EN Smart connections. Certificates PIKO-Inverter 3.0 3.6 4.2 5.5 8.3 10.1
EU Declaration of Conformity The company KOSTAL Solar Electric GmbH Hanferstraße 6 79108 Freiburg i. Br., Deutschland hereby declares that the inverters PIKO 3.0, PIKO 3.6, PIKO 4.2, PIKO 5.5, PIKO 8.3, PIKO 10.1 PIKO 3.0 DCS, PIKO 3.6 DCS, PIKO 4.2 DCS, PIKO 5.5 DCS, PIKO 8.3 DCS, PIKO 10.1 DCS to which this declaration refers, conform to the following guidelines and standards. and EMC Directive 2004/108/EEC DIN EN 61000-3-2:2006 (Harmonic currents) EN 61000-3-3:1995 + A1:2001 + A2:2005 (Flicker) DIN EN 61000-6-2:2005 (Interference resistance for industrial environments) DIN EN 61000-6-3:2007 (Interference emission for domestic environments) 2006/95/EEC Low Voltage Directive DIN EN 50178:1998 (Electronic devices in high voltage systems) This declaration applies to all identical copies of this product. This declaration loses its validity if the device is modifi ed or incorrectly connected. KOSTAL Solar Electric GmbH 2009-08-28 Werner Palm Managing Director) This declaration certifies the compliance with the mentioned regulations but does not ensure the properties. The safety instructions in the product documentation provided must be observed!
Bureau Veritas E&E Product Services GmbH Businesspark A96 86842 Türkheim + 49 (0) 8245 96810-0 cps-tuerkheim@de.bureauveritas.com Certificate of compliance Applicant: Product: KOSTAL Solar Electric GmbH Hanferstrasse 6 79108 Freiburg Automatic disconnection device between a generator and the public low-voltage grid Model: PIKO 3.0, PIKO 3.6, PIKO 4.2, PIKO 5.5, PIKO 8.3, PIKO 10.1 Use in accordance with regulations: Automatic disconnection device with three-phase (PIKO 3.0/3.6 single-phase) mains surveillance in accordance with DIN V VDE V 0126-1-1:2006-02 for photovoltaic systems with a three-phase (PIKO 3.0/3.6 single-phase) parallel coupling via an inverter in the public mains supply. The automatic disconnection device is an integral part of the aforementioned inverter. This serves as a replacement for the disconnection device with insulating function which the distribution network provider can access at any time. Applied rules and standards : DIN V VDE V 0126-1-1 (VDE V 0126-1-1):2006-02 and Generator at the public low-voltage grid, 4th edition 2001, guideline for connection and parallel operation of generators in the public low-voltage grid with VDN additions (2005) from the German Electricity Association (VDEW) and Association of network operator (VDN). The safety concept of an aforementioned representative product corresponds at the time of issue of this certificate of valid safety specifications for the specified use in accordance with regulations. Report number: 05KFS170-VDE0126 07THS186-VDE0126 09TH0062-VDE0126 Certificate nummer: U09-045 Date of issue: 2009-03-31 Valid until: 2012-03-31 Andreas Aufmuth
Bureau Veritas Consumer Product Services GmbH Businesspark A96 86842 Türkheim + 49 (0) 8245 96810-0 cps-tuerkheim@de.bureauveritas.com Certificate of compliance Applicant: Product: KOSTAL Solar Electric GmbH Hanferstrasse 6 79108 Freiburg Automatic disconnection device between a generator and the public low-voltage grid Model: PIKO 3.0, PIKO 3.6 Use in accordance with regulations: Automatic disconnection device with single-phase mains surveillance in accordance with Engineering Recommendation G83/1 for photovoltaic systems with a single-phase parallel coupling via an inverter in the public mains supply. The automatic disconnection device is an integral part of the aforementioned inverter. This serves as a replacement for the disconnection device with isolating function that can access the distribution network provider at any time. Applied rules and standards : DIN V VDE V 0126-1-1:2006-02 (Redundancy) and Engineering Recommendation G83/1. The safety concept of an aforementioned representative product corresponds at the time of issue of this certificate of valid safety specifications for the specified use in accordance with regulations. Report number: 09TH0062-G83 Certificate nummer: U11-023 Date of issue: 2011-01-19 Valid until: 2014-01-19 Achim Hänchen CERTIFICATION
Bureau Veritas E&E Product Services GmbH Businesspark A96 86842 Türkheim + 49 (0) 8245 96810-0 cps-tuerkheim@de.bureauveritas.com Certificate of compliance Applicant: Product: Model: KOSTAL Solar Electric GmbH Hanferstrasse 6 79108 Freiburg Disconnection device for PV generators Elektronischer DC-Freischalter DCS Use in accordance with regulations: Disconnection between a solar inverter and a photovoltaic generator Applied rules and standards : In dependence on IEC 60947-3:1999 + Corrigendum:1999 + A1:2001 + Corrigendum 1:2001 + A2:2005 DIN EN 60947-3; VDE 0660-107:2006-03 Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units and IEC 60364-7-712:2002-05 DIN VDE 0100-712:2006-06 Electrical Installations of Buildings - Part 7-712: Requirements for Special Installations or Locations - Solar Photovoltaic (PV) Power Supply Systems The safety concept of an aforementioned representative product corresponds at the time of issue of this certificate of valid safety specifications for the specified use in accordance with regulations. Report number: 09TH0063-IEC60947 Certificate nummer: U09-054 Date of issue: 2009-03-31 Valid until: 2012-03-31 Andreas Aufmuth
Test results UNDER / OVER VOLTAGE TESTS Under Voltage Over Voltage Parameter Voltage Time (sec) Voltage Time (sec) Output power level 10% 55% 100% 10% 55% 100% G83/1 Limit 207 V 1,5 s 264 V 1,5 s Actual setting 207 207,1 V 264 263,5 V 165ms 171ms 152ms 185ms 181ms 239ms Trip value 212 V to 202 V 155ms 154ms 172ms 165ms 177ms 177ms 159ms 163ms 158ms 259 V to 269 V 177ms 164ms 206ms 174ms 186ms 172ms 172ms 180ms 179ms 157ms 168ms 168ms 159ms 185ms 173ms UNDER / OVER FREQUENCY TESTS Under frequency Over frequency Parameter Frequency Time Frequency Time Output power level 10% 55% 100% 10% 55% 100% G83/1 Limit >=47 Hz 0.5s <=50.5 Hz 0.5s Actual setting 48,70 Hz 48,70 Hz 50.50 Hz 50.50 Hz 128ms 128ms 106ms 85ms 118ms 88ms Trip value 47,50 Hz to 46,50 Hz LOSS OF MAINS TEST 108ms 94ms 96ms 110ms 117ms 101ms 50 Hz to 103ms 96ms 72ms 105ms 103ms 105ms 51 Hz 124ms 102ms 52ms 105ms 103ms 108ms 101ms 98ms 103ms 94ms 100ms 97ms Output power level 10% 50% 100% G83/1 Limit 0.5s Trip value (sec): RECONNECTION TIMES Reconnestion Time Minimum value Actual settings Recorded value Harmonic Current Emissions 95,6ms 103ms 98ms 80,2ms 110ms 90ms 84,2ms 105ms 103ms 89,9ms 96,7ms 85ms 81,9ms 99,7ms 101ms Under/Over voltage Under/over frequency Loss of mains 180 s 180 s 210s Harmonics 2nd 3rd 5th 7th 9th 11th 13th 15 th n 39 th Limit 1,08 2,3 1,14 0,77 0,4 0,33 0,21 0,15 * (15/n) Test value 0,07 0,75 0,21 0,07 0,03 0,02 0,04 <Limit BS EN61000-3-2A Voltage Fluctuations and Flicker (covered by EMC Report) U N =230V, Output power: 100% Starting Stopping Running Limit 4% 4% Pst = 1.0 Plt = 0.65 Test values The stationary deviance of dc% is bigger than the dynamic deviance of dmax at starting and stopping. Limit dc% = 3,3 Pst = 1.0 Plt = 0.65 Test values 2,41 0,0624 0,0624 Power factor G83/1 Limit 0.95 lag-0.95 lead Output Voltage: 212V (U N -8%) 230V 259V (U N +12.7%) Test Value 0,977c 0,976c 0,974c DC injection G83/1 Limit 20 ma Output power: 10% 55% 100% Test Value 4,2 ma 4,0mA 1,9mA
Manufacturer s declaration for the operation of PIKO 3.0 and PIKO 3.6 single-phase feed-in solar inverters in photovoltaic systems with type A residual current protection switches: The KOSTAL PIKO solar inverters from the above-mentioned range can be used to safeguard the grid supply with FI protection switches of the type A and to ensure a trigger threshold of I = 100 ma. A residual-current circuit-breaker (Type AC) is suffi cient for the monitoring from the inverter to the building connection point. for the operation of the PIKO 4.2, PIKO 5.5, PIKO 8.3, PIKO 10.1 three-phase in-feed solar inverters in photovoltaic systems with residual protection switches of the type A: The KOSTAL PIKO solar inverters of the above-mentioned range supply power to the grid symmetrically via three network phases. The conversion topology developed for this is characterised by a constant supply of power from the PV generator to the grid, which ensures maximum operation reliability. Permanent residual current is principally avoided due to the inverter s operating features. Switching to the mains grid only takes place after an automatic inspection to ensure sufficient insulation of the PV generator to the grid. A fault in the system would also lead to a fault in the supply of direct current and is immediately prevented by the redundant internal residual current monitoring unit (RCMU) which disconnects it from the grid. The type A residual current devices (RCDs) also installed externally on the grid side are not disrupted due to the inverter in the monitoring unit. The trigger level for operation of 1-3 inverters is 100 ma. For operation of more than 3 inverters, the disconnection threshold is 300 ma. KOSTAL solar inverters conform to the following standards: DIN VDE 0100-712 IEC 60364-7-712 CEI 64-8/7 KOSTAL Solar Electric GmbH Freiburg, 03.03.2011 Werner Palm Managing Director
Total Harmonic Distortion for PIKO inverters Order PIKO 3.0 PIKO 3.6 PIKO 4.2 PIKO 5.5 PIKO 8.3 PIKO 10.1 n I [A] I [A] I [A] I [A] I [A] I [A] 1 12,4484 14,5607 5,599 7,246 10,793 12,696 2 0,0599 0,0669 0,067 0,054 0,068 0,079 3 0,6559 0,7498 0,111 0,139 0,142 0,185 4 0,0191 0,0162 0,011 0,003 0,021 0,024 5 0,2064 0,2089 0,027 0,083 0,058 0,122 6 0,0028 0,0018 0,002 0,004 0,02 0,029 7 0,0823 0,07 0,087 0,087 0,089 0,116 8 0,0024 0,0015 0,009 0,007 0,023 0,032 9 0,0314 0,0297 0,073 0,044 0,155 0,143 10 0,0024 0,0012 0 0,004 0,012 0,034 11 0,0141 0,0236 0,075 0,032 0,076 0,082 12 0,0024 0,0072 0,001 0,006 0,054 0,075 13 0,0363 0,0425 0,056 0,037 0,047 0,107 14 0,0038 0,0023 0,007 0,002 0,033 0,027 15 0,056 0,0555 0,045 0,057 0,103 0,206 16 0,0021 0,0054 0,008 0,007 0,014 0,004 17 0,0669 0,0664 0,071 0,057 0,067 0,151 18 0,0028 0,0057 0,007 0,002 0,034 0,01 19 0,0895 0,0892 0,03 0,025 0,066 0,101 20 0,0024 0,0048 0,003 0,006 0,023 0,013 21 0,0617 0,0596 0,06 0,023 0,066 0,055 22 0,0034 0,0065 0,002 0,005 0,016 0,015 23 0,0447 0,0461 0,092 0,054 0,123 0,143 24 0,0028 0,0034 0,008 0,005 0,017 0,008 25 0,0259 0,0295 0,049 0,043 0,083 0,061 26 0,0034 0,0023 0,002 0,003 0,005 0,005 27 0,0249 0,0283 0,02 0,025 0,024 0,036 28 0,0024 0,0049 0,001 0,002 0,007 0,003 29 0,0376 0,0496 0,048 0,045 0,069 0,089 30 0,0041 0,0088 0,001 0,002 0,004 0,006 31 0,0388 0,0646 0,025 0,021 0,04 0,044 32 0,0044 0,006 0,003 0,003 0,01 0,013 33 0,0349 0,0534 0,006 0,006 0,011 0,012 34 0,0031 0,0066 0,006 0,002 0,01 0,008 35 0,0153 0,036 0,047 0,013 0,048 0,049 36 0,0024 0,0052 0,006 0,003 0,008 0,004 37 0,0029 0,0166 0,024 0,01 0,025 0,032 38 0,0021 0,0044 0,002 0,001 0,013 0,022 39 0,0041 0,004 0,011 0,007 0,005 0,016 40 0,0025 0,0024 0,002 0,004 0,007 0,014 KOSTAL Solar Electric GmbH, 15-06-201115-06-2011 Werner Palm Managing Director
KOSTAL Solar Electric GmbH Hanferstr. 6 79108 Freiburg hereby confi rm that the PIKO 3.0, 3.6, 4.2, 5.5, 8.3 and 10.1 inverters demonstrate a good resistance to ammonia. Ammonia concentration, temperature and time play a decisive role. Based on the ammonia contamination levels (max. 20 ppm) specifi ed for agriculture, no impairment to the housing, seals, connecting plug and function of PIKO inverters is to be expected. Freiburg, April 2010 Werner Palm Managing Director
KOSTAL Solar Electric GmbH Hanferstr. 6 79108 Freiburg i. i. Br. Deutschland Telefon: +49 761 477 44 - - 100 Fax: +49 761 477 44 - - 111 KOSTAL Solar Electric Ibérica S.L. Edifi cio abm Ronda Narciso Monturiol y y Estarriol, 3 Torre B, B, despachos 2 y y 3 Parque Tecnológico de Valencia 46980 Valencia España Teléfono : : +34 961 824 - - 930 Fax: +34 961 824 - - 931 KOSTAL Solar Electric France SARL 11, rue Jacques Cartier 78280 Guyancourt France Téléphone: +33 1 61 38 - - 4117 Fax: +33 1 61 38 - - 3940 KOSTAL Solar Electric Hellas Ε.Π.Ε. 47 Steliou Kazantzidi st., P.O. Box: 60080 1st building 2nd entrance 55535, Pilea, Thessaloniki Greece / / Ελλάδα Τelephone: +30 2310 477 - - 550 Fax: +30 2310 477 - - 551 KOSTAL Solar Electric Italia Srl Via Genova, 57 10098 Rivoli (TO) Italia Telefono: +39 011 97 82 - - 420 Fax: +39 011 97 82 - - 432 www.kostal-solar-electric.com SEM 01-11