Texas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives

Similar documents
Advanced Protective Relay Training

Implementing a Microgrid Using Standard Utility Control Equipment

2017 Southeastern Tri Regional SAME Training Symposium Microgrids What are they, lessons learned 8/30/2017 Dan Dorn Eaton Corp

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

4-Day Power System Analysis, Coordination, System Studies

MICROGRIDS DESIGNING AN IMPROVED GRID

Energy Security Electrical Islanding Approach and Assessment Tools. Dr. Bill Kramer Senior Research Engineer Distributed Energy Systems Integration

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

Shippensburg University

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation

Welcome to the IDEA Webinar Series

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

Transformer Protection

Advanced controls of PV for microgrid applications

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

The Evolution of System Protection Schemes for the Sarawak Power System By Victor Wong Sarawak Energy Berhad Presented at PQSynergy 2012, Sarawak

DER Portfolio Optimization and Dispatch, Tertiary Control/Monitoring Strategies

GE Energy. Variable Frequency Transformers Grid Inter-tie

PARALLELING SWITCHGEAR

SEL Microgrid Lessons Learned

UNC-Charlotte's Power Engineering Teaching lab

TRANSMISSION PLANNING CRITERIA

COGENERATION PLANT SWITCHGEAR REPLACEMENT IMPROVES SAFETY AND RELIABILITY WHILE MAINTAINING SERVICE TO CRITICAL LOADS

EE 741 Over-voltage and Overcurrent. Spring 2014

BROCHURE. End-to-end microgrid solutions From consulting and advisory services to design and implementation

AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Copyright 2003 Advanced Power Technologies, Inc.

Smart Grid Automation and Centralized FISR

Burns & McDonnell ISU Senior Design Project 2010/2011

Control System for a Diesel Generator and UPS

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Innovation Pointe Progressive Energy Resource Park (PREP), an Application of Distributed Generation, Microgrid and Smart Grid

2015 WDC Disturbance and Protection Standards Overview

EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS

Wang Bin & Michael Ho, TIIAE Power management system

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear

Minnesota Dept. of Commerce, Division of Energy Resources. Distributed Generation Workshop Interconnection Standards

TIME REQUIREMENT GUIDE (TRG)

EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting

INTERCONNECT CHALLENGES IN THE DEVELOPING WORLD S DISTRIBUTED GENERATION INFANCY. David C. Oehl, P.E. President MAVEN POWER

Sub Regional RTEP Committee Mid-Atlantic

BC Hydro Case Study: Battery Energy Storage in Field, British Columbia, Canada. IEEE PES Meeting July 2014

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection System Impact Study For

S C ELECTRIC EUROPE LTD. Excellence Through Innovation. Harnessing the Wind. November 2011 Descriptive Bulletin E

Industry Automation Control Components

Sitras SCS, -RCI, -FFP, -TTU

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

Technology Roadmap for zzzzzzzzz Grid Automation

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management

Integrated Power Solutions

Arc-Flash Mitigation Technologies. Dennis Balickie

100 MW Wind Generation Project

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS

Application Note RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS

TD-2306B-001, Interconnecting Large 2-20MW Generation Systems. Employees involved with generation interconnection on electric distribution circuits.

ABB Automation & Power World: April 18-21, 2011 WPO MV outdoor products for smart grid demands. ABB Inc. April 19, 2011 Slide 1

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

North Oregon Coast Area Study. Adam Lint

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less

3.0 Radial Distribution Systems

Small Electrical Systems (Microgrids)

Chapter 3.1: Electrical System

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

SECONDS CAN COST MILLIONS

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

IEEE-PES Chicago Chapter Presentation November 11, Smart Grid. Mike Born. Principal Engineer, Capacity Planning

Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study

Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK

Interconnection System Impact Study Report Request # GI

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals. Mike Schmaderer

Project #148. Generation Interconnection System Impact Study Report

MEDIUM VOLTAGE PRODUCT CAPABILITIES OVERVIEW

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Future Proof Your Arc Flash Assessment

INTRODUCTION TO SMART GRID

Are the New 2005 NEC Selective Coordination Requirements Causing an Increase in Arc Flash Energies and Reducing Distribution System Reliability?

Summary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION AND FACILITIES STUDY. Short Circuit Analysis

Modular Standardized Electrical and Control Solutions for Fast Track Projects

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Recommended Procedures

FUSES. Safety through quality

MEDSolar Training Course Module 1 Microgrids with PV support

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)

XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado

A21M. Introduction: Functional Overview: Key Protection & Control Functions:

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

Transcription:

Texas A&M Microgrid and Electrical System Study Cushing Memorial Library & Archives

Introduction of Texas A&M Microgrid Study Purpose Why are we studying the TAMU electrical system? Process How do we want the distribution system to react? Plan What is the application of the data we saw? Presenter: Brad Shuffield, P.E., Class of 05 (bshuffield@burnsmcd.com) Sr. Electrical Engineer Burns & McDonnell Thanks to: Tyler Hjorth, P.E., Class of 91 Manager, Electrical Services TAMU UES Question: How many Aggies does it take to screw in a light bulb? 2

Purpose: Electrical System Study Need Why study the campus electrical distribution system? No defined response for system contingencies Goal is automated system response Answer the What if question ETAP model not updated for new loads New equipment and buildings have been added to campus recently No comprehensive relay protection philosophy Various methods of system protection methods are used Manual control of substation capacitors Microgrid Definition: A microgrid is a group of interconnected loads and distributed energy resources within clearly defined electrical boundaries that acts as a single controllable entity with respect to the grid. A microgrid can connect and disconnect from the grid to enable it to operate in both gridconnected or island mode. U.S. DOE MEG Building generators not tested and underutilized 3

Overview of TAMU Electrical Distribution System 138kV to 12.47kV Substation Separation of Utility Plants and Campus Buildings Utility Plants Central Utility Plant: CUP Satellite Utility Plants: SUP1/SUP2/SUP3 Campus Distribution Switchgear Distribution Points Building Feeders Control Systems Ovation SCADA Distribution Automation 4

UTILITY PLANTS GTG1=34MW STG2=11MW STG4=5MW CAMPUS DISTRIBUTION Heldenfels Switching Station Research Park Switching Station West Campus Switching Station 5

Process: System Study Approach How do we improve on the electrical system? Analyze and define system response options Utilize available meter data Update ETAP model Short circuit study Arc-Flash study Document relay settings philosophy Correct coordination issues Propose standards for new relays Analyze substation capacitors Investigate generators for paralleling 6

Plan: Automate Electrical System Response The What If Scenarios 138kV-12.47kV Substation Transformer Loss 12.47kV Bus Loss 138kV Bus Differential Trip Loss of Utility Power (Island Mode) Total Campus Power Loss TAMU Electrical Goals: 1. Keep the lights on. 2. Parallel transformers as needed. 3. Utilize on-site generation. 4. Shed campus load as last option. 7

138kV-12.47kV Substation Transformer Loss Campus Distribution: XFMRs T1, T2, T3, T6, T8 System Reaction: 1) One XFMR/ Two Bus 2) Three XFMR / Four Bus 3) Overload XFMR 4) Shed Load Single Transformer Rating = 20MVA 8

138kV-12.47kV Substation Transformer Loss Utility Plants: XFMRs T4, T5 System Reaction: 1) One XFMR/ Three Bus 2) Bus 106 Backup 9

12.47kV Bus Loss Cause: Bus Differential Trip Analyzed downstream switchgear meter data Campus Distribution: Bus 101, 102, 103, 106, 108 1) Switch Downstream Switchgear Breakers 2) Shed Load Utility Plant: Bus 104, 105, 107 1) Switch Downstream Switchgear Breakers 2) Reduce Power Output of Generation 10

138kV Bus Differential Trip 138kV Bus #1 XFMRs T1, T2 Only campus distribution affected 1) One XFMR/Two Bus (T8 backup) 2) Two XFMR/Four Bus 3) XFMR Overload 4) Load Shed 138kV Bus #2 XFMRs T3, T4, T5, T6 CUP generation transfers to island mode 1) One XFMR/Two Bus (T8 backup) 2) Two XFMR/Four Bus 3) XFMR Overload 4) Load Shed 11

Loss Of Utility Power Island Mode Automated Grid Separation GTG-1, STG-2, STG-4 switch to island mode Campus generators provide power to buildings Thermal process coordination Island Mode Operation Generation = Load Return to Utility Automatically Synchronize to BTU 12

Loss Of Utility Power No Utility Power or Campus Generation Zero Voltage Start (ZVS) Sequence CUP Diesel Generator starts GTG1 GTG1 supplies power to CUP Mechanical Systems Interaction Steam production balance Automation through Ovation system Energize select campus loads through breaker operation Return to Utility Automatically synchronize 13

Microgrid Control Solution Main Functions Breaker Control Switch breakers according to proposed response Automatic Islanding/Fast Load Shedding Detection before generator trip Automatic Generator Synchronization Power Factor Control Emergency Generator Integration Control System Interaction 14

Microgrid Control Solution System Diagram Windows Computer LSS HMI HMI DATA Loss of Source, Load Trips and Main Tie Main Transfer Blocks Meter and Misc. Data Meter and Misc. Data SEL SCADA Meter and Misc. Data Ethernet Network EMERSON DCS Loss of Source or BTU Breaker Trip Load trips and Main Tie Main Transfer Blocks BTU RELAYSBTU RELAYS SEL-2411 SEL-2411 SEL-2411 GOOSE DNP3 OPC/DNP3 15

Relay Protection Philosophy Goal: Trip downstream relays before upstream System coordination vs. equipment protection Analysis of 15kV relays.rdb files TCC curves Trip equations Proposed changes Improve transformer protection Coordinate instantaneous on main feeders Improve ground fault coordination Simplify trip equations 16

Relay Coordination Curves Before/After Relays not coordinated 17

Substation Power Factor Control 3000kVAR units at each 15kV substation bus Manually switched 3 of 7 units not functioning Recommend new, staged units Goal: Maintain.97pf Interaction with control system 18

Generator Investigation Current Issue: How to test building generators using load? Future Issue: How to use excess generator capacity to provide power to campus in an outage? Analyzed ratings of equipment and ratings of generators 500kW and larger. Result: Most generators can be paralleled to the system safely for testing and back up on a campus level. 19

Steps Forward and Application Next Steps Detailed Design of the Microgrid Control System Complete a detailed ZVS sequence Install metering at main 15kV system buses What is the application for your system? Know where power is flowing on your system Maintain current electrical system model with relaying Identify system coordination improvement Ask the What-if questions about your equipment Generation behind the meter Roadmap of potential automation & island operation Pro-active about system operation 20