MATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****

Similar documents
MATERIAL SPECIFICATION ELECTRIC OPERATIONS ORGANIZATION. M3902 ****Supercedes BECo Standard E and ComElectric Spec ****

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

1500 kva Pad Mount Transformer GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled

C. System Design and Performance Requirements

SECTION PADMOUNT TRANSFORMER - OIL FILLED

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115

GENERAL INFORMATION POLE MOUNT TRANSFORMER SINGLE PHASE PAD MOUNT TRANSFORMER SINGLE PHASE POLE MOUNT TRANSFORMER THREE PHASE 17

1TSF /CD Attachment B. City and County of San Francisco Office of Contract Administration

Distribution Transformers

DISTRIBUTION TRANSFORMERS SPECIFICATION #

TECHNICAL SPECIFICATIONS OIL FILLED PADMOUNTED THREE PHASE WYE-WYE TRANSFORMERS

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS

Technical Specification for Pole Mounted Capacitor Rack

SPECIFICATION FOR THREE PHASE PAD-MOUNT DISTRIBUTION TRANSFORMERS

Distribution Transformers

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

DISTRIBUTION TRANSFORMERS Single-Phase Pad-Mounted

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

Single phase pole mounted. 11kV. Electrical Engineer KEU ID#:

500 kva Pad Mount Transformer V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Effective March 2015 Supersedes S August 2012

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor

INSTRUCTION MANUAL #103

Technical Specification For Outdoor Substation Harmonic Filter Banks

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

Three-Phase Pole Mounted Recloser

Single-Phase Step Voltage Regulator

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Underground Distribution Switchgear

Single Phase Padmounted Transformers kva

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

Outdoor Power Transmission & Distribution

Power IT Liquid Filled Single Phase Padmounted Transformers kva

35-kV Safefront 200 Amp Primary Metering Station Pad-Mounted Outdoor

NEW Solutions for Underground System Growth

SUBSTATION TYPE TRANSFORMER - MINERAL OIL FILLED THREE PHASE OISC 65 C RISE 60 HERTZ

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Underground Distribution Switchgear

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

Padmount. Small Power Transformers 2500 kva Through 20,000 kva 5 kv Through 46 kv Primary Voltage 120V Through 25 kv Secondary Voltage

Single-Phase Step Voltage Regulators

100 / 110 DRYWELL FUSE SPECIFICATION

Single-phase step voltage regulators

Three Phase Padmounted Transformers kva

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

Generator Fire Safety: Generator assemblies should be located outside the building.

Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

www. ElectricalPartManuals. com WeSTinghouse Secondary Unit Substation Transformers (Power Centers) Descriptive Bulletin Page 1

10 Commercial, Industrial, Agricultural Services

Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

Disconnect & ByPass Switches

7. SERVICES OVER 600 VOLTS

Figure 1. Two and Three-phase MagneX.

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Howard Industries. Single-Phase Step

UNDERGROUND SERVICES - SECONDARY

Figure 1. Single-phase pad-mounted voltage regulator. STANDARD FEATURES

Cleaning Flooded Gear

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

www. ElectricalPartManuals. com Westinghouse PLAZAPADTM Tamper-Resistant Transformers For Underground Power Distribution 750 Thru 2500 Kva

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

MIRUS International Inc. TYPICAL SPECIFICATION ULLTRA & ULLTRA-H1E 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6

Approved Meter Sockets and Cabinets

15-kV Live Terminal Primary Metering Station Pad-Mounted Outdoor

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011

UPPCO SERVICE MANUAL

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

AMENDMENT ELECTRIC SERVICE MANUAL 2014

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

A. Fan motors and associated equipment shall be sized to operate at 110% of calculated loads and capacities.

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

25 kv class fused loadbreak elbow connector

SPECIFICATIONS - DETAILED PROVISIONS Section Vertical Hollowshaft Electric Motors C O N T E N T S

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

City of Ottawa Street Lighting. HID Shoebox Style Luminaire

STANDARD SPECIFICATION FOR PAD-MOUNTED CAPACITOR BANKS FOR 15kV or 25kV APPLICATIONS

15-kV Safefront 200 Amp Source Isolated Cable Switching Station Pad-Mounted Non-Fusible

C1000 Series Automatic Cap Bank

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak

TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV

M-Force three-phase switch

Unit Substation Transformers 5 and 15 KV Class

Transcription:

Page 1 of 8 ****Supercedes BECo Standard E2.12-2.14 and ComElectric Spec 7-0895**** THREE-PHASE DEADFRONT PAD-MOUNTED DISTRIBUTION TRANSFORMERS, LOOP & RADIAL FEED DESIGNS 1.0 General Requirements 1.1 These specifications cover three-phase deadfront pad-mounted transformers, loop and radial feed designs, that shall be mineral oil filled, Class OA, 60 Hertz, 65 C average winding temperature rise. 1.2 Transformers furnished under these specifications shall conform to the applicable portions of the latest version of IEEE/ANSI Standard C57.12.34, except where otherwise specified herein. 1.3 Sound levels for transformers shall meet NEMA TR1, latest revision. 1.4 No changes shall be made in any way that would affect agreement with these specifications after transformer designs have been approved by NSTAR Electric (the Company). No transformer shall be furnished or accepted unless the details of such proposed changes have first been submitted in writing and approved by the Company. Failure to comply with these terms may result in complete or partial removal from the approved supplier list. 1.5 Any exceptions to these specifications shall be clearly indicated with price quotations. Approval drawings shall be submitted upon request. 1.6 Unless otherwise specified on purchase order, transformer warranty must be for a minimum period of one year from date of installation or 18 months from the date of receipt, whichever occurs first. Written warranty policy must be on file with NSTAR Electric s Purchasing Department. 1.7 All units shall have the following additional information on their nameplate: year of manufacture, total weight with oil and volume of oil (in gallons). 1.8 All units shall meet the efficiencies in Table 2 of NEMA Publication TP-1, latest revision or DOE s final ruling of 10/12/07 as called for on the purchase order.

Page 2 of 8 1.9 NSTAR North and NSTAR South may be distinguished by primary voltage. The primary voltage for NSTAR North units is either 13800GY/7970 or 13800GY/7970 x 4160GY/2400. All other voltages are NSTAR South units. 2.0 Construction 2.1 For NSTAR North units, high voltage winding shall be delta. 2.2 The number, location and arrangement of the high voltage connectors and low voltage terminals shall be ANSI specific as shown in Figs 5-8. Low voltage terminals shall have staggered arrangement, with dimensions per Fig. 8(a). 2.3 For units sized 500 kva and smaller, the impedance range shall be from 3.0 to 4.75%, including manufacturing tolerances. 2.4 High Voltage Bushings: A. High voltage connectors shall be externally clamped bushing wells with replaceable stud. B. NSTAR North 15 kv class bushing well inserts shall be installed and properly torqued into each bushing well. NSTAR South Units with a primary voltage of 13200GY/7620, either straight or dual voltage, shall be provided with 15 kv class bushing well inserts, installed and properly torqued. C. Inserts shall have grounding tabs bonded to tank ground connector using #14 AWG solid copper wire. D. All NSTAR North units shall be arranged for loop feed. All NSTAR South units shall be either loop or radial feed arrangement as detailed in the ordering specifications on the purchase order. E. For NSTAR South units: All HV bushings, regardless of primary voltage, shall be spaced for 15.2 kv. 2.5 Low Voltage Bushings: A. Low voltage neutral terminal to be a fully insulated terminal. B. Low voltage line and neutral bushings must be furnished with J type, tinned copper spade terminals. Spades for units 150 kva and below shall be 6-hole and for units 300 kva and above shall be 10-hole. C. Low voltage terminal supports for static loads shall be supplied for all kva sizes.

Page 3 of 8 2.6 Wye-Wye connected units shall have the high-low neutral connection externally accessible/separable through a handhole (consistent with ANSI C57.12.34 sect 9.7.3.4). 2.7 Compartment sizes for NSTAR North units: A. HV compartment on units 500 kva and below shall have a maximum width of 38. B. HV/LV barrier shall terminate 18 from the bottom. 2.8 Coastal Zone Design transformers shall have tanks, sills, hinges, clamps and all other hardware fabricated of Type 304L stainless steel. 2.9 The paint color shall be Green (Munsell Notation 7GY3.29/1.5). Final finish shall exceed the requirements of ANSI C57.12.28 with a minimum dry film thickness of 4 mils on all surfaces and seams. All compartment and transformer surfaces in contact with the pad shall be treated to minimize corrosion and abrasion damage. 3.0 Accessories 3.1 All transformers with a 125 kv BIL primary winding (25 kv system) will have a 200A, under-oil loadbreak switch. The switch will be rotary type, hot-stick operable, and located in the primary compartment. A metallic nameplate shall identify each position. Radial transformers will have a two-position switch. Loop feed transformers will have two two-position switches for uninterrupted load transfer capabilities. 3.2 Tap changer: For NSTAR North, all units shall have an externally operated tap changer. Tap positions shall be 14400/14100/13800/13500/13200. Dual voltage units shall have taps only at the higher voltage. For NSTAR South, taps, if required, will be detailed in the ordering specifications on the purchase order. 3.3 All units will have an automatic pressure relief device with a minimum flow rate of 50 SCFM at 15-psi. 3.4 All units shall have a heavy-duty brass gate-type oil drain valve. An oilsampling device shall be included in place of the drain plug. 3.5 Single voltage unit fusing: See following tables.

Page 4 of 8 3.0 Accessories, cont d A. All NSTAR North units shall have a Bay-O-Net fuse in series with a partial range current limiting fuse (PRCLF). B. All NSTAR South units shall have a Bay-O-Net fuse in series with a PRCLF, unless otherwise specified. When PRCLF s are not used, an isolation link will be used in series with the Bay-O-Net. 3.6 Dual voltage unit fusing: See following tables. A. All NSTAR North units shall have a Bay-O-Net fuse in series with a partial range current limiting fuse. The units shall be shipped fused at the higher voltage. For coordination purposes, table shows Bay-O-Net fuse that will be used at lower voltage. B. All NSTAR South units shall be protected with a Bay-O-Net fuse in series with a PRCLF at the higher voltage and an isolation link at the lower voltage. Units shall not be shipped with fuse cartridge installed in the Bay-O-Net. Units shall be shipped with the fuse cartridges (not just the fuse links) for both voltage levels, secured in the primary compartment. 22,860 GrdY/ 13,200 or 24,940 GrdY/14,400 Volts Size (kva) BAY-O-NET LINK 75 3A (Cooper 358C03) 112.5 6A (Cooper 108C04) 150 8A (Cooper 358C05) 225 12A (Cooper 108C06) 300 15A (Cooper 108C07) 500 25A (Cooper 108C09) 750 40A (Cooper108C11) 1000 50A (Cooper 108C12) 1500 65A (Cooper 353C14) 2000 100A (Cooper 353C14 2500 140A Cooper 353C17) Table 1 Bayonet Fusing NSTAR South (25 kv)

Page 5 of 8 3.0 Accessories, cont d 13,200 GrdY/ 7,620 Volts Size (kva) BAY-O-NET LINK 75 8A (Cooper 358C05) 112.5 12A (Cooper 108C06) 150 15A (Cooper 108C07) 225 25A (Cooper 108C09) 300 25A (Cooper 108C09) 500 50A (Cooper 108C12) 750 65A (Cooper 353C14) 1000 65A (Cooper 353C14) 1500 100A (Cooper 353C14) 2000 140A (Cooper 353C17) 2500 125A (Cooper 4038361C05CB) Table 2 Bayonet Fusing NSTAR South (15 kv) 3740GrdY/2160 or 4,160GrdY/2400 or 2,400 x 4,800 Volts (NSTAR South only) Size (kva) BAY-O-NET LINK 75 25A (Cooper 108C09) 150 50A (Cooper 108C12) 300 65A (Cooper 353C14) 500 140A (Cooper 358C18CB) 750 140A (Cooper 358C18CB) Table 3 Bayonet Fusing NSTAR South (5 kv & Below)

Page 6 of 8 8,320GrdY/4800 Volts (NSTAR South only) Size (kva) BAY-O-NET LINK 75 12A (Cooper 108C06) 150 25A (Cooper 108C09) 300 50A (Cooper 108C12) 500 65A (Cooper 353C14) 750 140A (Cooper 358C18CB) Table 4 Bayonet Fusing NSTAR South (8.3 kv) 13,800 GrdY/7,970 Volts or 4160 GrdY/2400X13,800 GrdY/7,970 Volts Size (kva) Phase-Grd Voltage BAY-O-NET LINK 75 6A (Cooper 108C04) 112.5 12A (Cooper 108C06) 150 15A (Cooper 108C07) 300 25A (Cooper 108C09) 500 50A (Cooper 108C12) 750/1000 7970 65A (Cooper 353C14) 1500 100A (Cooper 353C16) 2000 140A (Cooper 353C17) 2500 125A (Cooper 4038361C05CB) 112.5 40A (Cooper 108C11) 150 2400 50A (Cooper 108C12) 300 65A (Cooper 353C14) Table 5 Bayonet Fusing for NSTAR North

Page 7 of 8 3.7 Primary connected under oil, heavy duty MOV surge arresters meeting ANSI/IEEE C62.11, shall be provided on all single voltage units. Dual voltage units needing under oil arresters will have the requirement detailed in the ordering specifications on the purchase order. Primary Voltage (Ph-Gnd kv) Arrester Class (kv) 4.8 6 7.62 10 7.97 12 13.2 and 14.4 18 Table 6 Under Oil Arrester Ratings 3.8 A means of containing the oil when bayonet fuses are operated shall be provided. This may be in form of a drip pan or drip cups. 3.9 All transformers 500 kva and larger shall be equipped with oil level and oil temperature (with resettable maximum temperature indication) gauges. 3.10 All units must be supplied with two (2) company approved tank-grounding lugs that will accommodate a 4/0 AWG copper conductor. 4.0 Labeling/Marking/Drawings 4.1 A PCB information statement will be placed either on the transformer s nameplate or on a separate distinct and equally durable label adjacent to the nameplate stating its PCB concentration as less than 2 PPM at the time of manufacture. In addition, a separate company approved, no-pcb label shall be affixed to the outside of the transformer. The label shall read No-PCB Less than 2PPM in bold-type white lettering on a green background. 4.2 A permanent bar code label meeting the latest revision of ANSI C57.12.35 shall be provided. 4.3 Each transformer shall be stenciled with numbers that identify the KVA- CODE of the transformer. This is in lieu of the KVA only stencil. The KVAcode shall be designated on the purchase order. Flat black, fade resistant

Page 8 of 8 paint shall be used. The lettering shall be approximately 2.5 high and will be located 3 from the top hinge, towards the handle, centered. Stenciling Examples: 75-308, 150-338 4.4 The manufacturer shall install an external warning label (Electromark # BOS044-W-PT-A72) and two, internal danger labels (Electromark # BOS045-W-PT-112) Outer label shall be located on the door, adjacent to the handle. Inner labels shall be located on the back wall of the low voltage compartment and the front barrier or back wall of the high voltage compartment near the elbow terminations. 4.5 Two approved warning decals advising field personnel to vent transformer prior to operating bayonet fuses shall be installed and located on each unit as follows: A. Under the bayonet fuse location and above the drip shield. B. Adjacent to the pressure relief device. 4.6 Each transformer shall be marked with the cat id using durable, weather proof, UV resistant labels or painted stencils. The lettering shall consist of 1 inch high bold black characters. Cat id shall be located above the No PCB label. 4.7 All units 500 kva and larger shall be shipped with one complete set of drawings and instruction manuals stored in the secondary compartment in a waterproof envelope. 5.0 Delivery 5.1 Unless otherwise specified on purchase order, all deliveries shall be made in an open top truck. All transformers shall be shipped secured to a wooden pallet unless their size prohibits it. The stacking of transformers may be cause for rejecting an entire shipment. 5.2 NSTAR South areas only require a 24-hour notification to the stockroom supervisor prior to delivery. 5.3 Transformers are subject to inspection by the Company upon delivery. Approved by: Amin Jessa Director, Distribution Engineering