Technical Specifications for Solar PV System for Retail Outlets. 5.3 Technical specifications of major components of Solar PV power plant

Similar documents
TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT

3.6 Kwp Solar system Supply, Installation, Commissioning & Maintenance of Solar Systems to YEMAC office in HADDA street, Sana a city

SOMALI ENERGY TRANSFORMATION (SET) PROJECT

Details and specification for 30 W solar powered LED street lights.

LOT Kwp Solar PV Power Solution with Battery Backup

Supply, Installation and Commissioning of 1 No 50 Watt LED. based SPV SLS at Nadia District Library, Krishna Nagar, Nadia.

.3 Section Waste Management and Disposal.

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Onix Structure Private Limited. Solar PV Power Generation System Detailed Project Report

Supply, testing, installation and commissioning of 5 ky A UPS system as per the following specification:

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

Technical standard for AC, DC and street light systems

Illuminator Series CR NEMA 3R

Distinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation

NOTICE INVITING TENDER

Distinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

SPECIAL SPECIFICATION 6576 Solar Panel Power Supply System

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

SPECIAL SPECIFICATION 8676 Solar Panel Power Supply System

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

Net +Plus Connection Code

Liebert. FP 50Z kva

Environmental benefits. Lamp disposal problems are eliminated due to the long life of LED lights, and no resources are used in routine maintenance.

UNIVERSITY OF CALCUTTA Centre for Research in Nanoscience and Nanotechnology JD-2, Sector-III, Salt Lake City Kolkata

Photovoltaic Solar Plan Review

SPG-400. Solar-powered generators

Generalised Technical Specifications for Grid Tie Solar Power plants

SOLAR OFF-GRID MPPT PCU ESM3K/48, ESM5K/96, ESM7K5/120, ESM10K/120

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

100kW GROUND MOUNTED SOLAR PHOTOVOLTIC POWER PLANT DETAILED PROJECT REPORT AERO SPACE MATERIALS PVT LTD

INDIAN INSTITUTE OF TECHNOLOGY, KANPUR DEPARTMENT OF ELECTRICAL ENGINEERING

BANGALORE ELECTRICITY SUPPLY COMPANY LIMITED

TECHNICAL SPECIFICATIONS FOR. 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS

Special Specification 6058 Battery Back-Up System for Signal Cabinets

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011

P H O T O V O LTA I C

SOLAR POWER PACKS OFF-GRID SYSTEMS (150Wp-10kWp:Single Phase)

OFF GRID SOLAR PV SYSTEMS

SECTION DC POWER SUPPLY/BATTERY CHARGER

User Manual. Solar Charge Controller 3KW

2016 Photovoltaic Solar System Plan Review List

E-15 Uninterruptible Power Systems (UPS)

Solar Photovoltaic Solutions

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist

Product Specifications

GRID CONNECTED 400kWp SOLAR ROOF TOP POWER PLANT NET METERING AT KARNATAKA STATE CRICKET ASSOCIATION M. CHINNASWAMY STADIUM, BENGALURU

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

شركة كهرباء محافظة القدس المساهمة المحدودة

Lot 26 WBS 1150 Bill of Quantities

LIGHTNING PROTECTION UNIT (LPU)

ABB central inverters PVS to 1000 kw

Renewable Hybrid / Off-grid Solutions

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

String Monitoring and Control System for Solar Photo Voltaic Power Plants

Technical specifications

INVERTER/CHARGERS Off-Grid Power Solutions

B kv T&D GAS INSULATED SWITCHGEAR

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM

OASIS-UM-01. User Manual. Inverter/Charger Oasis 6000 Rev 1.0. Oasis 6000 Series MAY 2012 ISSUE 01

E-15 Uninterruptible Power Systems (UPS)

INSTALLATION MANUAL THE / MODULE. IEC & UL version

Sine Wave Solar UPS. Owner s Manual. Thank you for choosing the intelligent NON STOP Solar UPS with state of art technology.

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

INSTALLATION MANUAL CRYSTALLINE SOLAR MODULES

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX

400W / 600W / 1000W / 1500W DIY Wind Turbine

MKN-DSP SERIES - THREE PHASE

SUBSIDY SCHEME FOR GRID CONNCTED AND OFF GRID SOLAR SYSTEMS AT IOCL PETROL PUMPS

MERU Solar Off-Grid Inverters

Battery Power Inverters

User Manual Solar Charge Controller 3KW

NB NB 1511 NB NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS

Solar inverter AX-series

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

GENERAL SPECIFICATIONS FOR THE DESIGN, SUPPLY AND INSTALLATION OF A SMALL SCALE PHOTOVOLTAIC SYSTEM (2014)

Components for your PV Solar Electric System

Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders

CHAPTER 10 ELECTRICAL. Notes:

AeroVironment Universal Solar Pump Controllers

Technical Specifications

USER MANUAL MPS 1-5KW SERIES

The Traveler Series: Wanderer

SPECIFICATIONS - DETAILED PROVISIONS Section Vertical Hollowshaft Electric Motors C O N T E N T S

TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III

Section V DC Nickel Cadmium Alkaline BATTERY

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

SMART 1000 / 2000 SERIES

off-grid Solutions Security of supply Basics: Off-grid energy supply

Ampd Silo. Energy Storage System. Maintenance-free Li-ion energy storage for mission critical backup. Power to Empower

Schneider Electric PV Skid. Optimized solar power conversion system tailored to enhance any North American PV power plant

QUEENSLAND URBAN UTILITIES

Bill of Quantity (BOQ) PAL / Renewable Energy for ALL: Photo Voltaic Cells for Gaza Hospitals

Transcription:

1. Introduction 2. Design basis 3. Transmission and distribution voltage 4. Scope of work 5. Operation of the system 5.1 Theory of operation 5.2 System features 5.3 Technical specifications of major components of Solar PV power plant 6. Battery room and control room 7. Bill of materials 8. Spare parts 9. Installation and commissioning 10. Packing, shipping and marking 11. Insurance 12. After sales & service 13. Minimum criterion for bidding 14. Health, safety and environment 15. Experience of the bidder 16. Delivery of the power plants 17. Documentation 18. Tender evaluation procedure Page 1 of 22

1. Introduction intends to ensure uninterrupted availability of power for its Retail Outlets (Petrol Stations) at locations where grid power supply interruption is too high thereby necessitating need for consistent power supply during the periods of interruptions. With this objective and also with an objective to utilize non-conventional sources of energy, is proposing to set up environmental friendly Solar Power plant at petrol stations. With this background the requirements for powering following loads through Solar PV System is proposed. 1. Dispensing Pump (4 DUs 2 of 1 HP & 2 of 0.75 HP) (3.5 HP motor). 4 hours/day on Solar 2. Fan (80 W) * 1 no 10 hours/day 3. CFL (11W) * 6 nos. 12 hours/day (for canopy) 5.94 kwp Solar PV Power System for COCO Outlets for powering, Autonomy for the system shall be two days including one day of zero sunshine. 2. Design Basis Solar PV Power plants shall be designed considering the following: 1. Loads: Total load that shall be supplied- for option 1- by 5.94 kwp Solar PV Power plant having 6 kva 230V, 1-ph, 50Hz inverter * 2 nos. The load usage indicated above shall be met by solar 2. Sun shine: 4.8 Peak hours 3. Battery bank shall be designed for 2 days (1 + 1 No Sun Day ) of autonomy. See battery details below. 4. System voltage : 48V / 96V dc (nominal) Vendors may quote for wattage and / or, capacities of the plant as well as inverter which shall be capable of meeting requirements as given in our requirement above. 3. Transmission and distribution voltage The output voltage shall be 230 V, 1-ph, 50 Hz supplied by PCU. Page 2 of 22

4. Scope of Work This job involves design, manufacture, supply, installation, commissioning of the Solar PV hybrid Power System as per specifications given in this tender document with 1 year warranty period followed by 3 years of comprehensive annual maintenance contract ( AMC). AMC shall include a minimum of 4 visits/year for preventive maintenance and attending break-down maintenance as and when required. The Scope of Work shall include the following, a. Design, manufacture, supply of Solar PV Power Plant b. Detailed planning of smooth execution of the project c. Performance testing of the complete system & warranty of the system for 1 year faultless operation. d. After sales service, directly or through local contractual arrangement e. Risk liability of all personnel associated with the implementation realization of the project f. Annual maintenance contract of the Power Plant for 3 Years after 1 year of warranty period. 5. Operation of the system M P P T PCU ACDB Battery Bank AC Loads Grid or DG The schematic requirement of the Solar PV hybrid power plant is shown above. Solar Photovoltaic array produces DC electricity directly from the sun light. The Power Conditioning Unit (PCU) shall provide conditional output to support load. The power conditioning unit shall consist of MPPT charge controller and bidirectional inverter to supply continuous power to the dedicated local load with support (power) to the load coming either from the solar array, battery bank or grid/dg in that order of preference. Battery bank is required to support the load in case of longer power cuts or grid/dg un-availability. Page 3 of 22

5.1 Theory of Operation The 1-phase system incorporating a bi-directional inverter shall be designed for capability to supply continuous power to a dedicated local load with the power to the load coming either from the solar array, battery bank or grid/dg in that order of preference. It shall be capable of operation in a grid interactive or grid charging mode and shall automatically change over to stand alone operation with no break in power in the event grid moves out of range in its individual phase voltages or frequency. When the grid does come back into range, the system shall change over to grid interactive mode. All the available solar power from the PV array shall be utilized by using a software based control algorithm on the DC input of the PCU. GRID INTERACTIVE or GRID CHARGING MODE The battery bank shall be kept at its nominated float voltage with the required charge coming from the solar array or the grid. The local load, up to the full instantaneous available capacity of the solar array and limited to the maximum capacity of the inverter, shall be supplied from the inverter with the balance of the energy coming from the grid/dg. STANDALONE MODE The local load shall be supplied directly from the inverter with the energy coming from the solar array and the battery bank in the event the load is greater than the available array power. In the event the local load being less than the available array power, battery charging shall occur until the float voltage is reached whereupon the array power shall be progressively offloaded. The load voltage and frequency shall be controlled to the inverter s nominal specifications. Feeding grid is not envisaged 5.2 System requirements Maximum point power tracking (MPPT) of PV energy. No break in change over from grid interactive/charging mode to stand alone operation and vice versa. Page 4 of 22

Maximum use of Solar Energy ( Priority of Solar over AC mains): The grid charging shall be switched on only when battery reaches 30% DOD apx (1.9-1.95 V/cell depending on the type of the battery) and stopped when battery has reached 60-70% DOD (2.1-2.15 V/cell depending on the type of the battery) thus ensuring solar energy is fully utilized. i.e., after grid charging has sopped, solar will have to put another 30% -40% of energy into the battery. When Solar, mains is available and battery is fully charged: The load shall be supplied by solar energy. Battery will act as reservoir to support in case of temporary cloud coverage and/or less sun intensity. Grid charging shall not take place unless until battery voltage goes below 1.95V/cell. When solar is not available but grid is available: If battery is also charged, then energy shall be drawn from the battery till such time battery voltage reaches below 1.95V/cell. Below 1.95V/cell, AC mains shall supply the load along with charging the battery bank. When battery is fully discharged and only solar is available: A part load may be connected to the system, there by ensuring load supply as well as battery charging. 5.3 Technical specifications of major components of Solar PV Power Plant 1 Solar PV modules and array 2 Module mounting structures for Solar PV Modules 3 Junction Boxes 4 Power Conditioning Unit ( MPPT solar charge controller+ Bidirectional Inverter) 5 Battery Bank with Accessories 6 Distribution Boards 7 Cables and installation accessories 8 Earthing and lightning protection 9 Battery and control room Solar PV modules and array Crystalline high power cells shall be used in the Solar Photovoltaic module. Each Solar module shall consist of 72(minimum) Photovoltaic cells redundantly interconnected and peak power rating shall not be less than 165 W. The bidder offering single module with highest wattage shall be given preference provided all other things are equal. To connect the solar module interconnection cable shall be provided. Photo / electrical conversion efficiency of SPV module shall be greater than 12%. Module shall be made of high transmissivity glass front surface giving high encapsulation gain and hot butyl rubber edge sealant for module protection and mechanical support. Page 5 of 22

All materials used shall have a proven history of reliable and stable operation in external applications. It shall perform satisfactorily in relative humidity up to 100% with temperatures between -10 Deg C and +85 Deg C and with stand gust up to 200km/h from back side of the panel. Solar module shall be crystalline type, employing lamination technology using established polymer (EVA) and Tedlar or Polyester laminate. Sample modules, representative of the production processes employed in the manufacture of the offered module shall be in accordance with the requirements of IEC 61215 or UL or CE approval. Offered module may also be intrinsically safe for being used in retail outlets. The bidder shall submit appropriate certificates. Other general requirements of PV module The rated output power of any supplied module shall not vary more than 3-5% from the average power rating of all modules. The module frame is made of corrosion resistant materials, which is electrolytically compatible with the structural material used for mounting the module. Protective devices against surges at the PV module shall be provided, if required. Low voltage drop bypass and / or blocking diode(s) may also be provided, if required. Module Junction box (weather resistant) shall be designed for long life out door operation in harsh environment. A minimum warranty of 10 years shall be given with degradation of power generated not exceeding 10% over the entire 10 year period. The solar modules shall have suitable encapsulation and sealing arrangements to protect the silicon cells from the environment. The arrangement and the material of encapsulation shall be compatible with the thermal expansion properties of the Silicon cells and the module framing arrangement/material. The encapsulation arrangement shall ensure complete moisture proofing for the entire life of the solar modules. Each module shall have low iron tempered glass front for strength and superior light transmission. It shall also have tough multi layered polymer back sheet for environment protection against moisture and provide high voltage electrical insulation. The fill factor of modules shall not be less than 0.70 (typical) Array capacity & PCU Capacity shall not be less than the requirement stated. Depending on size of the power plant, number of modules required shall be worked out accordingly Data sheet of the offered module shall be submitted along with the offer giving details of peak power, peak current, short circuit current, fill factor, open circuit voltage, peak power voltage etc. Page 6 of 22

Orientation and Tilt of PV Module Modules alignment and tilt angle shall be calculated to provide the maximum annual energy output. This shall be decided based on the location of array installation. Module mounting structure The array structure shall be made of hot dip galvanized MS angles of size not less than 50 mm x 50 mm x 6 mm size. The minimum thickness of galvanization shall be at least 70 microns. All nuts & bolts shall be made of very good quality stainless steel. The minimum clearance of the lowest part of the module structure and the developed ground level shall not be less than 500 mm. The structure shall have tilt span of 0 to 60 deg in steps of 5 deg. Leg assembly of module mounting structure made of different diameter galvanized tubes may be accepted. The work should be completed with supply, fitting fixing of clamps, saddles, nut & bolts etc. While quoting the rate, the bidder may mention the design & type of structure offered. All nuts & bolts shall be made of very good quality stainless steel. The structure shall be designed to allow easy replacement of any module and shall be in line with site requirements. The structure shall be designed for simple mechanical and electrical installation. It shall support SPV modules at a given orientation, absorb and transfer the mechanical loads to the ground properly. There shall be no requirement of welding or complex machinery at site. The array structure shall be so designed that it will occupy minimum space without sacrificing the output from SPV panels at the same time it will withstand wind speed as per IS 875 The supplier/manufacturer shall specify installation details of the PV modules and the support structures with appropriate diagrams and drawings. The drawings along with detailed design and calculations for wattage requirements shall be submitted to for approval before starting the execution work. PCC ARRAY FOUNDATION BASE: The legs of the structures made with GI angles will be fixed and grouted in the PCC foundation columns made with 1:2:4 cement concrete. The minimum clearance of the lowest part of any module structure shall not be less 500 mm from ground level. While making foundation design, due consideration shall be given to weight of module assembly, maximum wind speed as per Is 875 and seismic factors for the site. Page 7 of 22

The bidder can visit the site before quoting rate for civil works. After taking in to consideration all aspects of the site, condition of soil etc., the bidder shall quote for civil works. No extra claim shall be entertained at post project stage. The foundation design of module structure design shall be submitted to for approval. The work will be carried out as per designs approved by. Junction Boxes The junction boxes shall be dust, vermin and waterproof and made of FRP. The terminals shall be connected to copper bus bar arrangement of proper sizes. The junction boxes shall have suitable cable entry points fitted with cable glands of appropriate sizes for both incoming and out going cables. Suitable markings shall be provided on the bus bar for easy identification and cable ferrules shall be fitted at the cable termination points for identification. The junction boxes shall have suitable arrangement for the following: Combine groups of modules into independent charging sub-arrays that shall be wired to the PCU. Provide a test point for each sub-group for quick fault location. To provide group array isolation. The rating of the JB s shall be suitable with adequate safety factor to inter connect the Solar PV array. Power Conditioning Unit As SPV array produce direct current electricity, it is necessary to convert this direct current into alternating current and adjust the voltage levels before powering equipment designed for nominal mains AC supply. Conversion shall be achieved using an electronic Inverter and the associated control and protection devices. All these components of the system are termed the Power Conditioning Unit OR simply PCU. In addition, the PCU shall also house MPPT (Maximum Power Point Tracker), an interface between Solar PV array & the Inverter, to maximize Solar PV array energy input into the System. PCU refers to combination of charge controller and bi-directional inverter and shall be supplied as integrated unit. Maximum Power Point Tracker (MPPT) Maximum power point tracker (electronic) shall be integrated into the PCU to maximize energy drawn from the Solar PV array. The MPPT shall be microprocessor / micro-controller based to minimize power losses. The efficiency of the MPPT shall not be less than 94% and shall be suitably designed to meet array capacity. Page 8 of 22

The PCU shall be microprocessor / micro controller based suitable for automatic grid interaction. The time delay for grid interfacing should be minimum possible. Main features of PCU The PCU shall be capable of complete automatic operation, including wakeup, synchronization and shut down. The PCU shall be self commutated and shall utilize a circuit topology and components suitably for meeting the specifications listed above at low cost, high conversion efficiency and with high reliability. The PCU shall be designed to withstand starting in-rush current when pump is started and provide trip free operation. In PCU there shall be a direct current isolation provided at the output by means of a suitable isolating transformer. The PCU shall include appropriate self protective and self diagnostic features to protect itself and the PV array from damage in the event of PCU component failure or from parameters - beyond the PCU s safe operating range due to internal or external causes. The self-protective features shall not allow any operation from the PCU front panel to cause the PCU to be operated in a manner which may be unsafe or damaging. The PCU generated harmonics measured at the point of connection to the utility service, when operating at the rated power shall not exceed a total harmonic distortion of 3 %. The high voltage and power circuits of the PCU shall be separated from the low voltage and control circuits. All conductors shall be made of stranded copper and suitable insulation shall be used for the power and control cables. The PCU shall withstand a high voltage test of 2 kv rms, between either the input or the output terminals and the cabinet (chassis). Full protection against accidental open circuit, short circuit and reverse polarity at the input shall be provided. The PCU shall not produce Electromagnetic Interference (EMI) which may cause malfunctioning of electronic and electrical instruments including communication equipment, which are located within the facility in which the PCU is housed. The PCU shall include ground lugs for equipment and PV array grounding. The DC circuit ground shall be a solid, single point ground connection in accordance with prevailing national standards. All exposed surfaces of ferrous parts shall be thoroughly cleaned, primed and painted or otherwise suitably protected to survive a nominal 15 year design life of the unit. The PCU enclosure shall be weatherproof and Page 9 of 22

capable of surviving intact under all ambient conditions. Moisture condensation and entry of rodents and insects shall be prevented in the PCU enclosure. Components and circuit boards mounted inside the enclosures shall be clearly identified with appropriate permanent designations, which shall - also serve to identity the items on the supplied drawings. All doors, covers, panels and cable exits shall have gasket or otherwise designed to limit the entry of dust and moisture. All doors shall be equipped with locks. All openings shall be provided with grills or screens with openings not larger than 0.95 cm (about 3/8 inch). In the design and fabrication of the PCU the site temperature (0 to 50 degree C), incident sunlight and the effect of ambient temperature on component life shall be considered carefully. Similar consideration shall be given to the heat sinking of MOSFET s, blocking diodes and similar components. PCU Specifications Solar Charge Controller + Inverter+ Battery Charger Switching device Type Input voltage from PV array Protections MOSFET ( Metal Oxide Semi-Conductor Field Effect Transistor) MPPT based PWM charger to charge 96V/48 V (nominal) battery bank with not less than 94% Solar charge controller efficiency 48 /96V (nom) 68 V/136V max Short circuit protection Input under voltage / Deep discharge of battery Input surge voltage protection Over current Battery reverse polarity protection Solar array reverse blocking diode (provided in array junction box) DC rated fuse at input and AC rated fuse at output with suitable contactor/solid-state switches for safe start-up & shutdown of system Load surge current Over temperature Page 10 of 22

Under / Over output voltage Under / Over frequency Automatic / manual isolation at input & output Suitable protection for solid-state switching devices Dielectric strength Cooling Ambient operation (max) Relative humidity Assembly & mounting Finish Cable entry Load test at factory Features 1.1kV between input/output and ground with EMI protections removed Forced air cooling with temperature sensitive fan operation 50 deg C 95% maximum As per normal industry practice Epoxy powder coating From rear 200mm above ground level Minimum 6 hours at full load Bi-directional type inverter Efficiency %THD Stand-alone and hybrid mode of operation. High quality with high efficiency and reliability Microprocessor based intelligent controller Self monitoring capability. Integral design with MPPT solar charge controller and inverter Highly reliable & efficient solid-state switching devices Rated for continuous operation at full load High over-load capability of 200% surge for 10 seconds Inverter output power factor of 0.8 lag Automatic re-start facility after over load triggered shutdown Sleep mode feature: Inverter shall switch off output when output load falls below 1-2 % of rated capacity to save no load losses. Output voltage 230V +/- 1% 90% at rated load and normal operating conditions 83% (min) at 25% load and nominal input voltage with UPF load Sine wave output with 3% THD at full load UPF and nominal input voltage Page 11 of 22

Output frequency 50Hz ± 0.5Hz %Regulation Battery charger 2% against input voltage and load variation Bi-directional Inverter/Charger Indications Inverter ON Grid ON Array ON Inverter Under Voltage / Over Voltage Inverter Overload Inverter Over Temperature Battery Low Enclosure Weight / Dimension Battery type IP 30 (For indoor application) The details of the inverter will be provided in the specification / user manual Tubular lead acid type Battery Bank The batteries shall be solar photo voltaic batteries of flooded electrolyte, low maintenance, lead Acid and made of hard rubber container. The batteries shall use 2V cells and battery capacity is to be designed at C10 rate with end cell cut off voltage of 1.80V / cell. The battery shall be designed for negative temperatures prevailing a site. Battery terminal shall be provided with covers. Batteries shall be provided with micro porous vent plugs with floats. Charging instructions shall be provided along with the batteries. Suitable carrying handle shall be provided. A suitable battery rack with interconnections & end connector shall be provided to suitably house the batteries in the bank. The features and dimensions of the battery rack shall be provided along with the bid document. The batteries shall be suitable for recharging by means of solar charge controller. Bidder shall mention the design cycle life of batteries at 80%, 40% and 20% depth of discharge at 25 deg. C.. Page 12 of 22

The self discharge of batteries shall be less than 2 % per month. The charge efficiency shall be more than 90% up to 70% state of charge. The topping up frequency shall be >12 months. The batteries shall consist of individual cells, which can be carried separately with ease while transporting. Offered batteries shall comply to the following at 27 deg C: 10 % of DOD: 7200 cycles 50 % of DOD: 3000 cycles 80 % of DOD: 1200 cycles Battery Rack & Accessories Battery interconnecting links shall be provided for interconnecting the cells in series and in parallel as needed. Connectors for inter cell connection (series / parallel) shall be maintenance free screws. Insulated terminal covers shall be provided. DC Distribution Board (DCDB) Solar array side breaker and battery side breaker shall be housed in enclosure. These can also be housed within the PCU to save space. AC Distribution Board (ACDB) An ACDB shall be provided in between PCU and load/grid interface It shall have 32 A MCB of suitable rating for connection and disconnection of PCU from load. It shall have 6 A x 5 nos. MCB s to supply power to the loads Cables and accessories All the cables shall be supplied conforming to IS 1554 / 694 Part 1 of 1988 & shall be of 650 V/ 1.1 kv grade as per requirement. Only polyethylene copper cables shall be used. The size of the cables between array interconnections, array to junction boxes, junction boxes to PCU etc shall be so selected to keep the voltage drop and losses to the minimum. Page 13 of 22

Cables shall be of either CCI/Universal/ Finolex make. Scope of the work also includes cable laying including in trenches -, back-filling and restoration of excavated areas to original state. The bidder shall supply installation accessories, which are required to install and successfully commission the power plant. Earthing and lightning protection Earthing: The array structure of the PV yard shall be grounded properly using adequate number of earthing kits. All metal casing / shielding of the plant shall be thoroughly grounded to ensure safety of the power plant. Earth resistance readings for each site must be measured by a qualified and licensed electrical contractor and submitted.resistance values shall conform to either CCOE stipulations or that of IEE regulations.. Lightning: The SPV Power Plant shall be provided with lightning & over voltage protection. The main aim in this protection shall be to reduce the over voltage to a tolerable value before it reaches the PV or other sub system components. The source of over voltage can be lightning, atmosphere disturbances etc. Metal oxide variastors shall be provided inside the Array Junction Boxes. In addition suitable MOV s ( Metal Oxide Variastors) also shall be provided in the Inverter to protect the inverter from over voltage. 6. Battery room and control room The bidder shall give the details of array layout and control room/battery room layout along with the offer. The room shall be provided by to meet the space requirement to house PCU, Distribution Boards and Battery bank etc. 7. Bill of Materials A complete Bill of Materials inclusive of Solar PV Modules, array Junction box, main junction box, cables, Battery bank, PCU, Array mounting structures etc shall be provided along with the offer. The numbers of each component proposed for supply shall be clearly specified. The items not listed in BOM but required for successful installation/commissioning of power plants shall also be added, as required at no extra cost to. 8. Spare parts Page 14 of 22

Bidder shall keep stock of essential spares at their nearest service center and/or at each site at their cost for 3 years of Comprehensive AMC including 1 year of warranty. However bidder shall list out spare parts required for power plant. 9. Installation and commissioning The quotation shall include cost for Installation and commissioning of power plant. The bidder is responsible for arranging all the accessories and measuring instruments required to smoothly commission the power plants. The plant shall be commissioned in the presence of authorized personnel or its nominated representative. An acceptance report shall be prepared and signed by all participating parties. 10. Packing, shipping and marking The bidder shall be responsible for assuring that all commodities shipped are properly packed and protected to prevent damage or deterioration during shipment. Packaging and shipping costs shall be borne by the supplier. Customs clearance and all costs and actions associated with import duties, taxes and processing of documents within India are borne by the bidder. 11. Insurance The bidder shall provide insurance coverage ex-factory until commissioning, and acceptance for replacement or repair of any part of the consignment due to damage or loss. RATES QUOTED SHALL BE INCLUSIVE OF INSURANCE. 12. After sales & service The bidder shall give the details of their service centers in the states where it is intended to install Solar PV systems and ensure that all the essential men and materials are placed to ensure quick and efficient after sales service. An animated CD of the whole system shall be supplied to each site to demonstrate the operation of the system- one copy of CD may be submitted to HQO of. Training and after sales service is an important component of supply. The terms and conditions for training and after sales supply and service are to be presented clearly in the proposal and the extent and duration of after sales support clearly defined. An explanation of preventative maintenance schedule, plan of operation, scope and implementation of the after sales service is to be defined. Page 15 of 22

13. Minimum criterion for bidders Bidders must have following minimum criterion for bidding: a. The bidder must have ISO 9001. b. The bidder must have solar modules manufacturing facility in India and offered modules shall have IEC 61215 or UL or CE approval. c. The bidder must have experience of supplying, installing and commissioning Solar Photo Voltaic Power Plants for more than 5 years in India. The past record of installation of solar photo voltaic systems shall be substantiated by necessary certificates for satisfactory performance. d. The bidders must have their own office / service centre in different parts of India e. The bidder must be total integrated system designer including Power Conditioning Units, structures. f. The vendor should have an average annual turnover during the last 3 financial years of minimum Rs 3.6 crore in similar business line of supply/installation of Solar PV System. Prospective vendors have to submit documentary proof in support of the financial criteria. g. Prospective vendors should have completed successfully during the last 7 years three similar works (in business line of supply, installation, testing and commissioning of Solar PV System) each costing not less than Rs.4.8 crores or two similar works each costing not less than Rs. 6 crores or one similar work costing not less than Rs. 9.6 crores. 14. Health, Safety & Environment The bidder shall submit the following before starting the installation of the power plant. Safety and Environment policy of the Company HSE Manuals for Installation Emergency Management Plan 15. Delivery of the power plants The entire delivery shall be completed in nine months from the date of placement of order. However, each individual sites shall be completed within four weeks of hand over of site. 16. Documentation Two sets of installation manual / user manual shall be supplied along with the each power plant. The manual shall include complete system details such as array lay out, schematic of the system, inverter details, working principle etc. Page 16 of 22

Step by step maintenance and trouble shooting procedures shall be given in the manuals. 17. Tender evaluation procedure) : Bids are invited in two bid system techno- commercial bid and price bid. Price bids of bidders, whose techno- commercial offers are meeting technical and commercial parameters specified in this bid will be opened. Other criteria for qualification of the offer Offers not conforming to the requirements specified shall be considered non responsive and shall not be evaluated. Offers not providing technical and financial information as required by this tender are considered non responsive and shall not be evaluated. Offers not providing PV modules warranty of 10 years with no more than 10% degradation in performance shall be assessed as non responsive and shall not be evaluated. Offers not complying with delivery schedule shall be considered non responsive and shall not be evaluated. Offers not providing clause by clause compliance shall be considered nonresponsive and shall not be evaluated Offers not providing minimum array capacity of designated rating (Wp) shall be considered non-responsive and shall not be evaluated. Price comparison shall include the cost of comprehensive AMC. A sample format of clause wise statement for techno-commercial parameters is enclosed. Additional points of tender enquiry also need to be incorporated by bidders. Page 17 of 22

SPECIFICATIONS SOLAR YARD/STREET LIGHTING WITH SINGLE 11W CFL LAMP SYSTEM SPECIFICATION 11W CFL giving 900 Lumen light output Automatic Dusk to Dawn Operation Independent standalone solar street lighting system Powered by a 74Wp( MINIMUM) of solar array A 12V, 75Ah@C10 battery backup providing 5 days autonomy 4m height pole SOLAR MODULE High efficiency Mono / Multi crystalline silicon cells 1 No. or two Nos. of module/s per system Designed to withstand tough environment conditions BATTERY Capacity 12V, 75 AH (@ C10) >90% Charge efficiency <3% per month self discharge Estimated life greater than 5 years Topping up frequency once in 6 months LAMP 1 x PL11 compact flourescent lamp 900 Lumens (Equivalent to 75W incandescent bulb) ELECTRONICS Regulator: 5A Series regulator with Nominal system voltage 12V DC. Dusk to Dawn operation Voltage levels: Array disconnect (Charge cut-off) Voltage : 15.3 to 15.7V Array reconnect Voltage : 13.1 to 13.5V Battery low : 10.7 to 11.4V Battery reconnect : 12.1 to 12.8V Load On at array V : 2V to 3.5V Page 18 of 22

Load Off at array V : 4 to 7V Indications: Green-ON Charge Red-ON - Load Cut Idle current Inverter with preheating. : <10 ma : 4 Pin high efficiency inverter Efficiency : >80% Operating Temperature : 0 to 50 C Humidity : 95 % rh (N.C.) LUMINAIRE Aluminium Di-cast luminaire with transparent acrylic cover. Fitted with gasket & accessories for weather proof. POLE & STRUCTURE Made of MS, Painted with corrosion resistant paint. PROTECTIONS Over charge & deep discharge disconnects Short circuit protection for lamp Over load Battery reverse connection Lightening Against discharge through array by blocking diode OTHER FEATURES REQUIRED : The design must be rugged for operation under high temperature upto 50 degree C Integrated design Insect proof Luminaire 5 Mtrs Light spread Must meet MNES ( Ministry of Non- conventional sources of Energy) specifications Providing suitable stable foundation must be in the scope of vendor. Civil work is in the scope of vendor and construction of foundation must be in line with the best practices of civil engineering. Page 19 of 22

Vendor must provide drawings for Solar yard light poles and also the foundation details. Warranty for Solar Modules shall be for a minimum period of 10 years with degradation of power generated not exceeding 10% over the entire 10 year period. Necessary cabling is also in the scope of the vendor. SPECIFICATIONS SOLAR YARD/STREET LIGHTING WITH TWIN 11W CFL LAMP SYSTEM SPECIFICATION 2nos of 11W CFL giving 1800 Lumen light output Automatic Dusk to Dawn Operation Independent standalone solar street lighting system Powered by 120Wp of solar array A 12V,150Ah@C10 battery backup providing 4 days autonomy 4m height pole SOLAR MODULE High efficiency Mono / Multi crystalline silicon cells 2 Nos. or 3 Nos.of modules per system Designed to withstand tough environment conditions BATTERY Capacity 12V, 150 AH (@ C10) >90% Charge efficiency <3% per month self discharge Estimated life greater than 5 years Topping up frequency once in 6 months LAMP 2 x PL11 compact flourescent lamp 1800 Lumens (Equivalent to 150W incandescent bulb) ELECTRONICS Regulator: 5A Series regulator with Nominal system voltage 12V DC. Dusk to Dawn operation Indications: Load On Page 20 of 22

Load Off Battery High (Charged) Inverter preheating. : 4 Pin high efficiency inverter with Efficiency : >80% Operating Temperature : 0 to 50 C Humidity : 95 % rh (N.C.) LUMINAIRE Aluminium Di-cast luminaire with transparent acrylic cover. Fitted with gasket & accessories for weather proof. POLE & STRUCTURE Made of MS, Painted with corrosion resistant paint. PROTECTIONS Over charge & deep discharge disconnects Short circuit protection for lamp Over load Battery reverse connection Against discharge through array by blocking diode OTHER FEATURES REQUIRED : The design must be rugged for operation under high temperature upto 50 degree C Integrated design Insect proof Luminaire 5 Mtrs Light spread Must meet MNES ( Ministry of Non- conventional sources of Energy) specifications Providing suitable stable foundation must be in the scope of vendor. Civil work is in the scope of vendor and construction of foundation must be in line with the best practices of civil engineering. Vendor must provide drawings for Solar yard light poles and also the foundation details. Warranty for Solar Modules shall be for a minimum period of 10 years with degradation of power generated not exceeding 10% over the entire 10 year period. Necessary cabling is also in the scope of the vendor. Page 21 of 22

Page 22 of 22