DIN Rail Power Module

Similar documents
Adaptive Power Module

Adaptive Power Module

DIN Power Module - Phase Adaptive

GP Dimming Panels 230 Volt (CE)

GP Dimming Panels. GRAFIK Systems SPECIFICATION SUBMITTAL

LP Dimming Panels. GRAFIK Systems

Phase-Adaptive Power Module with 3-Wire Fluorescent Input

Phase-Adaptive Power Module

GP Dimming Panels 230 Volt (CE)

LCP128T Spec Grade Dimming System

Phase-Adaptive Power Module

Switching Power Module

3-Wire Fluorescent Power Module

EcoSystemT 5-Series LED Driver ( V~, CE)

QS Motor Group Controller QSE-CI-4M-D 4-Output AC Motor Controller. Energi Savr NodeTM Unit. seetouchr QS Wallstation. Wireless Communication

Hi-lume LED Overview. LED Dimming Driver Hi-lume LED Architectural Dimming

Installation & User Instructions

Series L9 UL489 Miniature Circuit Breakers

Wired Vareo Local Lighting Controls

Ecosystem 5 Percent 3-Wire and Ecosystem Digital Link Controlled T4 Compact, 1 Lamp, Ballast Factor Of 0.95, K-Can, Studded, 26/32W

AXA DALI P20. DALI Broadcast Controller. Installation Manual

EcoSystemR Multiple Control Input Ballasts

DSE201 Compact design with enhanced protection

Industry Compliance The cabinet and modules are Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc.

EcoSystem Multiple Control Input Ballasts

Spring-Return Damper Actuator NF24(-S)

NEMA Pump Controls Class 82 slim line NEMA pump controller for the agricultural industry Answers for industry.

Features. LED Driver. RACT09 9 Watt. TRIAC Dimmable. Single Output RACT09- AC/DC Converter

4 x 0-10Vdc Channels Fused 24V o/p terminals for actuator power Direct or buffered output signals

INSTALLATION. **Microprocessor Status LED:

Differential Temperature Controller

Electric Actuator Instructions

Compact SE Overview. High-Performance Dimming. Ballast

Thermal overload relays Type TA Class 10

Application Note #466 Revision I May 2018

User Manual. Solar Charge Controller 3KW

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

FDBT S 32W120V DM Bal

User Manual Solar Charge Controller 3KW

Electronic Circuit Breaker ESS20-0..

Series L9 UL-489 Miniature Circuit Breakers

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors

Constant Voltage TRIAC Dimmable Driver---120W Series. Features

MVF461H Series Modulating Control Valves with Magnetic Actuators, Positioning Control and Position Feedback for Hot Water and Steam

ELECTRIC ACTUATOR 94OE IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

Circuit Protection. Circiut Protection

Wired Maestro Local Controls

A.C.E.S. Series ACES 3 & 6 MODULE PANELS. System Manual. Touch-Plate Lighting Controls. ACES 3 & 6 Module System Manual

EcoSystem Multiple Control Input Ballasts

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

825-P Modular Protection System for motors Specification Guide

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS

DX³ 4-pole RCBO 6000 A/10 ka

Product Data Sheet. Damper Interface. Features

Soft Starter. Types RSBD. Product Description. Type Selection. Ordering Code RSB D E V 61 HP

Electronic Circuit Breaker ESS20

Pneumatic Isolation Module

HomeWorks QS Power Supply with Wire Harnesses

Btdin RCBO 6000A up to 63A (2P)

Fluorescent (non-capacitive) Metal Halide 10A. 2 Any load circuit can be connected to any phase.

SECTION MOTOR CONTROL

GRX-TVI Ten Volt Interface

Zurik EMLV LED Driver

DIN Rail UPS Model: DIN-UPS Installation/Operation Manual

Safety Control HR1S-AC. Safety Relay HR1S-AC

OTEC Transfer switch open transition

Sentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification

Controls. CONTROLS AND ACCESSORIES PRODUCT FAMILY FEATURES DIMMERS DIMENSIONS SPECIFICATION SERIES STANDARD FEATURES

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

Demarcation Fuse/Circuit Breaker Alarm Panel 125DM08. Installation Guide

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

EcoSystem Dimming Power Module for 3-wire Lutron Dimming Ballasts. EcoSystem One-Line. EcoSystem C5-BMJ-16A. EcoSystem Dimming Module

COMPLETE SOLUTIONS FOR POWER PROTECTION

GRX-TVI Ten Volt Interface

Compact SE Overview. High-Performance Dimming. Ballast

Power Supplies. Power Supplies. PS5R Standard Series. PS5R Standard Series Switching Power Supplies

FL ballasts Electronic fixed output PC BASIC, 4 28 W PC BASIC

LED Driver Linear / area fixed output

Zone Selective Interlocking

Models. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery

Motor Controllers AC Semiconductor Motor Controller Type RSHP Flexy

FL ballasts Electronic fixed output. PC BASIC sl, 4 28 W PC BASIC

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

EPS-ECONOMY PUMP STARTER

QUALITY ASSURANCE & DOCUMENTATION

Essential equipment for all your requirements

DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual

NEW The new PROmax power supplies offer a wide range of robust solutions for demanding application requirements.

Cat N 3. OVERALL DIMENSIONS

DX³ RCCBs - ID 4P up to 100 A

FT-10 Network Digital I/O Module Kits and

Technical Data Sheets

Transfer switch OTEC and OTECSE open transition

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left

1 Safety instructions. 2 Intended use. 3 Product characteristics. 4 Operation. LB management. Universal touch dimmer insert LED

Control Circuit Protection

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

and other modular devices for low voltage installation

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

Transcription:

800 W ax 500 W ax 500 W ax 500 W ax i Temp 230 V~ 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 DIN Rail odule omeworksr QS Phase Adaptive Fixture Controller DIN Rail odule The DIN Rail odule family is a group of modular products for the control of lighting loads. This document describes the following product: DIN Rail odule Phase Adaptive (model ) Features DIN Rail odules can be used in a omeworksr QS system. Automatically selects leading edge or trailing edge dimming for incandescent/halogen, electronic/magnetic low voltage and neon/cold cathode light sources. Controls dimmable CF/ED loads, contact utronr for compatibility with CF/ED light sources. RTISSR technology ensures that each output dims smoothly and is flicker-free. Unit is 12 DIN modules (216 mm) wide. 800 W ax 500 W ax 500 W ax 500 W ax i Temp 230 V~ 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 DIN Rail odule 369-583b 1 01.31.12 Provides air gap off (when all zones are off). Integral protection for common temporary overcurrent and over-voltage conditions. EDs on front of unit provide diagnostic information. Includes QS link for seamless integration of lights and controls. System Example Contact Closure seetouchr QS Wallstation DIN Rail odule omeworksr QS Panel QS Contact Closure Interface GRAFIK EyeR QS QS ink Up to 100 total QS devices DIN Rail odule Phase Adaptive DIN Rail odule 220 240 V~ Control { 4 Phase Adaptive outputs, 800 W (Zone 1) 1, 500 W (Zones 2, 3 and 4) 1 Notes: 1 See "Output Zone Ratings" in "Specifications" section, for specific load types ratings. odel Numbers:

DIN Rail odule omeworksr QS Phase Adaptive Fixture Controller Out of Box Functionality This section describes the default functionality when the unit is first installed. 369-583b 2 01.31.12 Emergency Contact Closure () When the is open, the DIN Rail odule will enter Emergency ode, which will turn on all loads to their emergency level and disable control of local zones and QS devices. When the is closed or jumpered, DIN Rail odule zones will return to the settings or levels they were at prior to entering Emergency ode. is local control only and cannot control other DIN Rail odule over the QS link. on multiple DIN Rail odule may be connected to an Emergency or anual override device in parallel if event is intended to affect multiple units. Emergency level is configurable for each zone. Normal ode Operation Zone and raise/lower buttons on the unit can be used to: turn loads on and off. dim loads up and down. odel Numbers:

DIN Rail odule omeworksr QS Phase Adaptive Fixture Controller Specifications DIN Rail odule 220-240 V~ 50/60 z ightning strike protection meets ANSI/IEEE standard 62.31-1980. Can withstand voltage surges of up to 6 000 V and current surges of up to 3 000 A. Standards IEC/EN 60669-2-1 CE marked utronr Quality Systems registered to ISO 9001.2008 Environment Ambient Temperature Operating Range (inside mounting panel within 2 cm of unit): 0 ºC to 35 ºC Calibration point maximum: 70 ºC (see ounting on page 4) Relative humidity: less than 90% non-condensing For indoor use only Terminals ains wiring: 1.2 N m 0.2-4 mm² (solid or stranded) Zone wiring: 1.2 N m 0.2-4 mm² (solid or stranded) wiring: 0.5 N m 0.2-4 mm² (solid or stranded) QS ink: 0.5 N m 0.5-4 mm² (solid or stranded) 369-583b 3 01.31.12 Output Zone Ratings Automatically selects leading edge or trailing edge dimming or can also be manually configured for a specific load type. Patented RTISSR circuitry compensates in real time for incoming line frequency variations: up to ± 2% change in frequency/second. Internal relay provides an air gap off when all zones are off. Each zone has no minimum load requirement. Each zone is rated for the following load types 1, 2 : oad Type Zone 1 Zone 2, 3 and 4 Rating Rating (per zone) Incandescent/alogen 800 W 500 W Electronic ow Voltage 800 W 500 W agnetic ow Voltage 800 VA (600 W 3 ) 500 VA (375 W 3 ) Neon/Cold Cathode 800 VA (600 W 3 ) 500 VA (375 W 3 ) 1 Additional load type options are available in the omeworksr QS GUI, some may require an interface. Contact utron for details. 2 Contact utron for compatibility with dimmable CF/ED light sources. 3 Actual lamp wattage One load type per zone. Output must be directly connected to the load. oad side switching is not recommended. Run a separate neutral for each load circuit. A common neutral connection is not recommended. Unit may be powered by Ground Fault Interrupter (GFI) or Residual Current Circuit Breaker with Overload (RCBO) protected circuit if required. oad circuit wiring (from breaker to unit to load) must be run in its own non-metallic conduit, or nuisance tripping may occur. aximum 30.5 m (100 ft) between power module and load. ounting Use an IP20 (minimum) rated consumer panel or breaker panel with integrated DIN rail. Unit is 12 DIN modules (216 mm) wide. odel Numbers:

DIN Rail odule omeworksr QS Phase Adaptive Fixture Controller ounting 369-583b 4 01.31.12 ount in IP20 (minimum) rated consumer panel or breaker panel with integrated DIN rail. ount unit in orientation shown. Unit may be mounted by unlocking the four mounting clips on the back of the unit. Clips must be locked once unit to securely attached the unit to the DIN rail. ount in an accessible and serviceable location. Unit generates heat, maximum 75 BTUs/our ount unit such that: Ambient Temperature Operating Range (inside mounting panel within 2 cm of unit): 0 ºC to 35 ºC -Calibration point maximum: 70 ºC - Derate unit or cool mounting panel as needed to maintain the above temperature requirements. 800 W ax 500 W ax 500 W ax 500 W ax i Temp 230 V~ 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 DIN Rail odule ocked 4 mounting clips on unit Unlocked echanical Dimensions Top View 800 W ax 500 W ax 500 W ax 500 W ax i Temp DIN Rail odule 90 mm 230 V~ 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 Side View 216 mm 70 mm 76 mm 55 mm 90 mm odel Numbers:

DIN Rail odule omeworksr QS Phase Adaptive Fixture Controller Overview of Wiring Terminals 369-583b 5 01.31.12 Contact Closure QS ink 800 W ax 500 W ax 500 W ax 500 W ax i Temp DIN Rail odule 230 V~ 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 N N N N N D1 D2 D3 D4 ains oad Neutrals Zone 1 Zone 3 ains Wiring Zone 2 Zone 4 Phase Adaptive Outputs odel Numbers:

DIN Rail odule omeworksr QS Phase Adaptive Fixture Controller Bypass Jumper 369-583b 6 01.31.12 Unit ships with bypass jumper pre-installed. Jumper should not be removed until load wiring is verified. 800 W ax 500 W ax 500 W ax 500 W ax i Temp DIN Rail odule 230 V~ 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 N N N N N D1 D2 D3 D4 Bypass Jumper odel Numbers:

DIN Rail odule omeworksr QS Phase Adaptive Fixture Controller ains Voltage Wiring 369-583b 7 01.31.12 800 W ax 500 W ax 500 W ax 500 W ax i Temp 800 W ax 500 W ax 500 W ax 500 W ax 230 V~ 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 DIN Rail odule r p DIN Rail odule Zone 1 Example 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 N N N N N D1 D2 D3 D4 Distribution Panel Earth ive Neutral Dim ive (220-240 V~) Neutral oad Wiring from Distribution to DIN Rail odule Turn off all circuit breakers or isolators feeding the DIN Rail odule at distribution panel. Run live, neutral, and earth( ) wires from a 220-240 V~ 50/60 z feed to the DIN Rail odule unit. Run a separate neutral for each load circuit. A common neutral connection is not recommended. ains Wiring and IEC PEV Separation Follow appropriate local and national codes to avoid violating required separation guidelines. odel Numbers:

DIN Rail odule omeworksr QS Phase Adaptive Fixture Controller Wiring: Emergency Contact Closure 800 W ax 500 W ax 500 W ax 500 W ax i Temp 230 V~ 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 DIN Rail odule Common 369-583b 8 01.31.12 IEC PEV Emergency Contact Closure Contact Closure () wiring is IEC PEV. Follow all applicable national and local codes for proper circuit separation and protection. Turn off all breakers or isolators feeding the DIN Rail odule at distribution panel before servicing unit. When in emergency mode, all zone outputs will be at their programmed emergency light level (configurable to each zone, default is 100%). All sensors and controls are locked out. Emergency contact closure input is normally closed (NC). The DIN Rail odule is shipped with a jumper pre-installed. Note: The DIN Rail odule will default to Emergency ode if the is left open. If no Emergency Contact Closure is required, please leave the wire jumper in the terminals. CO 800 W ax 500 W ax 500 W ax 500 W ax www.lutron.com +44.(0)20.7702.0657 odel Numbers:

DIN Rail odule omeworksr QS Phase Adaptive Fixture Controller Wiring: QS ink 800 W ax 500 W ax 500 W ax 500 W ax i Temp 230 V~ 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 DIN Rail odule QS ink IEC PEV Wiring 369-583b 9 01.31.12 ink communicates using IEC PEV wiring. Turn off all breakers or isolators feeding the DIN Rail odule at distribution panel before servicing unit. Follow all applicable national and local codes for proper circuit separation and protection. Wiring may be daisy chained or t-tapped. Total length of QS link must not exceed 600 m. For lengths under 150 m, use two 1,0 mm 2 conductors for control power (24 V-, CO). For lengths over 150 m, use two 4,0 mm 2 conductors for control power (24 V-, CO). Use one, twisted-shielded pair of 1,0 mm 2 conductors for data link (UX, _). 0 W ax (1) CO one 4 (2) Do Not Connect Teminal 2 1 (3) UX (4) UX Daisy-Chain Wiring Example seetouchr QS wallstations QSE-IO 702.0657 T-Tap Wiring Example seetouchr QS wallstations QSE-IO 1 Unit does not consume or supply PDUs on the QS link. Do not connect the 24 V- wire to unit. Note: 24 V- wire must bypass the unit if other devices on the link consume PDUs. odel Numbers: