Rosemount 1195 Integral Orifice Primary Element

Similar documents
Rosemount DP Flowmeters and Primary Elements

Rosemount 3051CFA Annubar Flowmeter

Product Data Sheet , Rev GA Catalog Content

Rosemount DP Flowmeters and Primary Elements

Product Data Sheet , Rev KA April 2010 Rosemount 1495 and Contents

Rosemount 3051T In-Line Pressure Transmitter

Rosemount 3051 Pressure Transmitter

Rosemount DP Flowmeters and Primary Elements

Rosemount Manifolds. Product Data Sheet September , Rev PA. Factory assembled, leak-tested, and calibrated

Rosemount 3051S Electronic Remote Sensor (ERS) System

Rosemount Manifolds. Product Data Sheet October , Rev PB. Factory assembled, leak-tested, and calibrated

Rosemount Engineered Assemblies

Rosemount 285 Annubar Primary Element Series

Rosemount 3051CF Flowmeter Series

Rosemount Manifolds. Rosemount Manifolds. Product Data Sheet , Rev LA Catalog Contents

TRANSMITTER ATTACHES TO THIS SURFACE

Rosemount Manifolds. Rosemount Manifolds. Product Data Sheet , Rev NB January Contents

Rosemount Manifolds. Rosemount Manifolds. Product Data Sheet , Rev MA August Contents

Dual Chamber Orifice Fitting

Model CO Compact Orifice for use with Foxboro Differential Pressure Transmitters

Bore (B) Pitch Diam. Drilling Template Flanges (1) Diam of Diam of. Groove. Neck D X G A Raised Face Raised Face P Raised face

Rosemount 3051S Series of Instrumentation

Rosemount 3051S Series of Instrumentation

Rosemount 3051 Pressure Transmitter

Annubar Flowmeter Series

Rosemount Integral Orifice Flowmeter Series

Rosemount 4088 MultiVariable Transmitter

Rosemount Twisted Square Thermowells

MODEL 5800 CONTENTS. Installation, Operation, and Maintenance Instructions 1.0 GENERAL

Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems

Rosemount Integral Orifice Flowmeter Series

Rosemount Manifolds. Product Data Sheet April , Rev PC. Factory assembled, leak-tested, and calibrated

Annubar Flowmeter Series

Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems

Rosemount DP Level Transmitters and 1199 Remote Seals

Rosemount 405 Compact Orifice Series

94D / 94F / 94M / 96M

WKM 320F. Flanged floating ball valves

Differential Pressure - Primary Flow Element Wedgemeter II Series WM: C/F/P

Rosemount DP Level Transmitters and 1199 Seal Systems

Rosemount 3051S Series of Instrumentation

Rosemount 4088 MultiVariable Transmitter

Manifold and Isolation Valve Mounting System for Direct Mounting DP Transmitters

IBV Series C-LF2 Carbon Steel Inverted Bucket Vertical Steam Trap

FPD220 meter 2 di Dual-chamber orifice fitting with double isolation

Rosemount DP Level Transmitters and 1199 Seal Systems

Rosemount 9901 Chamber for Process Level Instrumentation

INTRODUCTION AND STANDARD SPECIFICATIONS

The Annubar Flowmeter Series. Rosemount 3051SFA ProBar Flowmeter. Product Data Sheet , Rev EA Catalog

SV80H Safety and Relief Valves

Anderson Greenwood M4TL Liquid Level Manifolds

Datasheet Rev.3 Feb 2015 Venturi tube

Rosemount DP Level Transmitters and 1199 Seal Systems

ANDERSON GREENWOOD LARGE BORE INTELLIMOUNT SYSTEM

FLANGES PRODUCT: STANDARD FLANGE CLASSIFICATION: PRESSURE CLASS CLASIFICATION:

Rosemount DP Level Transmitters and Remote Seals

Rosemount 9901 Chamber for Process Level Instrumentation

Rosemount 3051S Series of Instrumentation

Rosemount Annubar Flowmeter Series

Accutubes. Accuracy True double averaging design +1% of rate accuracy +0.1% repeatability Tested and certified by independent flow labs

Anderson Greenwood M24A/M24T Differential Pressure Manifolds

RHM30. Coriolis Mass Flow Meter for Plant and Loading Flows. Features. Applications. Benefits

Thermowell for temperature sensors omnigrad M TW 13

IFOA Integral Flow Orifice Assembly

VALVES & CONTROLS ANDERSON GREENWOOD INSTRUMENTATION PRODUCTS LARGE BORE INTELLIMOUNT SYSTEM

Fisher V500 Rotary Globe Control Valve

Ref FIRE SAFE BALL VALVE ISO PN50 ANSI Model/Ref:

2 PIECES BALL VALVE PN63

Mars Series 88 Stainless Steel Reduced Bore Or Full Bore Ball Valve, Lever Operated, BSP Or Socket Weld Ends

ANDERSON GREENWOOD M4AP/M4TP STATIC PRESSURE MANIFOLDS

JUMO flowtrans DP R. Meter run R01 and orifice plate R02. Applications. Brief description. Special features. Customer benefits.

Ball Valves. Seal Welded Style BVS2...2 Carbon Steel Technical Data 2200 PSI ¼ Stainless Steel Technical Data 2160 PSI ¼

570, 571, 573 Control Valves

Rosemount 68 Sensor and Thermowell

Rosemount 485 Annubar Flanged Assembly

Fisher V500 Rotary Control Valve

Annubar Flowmeter Series

RHM015. Ultimate Performance Coriolis Mass Flow Meter for Critical Ultra Low Flow Applications. Features. Applications. Benefits

General Specifications

Datasheet Rev.1 Feb 2014 High precision flowmeter

ORIFICE PLATE flow meters

Fisher YD and YS Control Valves

RHM08. Versatile Coriolis Mass Flow Meter. Features. Applications. Benefits

RHM04. Compact Coriolis Flow Sensor With Enhanced Performance. Features. Applications. Benefits

RHM40. Coriolis Mass Flow Meter for Demanding Applications. Features. Applications. Benefits

Ref FIRE SAFE BALL VALVE ISO PN16/40 FLANGED. Model/Ref:

Masoneilan * Pressure Regulators Steam, Gas or Liquid Service Models 525 and 526

Fisher D4 Control Valve Assembly

Fisher HP Series Control Valves

EMCO Primary Elements for Flow Measurement

FPD350 Torbar Averaging pitot tubes

Fisher CV500 Rotary Control Valve

Model 5400 / 5450 Control Valve

Rosemount 485 Annubar Pak-Lok Assembly

Averaging Pitot Tube Flowmeter Catalogue ED IN AUSTRALIA

General Specifications

HOKE Monoflange Valves. Primary Isolation Valves

AccuTru Thermowells. Dedicated to those organizations that value improved temperature measurement for critical processes

Natural Gas Manifolds M6A, M6T, M6TA 5-Valve Manifolds

RHINO VALVES WORLDWIDE

Transcription:

September 2014 Rosemount DP Flow Rosemount 1195 Integral Orifice Primary Element Rosemount 1195 Integral Orifice Primary Element utilizes a self centering orifice plate design to eliminate installation error. Enables highly accurate flow measurement in small line sizes Available with a variety of process connections Available in 1 /2 to 1 1 /2-in. (15-40 mm) line sizes 1195 Integral Orifice Primary Element Additional Information Specifications: page 167 Dimensional Drawings: page 221 Installation and Flowmeter Orientation: page 181 Ordering information Table 1. Rosemount 1195 Integral Orifice Primary Element Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Model Product description 1195 Integral Orifice Primary Flow Element Body material S 316 SST H 005 1 /2-in. (15 mm) H 010 1-in. (25 mm) H 015 1 1 /2-in. (40 mm) H Process connection T1 NPT Female Body (not available with thermowell and RTD) H S1 (1) Socket Weld Body (not available with thermowell and RTD) H P1 Pipe Ends: NPT threaded H P2 Pipe Ends: Beveled H D1 Pipe Ends: Flanged, RF, DIN PN16, slip-on H D2 Pipe Ends: Flanged, RF, DIN PN40, slip-on H D3 Pipe Ends: Flanged, RF, DIN PN100, slip-on H W1 Pipe Ends: Flanged, RF, ANSI Class 150, weld-neck H W3 Pipe Ends: Flanged, RF, ANSI Class 300, weld-neck H W6 Pipe Ends: Flanged, RF, ANSI Class 600, weld-neck H A1 A3 A6 R1 R3 R6 P9 Pipe Ends: Flanged, RF, ANSI Class 150, slip-on Pipe Ends: Flanged, RF, ANSI Class 300, slip-on Pipe Ends: Flanged, RF, ANSI Class 600, slip-on Pipe Ends: Flanged, RTJ, ANSI Class 150, slip-on Pipe Ends: Flanged, RTJ, ANSI Class 300, slip-on Pipe Ends: Flanged, RTJ, ANSI Class 600, slip-on Special Process Connection 163

Rosemount DP Flow September 2014 Table 1. Rosemount 1195 Integral Orifice Primary Element Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Orifice plate material S 316 SST H H Alloy C-276 M Alloy 400 Bore size option 0066 0.066-in. (1.68 mm) for 1 /2-in. Pipe H 0109 0.109-in. (2.77 mm) for 1 /2-in. Pipe H 0160 0.160-in. (4.06 mm) for 1 /2-in. Pipe H 0196 0.196-in. (4.98 mm) for 1 /2-in. Pipe H 0260 0.260-in. (6.60 mm) for 1 /2-in. Pipe H 0340 0.340-in. (8.64 mm) for 1 /2-in. Pipe H 0150 0.150-in. (3.81 mm) for 1-in. Pipe H 0250 0.250-in. (6.35 mm) for 1-in. Pipe H 0345 0.345-in. (8.76 mm) for 1-in. Pipe H 0500 0.500-in. (12.70 mm) for 1-in. Pipe H 0630 0.630-in. (16.00 mm) for 1-in. Pipe H 0800 0.800-in. (20.32 mm) for 1-in. Pipe H 0295 0.295-in. (7.49 mm) for 1 1 /2-in. Pipe H 0376 0.376-in. (9.55 mm) for 1 1 /2-in. Pipe H 0512 0.512-in. (13.00 mm) for 1 1 /2-in. Pipe H 0748 0.748-in. (19.00 mm) for 1 1 /2-in. Pipe H 1022 1.022-in. (25.96 mm) for 1 1 /2-in. Pipe H 1184 1.184-in. (30.07 mm) for 1 1 /2-in. Pipe H 0010 0.010-in. (0,25 mm) for 1 /2-in. Pipe 0014 0.014-in. (0,36 mm) for 1 /2-in. Pipe 0020 0.020-in. (0,51 mm) for 1 /2-in. Pipe 0034 0.034-in. (0,86 mm) for 1 /2-in. Pipe Transmitter/body bolt material C 316 SST (1 1 /2-in. transmitter studs) H G (2) High temperature [850 F (454 C)] Options (include with selected model number) Extended product warranty WR3 3-year limited warranty H WR5 5-year limited warranty H Temperature sensor S (3) T (3) Thermowell and RTD (SST Temperature Housing) Thermowell and RTD (Aluminum Temperature Housing) Assemble to transmitter S4 (4) Factory assembly Attach to transmitter and manifold 164

September 2014 Rosemount DP Flow Table 1. Rosemount 1195 Integral Orifice Primary Element Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Optional bore calculation BC Bore Calculation H Optional connection G1 DIN 19213 Transmitter Connection H Adapters for remote mounting G2 1 /2 14 NPT Remote Adapters SST H G3 1 /2 14 NPT Remote Adapters Alloy C-276 Pressure testing P1 (5) Special cleaning P2 Hydrostatic Testing with Certificate Cleaning for Special Services PA Cleaning per ASTM G93 Level D (section 11.4) Material testing V1 Dye Penetrant Exam Material examination V2 Radiographic Examination (available only with Process Connection code W1, W3, and W6) Flow calibration WD (6) WZ (6) Discharge Coefficient Verification Special Calibration Special inspection QC1 Visual and dimensional inspection with certificate H QC7 Inspection and performance certificate H Material traceability certification Q8 Material Traceability Certification per EN 10204:2004 3.1 H Code conformance J2 (7) ANSI/ASME B31.1 J3 (7) ANSI/ASME B31.3 J4 (7) ANSI/ASME B31.8 Materials conformance J5 (8) NACE MR-0175/ISO 15156 Country certification J6 European Pressure Directive (PED) H J1 Canadian Registration Hardware adjustments and ground screw A1 A2 External Ground Screw for Temperature Connection Head Cover Clamp and External Ground Screw for Temperature Connection Head 165

Rosemount DP Flow September 2014 Table 1. Rosemount 1195 Integral Orifice Primary Element Ordering Information H The Standard offering represents the most common options. The starred options (H) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Typical model number: 1195 S 010 W3 S 0150 C (1) To improve pipe perpendicularity for gasket sealing, socket diameter is smaller than standard pipe O.D. (2) Not available with Assemble to Transmitter code S4 or 1.5" Line Option. (3) Thermowell material is the same as the body material. (4) Not available with Process Connection code S1. (5) Does not apply to Process Connection codes T1 and S1. (6) Not available for bore sizes 0010, 0014, 0020, 0034, 0066, or 0109. (7) Not available with DIN Process Connection codes D1, D2, or D3. (8) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments. 166

September 2014 Rosemount DP Flow Specifications Performance specifications Table 2. Discharge Coefficient Uncertainty (1) Orifice plate bore Bore < 0.160 ±2.50% 0.160 Bore < 0.500 ±1.50% 0.500 Bore 1.000 ±1.00% 1.000 < Bore ±1.50% s 1 /2-in. (15 mm) 1-in. (25 mm) 1 1 /2-in. (40 mm) Sizing Contact an Emerson Process Management sales representative for assistance. A Configuration Data Sheet is required prior to order for application verification. To complete the Configuration Data Sheet go to: http://www3.emersonprocess.com/rosemount/dp_flow/appli cation/pages/pcdefault.aspx Functional specifications Service Liquid Gas Steam Process temperature limits Standard (direct/remote mount) 40 F to 450 F ( 40 C to 232 C) Extended (remote mount only with option code G): 148 F to 850 F ( 100 C to 454 C) Discharge coefficient uncertainty (1) Without associated straight run piping, discharge coefficient uncertainty can add up to 1.5% - 5% additional error. Consult the factory for additional information. Maximum working pressure Pressure retention per ANSI B16.5 600# or DIN PN100 Table 3. 1195 Pressure Limits Physical specifications Material of construction Orifice Plate 316/316L SST Alloy C-276 316 SST (CF8M) A312 Gr 316/316L Flange 1 /2-in. (15 mm) 1-in. (25 mm) 1 1 /2-in. (40 mm) A182 Gr 316/316L Flange pressure limits are per ANSI B16.5 Flange face finish per ANSI B16.5, 125 to 250 RMS Body Bolts/Studs Alloy 400 Body Process connection code S1 or P2 T1 or P1 S1 or P2 T1 or P1 S1 or P2 T1 or P1 Maximum working pressure @ 100 F (1)(2) 3000 psig (207 bar) 1500 psig (103 bar) 2000 psig (138 bar) 1500 psig (103 bar) 1500 psig (103 bar) 1500 psig (103 bar) All Flanged Meets flange primary pressure rating per ANSI B16.5 (EN-1092-1 for DIN flanges) (1) For pressure ratings at temperatures less than -20 F (-29 C) or above 100 F (38 C) consult an Emerson Process Management representative. (2) Transmitter static pressure range may limit maximum working pressure. Refer to Static Pressure Ranges specification. ASTM A193 Gr B8M studs ASTM A193 Gr B8M Class 2 body studs provided for high temperature Option Code G 167

Rosemount DP Flow September 2014 Transmitter Connection Studs ASTM A193 Gr B8M studs Gaskets/O-rings Glass filled PTFE Alloy X-750 provided for high temperature Option Code G Gaskets and O-rings must be replaced each time the 1195 is disassembled for installation or maintenance. Orifice type Square edge orifice bore sizes Table 5. Torque Values of Standard Bolts Stud and nut torque specifications (1) Transmitter bolts All s and gasket types Manifold bolts All s and gasket types Torque 32 lb-ft (44 N-m) 32 lb-ft (44 N-m) Orifice body bolts (2) 1 /2-in. (15 mm) (all gasket types) 60 lb-ft (82 N-m) 1-in. (25 mm) (all gasket types) 60 lb-ft (82 N-m) 1 1 /2-in. (40 mm) (PTFE gasket) 60 lb-ft (82 N-m) 1 1 /2-in. (40 mm) (X-750 metal gasket) 75 lb-ft (102 N-m) 0.066-in. and larger Quadrant edge orifice bore sizes (for 1 /2-in. (15 mm) line size only) 0.034-in. (0.86 mm) 0.020-in. (0.51 mm) (1) Studs and nuts should be tightened to specification in two to three steps alternating between sides. (2) Never reuse gaskets. Always replace gaskets after disassembly to ensure proper seal. Figure 1. Bolt Types 0.014-in. (0.35 mm) 0.010-in. (0.25 mm) Note Integral orifice bodies contain corner tapped pressure ports. Pipe lengths Upstream and downstream associated piping sections are available on the 1195. The table below lists the standard overall length (lay length) as a function of end connections and line size. B C Transmitter connections 2 1 /8-in. (54 mm) center-to-center. Other transmitter spacing can be accommodated using the optional remote adapters and customer-supplied impulse piping. DIN 19213 connections are available. Table 4. Overall Length Dimension Overall length dimension 1 /2-in. (15 mm) 1-in. (25 mm) 1 1 /2-in. (40 mm) Beveled/Threaded pipe ends 18.27 (464.1) 28.98 (736.1) 40.35 (1024.9) RF slip-on, RTJ slip-on, RF-DIN slip 18.43 (468.2) 29.14 (740.2) 40.51 (1029.0) on RF 150#, weld neck 21.94 (557.2) 33.25 (844.5) 45.12 (1146.0) RF 300#, weld neck 22.32 (566.9) 33.77 (857.7) 45.60 (1158.2) RF 600#, weld neck 22.81 (579.4) 34.26 (870.3) 46.23 (1174.3) Dimensions are in inches (millimeters). A A. Orifice Body Bolts (2X) B. Transmitter Bolts (4X) C. Manifold Bolts (4X) Table 6. Weight (weights are approximate) 1195 only With flanged piping (1) lb kg lb kg 1 /2-in. (15 mm) 4.0 1.8 8 3.6 1-in. (25 mm) 6.0 2.7 12 5.4 1 1 /2-in. (40 mm) 8.0 3.6 25 11.3 (1) As supplied with standard lengths, ANSI Class 150 flanges. 168

September 2014 Rosemount DP Flow 1195 dimensional drawings Rosemount 1195 Integral Orifice Plate Top view 1 /2-in. NPT Bottom view End view 1.10 (27.94) 2.13 (53.98) 1.63 (41) B.D. (2) Flow K (1) Downstream J Upstream Dimensions are in inches (millimeters). Table 37. 1195 Integral Orifice Plate Dimensional Data Dimension 1 /2-in. (15 mm) 1-in. (25 mm) 1 1 /2-in. (40 mm) J (Beveled/Threaded pipe ends) 12.54 (318.4) 20.24 (514.0) 28.44 (722.4) J (RF slip-on, RTJ slip-on, RF-DIN slip-on) 12.62 (320.4) 20.32 (516.0) 28.52 (724.4) J (RF 150#, weld-neck) 14.37 (364.9) 22.37 (568.1) 30.82 (782.9) J (RF 300#, weld-neck) 14.56 (369.8) 22.63 (574.7) 31.06 (789.0) J (RF 600#, weld-neck) 14.81 (376.0) 22.88 (581.0) 31.38 (797.1) K (Beveled/Threaded pipe ends) 5.74 (145.7) 8.75 (222.2) 11.91 (302.6) K (RF slip-on, RTJ slip-on, RF-DIN slip-on) (1) 5.82 (147.8) 8.83 (224.2) 11.99 (304.6) K (RF 150#, weld-neck) 7.57 (192.3) 10.88 (276.3) 14.29 (363.1) K (RF 300#, weld-neck) 7.76 (197.1) 11.14 (282.9) 14.53 (369.2) K (RF 600#, weld-neck) 8.01 (203.4) 11.39 (289.2) 14.85 (377.2) B.D.(Bore Diameter) (2) 0.664 (16.86) 1.097 (27.86) 1.567 (39.80) Dimensions are in inches (millimeters). (1) Downstream length shown here includes plate thickness of 0.162-in. (4.11 mm). (2) B.D is diameter of the precision bored portion of the upstream and downstream piping. 221

Rosemount DP Flow September 2014 E F Orifice plate 2.46 (62.4) 0.162 (4.11) Socket-weld or threaded body A 0.44 0.47 (11.85) H D I.D. C B 1.625 (41.23) F 2.13 (53.93) 3.37 (85.6) Remote adapter NPT / Beveled piping (prepared for welding) 0.062 (1.57) L Upstream M (2) Downstream 0.81 (20.64) ½ 14 NPT 0.81 (20.64) 0.47 (11.91) 1.10 (27.94) Flow B.D. Temperature sensor Flow R RTDL Table 38. 1195 Integral Orifice Dimensional Data Dimension 1 /2-in. (12.7 mm) 1-in. (25.4 mm) 1 1 /2-in. (38.1 mm) A 3.4-in. 86 mm 3.8-in. 97 mm 4.5-in. 114 mm B 4.7-in. 119.4 mm 5.2-in. 132 mm 5.9-in. 149.9 mm C 3.0-in. 76 mm 3.3-in. 84 mm 3.7-in. 94 mm D (1) 0.805-in. 20.45 mm 1.280-in. 32.51 mm 1.865-in. 47.37 mm E 3.6-in. 91 mm 3.9-in. 99 mm 4.4-in. 112 mm F 2.6-in. 66 mm 3.0-in. 76 mm 3.5-in. 89 mm H 2.5-in. 64 mm 3.0-in. 76 mm 3.5-in. 89 mm L 12.54-in. 318.4 mm 20.24-in. 514 mm 28.44-in. 722.4 mm M 5.74-in. 145.7 mm 8.75-in. 222.2mm 11.91-in. 302.6 mm R 7.4-in. 187.96 mm 7.8-in. 198.12 mm 8.4-in. 213.36 mm RTDL 3.11-in. 78.9 mm 5.25-in. 133.4 mm 7.50-in. 190.5 mm B.D. (Bore Diameter) (2) 0.664-in. 16.87 mm 1.097-in. 27.86 mm 1.567-in. 39.80 mm I.D. (Inside Diameter) 0.622-in. 15.80 mm 1.049-in. 26.64 mm 1.500-in. 38.10 mm (1) To improve pipe perpendicularity for gasket sealing, socket diameter D is smaller than standard pipe O.D. Pipe O.D. must be machined smaller than socket diameter D to ensure proper fit. (2) B.D is diameter of the precision bored portion of the upstream and downstream piping. 222