SOLID CONE SPRAY NOZZLES TECHNICAL DATA

Similar documents
model E Spray nozzles vk810 - vk817

TECHNICAL DATA OBSOLETE

FRAME STYLE SPRAY NOZZLES TECHNICAL DATA

TECHNICAL DATA VK810 (65 ) VK811 (80 ) VK812 (95 ) VK813 (110 )

mirage standard and Qr concealed pendent sprinkler vk462 and hp sprinkler vk463 (K5.6)

TECHNICAL DATA SPRINKLER ESCUTCHEONS

MEDIUM VELOCITY WATER SPRAY NOZZLE

TECHNICAL DATA SHEET. Medium Velocity Water Spray Nozzle. Page 1. Description. Technical and Environmental Specification. Installation & Maintenance

GW THERMOCOOL NOZZLE STRUCTURAL STEEL PROTECTION

TECHNICAL DATA. Trimpac 244a. April 15, 2011

Model F1 Res Sprinklers engineered for the lowest flows to meet the minimum design density of.05 gpm/ft 2

TECHNICAL DATA. Trimpac 249a. September 16, 2013

Data Sheet Issue E

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA CAUTION

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications

Model F1 Model F1 Recessed Standard Response Sprinklers

Listings and Approvals. G5 QR Gasket culus QR G5 SR Gasket culus, FM SR G5

TECHNICAL DATA OBSOLETE

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P)

TECHNICAL DATA. Q= C v P S

TECHNICAL DATA 1-1/2 (dn40)

Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP804

Easy Riser swing check valve Models E-1 & F-1

Directional Spray Nozzles, Open, with Strainers High Velocity General Description

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150)

MODELS F822 THRU F834

Model DDX Deluge Valves 4" (100 mm), 6" (150 mm) and 165 mm Sizes

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

MEDIUM VELOCITY WATER SPRAY NOZZLE

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description

Wet pipe low flow foam/water manifold system

Q= C v P S. Flow control valve Model j-2 Halar coated

ALARM CHECK VALVE 3", 4" & 6" MODEL H-1 FLANGE/FLANGE 3" & 4" MODEL H-2 GROOVE/GROOVE 3", 4" & 6" MODEL H-3 FLANGE/GROOVE

Data Sheet High Velocity Water Spray Nozzle. Issue B. Rapidrop Global. Ref: SPTDHV/E TECHNICAL DATA MAINTENANCE DESCRIPTION

Fire Protection Systems

Data Sheet 11.1 Issue A

MODEL: HV-AS & HV-BS TECHNICAL DATA : MAINTENANCE DESCRIPTION PRESSURE (3/4 NPT OPTIONAL)

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11

TECHNICAL DATA. Table Standard Materials

HIGH VELOCITY WATER SPRAY NOZZLE (BRASS)

Instructions for Installation, Operation, Care and Maintenance

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL J-2 HALAR COATED 1-1/2 & 2 (DN40 & DN50) 1. DESCRIPTION

Data Sheet 11.2 Issue B

Model DDX Deluge Valve 8 (200mm) Features

Foam Ratio Controller Proportioning Devices Model KFP

In-Line Balanced Pressure Proportioner (ILBP) Proportioning Devices Model KBP

Features 1. Differential Latch-type, lightweight, dependable

Instructions for Installation, Operation, Care and Maintenance

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications

SPRAYTECS Series UP High Velocity Directional Spray Nozzles, Open, Non-Automatic. Suitable for Water Spray fixed systems.

Instructions for Installation, Operation Care and Maintenance

WATER SPRAY NOZZLE DATA SHEET

Instructions for Installation, Operation, Care and Maintenance

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS.

Data Sheet 3.03 Issue D

TECHNICAL DATA OBSOLETE

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

TECHNICAL DATA OBSOLETE

VNIV.EX454 Sprinklers, Automatic and Open. Sprinklers, Automatic and Open

Part 1: Land Applications Machinery Spaces, Industrial Hazards, Combustion & Gas Turbine Enclosures, Light & Ordinary Hazards

Data Sheet 3.01 Issue C

Foam Maker Discharge Devices Model KLF

I-VICFLEX.AB7 VicFlex Sprinkler Fittings for Ceiling Suspension Systems STYLE AB7

TECHNICAL DATA 2-1/2-8 (dn65 - dn200)

Installation Manual DIAPHRAGM WELL TANK

TECHNICAL DATA. mixture, with a freeze temperature

Model VKFD28 Flexible Sprinkler Drops (LPCB Approved) Installation Manual. January 2016 Form No. F_ Rev 16.1

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING

I-VICFLEX.AB11. Victaulic VicFlex Style AB11 Low-Profile Sprinkler Fitting for Suspended Ceiling Systems WARNING INSTALLATION INSTRUCTIONS

GW M5 WATER MIST NOZZLE K-5, LOW PRESSURE, NON-AUTOMATIC

2000 Series Heavy-Duty Irrigation Valves Recommended Applications Golf Courses Landscapes Parks Right-of-ways

The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York Bulletin 617 Rev. C

TotalPac 3 Deluge, Electric release Remote controlled system

7. Protection System Testing

DELUGE VALVE DATA SHEET

Installation, Operation and Maintenance Manual

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description

TECHNICAL DATA OBSOLETE. Inlet Type Outlet Type in mm. Thread Thread in. ANSI B Flanged Flanged in.

4077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE FAX

TotalPac 3 Deluge system Pneumatic release

INSTALLATION & MAINTENANCE GUIDE

OBSOLETE DESIGN DATA. 3", 4", 6" and 8" CONCENTRATE CONTROLLERS

MACH 1A HVLP (MACH 1AV HVLP) Automatic Airspray Gun

A. This Section includes natural gas piping, specialties, and accessories within the building.

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

TECHNICAL DATA P S. Q= Cv MODEL E-2 DELUGE VALVE HALAR COATED ANGLE STYLE

GROOVED COUPLINGS - STANDARD FLEXIBLE Model 101

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION. A. Pipe, fittings, valves, and connections for sprinkler systems.

SolidMatrix 1206 Fast Acting Surface Mount Fuses

I-VICFLEX.AB5. Victaulic VicFlex Style AB5 Sprinkler Fitting for Wood or Metal Joists/Studs and CD Profile (60 mm) Channel Ceiling Systems WARNING

TYPE-CERTIFICATE DATA SHEET

SERIES 670E End-of-Line Deflagration Flame Arrester

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 227b - d

SAM-e. Engineering Manual

Select Viking Replacement Parts (Use in Conjunction with Viking Replacement Parts Book) Item # Description List Price Item # Description List Price

ATTENTION! READ BEFORE ATTACHING THE AIR HOSE

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

Transcription:

November 2, 2007 Spray Nozzle 20 SOLID CONE SPRAY NOZZLES 1. DESCRIPTION Viking Model A-2, A-2X, B-2, C-2, and D-2 Solid Cone Spray Nozzles are non-automatic pattern, open, directional discharge spray nozzles. The spray nozzle units feature two-piece construction consisting of a cast bronze body and threaded insert. The insert determines the included angle of discharge and the body construction provides a uniform distribution throughout the discharge pattern. When spraying, the nozzle discharge forms a solid, cone-shaped spray pattern meeting the requirements for medium- and high-velocity water spray systems. Optional dust plugs are available to prevent foreign material from entering the open end of the spray nozzle. They are designed to blow off when the system piping is pressurized. 2. LISTINGS AND APPROVALS culus Listed: Category VGYZ FM Approved: Water-Spray Systems-consult FM Approval Guide for acceptable applications. NYC Approved: Calendar Number 219-76-SA, Bulletin No. 16, Vol. LXI NOTE: International approval certificates are available upon request. The nozzles are approved for use in medium- and high-velocity water spray systems. Refer to the Approval Charts on pages 23-24 and Design Criteria on page 25 for culus and FM approval requirements that must be followed. 3. Specifications: Available since 1971. The water inlet is at a 90 angle to the nozzle outlet. The smallest nozzle passage is 1/4 (6 mm) for Part Nos. 05133AAJ through 05134AJN; 11/32 (9 mm) for Part Nos. 05135AAJ through 05135AJN; 3/8 (10 mm) for Part Nos. 05136AAJ through 05136AJN; and 7/16 (11 mm) for Part Nos. 05137AAJ through 05137AJN. All bodies are permanently marked with the model number. All inserts are permanently marked with the angle of discharge and model. Inserts may be stamped with more than one model, which indicates the insert may be interchanged with either type of nozzle body. Inserts are available in spray angles of 30, 60, 90, 120, and 140, and are interchangeable in a given body model. Refer to pages 25-29 for spray nozzle water distribution patterns. Thread size: 1/2 (15 mm) NPT male thread is standard Nominal K-Factors: Refer to the Approval Charts Dust Plugs (Optional): Red Polyethylene Cap: 1 (25 mm) deep Rated for a continuous temperature of 220 F (104 C). Spray Nozzle Material Standards: Body Casting: Brass UNS-C84400 Insert: Brass UNS-C36000 Solid Cone Spray Nozzles Viking Technical Data may be found on The Viking Corporation s Web site at http://www.vikinggroupinc.com. The Web site may include a more recent edition of this Technical Data Page. Spray Nozzle Dust Plug Ordering Information: (Also refer to the current Viking price list.) Order Model A-2, A-2X, B-2, C-2, and D-2 Solid Cone Spray Nozzles by selecting the appropriate part number from the Approval Charts. Available Finishes: Brass or Electroless Nickel. Refer to the Approval Charts Form No. F_030789 Replaces pages 20-32, dated February 3, 2007. (Same VK# assigned for Brass and Electroless Nickel finishes.)

Spray Nozzle 21 November 2, 2007 SOLID CONE SPRAY NOZZLES For example, Spray Nozzle Model A-2 (VK740) with a 1.2 K-Factor, a 30 spray angle, and a Brass finish = Part No. 05133AAJ Dust Plugs (Optional): Dust plugs are used to prevent the depositing of foreign materials in the waterway, which could interfere with the discharge of the spray nozzles. The plugs are designed to blow off when the system piping is pressurized. Part Number 02409A for use with Spray Nozzle Part Nos. 05133AAJ through 05135AJN. Part Number 02410A for use with Spray Nozzle Part Nos. 05136AAJ through 05137AJN. 4. INSTALLATION WARNING: Viking Model A-2, A-2X, B-2, C-2, and D-2 Solid Cone Spray Nozzles are manufactured and tested to meet the rigid requirements of the approving agency. The nozzles are designed to be installed in accordance with recognized installation standards. Deviation from the standards or any alteration to the nozzle after it leaves the factory including, but not limited to: painting, plating, coating, or modification, may render the unit inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation. The Approval Charts on pages 23-24 show listings and approvals of Model A-2, A-2X, B-2, C-2, and D-2 Spray Nozzles for use on water spray systems. The charts show listings and approvals available at the time of printing. Other approvals are in process. Check with the manufacturer for any additional approvals. A. Spray nozzles are to be installed in accordance with the latest edition of Viking technical data, the latest published standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards whenever applicable. The use of Model A-2, A-2X, B-2, C-2, and D-2 Spray Nozzles may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction prior to installation. B. Spray nozzles are installed on fixed fire protection systems, such as deluge systems, where total flooding is required. C. Handle Spray Nozzles with care. They must be stored in a cool, dry place in their original shipping container. Never install a spray nozzle that has been dropped or damaged. D. Corrosion-resistant spray nozzles must be installed when subject to corrosive atmospheres. When installing corrosion resistant nozzles, take care not to damage the corrosion resistant coating. E. Spray nozzles must be installed after the piping is in place to prevent mechanical damage. F. Before installing, be sure to have the appropriate model, with the correct K-Factor, spray angle, and insert. Spray nozzle bodies are permanently marked with the model number. All inserts are permanently marked with the angle of discharge and model. Inserts may be stamped with more than one model, which indicates the insert may be interchanged with either type of nozzle body. 1. Apply a small amount of pipe-joint compound or tape to the external threads of the spray nozzle only, taking care not to allow a build-up of compound inside the inlet. 2. Install the nozzle on the fixed piping using a standard crescent wrench. Take care not to over-tighten or damage the spray nozzle. G. Spray nozzles must be protected from mechanical damage. Where open spray nozzles are used, care must be taken to prevent foreign materials from entering the orifice. Foreign materials may accumulate and restrict or plug the waterway and may prevent proper operation of the spray nozzle. H. Install dust plugs (if used): After installing the spray nozzle unit, press the dust cover over the end of the nozzle insert. 5. OPERATION Model A-2, A-2X, B-2, C-2, and D-2 Solid Cone Spray Nozzles are designed to apply cooling water to exposed vertical, horizontal, curved, and irregular shaped surfaces to allow cooling of objects externally when exposed to an adjacent fire. Cooling is done to prevent objects from absorbing heat that could cause structural damage and possible spread of fire to the protected object. In some applications, Model A-2, A-2X, B-2, C-2, and D-2 Spray Nozzles may be applied to control or extinguish fire of the protected area (depending on water design application density). 6. INSPECTIONS, TESTS AND MAINTENANCE NOTICE: The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the NFPA standard (e.g., NFPA 25) that describes care and maintenance of sprinkler systems. In addition, the Authority Having Jurisdiction may have additional maintenance, testing, and inspection requirements that must be followed.

November 2, 2007 Spray Nozzle 22 SOLID CONE SPRAY NOZZLES TABLE 1: SPRAY NOZZLE DIMENSIONS SIN A B C D E F G H VK740-VK769 1-7/8 (48 mm) 7/8 (22 mm) 1/2 (13 mm) 1-5/8 (41 mm) 13/16 (21 mm) 5/16 (8 mm) 1-17/64 (32 mm) 1-11/16 (43 mm) VK770-VK789 2-1/16 (52 mm) 1 (25 mm) 5/8 (16 mm) 2-3/16 (56 mm) 1 (25 mm) 3/8 (10 mm) 1-17/32 (39 mm) 2 (51 mm) Figure 1: Spray Nozzle Dimensions

Spray Nozzle 23 November 2, 2007 SOLID CONE SPRAY NOZZLES Part Number 1 SIN Nominal K-Factor Approval Chart 1 Model A-2, A-2X, B-2, C-2, and D-2 Spray Nozzles - Brass Finish Angle Listings and Approvals 3 (Refer also to Design Criteria on page 25.) Part Number 1 SIN Nominal K-Factor Angle Listings and Approvals 3 (Refer also to Design Criteria on page 25.) U.S. metric 2 culus 4 NYC 5 FM LPCB U.S. metric 2 culus 4 NYC 5 FM LPCB Model A-2 Brass Finish 05133AAJ VK740 1.2 17.3 30 Yes Yes Yes Yes 05133AAM VK743 1.4 20.2 120 Yes Yes Yes Yes 05133AAK VK741 1.2 17.3 60 Yes Yes Yes Yes 05133AAN VK744 1.4 20.2 140 Yes Yes Yes Yes 05133AAL VK742 1.2 17.3 90 Yes Yes Yes Yes -- -- -- -- -- -- -- -- -- Model A-2X Brass Finish 05134AAJ VK750 2.0 28.8 30 Yes Yes Yes -- 05134AAM VK753 2.2 31.7 120 Yes Yes Yes -- 05134AAK VK751 2.0 28.8 60 Yes Yes Yes -- 05134AAN VK754 2.2 31.7 140 Yes Yes Yes -- 05134AAL VK752 2.0 28.8 90 Yes Yes Yes -- -- -- -- -- -- -- -- -- -- Model B-2 Brass Finish 05135AAJ VK760 2.8 40.4 30 Yes Yes Yes Yes 05135AAM VK763 3.3 47.6 120 Yes Yes Yes Yes 05135AAK VK761 2.8 40.4 60 Yes Yes Yes Yes 05135AAN VK764 3.3 47.6 140 Yes Yes Yes Yes 05135AAL VK762 2.8 40.4 90 Yes Yes Yes Yes -- -- -- -- -- -- -- -- -- Model C-2 Brass Finish 05136AAJ VK770 3.4 49.0 30 Yes Yes Yes Yes 05136AAM VK773 3.9 56.2 120 Yes Yes Yes Yes 05136AAK VK771 3.4 49.0 60 Yes Yes Yes Yes 05136AAN VK774 3.9 56.2 140 Yes Yes Yes Yes 05136AAL VK772 3.8 54.8 90 Yes Yes Yes Yes -- -- -- -- -- -- -- -- -- Model D-2 Brass Finish 05137AAJ VK780 4.7 67.8 30 Yes Yes Yes Yes 05137AAM VK783 5.2 75.0 120 Yes Yes Yes Yes 05137AAK VK781 4.7 67.8 60 Yes Yes Yes Yes 05137AAN VK784 5.2 75.0 140 Yes Yes Yes Yes 05137AAL VK782 5.0 72.1 90 Yes Yes Yes Yes -- -- -- -- -- -- -- -- -- Footnotes 1 Spray nozzle bodies are permanently marked with the model number. All inserts are permanently marked with the angle of discharge and model. Inserts may be stamped with more than one model, which indicates the insert may be interchanged with either type of nozzle body. 2 Metric K-Factor shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-Factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 Approved by the NYC Board of Standards and Appeals, MEA No. 219-76-SA, Bulletin No. 16, Vol. LXI.

November 2, 2007 Spray Nozzle 24 SOLID CONE SPRAY NOZZLES Part Number 1 SIN Nominal K-Factor Approval Chart 2 Model A-2, A-2X, B-2, C-2, and D-2 Spray Nozzles - Electroless Nickel Finish Angle Listings and Approvals 3 (Refer also to Design Criteria on page 25.) Part Number 1 SIN Nominal K-Factor Angle Listings and Approvals 3 (Refer also to Design Criteria on page 25.) U.S. metric 2 culus 4 NYC 5 FM LPCB U.S. metric 2 culus 4 NYC 5 FM LPCB Model A-2 Electroless Nickel Finish 05133AJJ VK740 1.2 17.3 30 Yes Yes Yes Yes 05133AJM VK743 1.4 20.2 120 Yes Yes Yes Yes 05133AJK VK741 1.2 17.3 60 Yes Yes Yes Yes 05133AJN VK744 1.4 20.2 140 Yes Yes Yes Yes 05133AJL VK742 1.2 17.3 90 Yes Yes Yes Yes -- -- -- -- -- -- -- -- -- Model A-2X Electroless Nickel Finish 05134AJJ VK750 2.0 28.8 30 Yes Yes Yes Yes 05134AJM VK753 2.2 31.7 120 Yes Yes Yes Yes 05134AJK VK751 2.0 28.8 60 Yes Yes Yes Yes 05134AJN VK754 2.2 31.7 140 Yes Yes Yes Yes 05134AJL VK752 2.0 28.8 90 Yes Yes Yes Yes -- -- -- -- -- -- -- -- -- Model B-2 Electroless Nickel Finish 05135AJJ VK760 2.8 40.4 30 Yes Yes Yes Yes 05135AJM VK763 3.3 47.6 120 Yes Yes Yes Yes 05135AJK VK761 2.8 40.4 60 Yes Yes Yes Yes 05135AJN VK764 3.3 47.6 140 Yes Yes Yes Yes 05135AJL VK762 2.8 40.4 90 Yes Yes Yes Yes -- -- -- -- -- -- -- -- -- Model C-2 Electroless Nickel Finish 05136AJJ VK770 3.4 49.0 30 Yes Yes Yes Yes 05136AJM VK773 3.9 56.2 120 Yes Yes Yes Yes 05136AJK VK771 3.4 49.0 60 Yes Yes Yes Yes 05136AJN VK774 3.9 56.2 140 Yes Yes Yes Yes 05136AJL VK772 3.8 54.8 90 Yes Yes Yes Yes -- -- -- -- -- -- -- -- -- Model D-2 Electroless Nickel Finish 05137AJJ VK780 4.7 67.8 30 Yes Yes Yes Yes 05137AJM VK783 5.2 75.0 120 Yes Yes Yes Yes 05137AJK VK781 4.7 67.8 60 Yes Yes Yes Yes 05137AJN VK784 5.2 75.0 140 Yes Yes Yes Yes 05137AJL VK782 5.0 72.1 90 Yes Yes Yes Yes -- -- -- -- -- -- -- -- -- Footnotes 1 Spray nozzle bodies are permanently marked with the model number. All inserts are permanently marked with the angle of discharge and model. Inserts may be stamped with more than one model, which indicates the insert may be interchanged with either type of nozzle body. 2 Metric K-Factor shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-Factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 Approved by the NYC Board of Standards and Appeals, MEA No. 219-76-SA, Bulletin No. 16, Vol. LXI.

Spray Nozzle 25 November 2, 2007 SOLID CONE SPRAY NOZZLES DESIGN CRITERIA (Also refer to the Approval Charts on pages 23-24.) culus Listing Requirements: Refer to the installation standards, such as NFPA 15, for minimum water supply requirements, nozzle pressure, and installation guidelines. FM Approval Requirements: Consult FM Approval Guide for acceptable applications. For installation in accordance with the latest applicable FM Loss Prevention Data Sheets and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and distance below the ceiling. NOTE: The FM installation guidelines may differ from culus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Viking spray nozzles are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. A. Spray nozzles must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. Where open spray nozzles are installed, verify that foreign materials (such as dust, dirt, etc.) do not restrict or plug the waterspray. The frequency of inspections may vary due to corrosive atmospheres, water supplies, and activity around the device. It is also recommended that outdoor installations of Solid Cone Spray Nozzles with dust plugs be periodically inspected, during freezing weather conditions, for the presence of ice buildup from trapped condensate which could effect the proper release of the plugs. B. Spray nozzles that have been painted or mechanically damaged must be replaced immediately. Nozzles showing signs of corrosion shall be tested and/or replaced immediately as required. When replacing spray nozzles, use only new spray nozzles. 1. Using a standard crescent wrench, remove the old spray nozzle and install the new unit. Care must be taken to ensure that the replacement spray nozzle is the proper model, with the correct K-Factor and insert. Spray nozzle bodies are permanently marked with the model number. All inserts are permanently marked with the angle of discharge and model. Inserts may be stamped with more than one model, which indicates the insert may be interchanged with either type of nozzle body. C. The spray nozzle discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or otherwise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional nozzles installed. D. Fire protection systems that have been subjected to a fire must be returned to service as soon as possible. The entire system must be inspected for damage and repaired or replaced as necessary. Spray nozzles that have been exposed to corrosive products of combustion or high ambient temperatures, should be replaced. Refer to the Authority Having Jurisdiction for minimum replacement requirements. 7. AVAILABILITY The Viking Model A-2, A-2X, B-2, C-2, and D-2 Solid Cone Spray Nozzles are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking s current list price schedule or contact Viking directly.

November 2, 2007 Spray Nozzle 26 SOLID CONE SPRAY NOZZLES - WATER DISTRIBUTION PATTERNS A2X (VK750-VK754 ) 05134AA & 05134AJ* Angle: 30 K-Factor: 2.0 U.S. (28.8 A2X (VK750-VK754 ) 05134AA & 05134AJ* Angle: 60 K-Factor: 2.0 U.S. (28.8 A2X (VK750-VK754 ) 05134AA & 05134AJ* Angle: 90 K-Factor: 2.0 U.S. (28.8 A2X (VK750-VK754 ) 05134AA & 05134AJ* Angle: 120 K-Factor: 2.2 U.S. (31.7 Scale: Each square equals one square foot. Spray Nozzle Identification Numbers provided in accordance with the 1999 edition of NFPA 13, Section 3-2.2. * Base part numbers shown. For complete part number, refer to Viking s current price list.

Spray Nozzle 27 November 2, 2007 SOLID CONE SPRAY NOZZLES - WATER DISTRIBUTION PATTERNS A2X (VK750-VK754 ) 05134AA & 05134AJ* Angle: 140 K-Factor: 2.2 U.S. (31.7 A2 (VK740-VK744 ) 05133AA & 05133AJ* Angle: 30 K-Factor: 1.2 U.S. (17.3 A2 (VK740-VK744 ) 05133AA & 05133AJ* Angle: 60 K-Factor: 1.2 U.S. (17.3 A2 (VK740-VK744 ) 05133AA & 05133AJ* Angle: 90 K-Factor: 1.2 U.S. (17.3 Scale: Each square equals one square foot. Spray Nozzle Identification Numbers provided in accordance with the 1999 edition of NFPA 13, Section 3-2.2. * Base part numbers shown. For complete part number, refer to Viking s current price list.

November 2, 2007 Spray Nozzle 28 SOLID CONE SPRAY NOZZLES - WATER DISTRIBUTION PATTERNS A2 (VK740-VK744 ) 05133AA & 05133AJ* Angle: 120 K-Factor: 1.4 U.S. (20.2 A2 (VK740-VK744 ) 05133AA & 05133AJ* Angle: 140 K-Factor: 1.4 U.S. (20.2 B2 (VK760-VK764 ) 05135AA & 05135AJ* Angle: 30 K-Factor: 2.8 U.S. (40.4 B2 (VK760-VK764 ) 05135AA & 05135AJ* Angle: 60 K-Factor: 2.8 U.S. (40.4 Scale: Each square equals one square foot. Spray Nozzle Identification Numbers provided in accordance with the 1999 edition of NFPA 13, Section 3-2.2. * Base part numbers shown. For complete part number, refer to Viking s current price list.

Spray Nozzle 29 November 2, 2007 SOLID CONE SPRAY NOZZLES - WATER DISTRIBUTION PATTERNS B2 (VK760-VK764 ) 05135AA & 05135AJ* Angle: 90 K-Factor: 2.8 U.S. (40.4 B2 (VK760-VK764 ) 05135AA & 05135AJ* Angle: 120 K-Factor: 3.3 U.S. (47.6 B2 (VK760-VK764 ) 05135AA & 05135AJ* Angle: 140 K-Factor: 3.3 U.S. (47.6 C2 (VK770-VK774 ) 05136AA & 05136AJ* Angle: 30 K-Factor: 3.4 U.S. (49.0 Scale: Each square equals one square foot. Spray Nozzle Identification Numbers provided in accordance with the 1999 edition of NFPA 13, Section 3-2.2. * Base part numbers shown. For complete part number, refer to Viking s current price list.

November 2, 2007 Spray Nozzle 30 SOLID CONE SPRAY NOZZLES - WATER DISTRIBUTION PATTERNS C2 (VK770-VK774 ) 05136AA & 05136AJ* Angle: 60 K-Factor: 3.4 U.S. (49.0 C2 (VK770-VK774 ) 05136AA & 05136AJ* Angle: 90 K-Factor: 3.8 U.S. (54.8 C2 (VK770-VK774 ) 05136AA & 05136AJ* Angle: 120 K-Factor: 3.9 U.S. (56.2 C2 (VK770-VK774 ) 05136AA & 05136AJ* Angle: 140 K-Factor: 3.9 U.S. (56.2 Scale: Each square equals one square foot. Spray Nozzle Identification Numbers provided in accordance with the 1999 edition of NFPA 13, Section 3-2.2. * Base part numbers shown. For complete part number, refer to Viking s current price list.

Spray Nozzle 31 November 2, 2007 SOLID CONE SPRAY NOZZLES - WATER DISTRIBUTION PATTERNS D2 (VK780-VK784 ) 05137AA & 05137AJ* Angle: 30 K-Factor: 4.7 U.S. (67.8 D2 (VK780-VK784 ) 05137AA & 05137AJ* Angle: 60 K-Factor: 4.7 U.S. (67.8 D2 (VK780-VK784 ) 05137AA & 05137AJ* Angle: 90 K-Factor: 5.0 U.S. (72.1 D2 (VK780-VK784 ) 05137AA & 05137AJ* Angle: 120 K-Factor: 5.2 U.S. (75.0 Scale: Each square equals one square foot. Spray Nozzle Identification Numbers provided in accordance with the 1999 edition of NFPA 13, Section 3-2.2. * Base part numbers shown. For complete part number, refer to Viking s current price list.

November 2, 2007 Spray Nozzle 32 SOLID CONE SPRAY NOZZLES - WATER DISTRIBUTION PATTERNS D2 (VK780-VK784 ) 05137AA & 05137AJ* Angle: 140 K-Factor: 5.2 U.S. (75.0 Scale: Each square equals one square foot. Spray Nozzle Identification Numbers provided in accordance with the 1999 edition of NFPA 13, Section 3-2.2. * Base part numbers shown. For complete part number, refer to Viking s current price list.

THIS PAGE INTENTIONALLY LEFT BLANK Form No. F_030789 Replaces pages 20-32, dated February 3, 2007. (Same VK# assigned for Brass and Electroless Nickel finishes.)