Series 20 Installation Instructions

Similar documents
Series 44 Installation Instructions

Series 14R. Installation Instructions and Field Service Checklist

Series 14 Installation Instructions

Introduction. System Components

SERIES 14 INSTALLATION INSTRUCTIONS and field service check list

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

SERIES 20/30 INSTALLATION INSTRUCTIONS and field service check list

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi

ETP-5G & ETP-10G ECO-TECH PLUS GAS CONVECTION STEAMER PARTS AND SERVICE MANUAL

ICM325HN. Head Pressure Control with Optional Heat Pump Override. Installation, Operation & Application Guide

DFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR

ETP-5E & ETP-10E ECO-TECH PLUS ELECTRIC CONVECTION STEAMER PARTS AND SERVICE MANUAL

A/C-HEATER SYSTEM - AUTOMATIC

G96 Series BASOTROL Dual Operator Valve

Modulating Furnace Information. Warning on Meter Setting - Read First!

BLOWER VACUUM SWITCH FAILED OPEN

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

P445 Series Electronic Lube Oil Control

A/C-HEATER SYSTEM - AUTOMATIC

Northwest RV Supply Manual Compliments of Printed From TROUBLESHOOTING

Troubleshooting Guide

Troubleshooting Guide

Boston Gear Ratiotrol

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

Service and installation must be performed by a trained/experienced service technician.

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

FAIRCHILD T5220 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

FUEL INJECTION SYSTEM - MULTI-POINT

BGD278 Series BASOTROL CE Approved Gas Valve

FAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

Section Five - Troubleshooting Procedures

oubleshooting Guide diesel - gasoline - LPG electric P.O. Box 1160 St. Joseph, MO Fax:

HVF110, 210, 310, 410HD

ICM 326HN/327HN Line Voltage Head Pressure Control Installation, Operation & Application Guide

Service and installation must be performed by a trained/experienced service technician.

Boston Gear Ratiotrol DC Motor Speed Control

TS-E TURBO STEAM ELECTRIC COUNTERTOP CONVECTION STEAMER PARTS AND SERVICE MANUAL

G600 Series Replacement Intermittent Pilot Ignition Controls

Troubleshooting Guide

WALKIE HIGH LIFT HYDRAULIC SYSTEM

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

(For serial numbers before w/ analog control)

ARTICLE BEGINNING INTRODUCTION SELF-DIAGNOSTIC SYSTEM RETRIEVING DTCS ENGINE PERFORMANCE Volkswagen Self-Diagnostics - Gasoline

ANTI-LOCK BRAKE SYSTEM

COOKSON OWNER'S MANUAL

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

LC BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

California Friendly Landscape Training

F - BASIC TESTING Toyota Celica INTRODUCTION PRELIMINARY INSPECTION & ADJUSTMENTS VISUAL INSPECTION MECHANICAL INSPECTION

SERVICE BULLETIN REFERENCES 1983

Tension Control System MCS-166, MCS-203, MCS-204

ELECTRICAL SYSTEM RP-7

Tachometer, Ametek Electronic 54.21

TC62D Installation Instructions

CIRCLE SEAL CONTROLS

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

CIRCLE SEAL CONTROLS

Product Instruction. Door Control Board: Board 1Ø4 for PM/SSC (R3)

FAIRCHILD T5200 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

TABLE OF CONTENTS Subject Page

ESC2301. Universal Electronic Governor Controller Operation Manual

CAMS. Combustion Airflow Management System. Proven solutions for a tough industry. Precision Airflow Measurement An ONICON Brand

SERVICE MANUAL (INTERNATIONAL)

Application Engineering Europe

Troubleshooting Manual

A/C-HEATER SYSTEM - AUTOMATIC

P0441-EVAP PURGE SYSTEM PERFO... P0441-EVAP PURGE SYSTEM PERFORMANCE

INDIRECT FIRED FURNACE PARTS

1984 Jeep CJ7. IGNITION SYSTEM - SOLID STATE' 'Distributors & Ignition Systems MOTORCRAFT SOLID STATE IGNITION (SSI)

WEBER CARBURETOR TROUBLESHOOTING GUIDE

C7046A,B,C,D Air Temperature Sensors

CATALOG. 2 nd Edition

GV30 / GV30A SERIES GAS COMBINATION CONTROL SYSTEMS FOR COMMERCIAL COOKING APPLIANCES.

Flow Control & Pressure Reducing Valve with Hydraulic Control (Sizes 3''- 12"; DN80-DN300)

Transfer Switch GPTS 30

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not properly qualified.

RE Generation II Troubleshooting Guide Section I Preliminary Information and Evaluation

100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE

R & D SPECIALTIES ROTROL I USER'S MANUAL

Table of Contents Introduction 3 Chapter 2: Operation 4 Chapter 3: Components 5 Chapter 4: Specifications 8

OnCommand Troubleshooting Guide Hayward Industries

SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control

To ensure proper installation, digital pictures with contact information to before startup.

Field proven low emissions. State-of-the-art low NOx firing - adjustable for application flexibility

SERVICE MANUAL HWH TOUCH PANEL-CONTROLLED 305/325 SERIES LEVELING SYSTEM. FEATURING: Touch Panel Leveling Control

STEERING HYDRAULICS The steering system is a flow amplified, load sensing, hydraulics arrangement.

FG MACH I / MACH IIA OWNER S MANUAL AUTOMATIC BULK FEED PINSPOTTER MACHINERY DIVISION

Troubleshooting Guide

Starter, Delco Remy 15.01

PM300E Voltage Regulator Instruction Manual

Application Engineering

2. AC SERVICE AND MOTOR REQUIRED 1. ENCLOSURE REQUIRED

LPT50BRD (8x11x3 Enclosure)

4.0L CEC SYSTEM Jeep Cherokee DESCRIPTION OPERATION FUEL CONTROL DATA SENSORS & SWITCHES

Hayward error codes and troubleshooting

Transcription:

Series 20 Installation Instructions Installation Instructions and field service checklist Read these instructions carefully. Failure to follow them could result in a fire or explosion causing property damage, personal injury, or loss of life. The product must be installed and operated according to all local regulations. Service and or installation must be performed by a trained experienced service technician. Selectrastat: selector and integral sensing T120 - (60º to 5º F) TABLE OF CONTENTS Specifications...1 Dimensions...2 Installation of Components...3 Preliminary Circuit Analysis...3 Field Service Checklist...4 Performance Check...5 Extended High-Fire Ignition...5 Low Limit Stat...5 Wiring Diagrams...6 Valve Adjustments...7 Space Temperature Selector: selection only Space Temperature Sensor: remote sensing TD120 - (60º to 5º F) - For use with TS120 Optional: ETD-1 enclosure EFP-1 cover plate only - no enclosure DESCRIPTION TS120 - For use with TD120 Selectra SERIES 20 electronic gas flame modulation systems are designed primarily for commercial and light industrial space heating, as components of indirect fired units with atmospheric burners. All fuel gases are compatible. The SERIES 20 is designed for single or multiple furnace operation. It is capable of controlling up to four furnaces. It may be field installed on existing equipment or specified for new equipment installation. The system utilizes Modulator-Regulator valves. High Fire ignition selection (0, 5 or 25 second) is standard on all models. A wall mounted Selectrastat senses space temperature and has an integral selector with a 60º to 5º F range. Optionally, a remote Temperature Sensor paired with a separate Temperature Selector (60º to 5º F) can be substituted for the Selectrastat. SYSTEM COMPONENTS Series 20 Amplifiers ( shown): SPECIFICATIONS Power Requirements: Single Furnace...24V AC, 40VA capacity Multiple Furnace...24V AC, 100VA capacity NOTICE Transformer secondary must not be grounded in any portion of the circuit external to a Maxitrol amplifier. If existing transformer is grounded, a seperate isolated transformer must be used. Electrical interference may effect performance and/or damage equipment. Temperature Control Range: 60º to 5ºF Ambient Limits: -30º to 125ºF / -34º to 52ºC Gases: Suitable for natural, manufactured, mixed gases, liquefied petroleum gases and LP gas-air mixtures. Pressure Limits: Modulator-Regulator Valves MR410 (3/ and 1/2 pipe sizes) MR510 (1/2 and 3/4 pipe sizes) MR610 (3/4 and 1 pipe sizes) 1 Inlet (maximum) : MR410, 510, 610...1 psi / 69 mbar Outlet (maximum fire) standard spring*...3.0 to 5.0 w.c. / 7 to 12 mbar H - models... 7.5 to 12 w.c. / 19 to 30 mbar Max. set point not to exceed 10 w.c. above min. set point Outlet (minimum fire) standard spring*...0.2 to 1.2 w.c. /.5 to 3 mbar (-1) spring*...1 to 2. w.c. / 2.5 to 7 mbar (*other spring ranges available - Consult Maxitrol Company.)

DIMENSIONS 3.00 Mounting Holes 3.3 2.00 6.00 Power LED Relay LED Valve LED 2.25 1.75 1. Mounting Holes 2- Required 3.00 1.50 2.62 4.19 2.56.19 2.62 1.75 10-12 x 1/2 LG. BiINDING HD. SHEET METAL SCR. (2 REQ D.) 4.19 TD120 ETD-1 3.2 1.47.97 2.56 4.50 VALVE LED The PCB Valve LED illuminates when the output DC voltage to the valve is approximately 2 VDC or greater. It does not indicate valve positioning or whether the system is in modulation mode. 4.65 The Valve LED will be: T120 / TS120 1.79 OFF at maximum high fire (0VDC) and during the high fire ignition duration (if used) ON when PCB Relay LED is OFF ON or OFF when the Relay LED is ON 2

INSTALLATION OF COMPONENTS NOTICE Wiring Run: Control wires connecting the Selectrastat or Space Temperature Sensor must not be run close to or inside conduit with power or ignition wires. Doing so may cause the unit to function erratically or may destroy the amplifier. If shielded wires are used, shield must be insulated and grounded at the amplifier location only. Clip R55 off of circuit board. Amplifier: Slide or snap out circuit board from amplifier base. Mount base with two screws in chosen location protected from weather or contaminated atmosphere. Amplifier is ready for wiring when circuit board is replaced on base - protective cover need not be removed. Selectrastat: Pull dial and cover outward. Loosen screws in terminal strip, tilt out and lift up. Install in area where representative space temperature is to be sensed. Wire as shown in appropriate diagram, page 6 - reassemble. Space Temperature Sensor: Remove cover and install in area where representative space temperature is to be sensed. Wire as shown in appropriate diagram, page 6 - reassemble. Space Temperature Selector: Install in control cabinet or other chosen location. Remove cover and wire as shown in appropriate diagram, page 6 - reassemble. NOTE: For systems using up to four automatic gas valves with 0. amp maximum current each, a 100VA transformer will be adequate. In the event that the automatic valve(s) current exceeds 0. amps, it would be advisable to wire according to the Independent Power Supply diagram, page 6. The transformer for the modulating power - terminals and 9 - should be 40VA, and the automatic valve transformer should be capable of handling required loads up to 3.5 amps maximum. If exceeding 3.5 amps, it will be necessary to operate an auxiliary relay with contact rating sufficient to handle the automatic valves and any accessories. PRELIMINARY CIRCUIT ANALYSIS In order to diagnose the cause of problems in this system it is necessary to determine certain values. It is helpful to have an AC and DC voltmeter and an ohmmeter capable of reading 0 to 15,000 ohms. For ease in trouble shooting, it is necessary to rewire the system, replacing the discharge air sensor with a 4500 ohms, eg. 4300 ohm + 200 ohm, 1/2 watt test resistors in series. Modulating Function Test - when temperature at Selectrastat or Sensor is 60º to 5ºF (16º to 29ºC): Connect a DC voltmeter to amplifier terminals 1 and 2. If more convenient, the meter may be attached to the MR valve terminals. Rotate temperature selection knob to maximum setting. The DC volts should read zero, Valve LED is OFF. When the temperature selector is slowly rotated to its minimum setting, the voltage should gradually increase to 20+ volts, Valve LED is ON. See pg. 2, Valve LED. Automatic Valve Function - when temperature at Selectrastat or Sensor is 60º to 0ºF (16º to 29ºC): Disconnect the wires at amplifier terminals 10 and 11, and connect an ohmmeter. Rotate temperature selector to maximum setting - ohmmeter should show continuity, Relay LED is ON. Rotate temperature selector to minimum setting - ohmmeter should show open circuit, Relay is OFF. Reconnect the wires to terminals 10 and 11. Automatic Valve Function - when temperature at Selectrastat or Sensor is less than 60ºF (16ºC) or greater than 5ºF (29ºC): Disconnect the wires at amplifier terminals 10, 11 and 3. DC modulating voltage across terminals 1 and 2 should be zero. Ohm reading across terminals 10 and 11 should be zero ohms. Reconnect wire to terminal 3 of amplifier. Carefully connect a piece of jumper wire across the thermistor as shown (make only temporary connection). Ohm reading at terminals 10 and 11 should be infinite (open circuit). Modulating voltage at terminals 1 and 2 should be greater than 17 volts. Reconnect wires to terminals 10 and 11. Amplifier is not faulty if the above conditions are met. GAS TRAINS Valve: The MR valve must be in upright position, in a horizontal run of pipe only, with pilot gas supply upstream. If diaphragm type automatic gas valve is used with separate regulator, install MR valve downstream from diaphragm gas valve. Retain regulator in manifold and adjust 2 or 3 turns to compensate for pressure drop of MR valve. If full combination control is used, install MR valve downstream. Adjust regulator in combination control 2 or 3 turns to compensate for pressure drop at MR valve. If solenoid type automatic gas valve is used with separate regulator, replace regulator with the MR valve. 3

FIELD SERVICE CHECKLIST SYMPTOM POSSIBLE CAUSE FIELD TEST REMEDY A. Automatic control valve will not close despite full range of modulating voltage at terminals 1 and 2. B. Automatic control valve won t open despite full range of modulating voltage at terminals 1 and 2. 1. Automatic control valve not operating properly. 2. Installation wiring error. 3. Amplifier is not operating properly. 4. Automatic control valve not operating properly. 5. Open wire to automatic valve. 6. Amplifier is not operating properly. C. No gas flow. 7. Malfunctioning power supply.. MR valve installed backwards. D. Continuous high fire. 9. Open circuit in sensing and setting circuit. E. Continuous high fire but automatic valve cycles. F. Furnace won t activate due to constant high modulating voltage. (above 17 V DC) G. Continuous low or medium fire, but automatic valve cycles correctly. H. Incorrect discharge air temperature. I. Erratic or severely pulsating flame. 10. Open circuit in wiring to MR valve. 11. Plunger jammed or installed upside down. 12. MR valve not operating properly. 13. Short circuit in sensing and setting circuit. 14. Heat load requires low fire only. 15. Plunger and/or maximum spring missing. 16. Jammed plunger. 17. Other valve problems. 1. Inadequate supply pressure. 1. Remove wire from valve, if valve does not close - valve is not operating properly. 2. Remove wire from amplifier terminal 10 or 11. If valve remains open, check for miswiring. 3. If AC voltage will not drop to zero at terminals and 11 - when DC voltage at terminals 1 and 2 is above 20 VDC - amplifier is faulty. If space temperature is less than 60º or greater than 5ºF (<16º or > 29ºC), see Preliminary Circuit Analysis, page 3. 4. Read voltage across valve terminals. If 24 VAC, valve is not operating properly. 5. Read voltage across terminals and 11 on amplifier. If 24 VAC, check for open circuit to automatic valve. If space temperature is less than 60º or greater than 5ºF (<16º or >29ºC), see Preliminary Circuit Analysis, page 3. 6. If AC voltage reading remains zero - when DC voltage at terminals 1 and 2 is below 14 V DC - amplifier is faulty. If space temperature is less than 60º or greater than 5ºF (<16º > 29ºC), see Preliminary Circuit Analysis, page 3. 7. Read voltage at amplifier terminals and 11 (24 VAC).. Arrows on MR valve should point in the direction of gas flow. 9. Disconnect and measure across wires connected to amplifier terminals 3 and 4 ( models). Should read between,000 to 12,000 ohms. 10. Check wiring for defects. 11. Examine. Plunger should be smooth and clean and operate freely in solenoid sleeve. Must be installed as shown in Valve Adjustments pg. 7, M/MR Valve Diagram. 12. Measure voltage across MR valve. 13. Disconnect and measure across wires connected to amplifier terminals 3 and 4 ( models). Should read between,000 and 12,000 ohms. 14 Increase temperature setting 10 degrees. 15. Check for parts (see Valve Adjustments pg. 7, M/MR Valve Diagram ). 16. Examine. Plunger should be smooth and clean and operate freely in solenoid sleeve. Must be installed as shown in Valve Adjustments pg. 7, M/MR Valve Diagram. 17. Remove wire from MR valve. 1. Remove spring 5 from MR valve (see Valve Adjustments pg. 7, M/MR Valve Diagram ) push down on plunger. Insufficient manifold pressure with furnace operating indicates supply is too low. 1. Replace automatic control valve. 2. Correct wiring. 3. Replace amplifier. 4. Replace automatic control valve. 5. Correct wiring 6. Replace amplifier. 7. Power supply must be 24 V AC.. Install properly. 9. If above 12,000 ohms, check circuit for open or loose wires. 10. Repace wiring if necessary. 11. Clean plunger if necessary. 12. If modulating voltages are obtained but no gas modulation, MR valve is faulty. Replace if necessary. 13. If below,000 ohms, check circuit for shorts or miswiring. 14. If heater goes to high fire, system is working correctly. 15. Install correct parts. 16. Clean plunger if necessary. 17. If MR valve remains on low fire, valve is not operating properly. Check item 19 below, then replace valve if necessary. 1. Check for obstruction in gas pipe ahead of controls. Increase gas pressure if possible. 19. Calibration 19. Check seal on calibration potentiometer. 19. Recalibrate per Temperature Calibration procedure. 20. Dirty or sticking plunger. 21. Intermittent shorting in wiring. 22. Amplifier not operating properly. 20. Examine. Plunger should be smooth and clean and operate freely in solenoid sleeve. Must be installed as shown in Valve Adjustments pg. 7, M/MR Valve Diagram. 21. Inspect wiring. 22. Observe DC voltage across amplifier terminals 1 and 2. 20. Clean plunger if necessary. 21. Correct wiring. 22. If erratic or pulsating DC voltage is observed and wiring shows no defects, replace amplifier. If erratic or pulsating voltage continues, contact Maxitrol Company. *Control circuits external to the Series 20 can cause burner malfunction. Always check manual valve to be certain gas is on, and check limit controls for normal operation. 4

PERFORMANCE CHECK With the modulator-regulator valve installed as instructed (voltages are approximate)... Low Fire is above 14 volts DC. Manifold pressure can be adjusted as follows: Standard spring 0.2 to 1.2 w.c. (.5 to 3 mbar), MR*10B10L-1 spring 1 to 2. w.c. (2.5 to 7 mbar). High Fire is obtained at zero volts DC. Use manufacturer s pressure specifications when available. Maxitrol standard factory settings are 0.5 w.c. (1.25 mbar) minimum and 3.5 w.c. (.75 mbar) maximum. H-1 models 1.75 w.c. (4.35 mbar) minimum and 11 w.c. (27 mbar) maximum. At Selectrastat/Temperature Selector: 1) Set below room temperature and slowly increase setting until furnace begins operating. Furnace should ignite and remain on low fire. If high fire ignition is being used the furnace will ignite at high fire for the set duration or either 5 or 25 seconds (see Extended High Fire Ignition below), then modulate to low fire. At low fire (manifold pressure about 0.5 w.c. [1.25 mbar]), a reading of approximately 14 or more volts DC should be obtained. 2) Rotate 3º higher. EXTENDED HIGH-FIRE IGNITION The high fire start duration is field selectable. Amplifier will hold MR valve in the High Fire position for the set duration. High-Fire duration of 0 seconds, 5 seconds, 25 seconds. (Times are approximate). START TIME START TIME High Fire Ignition 5 Seconds Low Limit stat 25 Seconds When fresh outside air is introduced and the space being heated is up to temperature, the furnace will shut off. If the recirculated air should be too cool, temper it by wiring a duct-stat, as shown. J1 J1 J2 TIMER DISABLE 0 Seconds 3) Furnace should now be at high fire, manifold pressure about 3.5 w.c. (.75 mbar). Less than 2 volts DC should read across Modulator-Regulator valve terminals. Rotate slowly to a lower setting. Furnace should modulate to low fire, with voltage at modulator approximately 15-17 volts, internal relay will trip and solenoid automatic control valve (s) will close. If the preceding readings are obtained, proceed with Furnace Adjustments. If the preceding readings are not obtained: 4) Recheck wiring to ensure system is consistent with appropriate wiring diagram. A1010 9 10 11 12 5) Check power source for 24 volts, Power LED is ON. 6) Some automatic control valves require as much as 20 seconds to open. In this case, check fro 24VAC output at automatic valve terminals, Relay LED is ON. Furnace Adjustments: For space heating, first calculate heat loss. If reduction of furnace input is indicated, consult furnace manufacturer about changing to smaller orifices. Do not try to reduce by pressure adjustment or throttling the gas supply. LOW LIMIT DUCT STAT (not furnished by Maxitrol) Low Limit Duct Stat Note: Terminals 10 & 11 MAX LOAD is 3.5 Amps. An oversized furnace input is easily identified, particularly during cold weather. If outdoor temperature is low and the system cycles on and off instead of maintaining a low input, the furnace is oversized. Consult furnace manufacturer. 5

These wiring diagrams are for Series 20 space air sensing systems only. The R55 (Zero ohm Jumper) MUST be Clipped off of circuit board (located near terminals 5 & 7, outside of cover.) SINGLE FURNACE OPERATION MR VALVE 24V-40VA 24V-40VA 24V-40VA GAS VALVE GAS VALVE T120 R55 Removed. * Independent Power Supply Common Power Supply TS120 * R55 is a zero ohm jumper TD120 R55 Removed. * Remote Temperature Sensor with Separate Selector MULTIPLE FURNACE OPERATION (MR valves and automatic gas valves wired in parallel as shown) 24V-100VA MR VALVES 4 MAX. GAS VALVES (4 MAX.) 3.5 AMPS MAX Wired in Parallel Common Power Supply 24V-100VA 24V-100VA TS120 TD120 R55 Removed* GAS VALVES (4 MAX.) 3.5 AMPS MAX Remote Temperature Sensor with Separate Selector Independent Power Supply 6

VALVE ADJUSTMENTS (See bulletin MMR_MT_EN for additional M/MR valve information) Note: High Fire Adjustment should be checked whenever Low Fire Adjustment is changed. 10 1 2 3 5 4 Low Fire Adjustments: 9 A) Remove Cover (2) B) Remove maximum adjusting screw (4), spring (5), and plunger (). A small magnet is useful for this purpose. 7 NOTICE The plunger is a precision part. Handle carefully to avoid marring or picking up grease and dirt. Do not lubricate. 6 C) Using minimum adjusting screw (9), set manifold pressure to furnace manufacturer s specifications. D) Replace plunger, spring retainer, spring and maximum adjusting screw in proper order. E) Perform High Fire adjustment. M/MR Valve Diagram High Fire Adjustments: A) Disconnect wire from amplifier terminal 3, remove cover plate (2). B) Using maximum adjustment screw (4), set manifold pressure to furnace manufacturer s specifications. C) Reconnect wire to amplifier Terminal 3. D) Replace cover plate (2) on Modulator-Regulator valve and reconnect wire to amplifier terminal 3. 1. 2. 3. 4. 5. 6. 7.. 9. 10. Top Housing Cover Plate Seal Gasket Maximum Adjustment Screw Maximum Adjustment Spring Solenoid Minimum Adjustment Spring Plunger Minimum Adjustment Screw Minimum Adjustment Screw Stop 7

Maxitrol Company 23555 Telegraph Rd., PO Box 2230 Southfield, MI 4037-2230 SEL20_MI_EN_04.2010 www.maxitrol.com 2010 Maxitrol Company All Rights Reserved