SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 15 Troubleshooting Basic Controls

Similar documents
HVACR Electrical Systems

FAST-STAT. Model 3000 Installation Instructions. Application. Troubleshooting not operating. Before Installing This Product. Sender Installation

SECTION 4 ELECTRIC MOTORS UNIT 20 TROUBLESHOOTING ELECTRIC MOTORS UNIT OBJECTIVES 3/21/2012

SECTION 4 ELECTRIC MOTORS UNIT 20 TROUBLESHOOTING ELECTRIC MOTORS

Fan Coil Unit (FCU) Fan Motor Control

ALTERNATOR PRECAUTIONS. Some precautions should be taken when working on this, or any other, AC charging system.

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

Full file at

Single-Phase Meter Components

wiring diagrams SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS

1984 Jeep CJ7. IGNITION SYSTEM - SOLID STATE' 'Distributors & Ignition Systems MOTORCRAFT SOLID STATE IGNITION (SSI)

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

TROUBLESHOOTING GUIDE FOR HEAT PUMP BOOSTERS MODELS: HPB11, HPB15, & HPB22

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

Wiring Diagrams (Including Accessories) (50/60 Hz)

Two temperature sensors to protect against freezing and high head pressure in both the indoor evaporator and the outdoor condenser

16.3 Ohm s Law / Energy and Power / Electric Meters

Physics Experiment 9 Ohm s Law

Coil Data Nominal Current MA Nominal VA Sealed. Coil Data Nominal Current MA Nominal VA Sealed. Single Pole Double Throw (SPDT)

REPLACEMENT PARTS MANUAL

Basics of Control Components

Northwest RV Supply Manual Compliments of Printed From TROUBLESHOOTING

ENGINE COOLING FAN Toyota Celica ELECTRIC COOLING FAN RADIATOR COOLING FAN SYSTEM TEST ENGINE COOLING Toyota Engine Cooling Fans

ELECTRIC HEAT ACCESSORY INSTALLATION INSTRUCTION. 20, 30 & 40 kw for 15 Ton Split System Air Conditioners Models: LB180 & LL A-0102

Modern Auto Tech Study Guide Chapter 8 Pages Electricity & Electronics 37 Points. Automotive Service

P5RF Series Single Packaged Air Conditioner Single Phase

MOTOR CONTROLLERS. STATE the function of motor controllers.

Q5RD Series Single Packaged Heat Pump, Single Phase

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS

POWER METER. my2010 (c)

GQ3RD Series. Single Packaged Heat Pump, Single Phase TECHNICAL SPECIFICATIONS

Coil Data Nominal Current MA Nominal VA Sealed Single Pole Normally Open (SPNO) White Rodgers Q

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

THE ELECTRICAL CIRCUIT

A/C-HEATER SYSTEM - AUTOMATIC

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

GQ5RD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase 13 SEER, R-410A, WARRANTY

SPECTRACOOL Slim Fit Air Conditioners (Surface-Mount Units Only) Quick Start Operation Guide

715B CONTROL SERIES. Instruction Manual Line Voltage DC Brushless Motor Control CONTROLS. Phone (317) Fax (317)

WATER SOURCE HEAT PUMPS REPLACEMENT PARTS MANUAL MODELS: General Notes. Contents. Important

GP5RD Series. Single Packaged Air Conditioner, Single Phase TECHNICAL SPECIFICATIONS

Wiring Diagrams DIAGRAM INDEX

PAB SERIES 3thru6-1/3Ton. Belt Drive 10 SEER CONVERTIBLE SINGLE PACKAGE AIR CONDITIONING UNIT /01

BITZER Liquid Injection Guidelines for CSH Compressors

GQ5RD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase 13 SEER, R-410A, WARRANTY

MODEL 422 Submersible Pump Controller

Eclipse 2000 Service Parts

Equivalent Meter Resistance

CHARGING SYSTEM 8C - 1 CHARGING SYSTEM CONTENTS

This chapter contains information on DC Generation, External Power, and Electrical Load Distribution.

Electrical Controls. Syllabus

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

GP7RD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Air Conditioner, Single Phase WARRANTY

Electronically Commutated Motor Wiring Manual

National 4 Physics - Electricity and Energy Summary Notes

ELECTRICAL. CDTA Technical Training Center

24-00 ELECTRICAL POWER

Applied Decentralized Products Water Source Heat Pump / Rev.A HWH024D, HWH030D HWW024D, HWW030D PL

AC Leak Freeze AIR CONDITIONING. AC Leak Freeze permanently seals leaks in air conditioning and refrigeration systems

UNIT 3: GENErAL ELECTriCAL SySTEM DiAGNOSiS

JT4BD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. R-410A High Efficiency Heat Pump 13 SEER Residential System Ton Capacity WARRANTY

Shaft Voltage and Current Test

JT4BE Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. R-410A High Efficiency Heat Pump 14 SEER Residential System Ton Capacity WARRANTY

SUNLINE 2000 (WORLD 50 HZ)

Schematic Diagram Of Electric Fan Motor Winding

PARKING LOT CONTROLLER WITH LOGIC & MAIN CONTACTOR

ST Charger. Industrial Battery Charger

GQ4SD Series. Single Packaged Heat Pump 13 SEER TECHNICAL SPECIFICATIONS

SERVICE MANUAL (INTERNATIONAL)

GQ6SD Series. Single Packaged Heat Pump 13 SEER, R-410A 2-5 Ton Units TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS WARRANTY

Wiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents.

Technical Information and Diagnostic Guide

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Blank-off. HVAC unit screws. Spacer for 1" filter ILL. 3. Screw

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

600 Series Troubleshooting Guide for C651 and C654 Alternators

TESCO THE EASTERN SPECIALTY COMPANY Date: 05/04/15 Canal Street and Jefferson Avenue Bristol, PA 19007

WATER SOURCE HEAT PUMPS REPLACEMENT PARTS MANUAL MODELS: General Notes. Contents. Important

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

EconoMi$er, Power Exhaust, and Sensor Installation Instructions

ICM 326HN/327HN Line Voltage Head Pressure Control Installation, Operation & Application Guide

VT4BE Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. R-410A High Efficiency Heat Pump 14 SEER Residential System Ton Capacity WARRANTY

EXPERIMENT 2 THREE PHASE INDUCTION MOTOR, PART 1

12 CB30M SERIES UNITS INCLUDING ECB29 ELECTRIC HEAT

Power Factor Correction

Troubleshooting Bosch Proportional Valves

Q3RD Series. Single Packaged Heat Pump, Single Phase TECHNICAL SPECIFICATIONS FEATURES AND BENEFITS

SPC-PANEL Simplex, Single Phase Pump Control Panel

2015 EDITION SUBMERSIBLE MOTORS AIM MANUAL. APPLICATION INSTALLATION MAINTENANCE 60 Hz, Single-Phase and Three-Phase Motors. franklinwater.

Solstice Electric Fryers SE Series Service Manual

ICM325HN. Head Pressure Control with Optional Heat Pump Override. Installation, Operation & Application Guide

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Pressure Makeup Jockey Pump Controller

Building Operator Certification Level I

SECTION MOTOR CONTROL

P7RE Series Single Packaged Air Conditioner

INSTALLATION INSTRUCTIONS

Beware of Ghost Voltage

Electrical Control System Components Basics of Magnetic Control :

ELECTRICAL MAINTENANCE

Transcription:

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 15 Troubleshooting Basic Controls

UNIT OBJECTIVES After studying this unit, the reader should be able to Describe and identify power- and non-power-consuming Describe how a voltmeter is used to troubleshoot electrical circuits. Identify some typical problems in an electrical circuit. Describe how an ammeter is used to troubleshoot an electrical circuit. Describe how a voltmeter is used to troubleshoot an electrical circuit.

UNIT OBJECTIVES After studying this unit, the reader should be able to Recognize the components in a heat-cool electrical circuit. Follow the sequence of electrical events in a heat-cool electrical circuit. Differentiate between a pictorial and a line-type electrical wiring diagram.

INTRODUCTION TO TROUBLESHOOTING Recognize the control and its purpose in the system Controls are either electrical, mechanical or both Electrical devices Power consuming devices use power Example of a power consuming device: a light bulb Power passing devices pass power to the power consuming devices without consuming power themselves (ideally) Example of a power passing device: a switch

Power-passing device Power-consuming device 115V

TROUBLESHOOTING COMPLEX CIRCUITS Check the thermostat 0 volts from R to W when there is a call for heat The coil of the heating relay should be energized Check the fan circuit 0 volts from R to G when the fan relay coil is energized Check the cooling circuit The Y terminal controls the cooling circuit 0 volts from R to Y when there is a call for cooling

Thermostat wire Terminal block in air handler R C G W Y To cooling contactor coil Secondary Primary Transformer From heating, fan and cooling coils To fan relay To heating relay

Thermostat wire Terminal block in air handler R C G W Y Secondary Primary 0V Zero volts from R to G when fan relay is energized

Thermostat wire Terminal block in air handler R C G W Y Secondary Primary 0V Zero volts from R to W when heat relay is energized

Thermostat wire Terminal block in air handler R C G W Y Secondary Primary 0V Zero volts from R to Y when cooling coil is energized

TROUBLESHOOTING THE THERMOSTAT Control voltage must be present in order for the thermostat to operate Turn the fan switch to the ON position to see if the fan begins to operate If the fan comes on, there is low voltage present If the fan does not operate there may be a low voltage problem Check voltage supplied to the transformer primary Check voltage at the transformer secondary

Thermostat Fan switch FAN AUTO ON HEAT OFF COOL When switched to the ON position, the indoor blower should operate if there is low voltage present

TROUBLESHOOTING THE THERMOSTAT The thermostat can be removed from the subbase Install an insulated jumper between R and G (The fan should come on) Install an insulated jumper between R and W (The heat should come on) Install an insulated jumper between R and Y (The cooling should come on) If the circuits operate with the jumpers and not with the thermostat, the thermostat is defective

Line Voltage R G Fan circuit W Heating circuit Insulated jumper Y Cooling circuit Thermostat subbase

TROUBLESHOOTING THE THERMOSTAT On a call for heat, power is passed through the thermostat to the heating relays On electric heating systems, the fan will also be energized on a call for heat On a call for cooling, the following system components are controlled Compressor Condenser fan motor Evaporator fan motor

TROUBLESHOOTING THE THERMOSTAT The compressor and condenser fan motor are wired in parallel with each other Controlled by the Y terminal on the thermostat The Y terminal passes power to the contactor coil Contacts close and energize the compressor and condenser fan The indoor fan will operate continuously when the fan switch is in the ON position The indoor fan will operate only when the compressor is operating when the fan switch is in the AUTO position

TROUBLESHOOTING AMPERAGE IN LOW-VOLTAGE CIRCUITS Transformers are rated in volt-amperes, VA VA rating can be used to determine if the control circuit is drawing too much current Maximum amperage = VA rating/secondary voltage A 40 VA transformer with a secondary voltage can handle a maximum current of 1.67 amps Maximum amperage = 40/24 = 1.67

TROUBLESHOOTING AMPERAGE IN LOW-VOLTAGE CIRCUITS Using a clamp-on ammeter Coil a jumper wire around the jaws of the meter ten times Place the jumper is series with the circuit being checked Divide the ammeter reading by ten Actual circuit amperage should be lower than the calculated maximum circuit amperage Electronic clamp-on meters can often be used without using the 10-wrap method

Line Voltage R G Fan circuit W Heating circuit 7.0 amps Y Cooling circuit Actual amperage = 7/10 = 0.7 amps

TROUBLESHOOTING VOLTAGE IN THE LOW-VOLTAGE CIRCUIT Power consuming devices need to have the proper voltage supplied to them If a relay s holding coil is rated at 24 volts, there should be 24 volts applied to the coil If there is a reading of zero volts across the coil, the problem is likely not the coil If there is a reading of 24 volts across the coil and the relay contacts do not switch position, the coil is defective and the relay should be replaced

GENERAL PURPOSE RELAY 24-volt coil Normally closed contacts Relay Normally open contacts

RELAY NORMAL OPERATION 24-volt coil Coil energized Current flows through closed contacts Relay Normally closed contacts are now in the open position Normally open contacts are now in the closed position

RELAY DEFECTIVE COIL - CONTACTS DO NOT CHANGE POSITION 24-volt coil Voltage applied to the coil Current flows through closed contacts Normally closed contacts remain closed Relay Normally open contacts remain open

TROUBLESHOOTING VOLTAGE IN THE LOW-VOLTAGE CIRCUIT Thermostats can be removed from the subbase to check the low voltage circuits There should be a reading of 24 volts between the R (hot) terminal and the Y (cooling) terminal There should be a reading of 24 volts between the R (hot) terminal and the W (heating) terminal There should be a reading of 24 volts between the R (hot) terminal and the G (indoor fan) terminal

Line Voltage R 24V G Fan circuit 24V W Heating circuit 24V Y Cooling circuit Thermostat subbase

TROUBLESHOOTING ELECTRICAL SWITCHES AND LOADS Switches are wired in series with power-consuming devices (light switch in series with a light bulb) When switches are wired in series with a load, all of the switches must be closed for the load to operate Switches in parallel provide alternative control sequences for the load If there is line voltage supplied to the circuit, there will be line voltage across an open switch

LINE VOLTAGE READING ACROSS THE OPEN SWITCH 115V 115V

115V BOTH SWITCHES MUST BE CLOSED FOR LOAD TO BECOME ENERGIZED

115V BOTH SWITCHES MUST BE CLOSED FOR LOAD TO BECOME ENERGIZED

115V BOTH SWITCHES MUST BE CLOSED FOR LOAD TO BECOME ENERGIZED

SWITCHES IN PARALLEL PROVIDE ALTERNATIVE CONTROL PATHS 115V

SWITCHES IN PARALLEL PROVIDE ALTERNATIVE CONTROL PATHS 115V

SWITCHES IN PARALLEL PROVIDE ALTERNATIVE CONTROL PATHS 115V

SWITCHES IN PARALLEL PROVIDE ALTERNATIVE CONTROL PATHS 115V

SWITCHES IN PARALLEL PROVIDE ALTERNATIVE CONTROL PATHS 115V

TROUBLESHOOTING ELECTRICAL SWITCHES AND LOADS There will 0 volts across a closed switch The voltage reading across the windings of a de-energized motor will be 0 volts An ohmmeter can be used to check switches and loads if all power and wires are disconnected Infinite resistance reading indicates an open circuit Never use an ohmmeter on energized circuits

READING OF ZERO VOLTS ACROSS THE CLOSED SWITCH 0V 115V

PICTORIAL WIRING DIAGRAMS Schematic diagram Used to show the location of circuit components Diagram configured to show the circuits as they are seen in the actual unit Wires are color coded in the diagram to make wire identification easier All wires and connections are included

PICTORIAL DIAGRAM (SIMPLIFIED) BK P1 BK TRANS S1 BL S2 RED L1 L2 P2 COM Hi Lo LIM1 LIM2 G2 6 5 4 C 1 2 3 4 G3 G1 3 2 1 C Y Gc Gh R W Gas GRN

Used to follow the logic of the circuit LINE DIAGRAMS Shows circuits and component functions Easier to use in the troubleshooting process as each circuit is on a separate line (ladder diagram) Lines representing the power supply are located on the left and right sides as vertical lines Power passing and power consuming devices are located on horizontal lines between the power lines The right side of the diagram often has no switches

SIMPLIFIED LADDER (LINE) DIAGRAM L1 L2 Load Load Load

UNIT SUMMARY - 1 Recognize each control and its purpose in the circuit Electric components can be power consuming or power passing devices A measurable voltage reading across a switch indicates that the switch is in the open position A reading of zero volts across a switch in an energized circuit indicates that the switch is in the closed position The thermostat can be evaluated by removing it from the subbase Jumper wires at the subbase can be used to check the individual circuits Control voltage must be present in order for the system to operate

UNIT SUMMARY - 2 If the system does not operate, the voltage at the primary and secondary of the transformer should be checked The indoor fan motor will operate if the fan switch is turned to the ON position The indoor fan motor will cycle on and off with the compressor (in the cooling mode) when the fan switch is turned to the AUTO position Max. control circuit amps = VA rating/secondary voltage Control circuit amperage is measured with an ammeter Power consuming devices must be supplied the proper voltage

UNIT SUMMARY - 3 If proper voltage is supplied to a component and it fails to operate, the component should be evaluated Switches are wired in series with the power consuming device in the circuit Multiple switches can be wired in series Switches in parallel provide alternate control sequences Pictorial diagrams show component locations, color-coded wires, and all electrical connections Line or ladder diagrams show each circuit on a separate line and make the troubleshooting process easier