Influence of Electric Field Distribution along the Line Post and Pin Post Insulator due to Lightning Strike

Similar documents
PORCELAIN INSULATORS

ELECTRIC STRESS ANALYSIS ON 11KV INSULATOR

Distribution of Electric Field Analysis in 36 kv Roof Top Bushing by using FEM Techniques

BOWTHORPE EMP MEH SURGE ARRESTERS (IEC) ENERGY /// MEH SURGE ARRESTERS IEC

POLYMER INSULATOR. Index

Analysis of Electric Field and Magnetic Field from Overhead Subtransmission Lines Affecting Occupational Health and Safety in MEA s Power System

PROVINCIAL ELECTRICITY AUTHORITY

Energy Division. PCA Single Column Polymeric Surge Arrester

An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks

BOWTHORPE EMP MCA/MDA SURGE ARRESTERS (IEC) ENERGY /// MCA/MDA SURGE ARRESTERS IEC

VEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY

ANSI Design Test Report ANSI Glass Bells Catalog # PSN21156

MEDIUM VOLTAGE NETWORKS

PPC Porcelain Solid Core Post Insulators and Operating Rods ANSI

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

Design of 33kV Transformer Bushing Insulator from NR and HDPE

Station Class Polymeric Surge Arresters

H U B B ELL L ABOR ATORIES CAPABILITY GUIDE

Station Post Insulators

CONTENTS About the company 1. Low-voltage arresters LVA type 2. Metal-oxide surge arresters for distribution systems. 3.

CATALOG NUMBER 081 BALTIMORE, MARYLAND

Impact Analysis of Fast Charging to Voltage Profile in PEA Distribution System by Monte Carlo Simulation

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

High Voltage Technology & Testing

Figure 1 I-V characteristics of PV cells. Meenakshi Dixit, Dr. A. A. Shinde IJSRE Volume 3 Issue 12 December 2015 Page 4687

produces and delivers products worldwide can provide the optimal solution for your requirements. are dedicated to supplying you with

Impact Analysis of Off-board Charger to Power Quality

BHATINDA CERAMICS PRIVATE LIMITED (Mfrs/Exporters of High Tension Porcelain Insulators)

Polymer Insulators A Better Solution

On-load tap-changer OILTAP V

Finite Element Analysis on Thermal Effect of the Vehicle Engine

Switching Impulse Flashover Tests and Analysis for 765kV Jumper V-strings with Damaged Insulators

Bowthorpe EMP LV/MV Outdoor Surge Arresters

Investigating The Effect of Switching and tripping on Flashover and Breakdown in Circuit Breaker

Simulation Analysis of Closed Loop Dual Inductor Current-Fed Push-Pull Converter by using Soft Switching

SciVerse ScienceDirect

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set.

Transformer bushings, type GOH. Technical guide

Analysis Of Vehicle Air Compressor Mounting Bracket

Surge arresters Product overview

Zinc Oxide Surge Arrester EXLIM R

GE TRANQUELLTM Surge Arresters

Effect of Permanent Magnet Rotor Design on PMSM Properties

KEE HING CHEUNG KEE CO., LTD. DLFTZ CHANG HING KEE INT L INDUSTRY & TRADE CO., LTD.

DAQO Technical Differences of Isolated Phase Bus Standards. Study of Design Standard Variances, Insulator Design and Shipping Section Design

FAULT ANALYSIS FOR VOLTAGE SOURCE INVERTER DRIVEN INDUCTION MOTOR DRIVE

High Voltage Surge Arresters Buyer s Guide Section PEXLIM R

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

High Voltage Surge Arresters Station Class

Dynamic Modelling of Hybrid System for Efficient Power Transfer under Different Condition

GENERAL. CONSTRUCTION External

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

GLASS INSULATORS FOR OVERHEAD POWER TRANSMISSION LINES

34-SDMS-01 SPECIFICATIONS FOR

PABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY

The comprehensive portfolio of the testing laboratories at Schaltwerk Berlin siemens.com/energy/psw

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

3EK7 Medium Voltage Silicone Insulated Surge Arresters

HIGH VOLTAGE SURGE ARRESTER SPECIFICATION

Section 2 - Substation Switchgear

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

Rotor Position Detection of CPPM Belt Starter Generator with Trapezoidal Back EMF using Six Hall Sensors

Improved PV Module Performance Under Partial Shading Conditions

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran

Experimental Results versus FEM Based Analysis of a Squirrel Cage Induction Motor

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

Silicone Suspension/Tension Insulator 120kN. up to LIWV 450kV (BIL)

International Journal of Scientific & Engineering Research, Volume 7, Issue 3, March ISSN DESIGN AND ANALYSIS OF A SHOCK ABSORBER

Forced vibration frequency response for a permanent magnetic planetary gear

BIDIRECTIONAL DC-DC CONVERTER FOR INTEGRATION OF BATTERY ENERGY STORAGE SYSTEM WITH DC GRID

Transmission Porcelain Surge Arresters

Procedia - Social and Behavioral Sciences 195 ( 2015 ) World Conference on Technology, Innovation and Entrepreneurship

Protection and Disconnection Equipment for High and Medium Voltage and Transformers Line

Design and experiment of hydraulic impact loading system for mine cable bolt

ELECTRICAL ENGINEERING & COMPUTER SCIENCE NEWSLETTER Volume

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

DESIGN AND ANALYSIS OF LEAF SPRING FOR SOLAR VEHICLE

Induction Motor Condition Monitoring Using Fuzzy Logic

High Power Semiconductor Devices and Solid State Switches for Pulsed Discharge Applications

e t Performance of Extended Inlet and Extended Outlet Tube on Single Expansion Chamber for Noise Reduction

Zinc Oxide Surge Arrester PEXLIM Q

On the potential application of a numerical optimization of fatigue life with DoE and FEM

power cable accessories

Interruption Technology of Breakers for High-voltage Direct Current

Characteristics of High Voltage Polymer Insulator Under Accelerated Artificial Tropical Climate Multi Stress Aging

RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE.

Fluid characteristics impact performance capabilities in transformer application

Influence of Internal Combustion Engine Parameters on Gas Leakage through the Piston Rings Area

STRUCTURAL ANALYSIS OF REAR AXLE CASING OF TRACTOR

Design and Analysis of Arc Springs used in Dual Mass Flywheel

The Effects of Magnetic Circuit Geometry on Torque Generation of 8/14 Switched Reluctance Machine

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv

LV Bushing Oil to Air Dry Insulation PTAB-SLV832

Experimental Investigation of Effects of Shock Absorber Mounting Angle on Damping Characterstics

Research in hydraulic brake components and operational factors influencing the hysteresis losses

VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC (99-4)

6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET)

Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress.

Technical Journal September 2012

Transcription:

Influence of Electric Field Distribution along the Line Post and Pin Post Insulator due to Lightning Strike Pramuk Unahalekhaka and Karun Sirichunchuen Abstract This paper presents a simulation of electric field distribution along the insulator in case of lightning strike to the wires on top and at the side of line post type 57-2 TIS.1077 and pin post type 56/57-2 TIS.1251 by using Finite Element Analysis Program and ATP-EMTP program. The insulators were used in 22 kv distribution system of Provincial Electricity Authority (PEA) in case of a lightning strike on a pole directly. The model took the lightning surge current 10/350μs at 20kA, 40kA, and 80kA respectively. The simulation results found that all surface area of line post insulator was distributed by electric field and partial surface area of pin post insulator which was distributed by electric field in case of installation the distribution line on the top and at the side of insulation. Therefore, the installation of distribution line on the top of insulation along straight path or the installation of distribution line at the side of insulation along curve path should be used suitable for the installation by pin post insulator. Keywords Electric Field, Pin post Type Insulator, Line Post Type Insulator, Finite Element, ATP-EMTP, lightning strike. 1. INTRODUCTION Nowadays, the power system at 22 kv of the provincial electricity authority (PEA) is a distribution system by using the overhead power line insulators for supporting and holding the space of the distribution lines steadily. The insulators selected were applied for distribution system based on the IEC 60815 standard, as shown in Fig 1. Poles Installation for the distribution line on the curved road were equipped with beside of insulator for supporting the tension weight of the distribution lines as shown in Fig 2. Line post and pin post insulators are applied for the distribution system in PEA. They are installed on distribution overhead line on the poles and outdoors area, where the insulators are damaged by the lightning strike on the ground wire. The dropped voltage occurred was higher than the resistance and flashover occurred from the resulting in the loss of stability of the power distribution system. From the reasons mentioned above, this research focused on the simulation electric field of line post insulators and pin post insulators in the crisis conditions by ATP-EMTP program. In addition, it could be analyzed the distribution of the electric field by the Finite Element Analysis program. The data obtained from this study was used for considering and planning the selection of insulators for distribution system installation properly and efficiently. It was able to protect against the loss of stability of the distribution system. a) b) Fig. 1. Clamping to hold the power lines on the top insulators. Pramuk Unahalekhaka is with Dept. of Electrical Engineering, Faculty of Industrial Education, Rajamangala University of Technology Suvarnabhumi, 7/1 Nonthaburi 1 Rd, Nonthaburi, 11000, Thailand. Email: Pramuk.u@rmutsb.ac.th and Sabuy8888@hotmail.com. Karun Sirichunchuen (corresponding author) is with Dept. of Electrical Engineering, Faculty of Engineering and Architecture, 7/1 Nonthaburi 1 Rd, Nonthaburi, 11000, Thailand. Email: Karun_ep@hotmail.com. a) b) Fig. 2. Clamping to hold the power line at the side of insulators. 23

2. LINE POST AND PIN POST INSULATORS Porcelain insulator, line post insulator and pin post insulator were used in the power distribution systems 22 kv and 33 kv, which were made of the clay and coated with a coating including the base of the insulators is the casted iron. This paper was to simulate the dielectric insulators as line post type CLASS ANSI 57-2 and pin post type CLASS ANSI 56 / 57-2 in distribution system 22 kv as shown in Fig 3. In the technical data is shown in Table 1. a) b) Fig. 4. Finding the dimensions size of insulators. a) b) Fig. 3. The Characteristics of Insulators Table 1. Technical data of line post and pin post Insulators Class ANSI 56/57-2 57-2 Leakage distance min. 534 mmm 559 mm Protected leakage distance min. 267 mmm 241 mm Cantilever strength 12.5 kn 12.5 kn Cantilever proof load 5 kn 5 kn a) Low-frequency dry flashover 110 kv 110 kv Low-frequency wet flashover 80 kv 85 kv Critical- impulse flashover, positive 180 kv 180 kv Critical- impulse flashover, negative 205 kv 205 kv Low-frequency test voltage, rms to ground 22 kv 22 kv Maximum RIV at 1000 khz 100 µv 100 µv 3. ELECTRIC FIELD MODELING Modeling of dielectric insulators used the data of the spatial dimension and leaking stage of insulator that was in the modeling of the two types in order to measure the dimensional with the cutting a half way as shown in Fig 4. Also, it applied for modeling in 3D Programs and the scale of the completed model was 1:1 as shown in Fig 5. b) Fig. 5. Insulators model. 24

4. SIMULATION OF IMPULSE VOLTAGE The simulation of the ATP-EMTP program was considered the surge voltage happened at the distribution line. Due to the lightning strike on the overhead ground wire (OHGW) of the power distribution system. The lightning surge current is 10/350 μss that could be shown in 20 ka, 40 ka and 80 ka. The fig 6 was shown as the waveforms currents lightning at 80 ka and the lightning surge voltage up to 495 kv was shown in Fig 7. The results of simulation as shown in Table 2. Table 2. Lightning surge voltage at distribution line. Lightning surge current (ka) 20 40 80 Lightning surge voltage (kv) 137 256 495 This research is to study of the distribution of the electric field on the insulators surface of line post insulator and pin post insulator by using the Finite Element Analysis Program, which defined the parameters for modeling. It could comprise the electrical permittivity of the material (Relative permittivity) and a density electric charge spatial (Conductivity) according to Table 2. From simulation a lightning surge voltage occurred at the distribution line were 137 kv, 256 kv, and 495 kv. Also each segment was divided from the intensity electric field on the surface of a dielectric insulator as shown in Fig 8. Table 2. Parameters used in the simulation Material Parameters Relative permittivity ε r Conductivity σ (s/cm) Porcelain 5.7 1x10-14 Cast iron 1 1.12x10 7 Cement 4.5 1x10 7 Nut 1 1.12x10 7 Aluminium 1 3.56x10 7 5. SIMULATION AND RESULTS From the modeling results, an electric field distribution in 3D figure was on the surface of dielectric of line post insulator and pin post insulator in the conditions of a lightning surge voltage as 135 kv, 256, and 495 kv, which distribution line insulator was mounted on the insulators and the electricall cable at the side of insulator. 5.1 The electrical cable insulator clamped to hold on the top The electric field was distributed on the insulator surface and around the distribution lines mostly. Also, it could distribute through the base of insulator as shown in Fig 9. From the analyzing, the intensity electric field of the two types insulators, which was found that the increased lightning surge voltage in distribution lines towards the valuable of the electric field increased and spread on insulators mostly. The line post insulator was the maximum valuable in the electric field strength at the point B as 2.27 x10 6 V/m and minimum point L as 4.46 x10 5 V/m. For the pin post insulator was the maximum valuable of the electric field strength at the point B as 1.91x10 6 V/m and minimum point I as 5.14 x105 V/m. In case of lightning surge voltage in distribution lines were distributed at 495 kv which was the maximum valuable in the electric field strength at each analyzed segment as shown in Fig 9c. Fig. 6. Lightning surge currents at 10/350 μs, 80 ka. Fig.7. Lightning surge voltage at 10/350 μs, 80 ka. a) b) Fig. 8. Each segment the intensity electric field on the surface of a dielectric insulator. 25

a) Lightning surge voltage at 137 kv in Fig 10c. From the results of simulation in the two types of insulator the electric field distribution were analyzed a segment near ground of line post insulator which was located between point K to M, which the electric field was distributed massively as shown in Fig 11a. The pin post insulator was located between point J to M, which the electric field was distributed less than of line post insulator massively because there was more air gap as shown in Fig 11b. b) Lightning surge voltage at 256 kv Line Post Insulator a) Lightning surge voltage at 137 kv Line Post Insulator b) Lightning surge voltage at 256 kv c) Lightning surge voltage at 495 kv Fig. 9. Electric field contour with lightning surge voltage of distribution line on the top of insulator. 5.2 The electrical cable clamped to hold at the side of insulator. The electric field was distributed on the insulator surface and around the distribution lines mostly. Also it could distributed through the base of insulator as shown in Fig 10. From the analyzing, the intensity electric field of the two types insulators, which was found that the increased lightning surge voltage in distribution lines towards the valuable of the electric field increased and spread on insulators mostly. The line post insulator is the maximum valuable in the electric field strength at the point B as 2.21 x10 6 V/m and minimum point L as 4.27 x10 5 V/m. For the pin post insulator is the maximum valuable of the electric field strength at the point B as 2.54x10 6 V/m and minimum point M as 5.14 x10 5 V/m. In case of lightning surge voltage in distribution were distributed at 495 kv which was the maximum valuable in the electric field strength at each analyzed segment as shown c) Lightning surge voltage at 495 kv Fig. 10. Electric field contour with lightning surge voltage of distribution line at the side of insulator. 6. CONCLUSION From the results of simulation, both of the line post type 57-2 insulator and pin post type 56/57-2 underlightning surge voltage were analyzed the lightning surge currents at 10/350 μs by lightning currents 20 ka, 40 ka and 80 ka. The pin post insulator was analyzed that the distribution electric field was the most suitable for the installation of distribution line on the top of insulation along the straight path and at the side of insulation along 26

curved path. Since an electric field distribution near the ground area was distributed at least and more the air gap. The chance of flashover and breakdown might be tougher than line post insulator. a) Electric field REFERENCES [1] Mayer, A. and Biscaglia, S. 1989. Modelling and analysis of lead acid battery operation. In Proceedings of the Ninth EC PV Solar Conference. Reiburg, Germany, 25-29 September. London: Kluwer Academic Publishers. [2] R.Arora and W.Mosch, High voltage insulation engineering. New age internal (p) Limited. [3] Chinnusamy Munira, Subramaniam Chandrasekar, Finite Element Modeling for Electric Field and Voltage Distribution along the Polluted Polymeric Insulator ISSN 1 746-7233, England, UK World Journal of Modelling and Simulation Vol. 8 (2012) No. 4, pp. 310-320 [4] Mu Liangl, and K. L. Wong I' Study of Electric Field Distribution on 22 kv Insulator under Three Phase Energisation Conference Proceedings of ISEIM 2014. [5] Tung, F. Y.-T., & Bowen, S. W. (1998). Targeted inhibition of hepatitis B virus gene expression: A gene therapy approach. Frontiers in Bioscience [Online serial], 3. Retrieved February 14, 2005. b) Electric field Fig. 11. The electric field near ground in case of voltage surge 495 kv. 27