C-Source) Power User Manual

FUSE PANEL Technical Practice N N-L34 20/20 GMT (23 panel) NEBS Level 3 Certified

Noran Tel. Fuse Panel Technical Practice N NCY 4/4TPA & 6/6 GMT NEBS Level 3 Certified

Noran Tel. FUSE PANEL Technical Practice N21C110-NCY 5/5 GMT (20Amp GMT) NEBS Level 3 Certified

:: :: TFD4 :: TFD6

FUSE PANEL Technical Practice FDP /10 GMT NEBS Level 3 Certified

Installation Manual. AC Edge. Split Phase 60 A (6/6) AC Power Distribution Unit. AC Edge. Model AC60DF 6/6 Part#

PowerWorx DSX Series GMT Fuse Panel User Manual

GMT Fuse Panel Installation Guide

PowerWorx Power Distribution Products Select Series Circuit Breaker for ±24 or ±48 Vdc User Manual

nrgsmart Power Distribution Remote Monitoring

TPM/GMT Panel Installation Guide

Noran Tel. a subsidiary of Westell Inc. Fuse Panel Technical Practice NPGMT /10 GMT NEBS Level 3 Verified

Total Front Access Wall Mount Fuse Panel Installation Guide. Document INS This manual covers the following part numbers

Westell FUSE PANEL. Technical Practice N Position Type VDC Floating

Installing Power Components

TPM Fuse Panel Installation Guide. Document INS-727XXXXXXX This manual covers the following part numbers- Trimm 727XXXXXXX Family

FUSE PANEL. NTI-N NC(Y)/M3 NEBS Level 3 Certified NTI NCD(Y)/M3 Standard Panel with Diodes

FUSE PANEL Technical Practice FDP /20 GMT NEBS Level 3 Certified

OPERATING MANUAL BDP600 UNIVERSAL BATTERY DISTRIBUTION PANEL

DC Distribution Panel User Guide # S

Secondary DC Distribution E R P R P I 2. Technical Reference Guide

DS1 Plug-In Digital Signal Cross-Connect (PIX-DSX-1) 19-Inch Shelf Kit Installation Instructions

BLADE TERMINAL AND SPECIAL PURPOSE FUSES

IOE-XXX-XXXX Training Guide

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

NTK599BAE5 and NTK599BGE5 Breaker Interface Panel (BIP) Installation Manual

Fuse Panels, Fuse Holders and Fuses

Application Note. Best Solutions for Managing High-Current Power Distribution

Fuse / Circuit Breaker Panels

WAVETRAX USER MANUAL

L007 LIQUID LEVEL FLOAT SWITCH. Side-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

Product Manual Select Code Comcode Issue 9 September Secondary DC Power Distribution Bay H


Products. Section Contents

HMW Filtered Fuse Panel for GMT Fuses

Circuit protection for telecom applications

Dimensions 12/800N 12/1200N D. DC to AC Power Inverters. OWNERS MANUAL for Models: OWNERS MANUAL April ISO 9001:2000 Certified Company

TPC & TPCDS. Telpower Compact Fused Disconnect Switch. Bussmann. Telpower. DC Power Protection Systems

ATT DC POWER AND GROUNDING MINOR MATERIAL LIST A/

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

Power and Cooling. Chassis Power System

OLYMPIAN MODEL 740 Operation and Service Manual

Application Specification.062 Diameter Pin and Socket Contacts and Housings 21 MAR 11 Rev E

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

Power Distribution Units

E.S.P. Embedded Sensing Probes for Motor Brushes

GROUNDING & BONDING PRODUCTS

METROLOGIC INSTRUMENTS, INC. MX001 Industrial Control Interface Installation and User s Guide

5000 SERIES POWER SUPPLY/CHARGERS INSTALLATION GUIDE

INSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R

Fuse Panels, Fuse Holders and Fuses

Shelf 19 version) (Expansion Shelf 19 version) (Main Shelf 23 version) (Expansion Shelf 23 version)

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

CPS2000 Cabinet Power System

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

w w w. h d o n l i n e s h o p. d e HEATED HAND GRIP KITS GENERAL REMOVAL -J02983 REV Kit Number Models Kit numbers Service Parts

L-Series: LIQUID LEVEL FLOAT SWITCH. Single-Point, Vertically-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

RU SERIES UPGRADE TempAssure Compatible

Fuse and Distribution Module

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

Raritan PX. Power Cord Installation Guide. Safety Guidelines. Safety Instructions

ANZI Transfer Switch and Generator Wiring Installation Addendum

S003 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

AMPLIMITE* HDP- 20 and Economy

Installing the Switch Chassis

Installation, Operation and Maintenance Manual

Connecting to DC Power

Infinity 1U 19 Converter Shelf Models: J L224-48V to +24V, L V to -48V

miconverter 18-Module Rack-Mount Power Chassis User Manual 38 Tesla, Irvine, CA USA Phone: (949) ; Fax: (949) Page 12

Power Distribution WESTELL.COM

JUL 14 Rev B

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation

Dual-Lite Trident TRF 40 Wide Battery Cabinet 20-40kVA Systems USER MANUAL

HP BladeSystem c7000 Carrier-Grade Options Installation Guide

MODEL ELC-12/40-CVM-D BATTERY CHARGER

Unity Low Voltage Disconnect & Monitor

Installation and Operations Manual

MIL-24/2600Q MIL-24/3200DQ

INSTALL INSTRUCTIONS DC C-EV. Installation Instructions: DC C-EV.

USER MANUAL 6 Position Powered Rack for TD Series Modules TDR 01 AC

HYGRODYNAMICS DIGITAL DEW POINT MONITOR PC BOARD MODEL 6392N & 6392N2 TABLE OF CONTENTS

Battery Charger Retrofit Kit Q-DCCHG1 for DC Cabinet Retrofit Manual

REMOTE POWERING Central Energy System ( HUB )

I-BFV.KIT Butterfly Valve Gear Operator Replacement

Spreader and Vehicle Battery Kits

Sentinel Field Satellite Controller

Transcription:

Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel Model 009-8005-0404 Installation Guide

Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel Model 009-8005-0404 Installation Guide, Part number 123518-6 Copyright 2010, Telect, Inc., All Rights Reserved Telect and Connecting the Future are registered trademarks of Telect, Inc. 1730 N Madson St., Liberty Lake, Washington Telect assumes no liability from the application or use of these products. Neither does Telect convey any license under its patent rights nor the patent rights of others. This document and the products described herein are subject to change without notice. About Telect Telect offers complete solutions for physical layer connectivity, power, equipment housing and other network infrastructure equipment. From outside plant and central office to inside the home, Telect draws on more than 25 years of experience to deliver leading edge product and service solutions. Telect is committed to providing superior customer service and is capable of meeting the dynamic demands of customer and industry requirements. This commitment to customer and industry excellence has positioned Telect as a leading connectivity and power solution provider for the global communications industry. Technical Support E-mail: getinfo@telect.com Phone: 888-821-4856 or 509-921-6161 Page ii

Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel Model 009-8005-0404 Installation Guide Table of Contents 1.1 Specifications... 1 1.2 Inspection... 3 1.3 Installation... 4 1.4 Accessories... 10 1.4.1 Compression Lugs... 11 1.5 Schematic Drawing... 13 1.6 Assembly Drawing... 14 List of Figures Figure 1 - Model 009-8005-0404...1 Figure 2 - Bracket Orientation... 4 Figure 3 - Rack Mounting... 4 Figure 4 - Ground Lug Connection... 5 Figure 5 - Input Lugs... 5 Figure 6 - Disengaging a TPA Fuse Holder... 6 Figure 7 - Alarm Indicators... 6 Figure 8 - Alarm Terminals... 7 Figure 9 - TPA Output Lug Connections... 7 Figure 10 - GMT Output Lug Connections... 8 Figure 11 - Installing TPA Fuses... 8 Figure 12 - Installing GMT Fuses... 9 Figure 13 - Designation Card... 9 Page iii

Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel Model 009-8005-0404 Installation Guide Telect's dual 200A fuse alarm panel provides power protection for a variety of telecommunications equipment. Panel includes 8 TPA output fuse holders (4 per side) and 10 GMT fuse holders (5 per side). Figure 1 - Model 009-8005-0404 Sides A and B are electrically independent except for the replaceable alarm card, which contains power and alarm LEDs for both feeds. Also included are fuse alarm and power-fail relay terminals for external indicators. Model 009-8005-0404 is NEBS- and CE-certified, and listed by UL for the USA and Canada. 1.1 Specifications Inputs: Voltage & Range ±24Vdc, ±20V to ±30V -48Vdc, -40V to -60V Max. Input Load Rating 200A per side Nominal Power Loss at Full Load 70W per side @ 9600W full load per side (200Ax48V) Percentage of Full Load Power Dissipation at less than 1% Nominal Voltage Max. Input Interrupt Device 250A Input Terminal Studs (With Split Ring Lock Washers & Nuts) for Dual-Hole Compression Lugs Input Wire Size TPA Outputs: Two pairs of 1/4-20 studs on 3/4 in. centers. (Torque nut [using 7/16 in. or 12 mm socket] to ~45 in.-lb [~5 N m]). #8 to #4/0 AWG (depends on input interrupt device); 1 lug width Max. TPA Output Fuse (ea.) 50A. Max. TPA Output Load (ea.) - continuous 40A. Max. Total TPA Output Load 160A per side TPA Output Terminal Studs with nuts 16, single, #10-32 studs (max. lug width of 0.46 in. [1.17 cm]). Torque nut (using 3/8 in. or 10 mm socket) to ~20 in.-lb (~2.3 N m) TPA Output Wire Size #18 to #6 AWG (depends on output fuse rating) Page 1

GMT Outputs: Max. GMT Output Fuse (ea.) 15A. Max. GMT Output Load (ea.) - continuous 10.5A Max. Total GMT Output Load 65A per side GMT Output Terminal (Wire Binding) 20, #6 panhead screws (max lug width of.32 in. [.81 cm]). GMT Output Wire Size #20 to #12 AWG (depends on output fuse rating) Grounding: Earth GND Terminal Studs (With Split Ring Lock Washers & Hex Nuts) for Dual-Hole Compression Lug Ground Wire Size Two pair of 1/4-20 threaded holes on 5/8 in. (1.59 cm) centers. Torque supplied bolt (using 7/16 in. or 12 mm socket) to 45 in.-lb (5 N m). Up to #4 AWG (depends on input interrupt device) Alarms: Alarm Relay Contacts Max. Alarm Card Power Rating Alarm Wire Size Indicators: INPUT POWER LEDs (Green) FUSE ALARM LED ((Red) Dimensions: Nominal, without brackets:* *See Page 14 for exact dimensions. Weight: Weight, Without Packaging Weight, Shipping Width Height Depth 2A @ 30 Vdc 0.6A @ 60 Vdc @20V: 85 ma (1.70W) @24V: 103 ma (2.47W) @27V: 109 ma (2.94W) @30V: 112 ma (3.36W) @42V: 123 ma (5.17W) @48V: 128 ma (6.14W) @56V: 135 ma (7.56W) @60V: 139 ma (8.34W) #24 AWG, typ (#26 to #20 AWG) Lights when power is applied to that feed Lights if any GMT fuse blows 17.25 in. (43.82 cm) 1.75 in. (4.44 cm) 10 in. (25.40 cm) ~14 lb (~6 kg) ~15 lb ( ~7 kg) Page 2

Environment: Operating Temperature Range Hardware is included for flush or extended mounting in 19" or 23" relay racks. Visit our website to order Telect accessories and replaceable parts: output fuses (3A-50A TPA; ¼A-15A GMT), dummy fuses, lugs, ETSI mounting kit, and more.! ALERT ALERT! Only qualified personnel may install and maintain this product. Verify that all connections meet requirements specified in local electric codes or operating company guidelines before supplying power. Protect this equipment with a fuse or breaker sufficient to interrupt power levels specified on preceding page. Install this product in locations accessible only by qualified personnel. 1.2 Inspection -10 C (14 F) to 55 C (131 F) Please read these instructions carefully before beginning installation. If you need assistance, call Technical Support at 1-888-821-4856 (domestic calls), or 509-921-6161 (Option 2), or email us at getinfo@telect.com. Inspect equipment after unpacking and compare it to the packing list. Immediately report any shipping damage, defects, or missing parts to Telect at 1-800-551-4567. Keep all documentation that comes with your shipment. Telect is not liable for shipping damage. If the product is damaged, notify the carrier and call Telect s Customer Service Department at 1-800-551-4567 (domestic only) or 1-509-926-6000 for further recourse. NOTE: For service or warranty information, please visit the telect.com website, or email inquiries to getinfo@telect.com and click on the Support tab, or phone us at 800-551-4567 (domestic only) or 509-926-6000. Page 3

1.3 Installation Panel brackets provide flush or extended EIA or WECO mounting in a 19 or 23 in. rack. The panel is configured at the factory for 1-in. extended mounting in a 19-in. rack. 1. If necessary, remove three screws and reposition/re-align the brackets on the sides of the distribution panel, as shown in Figure 2. 2. Locate an unused rack position and mount the panel using four screws and lock washers provided, as shown in Figure 3. (Place the mounting panel as high as possible on the rack.) 3. Tighten the screws to 35 in.-lb. (4.29 N m). 4. Loosen (you need not remove) two screws securing the rear terminal cover on the back of the panel. 5. Remove the cover.! WARNING WARNING! Failure to properly ground this equipment can create hazardous conditions to installation personnel and to the equipment.! ALERT Figure 2 - Bracket Orientation ALERT! Only use components and crimping tools Figure 3 - Rack Mounting approved by agencies or certifying bodies recognized in your country or region, such as Underwriter s Laboratories (UL), TUV, etc. Page 4

6. Use a listed (approved) crimping tool to attach a listed (approved), dual-hole compression lug onto suitable ground wire. (Size of the ground depends on input interruption device.) 7. If required, lightly coat anti-oxidant on the lug and grounding surface on the side of the panel. 8. Connect the lug using the ¼ - 20 bolt, split ring washer and flat washer provided, as shown in Figure 4. 9. Tighten the bolt to 45 in.-lb. (5 N m).! WARNING WARNING! Before connecting the input power cables, make sure the input power to the panel is turned off. 10. Make sure the input power is off (open breaker, dummy fuse, or open fuse holder at power distribution unit [PDU]) before connecting this panel s input cables to the PDU. Figure 4 - Ground Lug Connection 11. For input wiring wiring used as inputs to this distribution panel crimp dual-hole compression lugs onto #8 AWG to #4/0 AWG copper wires. Insulate lug barrels with UL94 V-0 rated heat-shrink tubing. 12. Clean the terminals and lugs with a nonabrasive, nonmetallic pad. 13. If required, lightly coat anti-oxidant on lugs and input BATTERY and RETURN terminals. 14. Connect the lugs to input terminals on back of panel, as shown in Figure 5. 15. Tighten the lugs to 45 in.-lb. (5 N m). 16. Make sure TPA and GMT fuse positions are either empty or contain dummy fuses (phoney, inoperative all-plastic slugs). Figure 5 - Input Lugs Page 5

If necessary, pull out the TPA carrier about an inch from its holder to disengage the TPA fuse, as shown in Figure 6. 17. Enable the fuse or breaker at PDU (250A max.) to turn on Feed A to Side A and then check voltage and polarity at input connectors of panel. Also, check that PWR ON A LED on front of panel turns on (green). (See Figure 7 for location.) Figure 6 - Disengaging a TPA Fuse Holder PWR ON B, FUSE ALARM, and TPA Fuse LEDs must be off. Figure 7 - Alarm Indicators Page 6

18. At the rear of the panel, pull to extend plastic reference card below alarm terminals. (See Figure 8.) 19. With PWR ON A lit (normal operation) but with PWR ON B LED off (failure operation) test power-fail relay and contacts at PWR ALM terminals on the rear of the panel: Expect an open circuit ( Ω) between Terminals C and NC. Expect continuity (0Ω) between Terminals C and NO. 20. Also, test the fuse alarm relay contacts at the FUSE ALARM terminals on the rear of the panel. For both the VIS (visual) and AUD (audible) indicator contacts, Expect continuity (0Ω) between Terminals C and NC. Expect an open circuit ( Ω) between Terminals C and NO. 21. Repeat Steps 17 through 20 to power up Side B. PWR ON A and PWR ON B must both be lit. 22. With PWR ON A and B lit (normal operation), test power-fail relay and contacts at PWR ALM terminals on the rear of the panel: Expect continuity (0Ω) between Terminals C and NC. Expect an open circuit ( Ω) between Terminals C and NO. 23. Make sure none of the fuse positions contain operable fuses. 24. For TPA output wiring, crimp single-hole lugs onto one end of #18 to #6 AWG copper output wires, as required by NEC. (Work with one output wire at a time.) 25. Clean the panel terminals and lugs with a nonabrasive, nonmetallic pad. 26. If required, lightly coat anti-oxidant on lugs and output BATTERY and RETURN terminals, and then connect lug to terminals, as shown in Figure 9. (NEC specifies only one lug and load at each output terminal.) 27. Tighten the nuts to 20 in.-lb. (~2.3 N m). Figure 8 - Alarm Terminals Figure 9 - TPA Output Lug Connections Page 7

28. Connect the other end of the output wire to load. 29. For GMT output wiring, use #20 to #12 AWG copper wire. (Work with one wire at a time.) At the panel end of the wire, either Crimp a single-hole ring or fork lug, as required by NEC, or Strip 3 /8 in. (1 cm) of insulation for a bare wire connection. 30. Clean the panel terminals and lug (if applicable) with a nonabrasive, nonmetallic pad. 31. If required, lightly coat anti-oxidant on the lug/wire and output BATTERY and RETURN terminals. 32. Connect to the terminals, as shown in Figure 10. (NEC specifies only one load at each output terminal.) 33. Tighten the panhead screws to no more than 8 in.-lb. (~1 N m). 34. Connect the other end of the output wire to load.! ALERT ALERT! GMT fuses have a small inherent electrical resistance resulting in a small inherent power loss. For this reason, the GMT fuse manufacturer recommends that the load for GMT fuses up to and including 7.5A not exceed 80% of the fuse rating and that the load for GMT fuse sizes between 10A and 15A not exceed 70% of the fuse rating. For example, the load for a 15A GMT fuse should not exceed 10.5A (15A x.70 = 10.5A). 35. Make sure the load devices are switched off and then install the fuses: Figure 10 - GMT Output Lug Connections NOTE: Under load, TPA modules are disconnect devices only and must not be used to reconnect power to enabled Figure 11 - Installing TPA Fuses equipment loads. Reconnecting a TPA module under power with an enabled load may damage the TPA module. For a TPA fuse, pull out the TPA fuse carrier and insert the operable fuse, as shown in Figure 11. Page 8

For a GMT fuse, pull out the dummy fuse and insert the operable fuse, as shown in Figure 12. Test the power and polarity at the input of each equipment load. 36. If possible, Temporarily replace one of the operable TPA fuses with a blown fuse to check that the FUSE ALARM and the TPA Fuse LEDs light red. Also, check the FUSE ALARM terminals on the rear of the panel: Expect an open circuit ( Ω) between Terminals C and NC. Expect continuity (0Ω) between Terminals C and NO. Re-install operable TPA fuse before proceeding. Likewise, replace one of the operable GMT fuses with a blown fuse to verify that the FUSE ALARM LED and FUSE ALARM terminals are also as specified above. Then, also, re-install the operable GMT fuse before proceeding. 37. If desired, connect the remote external audio/visual alarm indicator wires (solid or tinned wires, #26 to #20 AWG) to the PWR ALARM and FUSE ALARM terminals. 38. Carefully re-install the rear cover. 39. Record TPA and GMT output destinations on the pull-out designation card below the front panel LEDs, as shown in Figure 13. 40. Turn on equipment loads one at a time to verify proper operation of loads. Figure 12 - Installing GMT Fuses Figure 13 - Designation Card Page 9

1.4 Accessories! WARNING WARNING! Use only UL-listed fuses or UL-recognized component secondary protection devices. The following lists optional and replacement items for the panel. For selecting conductors, please refer to Wire Sizing & Label Convention Chart (Telect Part No. 117995) included with your panel. Item Description Part Number Alarm Card, Standard PWR ON / FUSE ALARM LEDs & Contacts 400497 TPA Fuses 5A 124818 10A 124819 15A 124820 20A 124821 30A 122734 40A 122738 50A 122739 GMT Fuses ¼A Violet (VIO) 100151 ½A Red (RED) 004001 ¾A Brown (BRN) 004008 1A Gray (GRY) 100991 1 1 /3A White (WHT) 004006 1½A White/Yellow (WHT/YEL) 004011 GMT Fuses (continued) 2A Orange (ORN) 004002 3A Blue (BLU) 004012 4A White/Brown (WHT/BRN) 004013 5A Green (GRN) 004014 7½A Black/White (BLK/WHT) 004010 10A Red/White (RED/WHT) 004015 12A Yellow/Green (YEL/GRN) 102287 15A Red/Blue (RED/BLU) 102288 Dummy, Phoney, Plastic Slug 132748 Page 10

Item Description Part Number Safety Covers 116915 ETSI Mounting Brackets Black 090-0041-0030 White 090-0041-0031 Designation Card For recording outputs 119807 1.4.1 Compression Lugs Table 1 - Input Power Lugs (¼ in. Dual Holes on ¾ in. Centers, Uninsulated) 2 AWG 1 AWG 1/0 AWG 2/0 AWG 3/0 AWG T & B 54208-0416 (T & B Die Code 37) 54255-0416 (T & B Die Code 42) 54210-0416 (T & B Die Code 45) 54211UB-0416 (T & B Die Code 50) Burndy YA2CL2TC14 E2 Code 10) YA1CL2TC14E 2 Code 11) YA25L2TC14E2 Code 12) YA26L2TC14E2 Code 13) YA27L2TC14E2 Code 13) Panduit LCD2-14B-Q (Panduit Die Code 33) Code 10) LCD1-12B-E (Panduit Die Code 37) Code 11) LCD1/0-14B-X (Panduit Die Code 42) Code 12) LCD2/0-14B-X (Panduit Die Code 45) Code 13) LCD3/0-14B-X (Panduit Die Code 50) Code 14) Table 2 - Ground Lugs (¼ in. Dual Holes on 5 /8-in. Centers, Uninsulated) 6 AWG 4 AWG T & B 54205 (T & B Die Code 24) 54206 (T & B Die Code 29) Burndy YA6CL2TC14 Code 7) YA4CL2TC14 Code 8) Panduit LCD6-14A-L (Panduit Die Code 24) Code 7) LCD4-14A-L (Panduit Die Code 29) Code 8) Page 11

Table 3 - TPA Output Ring Lugs (#10 Screw Terminals, Nylon Insulated Except Where Noted) 14 AWG 12 AWG 10 AWG 8 AWG AMP 36160 35109 35109 324043 Burndy YAE12NBOX YAE12NBOX YAV10BOX YA8CLBOX (Uninsulated) Code 21) Panduit LCA10-10-L LCA10-10-L LCA10-10-L LCA8-10-L (Uninsulated) (Panduit Die Code 21) Code 21) Table 4 - GMT Output Ring Lugs (#6 Screw Terminals, Nylon Insulated) 26 AWG 22 AWG 20 AWG 16 AWG 14 AWG AMP 152658 Burndy YAE22N66FBOX YAE18N25BOX YAE14N76FBOX YAE12N1BOX Page 12

1.5 Schematic Drawing RTN BATT INPUT A C GND TPA OUTPUT RTN A 1 2 3 4 TPA OUTPUT BATT A TPA FUSE HOLDER LEDS NOTE See assembly drawing (rear view, Page 8) for physical location of terminations & labeling. 5 GMT OUTPUT RTN A 4 Panel is not shipped with operable bay alarms. 2 3 GMT OUTPUT BATT A 1 PWR A TPA/GMT FUSE ALARM PWR B REMOVABLE ALARM CARD PWR FUSE BAY ALARMS ALARM ALARM CONTACTS ACTIVATE NO NC CR NC NC NO C A R NO MJ C NC NO C A R C MN C GND 1 TPA FUSE HOLDER LEDS 2 3 4 TPA OUTPUT BATT B TPA OUTPUT RTN B 5 4 3 2 1 GMT OUTPUT BATT B GMT OUTPUT RTN B RTN BATT INPUT B C GND Page 13

1.6 Assembly Drawing NOTES: 1. Dimensions are in in. (cm) or in. (cm) 2. Panel not supplied with fuses. 0.46 (1.17) #10-32 Stud & Nut (Use 3/8" Socket) Lug width 1.00 [2.54] 1/4-20 Hexhead Bolt (Use 7/16" Socket) T P A T P A GMT GMT 0.32 (0.81) #6 Panhead 1/4-20 Stud 0.75 (1.90) 0.625 (1.59) SIDE VIEW (DETAIL) REAR VIEW (ROTATED) 1.15 (2.92) 0.10 (0.25) 10.01 (25.42) 11.86 (30.14) 1.00 (2.54) 2.00 (5.08) 1.00 (2.54) 0.39 (0.98) TOP VIEW 23.00 (58.42) 22.31 (56.67) 19.00 (48.26) 18.31 (46.51) 17.25 (43.82) 1.00 (2.54) 1.72 (4.37) Holes Accommodate EIA/WECO Mounting Patterns Pull-Out Designation Card Below Replacable Alarm Board FRONT VIEW Universal Bracket Reversed for 23" Rack Telect assumes no liability from the application or use of these products. Neither does Telect convey any license under its patent rights or the patent rights of others. This document and the products described herein are subject to change without notice. Page 14