GV30 / GV30A SERIES GAS COMBINATION CONTROL SYSTEMS FOR COMMERCIAL COOKING APPLIANCES.
|
|
- Roberta Reeves
- 6 years ago
- Views:
Transcription
1 GV0 / GV0A SERIES GAS COMBINATION CONTROL SYSTEMS FOR COMMERCIAL COOKING APPLIANCES R
2 CONTENT GENERAL INFORMATION GV0 AND GV0A STANDARD FEATURES OPTIONAL TEMPERATURE KNOBS AND D-STEMS GV0 SERIES FEATURES AND OPTIONS GV0A SERIES FEATURES AND OPTIONS TECHNICAL DATA CONNECTIONS 5 MAIN VALVE FUNCTION 6 GV0 SERIES VALVE FUNCTION 7 GV0A SERIES VALVE FUNCTION 8 TEMPERATURE SENSORS 9 GV SERIES SENSORS TEMPERATURE CONTROL CHARACTERISTICS WORKING DIAGRAM 0 PRESSURE DROP DIAGRAMS DIMENSIONS AND WEIGHTS GV0A SERIES COMPONENTS AND OPTIONS ACCESSORIES CERTIFICATIONS AND FUELS CE Multifunctional controls for gas burning appliances group according to DIN EN 6 and Gas Appliances Directive 009//EEC Thermoelectric flame supervision device according to EN 5 and Gas Appliances Directive 009//EEC Temperature control according to EN 57 Suitable for use with gases of EN 7 gas family, and CSA Combination controls for gas appliances according to: - ANSI Z.77/CSA 6.0 for U.S. and Canada - ANSI Z.78/CSA 6.0 for U.S. and Canada Suitable for natural, manufactured, mixed gases, liquefied petroleum gases, and LP gas-air mixtures On request: UA.TR.0-
3 GENERAL INFORMATION GV0 AND GV0A STANDARD FEATURES OPTIONAL TEMPERATURE KNOBS AND D-STEMS GENERAL INFORMATION Mertik Maxitrol s GV series gas combination control systems precisely and efficiently control the pilot and the main burner of gas appliances. The GV series suits a wide range of commercial cooking appliances, including ovens, griddle plates, fryers, and bain-maries. Valves can be customized to OEM specifications. Oven Griddle Plate Bain-Marie Fryer ~ Main Applications (additional applications may be supported upon review) GV0/GV0A Valves for commercial cooking GV0 AND GV0A STANDARD FEATURES Compact design Pilot gas filter Inlet screen Thermoelectric flame supervision device Pilot gas adjustment screw Separate temperature knob Min. rate setting with fixed or adjustable orifices Liquid filled stainless steel temperature sensor Inlet/outlet connections at bottom, side, or both, providing various inlet/outlet combinations OPTIONAL TEMPERATURE KNOBS AND D-STEMS 06 Mertik Maxitrol GmbH & Co. KG, All Rights Reserved. Mertik Maxitrol offers various D-stems and knobs for both the GV0 and GV0A. The GV series can be equipped with aluminum D-stems (brass optional) allowing OEMs to use their own knobs, personalizing the appliance front. The recalibration version allows a change of the temperature setting within a defined range. The value of the temperature change is visible at the scale. D-stems Temperature knobs Operating knobs
4 GV0 SERIES FEATURES AND OPTIONS GV0 SERIES FEATURES AND OPTIONS FEATURES Temperature control or manual operation Temperature sensors: various ranges between C (55. F) and 0 C (6 F) Customized to OEM specifications Stand-by position independent of temperature setting with rotary slide valve to shut off main gas OPTIONS Integrated piezo igniter Microswitch for electronic igniter (9V/0V) Use of external ignition (piezo or match) D-stem for large temperature knobs D-stem recalibration knob Integrated pressure regulator or throttle (Throttle CE only) Faceplate and large temperature knob GV0 with D-stem and integrated piezo igniter Operating knob Temperature knob D-stem Pressure regulator GV0 with plastic knob and integrated piezo igniter GV0 with microswitch for electronic igniter
5 GV0A SERIES FEATURES AND OPTIONS GV0A SERIES FEATURES AND OPTIONS FEATURES Temperature control or manual operation Temperature sensors: various ranges between 0 C (86 F) and 0 C (6 F) Higher capacity flow rates: up to 0 % higher capacity* Customized to OEM specifications Microswitch that interrupts thermocurrent circuit OPTIONS Electronic ignition module with LED pilot flame indication Microswitch for electronic igniter (9V) Use of external ignition (piezo or match) D-stem for large temperature knobs D-stem recalibration knob Faceplate and large temperature knob GV0A manual operation Operating knob Temperature knob D-stem LED 5 Faceplate GV0A (thermostatic operation) with D-stem (Aluminum) 06 Mertik Maxitrol GmbH & Co. KG, All Rights Reserved. 5 GV0A thermostatic version with faceplate, large temperature knob and an electronic ignition module with LED pilot flame indication * Compared to GV0 series
6 TECHNICAL DATA CONNECTIONS TECHNICAL DATA CE Certification GAD 009//EEC, EN 6 CSA Certification ANSI Z.77/CSA Z.78/CSA 6.0 Maximum Inlet Pressure 5 kpa (50 mbar) (0" w.c.) / psi =.5 kpa (.5 mbar) (" w.c.) Pressure Drop / Capacity.5 m /h air at 0.5 kpa (.5 mbar) pressure drop ( m /h air for GV0A) 65,000 BTU/hr* at " w.c. pressure drop (85,000 BTU/hr* at " w.c. for GV0A) Ambient Temperature GV0/GV0A gas combination control GV0A (optional) 0 C 0 C 0 C 0 C (optional) F 0 F F 8 F (optional) Integral Pressure Regulator (GV0 only) Class C according to EN 88 adj. range 0.5 kpa (5 0 mbar) 0,000 to 85,000 BTU/hr* (ANSI.8) adj. range " " w.c. Pipe Connection Thread (various inlet /outlet combinations) Rp /8" (ISO 7-/EN 06- ) /8" NPT * Natural gas (dv = 0.6;,000 BTU/cu.ft) CONNECTIONS Valve connections 5 Inlet pressure tap 0 Outlet pressure tap Gas side inlet Gas side outlet 9 5 Mounting points 6 Gas bottom outlet 8 7 Gas bottom inlet 8 Thermocouple connection 9 Pilot gas outlet Min. rate setting with fixed or adjustable orifice
7 MAIN VALVE FUNCTION MAIN VALVE FUNCTION MAIN VALVE FUNCTION FOR MAIN GAS Gas flow. m /h air at 0.5 kpa (.5 mbar) HIGH TO LOW AND SHUT OFF Thermostatically controlled modulating valve that maintains the set point temperature. After reaching the set point temperature, the valve supplies the amount of gas required to maintain that temperature. When low fire increases temperature above the set point, the valve will shut off gas to main burner. Temperature Gas flow 0.9 m /h air at 0.5 kpa (.5 mbar) HIGH AND SHUT OFF Thermostatically controlled ON/OFF valve. The valve operates at maximum BTU rate until the set point temperature is reached, and then it snaps off. Temperature Gas flow.5 m /h air at 0.5 kpa (.5 mbar); 0.9 m /h air at 0.5 kpa (.5 mbar) MAX. TO HIGH AND SHUT OFF Thermostatically controlled ON/OFF valve with additional range of modulation and increased capacity. Temperature Gas flow. m /h air at 0.5 kpa (.5 mbar) 06 Mertik Maxitrol GmbH & Co. KG, All Rights Reserved. HIGH TO LOW After reaching the set point temperature, the thermostatically controlled valve goes to low fire without shutting off. When required, additional heat is quickly provided. HIGH TO LOW The manually operated valve is adjustable between low fire and high fire. Gas flow Temperature. m /h air at 0.5 kpa (.5 mbar) 5 Temperature / Knob position
8 GV0 SERIES VALVE FUNCTION GV0 SERIES VALVE FUNCTION. OFF The operating knob is in OFF position. The magnet unit is closed. Magnet unit Outlet to pilot ON/OFF valve High fire modulation valve 5 Temperature sensor Operating Knob Temperature Knob. PILOT IGNITION Turn the operating knob to IGN position; push down and hold. The magnet unit opens. Continue turning counterclockwise to pilot, creating spark to ignite pilot. Repeat sequence if pilot does not light.. LOW FIRE OPERATION The operating knob is in ON position. The temperature at sensor is slightly lower than the set temperature. Gas flows through the low fire ON/OFF valve.. HIGH FIRE OPERATION The operating knob is in ON position. The temperature at sensor is lower than the set temperature. Gas flows through the high fire modulation valve and low fire ON/OFF valve. 6 5
9 GV0A SERIES VALVE FUNCTION GV0A SERIES VALVE FUNCTION. OFF The operating knob is in OFF position. The magnet unit is closed. Main gas closed. OFF Magnet unit Outlet to pilot ON/OFF valve High fire modulation valve 5 Temperature sensor ON IGN Operating Knob Temperature Knob. ELECTRONIC IGNITION Turn the operating knob counterclockwise to ON/IGN position. Press down and hold to open the magnet unit. The electronic ignition to pilot starts. Either the external piezo or battery igniter can be used to start the ignition. Main gas closed. ON IGN OFF. LOW FIRE OPERATION The operating knob is in ON/IGN position. The temperature at sensor is slightly lower than the set temperature. Gas flows through the low fire ON/OFF valve. OFF ON IGN 06 Mertik Maxitrol GmbH & Co. KG, All Rights Reserved.. HIGH FIRE OPERATION The operating knob is in ON/IGN position. The temperature at sensor is lower than the set temperature. Gas flows through the high fire modulation valve and low fire ON/OFF valve. ON IGN OFF 5 7
10 TEMPERATURE SENSORS TEMPERATURE SENSORS GV0 and GV0A gas combination control valves were specifically designed for commercial cooking equipment and appliances. Temperature sensors are stainless steel, and each assembly is precisely calibrated for the applications shown below. mm ø 6 mm (. inch ø 0. inch) Bain-Marie L 0 00 C 60 mm ø 5 mm (6. inch ø 0.0 inch) Fryer Y 0 90 C 0 mm ø mm (.06 inch ø 0.6 inch) Griddle Plate Q C 86 mm ø mm (.9 inch ø 0.6 inch) Oven Z C
11 GV SERIES SENSORS TEMPERATURE CONTROL CHARACTERISTICS WORKING DIAGRAM GV SERIES SENSORS Sensor Application Temperature Range Capillary Length Sensor Length Sensor Diameter ø Sensor Material C F mm ft mm inch mm inch L Bain-Marie , stainless steel Y Fryer ,00, stainless steel Q Griddle Plate , stainless steel Z Oven , stainless steel TEMPERATURE CONTROL CHARACTERISTICS 06 Mertik Maxitrol GmbH & Co. KG, All Rights Reserved. Sensor Application Set Point Range T T T Ambient temperature influence C F C F C F C F L Bain-Marie : 0.0 Y Fryer : 0. Q Griddle Plate : 0.60 Z Oven : 0.80 WORKING DIAGRAM 00 % MIN Temperature knob position MAX GV0 SERIES Example for set point range (Oven) 00 C to 0 C ( F to 6 F) Flow Rate (% of Nominal Value) Thermostatically controlled modulating valves regulate the set point temperature. Once the set point temperature is reached, the valve supplies the amount of gas required to maintain temperature. Minimum Rate When low fire increases temperature (partial load) T above the set point, the valve will shut off gas to main burner. T 9 T 00 C 0 C Set Point Range (Temperature C)
12 PRESSURE DROP DIAGRAMS PRESSURE DROP DIAGRAMS PRESSURE DROP CAPACITY FOR NATURAL GAS Density ratio of gas to air: dv = 0.6 NG;,000 BTU/cu.ft PRESSURE DROP CAPACITY FOR NATURAL GAS Density ratio of gas to air: dv = 0.55 NG; Hi = 9.99 kwh/m Flow rate (BTU per hour) Flow rate (kw) Pressure drop (" w.c.) Pressure drop ( p kpa) PRESSURE DROP CHART GV GV0A GV0 MAX GV0 Pressure drop ( p kpa) Air NG (dv = 0.6) LPG (dv =.56) Flow rate (m /h)
13 DIMENSIONS AND WEIGHTS DIMENSIONS AND WEIGHTS GV0 SERIES Weight approx. 0 g (5 ounces) GV0A SERIES Weight approx. 90 g (7 ounces) [.6 ] ø 60 mm [.06 ] ø 7 mm [.06 ] ø 7 mm 5 [ 0.7 ] ø 8.8 mm [ 0. ] ø 5. mm [.95 ] ca. 00 mm [ 0. ] ø 5. mm [.69 ± 0.0 ] ± 0.5 mm [.69 ± 0.0 ] ± 0.5 mm [ 0. ] 5. mm [ 0. ] ø 5. mm [. ± 0.0 ] 6 ± 0.5 mm [.0 ± 0.0 ] 6. ± 0.5 mm [.0 ] ca. 77 mm [ 0. ] ø 5. mm [ 0. ] ø 5. mm [. ± 0.0 ] 6 ± 0.5 mm [.9 ] 5 mm 6 [.0 ± 0.0 ] 6. ± 0.5 mm [ 0.9 ] ca. mm [.86 ] 98 mm [.59 ] 0.5 mm [.07 ] 78 mm [.86 ] 98 mm [.59 ] 0.5 mm 8 7 [.05 ] 5 mm [. ] ca. 8 mm [. ] ca. 8 mm [ 0. ] 8 mm [ 0.98 ] 5 mm [ 0.87 ] mm [ 0. ] 8 mm [.06 ] ø 7 mm 06 Mertik Maxitrol GmbH & Co. KG, All Rights Reserved. [ 0.98 ] 5 mm Temperature sensor Cover printing US (optional) Cover printing EU (optional) Connection for igniter [ 0.87 ] mm [ 0. ] 8 mm [ 0. ] mm [ 0.98 ] 5 mm [ 0.98 ] 5 mm [ 0.87 ] mm [.5 ] ca. 9 mm [ 0. ] 8 mm 5 Temperature knob (optional, with different printing) 6 Thermocurrent interrupter [ 0. ] mm 7 Faceplate (optional, with different printing and opening for LED) 8 LED
14 GV0A SERIES COMPONENTS AND OPTIONS GV0A SERIES COMPONENTS AND OPTIONS ) GV0A WITH PUSH BUTTON IGNITION Pilot burner 5 Temperature knob (optional) Operating knob Faceplate 5 Cover Microswitch (optional) 7 Microswitch (standard) 8 Interrupter cable Top view 9 Thermocurrent interrupter 0 Temperature sensor Ignition cable (optional) A B A Cable for electronic igniter (optional) B Electronic igniter (optional) C Battery box BATTERY D Cable for battery box E Electronic ignition module with LED pilot flame indication F 8 wire connection cable ) GV0A WITH PUSH BUTTON IGNITION AND LED G Bicolor LED with cable G 9 BATTERY 0 C D E F
15 ACCESSORIES ACCESSORIES Temperature knob (G0A-ZKB ) Faceplate for GV0A (G0A-ZBB ) Cover for GV0 Battery box x CC for GV0A LED version (G0A-ZBC) Electronic igniter (9V) (G0A-ZZI) Electronic ignition module with LED pilot flame indication (G0A-6M0B00) 8 wire connection cable (G6R-C ) Cable for battery box (G60-ZCB90/ ) Cable for electronic igniter (G0A-ZCI/000) Ignition cable for GV0A (G60-ZKIS ) Bicolor LED with cable (G0A-ZLB ) Compression fittings Adapter and fitting for 5 mm inlet pipe (G0-ZAH5) Plugs Adjustable and fixed orifices Thermocurrent interrupter (G0-ZUS ) Thermocurrent interrupter (G60-ZUS ) Thermocouple (G0-ZPT ) Pilot burner (Europe only) (G0-ZPM) 06 Mertik Maxitrol GmbH & Co. KG, All Rights Reserved. Ignition cable for GV0A G60-ZKIS Ø Connector mm (inch) (0.6) Flat connector.8 x 0.5 Length mm (inch) 500 (9.7) 900 (5.),500 (59.) without 900 (5.).6 (0.06) 900 (5.). (0.05) 900 (5.) Cable for electronic igniter G0A-ZCI/000 Length mm (inch) Bicolor LED with cable G0A-ZLB Length mm (inch),000 (9.) 0 (.7) Cable for battery box with 90 plug G60-ZCB90/ Length mm (inch) 500 (9.7),500 (59.),000 (8.) 8 wire connection cable G6R-C Length mm (inch) 50 (.8) 500 (9.7),800 (70.9)
16 R 06 Mertik Maxitrol GmbH & Co. KG, All Rights Reserved. Mertik Maxitrol GmbH & Co. KG Warnstedter Str Thale Germany Tel.: (+9) Fax: (+9) Mertik Maxitrol GmbH & Co. KG The Valleys Innovation Centre Abercynon, South Wales CF5 SN UK Direct: (+) Mobile: (+) Mertik Maxitrol GmbH & Co. KG Industriestr. 808 Senden Germany Tel.: (+9) Fax: (+9) EXCLUSIVE AGENT Maxitrol Company 555 Telegraph Road P.O. Box 0 Southfield, MI USA Tel.: (+) Fax: (+) info@maxitrol.com GV0.GV0A-LC-EN-09.05_Cooking
Service and installation must be performed by a trained/experienced service technician.
CATALOG Service and installation must be performed by a trained/experienced service technician. All products used with combustible gas must be installed and used strictly in accordance with the instructions
More informationCATALOG. 2 nd Edition
CATALOG 2 nd Edition Service and installation must be performed by a trained/experienced service technician. All products used with combustible gas must be installed and used strictly in accordance with
More informationService and installation must be performed by a trained/experienced service technician.
CATALOG Service and installation must be performed by a trained/experienced service technician. All products used with combustible gas must be installed and used strictly in accordance with the instructions
More informationG196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve
Product Bulletin Issue Date March 13, 2013 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve The G196 Series valves use the reliable valve body and magnetic operators from
More informationBGD258 Series BASOTROL CE Approved Class A Gas Valve
Product Bulletin Issue Date May 21, 2010 BGD258 Series BASOTROL CE Approved Class A Gas Valve The BGD258 Series multi-function gas control valve works in conjunction with an electronic sequence control
More informationCATALOG. 2 nd Edition
CTLOG 2 nd Edition Service and installation must be performed by a trained/experienced service technician. ll products used with combustible gas must be installed and used strictly in accordance with
More informationBGD278 Series BASOTROL CE Approved Gas Valve
Product Bulletin Issue Date November 16, 2012 BGD278 Series BASOTROL CE Approved Gas Valve The BGD278 Series gas valve is a combination main and pilot valve intended for use in conjunction with solid-state
More informationH15 Series BASO Automatic Shutoff Pilot Gas Valve
Bulletin Issue Date June 5, 2017 H15 Series BASO Automatic Shutoff Pilot Gas The H15 Series pilot valves provide safe lighting and complete shutoff of pilot and main burner gas in the event that the flame
More informationDEXEN INDUSTRIES Inc. GENERAL CATALOG. DEXEN INDUSTRIES Inc.
DEXEN INDUSTRIES Inc. GENERAL CATALOG DEXEN INDUSTRIES Inc. 6003 GAS VALVES 6003-series gas valve is an effective and reliable gas valve for low-btu gas product and application. The product is most commonly
More informationM/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners
M/MR Modulating Valves design certified For Atmospheric, Infrared, and Direct Fired urners TALE OF CONTENTS Description/Specifications... 1 Introduction... 2 Direct Fired Applications (Negative Pressure)...
More informationG96 Series BASOTROL Dual Operator Valve
Product Bulletin Issue Date March 5, 2013 G96 Series BASOTROL Dual Operator Valve The G96 Series BASOTROL valves are combination, dual operator, automatic valves available with or without a pressure regulator.
More informationH15 Series BASO Automatic Shutoff Pilot Gas Valve
Product Bulletin Issue Date February 11, 2008 H15 Series BASO Automatic Shutoff Pilot Gas The H15 Series pilot valves provide safe lighting and complete shutoff of pilot and main burner gas in the event
More informationGasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 057 D01
Gasloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating G-M(P) 057 D01 Two stage operating mode G-(LEP)Z 057 D01 Technical Description Multifunctional gas
More informationSeries 20 Installation Instructions
Series 20 Installation Instructions Installation Instructions and field service checklist Read these instructions carefully. Failure to follow them could result in a fire or explosion causing property
More informationEclipse RatioAir Burners
Parameter Maximum Input, BTU/hr (kw) 1, Minimum Input, BTU/hr (kw) Lower inputs may be achieved. Contact factory. Main Gas Inlet Pressure, "w.c. (mbar) 3 Fuel pressure at ratio regulator inlet. High Fire
More informationNatural Gas Reference Guide
Natural Gas Reference Guide NICOR GAS NATURAL GAS REFERENCE GUIDE A guide to industry code specifications and guidelines Always check your local building code department to ensure correctness of information
More informationVGD Series VGDxx.xxxU Gas Valves for use with SKPxx.xxxU electro hydraulic actuators
VGD Series VGDxx.xxxU Gas Valves for use with SKPxx.xxxU electro hydraulic actuators Technical Instructions Document No. 7631 VGDxx.xxxU VGD20.xxxU VGD40.xxxU ISO 9001 and 14000 REGISTERED FIRM Only with
More informationMBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N
GasMultiBloc Combined servo pressure regulator and safety shut-off valves MBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N 7.01 Max. operating pressure 3 mbar (36 kpa) Compact design High flow rates
More informationGEMINI GAS CONTROL PRODUCT INFORMATION
GEMINI GAS CONTROL PRODUCT INFORMATION The Gemini (6G) combination gas control valve is a versatile multifunction control designed to meet the requirements for use with non-piloted intermittent ignition
More informationMULTIFIRE. High temperature dual fuel burner
MULTIFIRE High temperature dual fuel burner High temperature burners - MULTIFIRE 3-11.3-1 Operates on-ratio or with excess air to meet the specific demands of your combustion process needs Burns most clean,
More informationGAS COUNTER EQUIPMENT PARTS / SERVICE MANUAL
THERMA-TEK RANGE CORPORATION QUALITY AND STRENGTH GAS COUNTER EQUIPMENT PARTS / SERVICE MANUAL Models covered in this manual include: Open Top Hot Plates: TCHP12-1, TCHP12-2, TCHP24-2, TCHP24-4, TCHP36-6,
More informationOld documentation - Only for your information! Product is not available any more!
GasBloc Solenoid valve Single or multiple actuator GB 0 D0.1 Printed in Germany Edition 0.10 Nr. 0 9 1 6 Technical description The GB 0 gas valve family comprises 1, or solenoid valves as single or multiple
More informationGasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF
GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-00-VEF 7.03 Max. operating pressure 30 mbar (3 kpa) Compact design High flow values Low weight Low power
More information/
45.900.444-/45.900.446- VENTURI MANIFOLD FOR VK41.5V/VK81.5V GAS CONTROLS PRODUCT HANDBOOK APPLICATION The venturi manifold combined with the VK41.5V/VK81.5V gas controls and a specific DC-fan is called
More informationV5197A Firing Rate Gas Valve
V5197A Firing Rate Gas Valve FEATURES PRODUCT DATA APPLICATION The V5197A is a firing rate valve used to provide variable flow control of air, natural gas, liquefied petroleum (LP), and manufactured gases.
More informationMBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N
GasMultiBloc Combined servo pressure regulator and safety shut-off valves MBC-00-SE MBC-700-SE MBC-100-SE MBC-00-N MBC-700-N 7.01 Max. operating pressure mbar Compact design High flow rates Low weight
More information822 NOVAMIX GAS FLOW RATE ADJUSTMENT AS A FUNCTION OF THE AIR FLOW GAS/AIR RATIO 1:1 DOUBLE AUTOMATIC SOLENOID SHUT-OFF VALVE
SIT Group 822 NOVAMIX MULTIFUNCTIONAL GAS CONTROL GAS FLOW RATE ADJUSTMENT AS A FUNCTION OF THE AIR FLOW GAS/AIR RATIO 1:1 DOUBLE AUTOMATIC SOLENOID SHUT-OFF VALVE SERVO-CONTROLLED PRESSURE REGULATOR PIN
More informationIntroduction. System Components
The Selectra SERIES 94 is for use with either direct or indirect gas fired units (furnaces, ovens, etc.). The system may be field installed on existing equipment or specified for new equipment installation.
More informationSeries 44 Installation Instructions
and field service checklist Series 44 Installation Instructions Table of Contents Page 1 Page 2 & 3 Page 4 Page 5 Page 6 Page 7 Page 8 System Components Amplifiers System Components Introduction and Dimensions
More informationGasMultiBloc Combined regulator and safety shut-off valves Single-stage function Integrated bypass valve MB-D(LE) B07
GasMultiBloc Combined regulator and safety shut-off valves Single-stage function Integrated bypass valve MB-D(LE) - B07 7.08 Printed in Germany Rösler Druck Edition 08.00 Nr. 9 6 Technical description
More information1200 SERIES FTR HOT AIR BAFFLE BURNER
CAPABILITIES High release rates with moderate air pressure Good turn down with flame characteristics and direction maintained Stable flames tailored to the job applications can be from highly oxidizing
More informationG76x Direct Spark Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G76x Issue Date 0400 G76x Direct Spark Ignition Controls Figure 1: G76x Direct Spark Ignition
More informationManually operated safety shut-off valve HSAV HSAV/5
Manually operated safety shut-off valve HSAV HSAV/5.23 Printed in Germany Edition 02.10 Nr. 214 758 1 Technical description The DUNGS manual operated shut-off valve HSAV, HSAV/5 is semi-automatic as per
More informationField proven low emissions. State-of-the-art low NOx firing - adjustable for application flexibility
-.9- KINEDIZER LE High capacity low NOx gas burners Field proven low emissions. State-of-the-art low NOx firing - adjustable for application flexibility Lower NOx and less excess air than standard KINEDIZER
More informationToll Free Phone, (US & Canada): (800) Toll Free Fax, (US & Canada): (800)
PII PERFORMER SERIES Toll Free Phone, (US & Canada): (800) 427-6668 Toll Free Fax, (US & Canada): (800) 361-7745 http://www.garland-group.com FORM # PII Performer Series Parts (Rev 02) Page 2 FORM # PII
More informationNEW INJECTOR KITS FOR GAS APPLIANCES N900 AND N700 LINE.
Page /2 Identification: Tech. Bulletin n : Date: Issuer: Factory: A N900, A6 N700 PDX20068 222006 M. Scalon (TT&S) PDVallenoncello Modular Cooking Subject NEW INJECTOR KITS FOR GAS APPLIANCES N900 AND
More informationB21 Series BASOTROL Gas Valve
Installation Instructions B21 Issue Date September 19, 2017 Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing BASO Gas Products. Carefully
More informationGAS CONVERSION KIT INSTALLATION INSTRUCTIONS
GAS CONVERSION KIT INSTALLATION INSTRUCTIONS These instructions apply to the following gas conversion kits: 8261139 8261140 8261141 8261142 8261143 8261144 8261158 8261747 8261748 8261964 8261965 8263059
More informationGasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) B01
GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 5-0 B0 7. Printed in Germany Rösler Druck Edition 06.0 r. 5 758 6 Technical description The DUGS GasMultiBloc integrates
More informationSingle-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5
Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5 6.20 Printed in Germany Edition 02. Nr. 214 6 1 6 Technical description The DUNGS safety solenoid valve MV/4, MVD, MVD/5, MVDLE/5 is a single-stage
More informationW801T (Downflow) Series Models with Input Rates from 75 to 125 kbtu [15 to 37 kw] (80% A.F.U.E. )
FORM NO. G66-549 REV. 3 Supersedes Form No. G66-536 Rev. 3 DOWNFLOW GAS FURNACE Features 80% residential Gas Furnace CSA certified 7 Segment LED all units Direct Spark Ignition System for reliability and
More informationSingle-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5
Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5 6.20 Printed in Germany Edition 09.17 Nr. 214 756 1 6 Technical description The DUNGS safety solenoid valve MV/4, MVD, MVD/5, MVDLE/5 is a single-stage
More informationRheem Classic Plus Series Downflow Gas Furnace
Gas Furnaces Rheem Classic Plus Series Downflow Gas Furnace R801T Downflow Series 80% A.F.U.E. Input Rates 75-125 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with Department
More informationGriddle, Manual Viking Commercial Division 19
, 60-30-12 2009 Viking Commercial Division 19 V60G- V30G- Part Number Part Description QTY QTY QTY 1 AV60PS Plate Shelf, Standard 60" 1 AV30PS Plate Shelf, Standard 30" 1 AV12PS Plate Shelf, Standard 12"
More informationGasMultiBloc Combined regulator and safety shut-off valves Two-stage function MB-ZRD(LE) B01
GasMultiBloc Combined regulator and safety shut-off valves Two-stage function MB-ZRD(LE) - 12 B01 7.0 Printed in Germany Rösler Druck Edition 0.98 21 76 1 6 Technical description The DUGS GasMultiBloc
More informationDouble solenoid valve Rp 3/8 - Rp 2 nominal diameters DMV-D/11 DMV-DLE/11
Double solenoid valve Rp 3/8 - nominal diameters DMV-D/11 DMV-DLE/11 7.30 Printed in Germany Rösler Druck Edition 10.02 Nr. 218 375 1 6 Technical description The DUNGS double solenoid valve DMV integrates
More informationGasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 403 B01 MB-D(LE) 053 B01
GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 0 B0 MB-D(LE) 05 B0 7.0 Printed in Germany Rösler Druck Edition 0.0 r. 765 6 Technical description The DUGS GasMultiBloc
More informationGasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) B01
GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 0-2 B0 7.0 Printed in Germany Rösler Druck Edition 08.00 r. 2 72 Technical description The DUGS GasMultiBloc integrates
More informationG600 Series Replacement Intermittent Pilot Ignition Controls
Installation Instructions G600 Issue Date 0601 G600 Series ment Intermittent Pilot Ignition Controls Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing
More informationSIT Pilot Assembly Retrofit - # 308 (Replaces R. Shaw Pilot Asbly) (SKU # )
Check Condition of Shipment SIT Assembly Retrofit - # 308 Upon receipt of this kit, check the condition of the packaging. Damage to the package should be noted on the carrier's freight receipt. Any damage
More informationKINEMAX. Medium velocity gas or oil burners
KINEMAX Medium velocity gas or oil burners High Temperature Burners - KINEMAX -.- Exit velocities up to 00 km/h (8 m/s) to promote workload heat penetration and better furnace temperature uniformity Operate
More informationGasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 403 B01
GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 0 B0 7.0 Printed in Germany Edition 0.8 r. 765 6 Technical description The DUGS GasMultiBloc integrates filter,
More informationSingle-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5
Single-stage safety solenoid valves COMBUTEC MV/4 MVD, MVD/5, MVDLE/5 6.20 Printed in Germany Edition 09.12 Nr. 214 6 1 6 Technical description The DUNGS safety solenoid valve MV/4, MVD, MVD/5, MVDLE/5
More informationSingle-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5
Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5 6.20 Printed in Germany Rösler Druck Edition 02.08 Nr. 214 6 1 6 Technical description The DUNGS safety solenoid valve MV/4, MVD, MVD/5, MVDLE/5
More informationStart-up Instructions
RadMax Burners Page 400-S- Start-up Instructions Read complete instructions before proceeding and familiarize yourself with all the system s equipment and components. Verify that all equipment has been
More informationHEAVY DUTY RANGES GRIDDLE TOP
GRIDDLE TOP Model Numbers IHR-G36 IHR-GT36 IHR-G36-C IHR-GT36-C IHR-G36-XB IHR-GT36-XB IHR-G36-M IHR-GT36-M 1" (25 mm) thick steel polished griddle plate. M shaped burner for even heating throughout the
More information5270 Edison Ave., Chino, CA (Tel) (Fax)
5270 Edison Ave., Chino, CA 91710 (Tel) 800-790-1299 (Fax) 909-718-1949 NOTICE Dear Customers: Thank you for choosing our barbeque grill and hope that you enjoy our product. Our gas valves and components
More informationGasMultiBloc Combined regulator and safety shut-off valves Single-stage function Integrated bypass valve MB-D(LE) B07
GasMultiBloc Combined regulator and safety shut-off valves Single-stage function Integrated bypass valve MB-D(LE) 07 - B07 7. Edition 0.6 Nr. 9 6 Technical description The DUNGS GasMultiBloc integrates
More informationJ Series Pilot Burners/Y90 Series Inlet Fittings
Product Bulletin Issue Date September 8, 2008 J Series Pilot Burners/Y90 Series Inlet Fittings J Series Pilot Burners/Y90 Series Inlet Fittings are used with Intermittent Pilot Ignition (IPI) and Standing
More informationValve monitoring system VDK 200 A S02
Valve monitoring system VDK 200 A S02 8.11 Printed in Germany Edition 11.17 Nr. 214 768 1 6 Technical description The VDK 200 A S02 is the compact valve monitoring system as per EN 1643 for automatic shut-off
More informationGasMultiBloc Combined regulator and safety shut-off valves Two-stage function Integrated bypass valve MB-ZRD(LE) B07
GasMultiBloc Combined regulator and safety shut-off valves Two-stage function Integrated bypass valve MB-ZRD(LE) - B07 7. Printed in Germany Rösler Druck Edition 0.0 r. 9 Technical description The DUGS
More information1070 SERIES ULTRA LOW NO X
CAPABILITIES High release rates with moderate air Good turndown with flame characteristics and direction maintained Stable flames can be from highly oxidizing for tempered flame operation to highly reducing
More informationPressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG Variable air/gas ratio control with solenoid valve VAV
Pressure regulator with solenoid valve Air/gas ratio control with solenoid valve Variable air/gas ratio control with solenoid valve VAV Product brochure GB 3.1.0.4 Edition 03.08 All-purpose servo regulator
More informationMODERUSTIC Battery Operated Remote Control Electronic Safety Pilot System IPI Intermittent Pilot Light For Fire Pits or Fireplaces
MODERUSTIC Battery Operated Remote Control Electronic Safety Pilot System IPI Intermittent Pilot Light For Fire Pits or Fireplaces Model: AFVK-SP-MH/L Remote flame height adjustment DC Motor Drive Hi,
More informationCOMETTO. Cooking equipment. Spare parts for: Suitable for:
Spare parts for: Cooking equipment This catalogue is automatically generated. Therefore, the sequence of the items might not be always shown at best. Updates will be issued in case of additions and/or
More information36H Gas Control Product Information
Single Stage 36H Two Stage 36H 36H Gas Control Product Information The 36H combination gas control valve is a versatile multifunction control designed to meet the requirements for use with intermittent
More informationRatioAir Burners. Model RA0750. Data /31/05. Main Specifications - RA0750
Main Specifications - RA0750 PARAMETER Maximum input, Btu/hr (kw) at neutral chamber conditions. (Natural Gas) 60Hz Packaged 50Hz Packaged Minimum input, Btu/hr (kw) Lower inputs may be achieved. Contact
More informationThe installation and maintenance of this product must be done under the supervision of an experienced
AA...A2 Differential Air Pressure Switch Installation Instructions USA CDN Table of Contents Table of Contents...Page 1 Approvals...Page 1 Attention...Page 1 Specification...Page 2 Model Description &
More informationG72x Series Direct Spark Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G72x Issue Date 1299 G72x Series Direct Spark Ignition Controls Figure 1: G72x Direct Spark Ignition
More information36C and 36D Gas Control Product Information
6C and 6D Gas Control Product Information The 6C and 6D combination gas control valves are compact multifunction controls designed to meet requirements for use with Standing Pilot systems and all types
More informationSERVICE MANUAL (INTERNATIONAL)
SERVICE MANUAL (INTERNATIONAL) IMPINGER CONVEYOR OVEN MODEL 1100-000-A SERIES (SN 2038615 & BELOW) SERVICE MANUAL Lincoln Foodservice Products, LLC 1111 North Hadley Road Fort Wayne, Indiana 46804 United
More information(For serial numbers before w/ analog control)
SEQUENCE OF OPERATIONS (For serial numbers before 2038616 w/ analog control) MODEL 1154-000-EA NAT. GAS 230 VAC 50 HZ. 1 PHASE MODEL 1155-000-EA LP GAS 230 VAC 50 HZ. 1 PHASE POWER SUPPLY Electrical power
More informationRatioAir Burners. Model RA1000. Data /31/05. Main Specifications - RA1000
Main Specifications - RA1000 PARAMETER Maximum input, Btu/hr (kw) at neutral chamber conditions. (Natural Gas) 60Hz Packaged Blower 50Hz Packaged Blower Minimum input, Btu/hr (kw) Lower inputs may be achieved.
More informationSERVICE MANUAL RRG SERIES HEAVY DUTY GAS GRIDDLE - NOTICE - ML ML ML RRG Shown
SERVICE MANUAL RRG SERIES HEAVY DUTY GAS GRIDDLE 24RRG 36RRG 48RRG 60RRG ML-135339-00024 ML-135340-00036 ML-135341-00048 ML-135342-00060 24RRG Shown - NOTICE - This Manual is prepared for the use of trained
More informationSolenoid valves for gas VAS, Double solenoid valves VCS
Solenoid valves for gas VAS, Double solenoid valves VCS A further development of the solenoid valves for gas VG and VS Suitable for a max. inlet pressure of 500 mbar (7 psig) Easy installation into a system
More informationSafety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 07.15
17 Elster GmbH Edition 1.17 Translation from the German 519 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Solenoid valve for gas VG VG 15/1 Contents Solenoid valve for gas
More informationInnovations in Remote Controls
Innovations in Remote Controls Terry Brumbaugh SkyTech Products Group This session will cover various types of remote controls that are used in the hearth industry. From ultra-sonic remotes to infrared
More information1630 SERIES CYCLOPS TM ULTRA 4 LOW NOX TM HOT AIR BAFFLE BURNER
CAPABILITIES Industry leading low NOx emissions High momentum. luminous flames at all furnace temperatures High release rates with moderate main combustion air pressure Good turndown with flame characteristics
More informationMODEL RVS304. REMOTE CONTROLLED SAFETY PILOT KIT Supplemental Installation Instructions for use with Natural Gas Log Sets
MODEL RVS304 REMOTE CONTROLLED SAFETY PILOT KIT Supplemental Installation Instructions for use with Natural Gas Log Sets NOTE: This kit is for both Natural Gas and LP Gas applications. For LP (Propane)
More informationParts Catalog GAS COOKING EQUIPMENT FRYERS NATURAL GAS MODELS: GF15G & GF30G LP GAS MODELS: GF15PG & GF30PG
Parts Catalog GAS COOKING EQUIPMENT CHARBROILERS RADIANT MODELS: GCB5G, GCB24G, GCB36G & GCB48G CHAR ROCK MODELS: GCBRK5G, GCBRK24G, GCBRK36G & GCBRK48G FRYERS NATURAL GAS MODELS: GF5G & GF30G LP GAS MODELS:
More informationTroubleshooting Electronic Ignition
Troubleshooting Electronic Ignition Bob Wise CVC Coaching This session is designed to provide a broad approach to troubleshooting electronic ignition systems. Various hearth electronic systems will be
More informationGF802D SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (U.S. & Canadian Models)
FORM NO. GSC-515 GF802D SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (U.S. & Canadian Models) TWO STAGE DOWNFLOW GAS FURNACES The Sure Comfort 2-Stage line of downflow gas furnaces
More informationFlow limiter SP/SMB9 for mounting plates
1-3002-EN Flow limiter SP/SMB for mounting plates Advantages reliable perpetual dispensation of individual volume flows - self-adjusting metering, thus identical volume flows despite different back pressures.
More information36/60/160/260 L Series Gas Ranges
VULCAN L Series Gas Ranges 36/60/160/260 L Series Gas Ranges 34 THRU 41 1 5 51 52 26 42 THRU 49 55-56-57 2-3-4 33 31-32 25 29-30 27 15 PL-53065 14 13 12 28 24 23 22 21 20 19 18 16 17 52 11 10 9 8 7 6 632
More informationGAS FURNACES CLASSIC SERIES SUPER QUIET 80 80% A.F.U.E. DOWNFLOW GAS FURNACES
FORM NO. G11-487 REV. 1 Supersedes Form No. G11-487 Rev. 8 GAS FURNACES RGLN- SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] (U.S. & Canadian Models) Annual Fuel Utilization
More informationTypetested for liquid fuels and liquefied petroleum gas (LPG) in the liquid phase (see Data Sheet T 8022 EN) Version according to ANSI standards
Series 240 Pneumatic Control and Quick-acting Shut-off Valves for gases Type 3241-1-Gas and Type 3241-7-Gas DIN-DVGW typetested acc. DIN EN 161 (1996-08) Application Control valves for control equipment
More informationPARTS LIST GAS TILTING SKILLETS MODELS: ACGTS-30 ACGTS-40
PARTS LIST GAS TILTING SKILLETS MODELS: ACGTS-30 ACGTS-40 ACCUTEMP PRODUCTS, INC. 8415 North Clinton Park Dr. Fort Wayne, IN 46825 800 210-5907 Office 260 493-0415 Fax www.accutemp.net PART 10006R13 1
More informationRheem Classic Series Downflow Gas Furnace
Gas Furnaces Rheem Classic Series Downflow Gas Furnace R801S (Downflow) Series 80% A.F.U.E. Input Rates 50-150 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with Department
More information3/2-way Solenoid Valve for pneumatics
656 3/-way Solenoid Valve for pneumatics Compact design Single and manifold mounting Low power consumption Rocker pilot in DC Type 656 can be combined with... Fast response times Type 506 Type 510/511
More informationPT-M90 Automatic Full-Sequence Modulation Gas Control System
PT-M90 PT-M90 Automatic Full-Sequence Modulation Gas Control System PT-M90 Module System Illustration Pucada.Tech M901-0316 Gas Valve (PT-V1C-with step motor) A Profile Dimension: Length(84mm) * Width(40mm)
More informationRuud Achiever Plus Series Upflow/Horizontal Gas Furnace
Gas Furnaces Ruud Achiever Plus Series Upflow/Horizontal Gas Furnace R802P- Upflow/Horizontal Series 80% A.F.U.E. Input Rates 50-150 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance
More informationGARLAND WENDY S COMBO RANGE STW286, STW28 SERIES
GARLAND WENDY S COMBO RANGE STW286, STW28 SERIES Toll Free Phone, (US & Canada): (800) 427-6668 Toll Free Fax, (US & Canada): (800) 361-7745 http://www.garland-group.com Form # stwparts (2/2000) Page 2
More informationRheem Value Series Downflow Gas Furnace
THIS MODEL 80.0% 78% 82% 88% 97% Air Gas Furnaces Rheem Value Series Downflow Gas Furnace RGLS- Series 80% A.F.U.E. Input Rates 50-150 kbtu ENER UIDE Annual Fuel Utilization Efficiency - AFUE MID A.F.U.E.
More informationO.K. Safety first CDN USA. Table of Contents. Approvals. Attention IFGC CSA UL ANSI NFPA
AA...A2 Differential Air Pressure Switch Installation Instructions USA CDN Table of Contents Table of Contents...Page 1 Approvals...Page 1 Attention...Page 1 Specification...Page 2 Model Description &
More informationData /1/07 Eclipse RatioAir Burners Model RA0040
Maximum input, () at neutral chamber conditions 60Hz Packaged Maximum input, () at neutral chamber conditions 50Hz Packaged Minimum input, () Lower inputs may be achieved. Contact factory. Main Gas Inlet
More informationVKF41...C. Butterfly Valves. Building Technologies Division Industry Sector
7 62 Butterfly Valves VKF41...C Butterfly valves designed for fitting between counter-flanges, for integration into gas trains Disk with metallically tight shutoff DN40...DN200 Angle of rotation 85 No
More information2-Way/2 Position Valves
4 2-Way/2 Position Valves Two-way solenoid valves have one inlet and one outlet, and are used to permit and shut off fluid flow. Two Types of Operations Apply Normally Closed (NC) Fluid is shut off when
More informationf i r e - p a r t s. c o m
A M E R I C A N F L A M E A F AF-4000 Series Electronic Gas Control Valve APPLICATION The AF-4000 Electronic Gas Control Valve is designed for use in gas in hearth products, wall mount furnaces, and space
More information80% A.F.U.E. DOWNFLOW GAS FURNACES
FORM NO. G66-496 REV. 5 Supersedes Form No. G66-496 Rev. 4 RGLS- SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] (U.S. & Canadian Models) 80% A.F.U.E. DOWNF GAS FURNACES The
More informationToll Free Phone, (US & Canada): (800) Toll Free Fax, (US & Canada): (800)
Toll Free Phone, (US & Canada): (800) 427-6668 Toll Free Fax, (US & Canada): (800) 361-7745 http://www.garland-group.com MODEL: MCO-GS/GD-10 MU - CE UNITS Oven Manufactured Up To May 29, 2008 DESCRIPTION
More information