NMSU FIRE DEPARTMENT FIRE PUMP ACCEPTANCE TEST

Similar documents
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Application & Reference Data Typical Specifications. Section 914 Vertical Turbine Fire Pump

FIRE PROTECTION PUMPS. Table of Contents

Pump Acceptance Test Data

Diesel Engines for Fire Protection Applications

FIRE PUMPS F AI LISTED R LISTED N K S MOR S E P U IT Y S Y S T E M CE R T IF IE D

PRODUCT OF FIRE PUMPS SYSTEMS

of Fire Pump Assemblies

NFPA , Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems REVIEW SUMMARY

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

Fire Pumps Inspection, testing and maintenance of fire pumps

Inspection, Testing, and Maintenance Fire Pumps NFPA 25, Chapter 8 as amended by CCR, Title 19 Page 1 of 8

Table Summary of Sprinkler System Inspection, Testing, and Maintenance. Reference. Inspection , ,

Fire Pump Systems. For the protection of life and property, A-C Fire Pump offers package systems that meet every fire protection need.

Instructions for Installation, Operation, Care and Maintenance

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

PROJ. NO SECTION HYDRONIC PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

LACT MEASUREMENT. Total Head = Or PSI = S.G. 2.31

FIRE PUMP SYSTEMS. FIRE PUMP SINGAPORE PTE LTD No.8 Keng Chin Road #13-11 Cyan South Tower Singapore

S200-P Series Centrifugal Fire Pumps Operation and Maintenance Instructions

Series 4600F. HSC Fire Pumps & Packaged Systems

Operation and Maintenance. S100 Series Centrifugal Fire Pumps. Table of Contents. Visit us at F /22/02 6/21/18

WATEROUS CX SERIES PUMPS. Model Intake Discharge

SECTION PUMPS GENERAL PUMPS PART RELATED DOCUMENTS

TotalPac 3 Deluge, Electric release Remote controlled system

SINCE Double Suction Split Case Fire Pump. Series 4800 & (New Generation) 001-cat f

DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS

University of Houston Master Construction Specifications Insert Project Name

SECTION METERS AND GAGES FOR PLUMBING PIPING

BUREAU OF STANDARDS. Effective Date: 8/19/2016 Section No. 4. Version: 1.2 Procedure No. 3

SPECIFICATIONS FOR GASOLINE DRIVEN ENGINE ULTRA HIGH PRESSURE FIRE FIGHTING SYSTEM B1000 M-G

AS Electric Fire Pumpset Check List Please answer YES or No as appropriate. (if the answer is "NOT SURE" then answer "NO!

FIRE PUMPS & PACKAGED

Multi-Institutional Academic Health Science & Research Center Evansville, IN

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Instructions for Installation, Operation, Care and Maintenance

900 Series Split Case Fire Pump Systems

SECTION (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Series Base mounted pump. Installation and operating instructions

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description

TotalPac 3 Deluge system Pneumatic release

TYPE PC Propeller Condensate Pumps

MODEL: ATV Volt, 15 Gallon ATV Mounted Sprayer ASSEMBLY / OPERATION INSTRUCTIONS / PARTS

Chapter Quiz. Directions: Write the correct letter on the blank before each question.

1. Wiring Diagrams: Power, signal, and control wiring.

TotalPac 3 Firecyle III Wet pipe Remote controlled system

Fire Water Utility 2002 Training Manual Raw Water Storage Area

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

.2 Section Waste Management and Disposal..5 Section Thermometers and Pressure Gauges Piping Systems.

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT.

SUGGESTED SPECIFICATIONS Pump Frames NS3 thru OMC5

Installation & Operating Manual

Head - m. Flow - US gpm. Comments. Customer : Contact : Re Cotizacion Metro Linea 4 EDB Project : Quote No. :

Awide choice of devices

Waterfall Pumps Manufacturing

SPECIFICATIONS FOR DIESEL DRIVEN ENGINE ULTRA HIGH PRESSURE FIRE FIGHTING SYSTEM B2000 M-D

S200-G Series Centrifugal Fire Pumps Operation and Maintenance Instructions

Flood Control Integrated System (FCIS)

Technical Information for PVX Series Pumps

W4100, W4200 & W4300 Electric Pump

A. American National Standards Institute: 1. ANSI Z Relief Valves for Hot Water Supply Systems.

Wet pipe low flow foam/water manifold system

Series CC Condensate Units

Operation and Maintenance. CG Series Centrifugal Fire Pumps. Illustrations

LAWN SPRINKLER, IRRIGATION PUMP

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system

P239-1 Supply Pumper Instructions

Series 867 Reduced Pressure Zone Assemblies

Wilfley. Model. Technical Handbook. Centrifugal Slurry Pump

Pyrolance, LLC SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE FIRE FIGHTING SYSTEM B2000 M-D

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

END SUCTION CENTRIFUGAL PUMPS

September 22, 2016 To: All Contractors Re: Boiler Back-Up Fuel Tank System Renovation. Dear Sir:

Start-Up and Installation Checklist

SUGGESTED SPECIFICATIONS

PROMAG SR SERIES SEAL-LESS CENTRIFUGAL PUMPS

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

Peerless Pump FIRE PUMPS. Horizontal Split-Case, Vertical Turbine, In-Line and End Suction. Sterling Fluid Systems (USA), Inc.

HL Series Centrifugal Fire Pumps Operation and Maintenance Instructions

BOILER FEED SYSTEM OPERATION AND MAINTENANCE MANUAL

Instructions for Installation, Operation Care and Maintenance

Hydropak Booster Systems. Series motralec

Technical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE

Underground Tank Applications Installation Guide

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system

NC State University Design and Construction Guidelines Division 23 Hydronic Pumps

TotalPac 3 Non interlock Preaction system Pneumatic release

Installation, Maintenance, & Repair Series 995 Reduced Pressure Zone Backflow Preventers

MODEL NO GALLON H.P. SKID SPRAYER ASSEMBLY / OPERATION INSTRUCTIONS / PARTS

VSPS PACKAGE BOOSTER SYSTEM (END SUCTION PUMP DESIGN) FEATURES T Y P E

MODEL NO. SK-61-12V 12 VOLT SKID MOUNTED LAWN & GARDEN SPRAYER ASSEMBLY / OPERATION INSTRUCTIONS / PARTS

PRESSURE LIMITING DRIVERS

DELUGE VALVE DATA SHEET

Wilo IL Vertical Inline Pumps. Engineering Specification

Darley UHP-HV Diesel Specification 1

Minuteman Vertical Pumps

4500C Series Vortex Pumps

Transcription:

Date Documents Submitted: Log No.: File No.: Plan Examiner: Permit No.: Property Information Building Name: Building Address: Building Manager's Name: Building Manager's Phone: Fax: System Designer/Contractor Company Name: Company Address: Contact Person (Designer): Designer Qualification: Phone: E-mail: Date of Approval: E-mail: Fax: General Type of building: New Existing Renovation Pump make: Drive: Electric Diesel Model No.: Pump rating: gpm @ psi Rated speed: rpm What is fire pump feeding? Automatic sprinkler system Fire hydrants Standpipe system Other: Present at test: Authorized Representative Manufacturer Pump Engine (if diesel) Controller Transfer switch 2012 National Fire Protection Association NFPA 20 (p. 1 of 5)

Date the suction piping was flushed prior to hydrostatic test: Flow rate: gpm Pressure at which piping hydrostatic tested: Fire Pump Acceptance Test Yes No Installation psi Certificate for flushing and hydrostatic testing furnished Centrifugal fire pump listed for fire protection service Horizontal pump/driver on common base plate and connected by a listed flexible coupling Guards provided for flexible couplings and flexible connecting shafts Base plate securely attached to a solid reinforced concrete foundation Indoor fire pump units separated from all other areas of the building by 2-hour fire-rated construction; 1-hour fire-rated construction in buildings protected with an automatic sprinkler system I f fi re pump unit is located outdoors or if fire pump installation is in a building other than that building being protected by the fire pump, it is located at least 50 feet away from the protected building A suitable means for maintaining 40'F provided; 70'F if drive is diesel engine. (Portable units, plug-in units and hardwired electric units without secured circuit breakers are not reliable) Pump room/house provided with normal lighting and emergency lighting Pump room/house adequately ventilated and floor is pitched toward drain Suction piping is the proper size. (5 inch for 500 gpm) (6 inch for 750 gpm) (8 inch for 1000 or 1500 gpm) (10 inch for 2000 or 2500 gpm) OS&Y valve provided in the suction piping (butterfly values not permitted in suction piping) No backflow prevention or other devices are in the suction piping No elbows perpendicular to impeller of horizontal pump are within 10 pipe diameters of the intake flange Reducer at pump intake is eccentric and installed with flat side up A bypass, at least the required size of the discharge pipe, is provided if the suction supply is of sufficient pressure to be of material value without the pump Listed indicating type valves are on each side of the check valve in the bypass and are normally open A 3½inch compound gauge, having a rating of at least 100 psi and a range of at least twice the maximum suction pressure, is provided on the suction piping A 3½ inch pressure gauge, with a rating of at least 200 psi and a range of at least twice the working pressure of the pump, is provided near the discharge casting A ¾ inch circulating relief valve (1 inch if pump is rated over 2500 gpm) is provided and piped to a drain. (Not needed for engine driven pumps cooled by water from pump discharge) A listed, float-operated, automatic, air release valve (no less than ½ inch in size) is provided 2012 National Fire Protection Association NFPA 20 (p. 2 of 5)

Yes No Installation (continued) Discharge piping is of the proper size. (5 inch for 500 gpm) (6 inch for 750 or 1000gpm) (8 inch for 1250or 1500 gpm) (10 inch for 2000 or 2500 gpm) A listed indicating valve is installed on the fire protection system side of the pump A check valve is provided between the discharge valve and the pump The pump driver, regard less of diesel or electric, is listed for fire pump service A properly sized relief valve has been provided if pump is diesel driven or if churn pressure can exceed rating of system components. (5 inch for 500 gpm) (6 inch for 750 gpm) (8 inch for 1000 and 1500 gpm) (10 inch for 2000 gpm) No valves are installed in the relief valve piping For diesel engine drivers, there are two storage battery units provided and rack-supported above the floor, secured against displacement, and located where they are readily accessible for servicing and not subject to excessive temperature, vibration, mechanical injury, or flooding For diesel engine driver, storage battery units are provided with battery chargers specifically listed for fire pump service, arranged to automatically charge at the maximum rate whenever required by the state of charge of the battery, and arranged to indicate loss of current For diesel engine driver cooled by a heat exchanger, the cooling water supply is from the discharge of the pump and taken prior to the discharge check valve The heat exchanger piping for a diesel engine driver is equipped with an indicating manual shutoff valve, an approved flushing-type strainer, a pressure regulator, an automatic valve listed for fire protection service, and a second indicating manual shutoff valve Heat exchanger piping of a diesel engine driver is equipped with a pressure gauge installed in the cooling water supply system on the engine side of the last manual valve Heat exchanger piping of a diesel engine driver is provided with a bypass line The outlet provided for the wastewater line from the heat exchanger has a discharge line not less than one size larger than the inlet line, discharges into a visible open waste cone, and has no valves Diesel fuel supply tank has a capacity of 1gallon per engine horsepower plus 10% Diesel fuel supply tank is located above ground Exposed fuel lines are provided with guard or protecting pipe The test header or flow-meter is tapped between the discharge check valve and the discharge valve provided for annual fire pump flow testing (if a flow-meter is used, verify that it is arranged so as to test both pump performance and suction supply) Proper number of listed 2½inch hose valves is provided on test header (2 for 500 gpm) (3 for 750 gpm) (4 for 1000 gpm) (6 for up to 2500 gpm) Test header piping is of the proper size (4 inch for 500 gpm) (6 inch for 750 and 1000 gpm) (8 inch for up to 2500 gpm) (10 inch for 2500 gpm) If test header pi ping is over 15 feet in length, the next larger piping size is used A drain valve is located at a low point of the test header pipe between the normally closed test header valve and the test header 2012 National Fire Protection Association NFPA 20 (p. 3 of 5)

Yes No Installation (continued) If a flow-meter is provided, meter system piping is of the proper size. (5 inch for 500 and 750 gpm) (6 inch for 1000and 1250 gpm) (8 inch for up to 2500 gpm) If the meter system piping exceeds 100 feet equivalent of pipe, the next larger size pipe is used Jockey pump is provided with sensing line totally independent from that of main pump sensing line The sensing lines both tap the discharge pipes between the check valve and the discharge control valve of the pumps they respectively serve Both sensing lines are ½ inch and brass, copper, or series 300 stainless steel piping, tube, and fittings Two check valves are installed in each pressure sensing line at least 5 feet apart No shut off valves in the sensing lines For diesel driven pumps, verify that the following alarms are provided on the controller and operative: Low oil pressure High engine temperature Failure to start Shutdown on over-speed Battery charger failure Battery failure/battery missing Low (less than X\c} fuel level For diesel driven pumps, verify that the following alarms are provided and transmit to a constantly attended location: Pump running Controller main switch in a position other than "AUTOMATIC" Trouble on controller or engine For electric driven pumps, verify that all the following alarms are operative: Other: Loss of power Phase reversal Pump running Yes No Verification Verify that the cut-in and cut-out of the jockey pump is properly set. Verify that the cut-in of the main pump is properly set. Verify that all valves are supervised open. (Test header and flow-meter values should he supervised shut) Verify that the pump performance met or exceeds the demands of the systems supplied by pump. (See results below.) 2012 National Fire Protection Association NFPA 20 (p. 4 of 5)

Test Results Test Discharge Pressure Intake pressure Net pressure Speed Nozzle Size and Pitot Pressures gpm 1 2 3 4 5 Inspector: Date: Approval Inspector: Date: Approved: Yes No If no, reason(s): Notes: This form is to be completed by the system inspection and testing contractor at the time of a system test. Attach additional sheets, data, or calculations as necessary to provide a complete record. Number of Supplemental Form(s) Attached: Inspection/ Test Start Date/Ti me: Inspection/ Test Completion Date/ Time: 2012 National Fire Protection Association NFPA 20 (p. 5 of 5)