3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Similar documents
3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

Cold Shrink QS T Trifurcating Transition Splice Kit

QT-III Cold Shrink Silicone Rubber

3M Mechanical Shearbolt Connectors, QCI Series

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

ELB ES. Product Installation Instructions

Branch Splice QS-2001B

Cable Ties. Data Sheet

3M Cold Shrink Splice Kits, QS T Series

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

3M Cross-Connect Cabinets 4220SVC and 4220SVE Tall Skirt Installation Guide

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

ELB ELB

3M Locator Plate

3M Locator Plate

3M Products for Electrical Networks Wind Farm Capabilities. Leading Edge. Electrical Solutions for. Wind Farms

3 Reenterable Encapsulated PST Dome Closure

3M Electrical Tapes Product Selection Guide. Insulate & Protect. with Quality Tapes. Preliminary

3M Closure System 2-Type Cover (505)

3M Ladder Kit 3M710/MS 2 -TMK-LK

HVS S 15kV Class

Data Sheet July For RoHS information, please visit

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900 µm Instructions

Installation Instructions

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

710 Splicing Rig. Instructions. January E

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900-µm. Instructions. October C

3M No Polish LC/APC Connector SM, Angle Splice, 250/900 µm 8830-APC/AS

3M Electrical Markets Division. Rubber, Mastic and Specialty Tapes Application Guide. Choose the. Right Tape. for your. Electrical Project

3M Mini D Ribbon (MDR) Cable Assembly.050 High Speed Video Data Transmission System, 50 Position 14X50-SZWB-XXX-0NC

DISTRIBUTION CONNECTORS SECTION DF COMPRESSION TERMINALS. Aluminum Compression Lugs Aluminum Bi-Metal Pin Terminals Copper Compression Lugs

3M Pleated Foil I/O Cable Assemblies MDR Series

High Voltage Joints and Terminations up to 72,5 kv 145 kv

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

3M Textool Test and Burn-In Sockets for 1.0 mm Area Array Packages Including Ball Grid Array and Land Grid Array

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

(K),(M)430TB/G Up to 36 kv

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

3M No Polish LC Connector SM and MM, Flat Splice, 250/900 µm

3M Cable Ties Product Guide. Made in USA. & Plenum Rated

3M Cushion-Mount Plus Plate Mounting Tapes with Easy Mount Adhesive

Installation Instruction EPP /92

CP 600V Cable Protectors

Installation Instructions

3M Fiber Dome Closure FDC 10

8400 Series Fiber Distribution System

Door Edge Protection Film 36 inch

(K),(M),(P)489TB/G Up to 42 kv

3M Cold Shrink QT-III Silicone Rubber Skirted and Inverted Skirted Termination Kits, 7640-S, 7650-S and 7660-S Series 5, 8, 15, 25/28 and 35 kv

3M Connector System 0.050" x 0.100" Pitch. 3M Tripolarized Wiremount Socket - Series 820 3M 4-Wall, Tripolarized Header - Series 810

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv

Repair Method for 3M Resilient Floor Protection System

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

K SERIES PUSH ON & BULLET TERMINALS

C Power Connection Kit

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

Wind Energy Catalog Solutions for the Wind Industry

3M CP2 Press-Fit Headers and Sockets, 2 mm

GM Specification Annual Test Data

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

Transcription:

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief For Tape Shielded, Wire Shielded and UniShield Cable 7685-S-8 Instructions IEEE Std. No. 48 Class 1 Termination 35 kv Class 200 kv BIL F CAUTION Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product. January 2013 3 78-8119-6018-2 Rev C

1.0 Kit Contents 3 High-K, Tracking Resistant, Silicone Rubber Terminations 3 Pre-formed Ground Braids 3 Constant Force Springs 3 3M EMI Copper Foil Shielding Tape 1181 Strips, " x 10" 6 Strips Scotch Mastic Strip 2230 (black with white release liners, bagged) 1 3M Cable Cleaning Preparation Kit CC-2 1 Instruction Sheet NOTE: Do Not use knives to open plastic bags. Kit Selection Table NOTE: Final Determination Factor is cable insulation diameter. Kit Number Primary Insulation O.D. Range Jacket O.D. Range Conductor Size Range (AWG & kcmil) 15 kv 25/28 kv 35 kv 7685-S-8 1.05" - 1.80" (26,7-45,7 mm) 1.39" - 2.40" (35,3-61,0 mm) 500-1000 kcmil (240-500 mm 2 ) 250-800 kcmil (125-400 mm 2 ) 3/0-600 AWG (95-325 mm 2 ) Table 1 2 78-8119-6018-2 Rev C

Instructions For Tape Shielded Cable 2.0 Prepare Cable 2.1 Check to be sure cable size fits within kit size range as shown in Table 1. 2.2 Prepare cable using dimensions shown in Figure 1. Refer to Table 2 for semi-con cutback dimension. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG. If necessary to prevent tape shield from unrolling, hold down edge with a single wrap of 3M EMI Copper Foil Shielding Tape 1181. NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors as follows: Aluminum Connector Growth Allowance 2-350 1/4 (6 mm) 400-650 " (13 mm) 7501000 3/4" (19 mm) NOTE: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer. Kit Number Insulation 0.D. 15 kv AWG / kcmil 25/28 kv AWG / kcmil 35 kv AWG / kcmil Semi-con Cutback 7685-S-8 1.05" -1.46" (26,7-37,1 mm) 1.24" - 1.80" (31,5-45,7 mm) 500-700 (240-400 mm 2 ) 750-1000 (400-500 mm 2 ) 250-500 (125-250 mm 2 ) 600-800 (300-400 mm 2 ) 3/0-350 (95-150 mm 2 ) 500-600 (185-325 mm 2 ) 13.5" (342,9 mm) 13.0" (330,2 mm) Table 2 Jacket Removal Length Depth Of Terminal Lug + Growth Allowance 3 (76 mm) Semi-Con Cutback 1 1/ 2 (38 mm) Semi-Con Tape Shield Cable Jacket Figure 1 78-8119-6018-2 Rev C 3

3.0 Install Ground Braid 3.1 Select a Scotch Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a SINGLE WRAP of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 2). Cut off excess. 1/4 (6 mm) Semi-Con Tape Shield 1 ST Scotch Mastic Strip 2230 Cable Jacket Figure 2 3.2 Position pre-formed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. PLEASE NOTE: The ground braid needs to make full contact with the metallic shield. Position long tail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 3). Secure ground braid to cable jacket 4 l/2" (114 mm) from cable semi-con edge using vinyl tape (Figure 3). NOTE: Position vinyl tape with care, it also serves as a marker for positioning the termination. 4 (114 mm) Vinyl Tape Marker Tape Shield Ground Braid Cable Jacket Edge Solder Block 1 ST Scotch Mastic Strip 2230 Semi-Con Edge Figure 3 4 78-8119-6018-2 Rev C

3.3 Wrap ground braid around cable tape shield one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. Wrap spring in same direction as ground braid (Figure 4). Cinch (tighten) the spring after wrapping the final winding. 3.4 Select second Scotch Mastic Strip 2230 from kit and remove white release liners. Apply a second SINGLE WRAP of mastic over solder block on ground braid and previously applied mastic (Figure 4). Cut off excess. Constant Force Spring Tape Shield Ground Braid 1 ST Scotch Mastic Strip 2230 Solder Block 2 ND Scotch Mastic Strip 2230 Trim Cable Tape Shield Ground Braid Leg Figure 4 3.5 Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring and exposed tape shield (Figure 5). NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed. SPECIAL NOTE FOR CLOTH OR PAPER SEMI-CON INSULATION SHIELD In cables with cloth or paper semi-conductive shields, it is recommended the shield be over wrapped with one halflapped layer of highly stretched semi-conductive rubber tape such as Scotch Electrical Semi-Conducting Tape 13. Semi-Con Tape Shield Constant Force Spring Two Half-Lapped Layers of Electrical Grade Vinyl Tape Scotch Mastic Strip 2230 Vinyl Tape Marker Figure 5 78-8119-6018-2 Rev C 5

4.0 Install Lug or Connector 4.1 Check to insure 3M Cold Shrink QT-III Silicone Rubber Termination assembly fits over the selected lug or connector. If lug or connector (Figure 6) will not fit through the termination core, clean the insulation (per Step 5.0) and slide termination on cable before installing lug or connector. DO NOT REMOVE CORE AT THIS TIME. Clearance Connector/Lug Figure 6 NOTE: Refer to pages 19-21 for 3M Connector and Lug crimping information. NOTE: For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Immediately insert conductor into lug or connector barrel as far as it will go. 4.2 Position connector or lug and crimp according to manufacturer's directions. Remove excess oxide inhibitor and sharp crimp flashings following crimping. 5.0 Clean Cable Insulation and Lug or Connector Barrel Using Standard Practice 5.1 Wipe the cable insulation with one of the solvent saturated pads from the 3M Cable Cleaning Preparation Kit CC-2. DO NOT ALLOW SOLVENT TO TOUCH SEMI-CON INSULATION SHIELD! 5.2 If abrasive must be used: a. Use on insulation only. DO NOT USE ABRASIVE ON SEMI-CON INSULATION SHIELD! b. Use only aluminum oxide abrasive; grit 120 or finer, included in the 3M Cable Cleaning Preparation Kit CC-2. c. Be careful not to reduce the cable insulation diameter below that allowed by the kit. 6 78-8119-6018-2 Rev C

6.0 Install Termination 6.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 7). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 7). NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. DO NOT PUSH OR PULL ON THE TERMINATION ASSEMBLY WHILE UNWINDING THE CORE. Counter-Clockwise Vinyl Tape Marker NOTE: The material being removed at this step is mixed polymers and can be recycled with waste. Figure 7 6.2 Connect ground braid to system ground according to standard practice. Correct Installation of Termination on Tape Shielded Cable Vi nyl Tape Marker Ridge at End of High-K Tube Ridge at End of Cable Insulation Shield (Semi-Con) Semi-Con Insulation Shield Stress Controlling Compound Cable Insulation Conductor Envioronmental Top Seal High-K Stress Relief Tube 78-8119-6018-2 Rev C 7

Instructions for Wire Shielded Cable 7.0 Prepare Cable 7.1 Check to be sure cable size fits within kit size range as shown in Table 1. 7.2 Prepare cable using dimensions shown in Figure 8 and 9. Refer to Table 3 for semi-con cutback dimension. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG. NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors as follows: Aluminum Connector Growth Allowance 2-350 1/4 (6 mm) 400-650 " (13 mm) 7501000 3/4" (19 mm) NOTE: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer. Kit Number Insulation 0.D. 15 kv AWG / kcmil 25/28 kv AWG / kcmil 35 kv AWG / kcmil Semi-con Cutback 7685-S-8 1.05" -1.46" (26,7-37,1 mm) 1.24" - 1.80" (31,5-45,7 mm) 500-700 (240-400 mm 2 ) 750-1000 (400-500 mm 2 ) 250-500 (125-250 mm 2 ) 600-800 (300-400 mm 2 ) 3/0-350 (95-150 mm 2 ) 500-600 (185-325 mm 2 ) 13.5" (342,9 mm) 13.0" (330,2 mm) Table 3 Jacket Removal Length Depth Of Terminal Lug + Growth Allowance 3 (76 mm) Semi-Con Cutback Semi-Con Shield Wires Cable Jacket Figure 8 7.3 Bend leading 1 " (38 mm) of exposed shield wires back upon themselves to jacket edge (Figure 9). 1 (38 mm) 3 (76 mm) Cable Jacket Semi-Con Shield Wires Figure 9 8 78-8119-6018-2 Rev C

8.0 Install Ground Braid 8.1 Select a Scotch Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a SINGLE WRAP of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 10). Cut off excess. 1/4" (6 mm) 1 ST Cable Jacket Semi-Con Scotch Mastic Strip 2230 Figure 10 8.2 Position pre-formed ground braid with short tail over wire shield directly adjacent to cable jacket cut edge. Position long tail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 11). Secure ground braid to cable jacket 4 " (114 mm) from cable semi-con edge using vinyl tape (Figure 11). NOTE: Position vinyl tape with care, it also serves as a marker for positioning the termination. 4 (114 mm) Semi-Con Edge Shield Wire Ground Braid Cable Jacket Edge Solder Block 1 ST Scotch Mastic Strip 2230 Vinyl Tape Marker Figure 11 78-8119-6018-2 Rev C 9

8.3 Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. Wrap spring in same direction as ground braid (Figure 12). Cinch (tighten) the spring after wrapping the final winding. 8.4 Select second Scotch Mastic Strip 2230 from kit and remove white release liners. Apply a second SINGLE WRAP of mastic over solder block on ground braid and previously applied mastic (Figure 12). Cut off excess. Constant Force Spring Shield Wires Ground Braid 1 ST Scotch Mastic Strip 2230 Solder Block 2 ND Scotch Mastic Strip 2230 Trim Cable Wire Shield Ground Braid Leg Figure 12 8.5 Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring and exposed shield wires (Figure 13). NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed. 1 (38 mm) Semi-Con Shield Wires Constant Force Spring Two Half-Lapped Layers of Electrical Grade Vinyl Tape Scotch Mastic Strip 2230 Vinyl Tape Marker Figure 13 10 78-8119-6018-2 Rev C

9.0 Install Lug or Connector 9.1 Check to insure 3M Cold Shrink QT-III Silicone Rubber Termination assembly fits over the selected lug or connector. If lug or connector (Figure 14) will not fit through the termination core, clean the insulation (per Step 10.0) and slide termination on cable before installing lug or connector. DO NOT REMOVE CORE AT THIS TIME. Figur e 14 Clearance Connector/Lug Figure 14 NOTE: Refer to pages 19-21 for 3M connector and lug crimping information. NOTE: For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Immediately insert conductor into lug or connector barrel as far as it will go. 9.2 Position connector or lug and crimp according to manufacturer's directions. Remove excess oxide inhibitor and sharp crimp flashings following crimping. 10.0 Clean Cable Insulation and Lug or Connector Barrel Using Standard Practice 10.1 Wipe the cable insulation with one of the solvent saturated pads from the 3M Cable Cleaning Preparation Kit CC-2. DO NOT ALLOW SOLVENT TO TOUCH SEMI-CON INSULATION SHIELD! 10.2 If abrasive must be used: a. Use on insulation only. DO NOT USE ABRASIVE ON SEMI-CON INSULATION SHIELD! b. Use only aluminum oxide abrasive; grit 120 or finer, included in the 3M Cable Cleaning Preparation Kit CC-2. c. Be careful not to reduce the cable insulation diameter below that allowed by the kit. 78-8119-6018-2 Rev C 11

11.0 Install Termination 11.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 15). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 15). NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. DO NOT PUSH OR PULL ON THE TERMINATION ASSEMBLY WHILE UNWINDING THE CORE. Counter-Clockwise Vinyl Tape Marker NOTE: The material being removed at this step is mixed polymers and can be recycled with waste. Figure 15 11.2 Connect ground braid to system ground according to standard practice. Correct Installation of Termination on Wire Shielded Cable Vi nyl Tape Marker Ridge at End of High-K Tube Ridge at End of Cable Insulation Shield (Semi-Con) Semi-Con Insulation Shield Stress Controlling Compound Cable Insulation Conductor Envioronmental Top Seal High-K Stress Relief Tube 12 78-8119-6018-2 Rev C

Instructions for UniShield Shielded Cable 12.0 Prepare Cable 12.1 Check to be sure cable size fits within kit size range as shown in Table 1. 12.2 Prepare cable using dimensions shown in Figure 16, 17 and 18. Refer to Table 4 for dimension [A]. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG. NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors as follows: Aluminum Connector Growth Allowance 2-350 1/4 (6 mm) 400-650 " (13 mm) 7501000 3/4" (19 mm) Kit Number Insulation 0.D. 15 kv AWG / kcmil 25/28 kv AWG / kcmil 35 kv AWG / kcmil Dimension [A] 7685-S-8 1.05" -1.46" (26,7-37,1 mm) 1.24" - 1.80" (31,5-45,7 mm) 500-700 (240-400 mm 2 ) 750-1000 (400-500 mm 2 ) 250-500 (125-250 mm 2 ) 600-800 (300-400 mm 2 ) 3/0-350 (95-150 mm 2 ) 500-600 (185-325 mm 2 ) 13.5" (342,9 mm) 13.0" (330,2 mm) Table 4 12.3 Install constant force spring as shown in Figure 16. Pull shield wires through semi-conductive jacket to leading edge of constant force spring (Figure 16). Depth Of Terminal Lug + Growth Allowance [A] + 1 (38 mm) Constant Force Spring Shield Wires Semi-Conductive Jacket Figure 16 78-8119-6018-2 Rev C 13

12.4 Remove constant force spring. Carefully bend shield wires back upon cable jacket 1 " (38 mm). Cut excess shield wire and discard (Figure 17). 1 (38 mm) Depth Of Terminal Lug + Growth Allowance [A] + 3 (76 mm) Semi-Conductive Jacket Fold Back Shield Wires Figure 17 12.5 Remove semi-conductive jacket to dimension shown in Figure 18. NOTE: To ease jacket removal, install constant force spring as shown in Figure 18 and ring cut 80% through jacket. Remove jacket sections by pulling against constant force spring. DO NOT BELL SEMI-CON JACKET. Remove constant force spring. NOTE: It is imperative to remove all remnants of the semi-conductive jacket, even if the semi-conductive jacket comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer. Depth Of Terminal Lug + Growth Allowance [A] 1 (38 mm) 1 (38 mm) Semi-Conductive Jacket Cut Line Constant Force Spring Fold Back Shield Wires Figure 18 14 78-8119-6018-2 Rev C

13.0 Install Ground Braid 13.1 Select a Scotch Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a SINGLE WRAP of mastic around the cable semi-conductive jacket 1/4" (6 mm) from shield wires (Figure 19). Cut off excess. 1/4 (6 mm) 1 ST Semi-Con Shield Wires Scotch Mastic Strip 2230 Figure 19 13.2 Position pre-formed ground braid with short tail directly over cut edge of folded back shield wires. Position long tail of ground braid, extending over cable semi-conductive jacket with solder block over mastic strip (Figure 20). Secure ground braid to cable semi-conductive jacket 4 " (114 mm) from cable semi-con edge using vinyl tape (Figure 20). NOTE: Position vinyl tape with care, it also serves as a marker for positioning the termination. 4 (114 mm) Solder Block 1 ST Vinyl Tape Marker Shield Wire Ground Braid Scotch Mastic Strip 2230 Semi-Con Edge Figure 20 78-8119-6018-2 Rev C 15

13.3 Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. Wrap spring in same direction as ground braid (Figure 21). Cinch (tighten) the spring after wrapping the final winding. 13.4 Select second Scotch Mastic Strip 2230 from kit and remove white release liners. Apply a second SINGLE WRAP of mastic over solder block on ground braid and previously applied mastic (Figure 21). Cut off excess. Constant Force Spring Shield Wires Ground Braid 1 ST Scotch Mastic Strip 2230 Solder Block 2 ND Scotch Mastic Strip 2230 Trim Cable Wire Shield Ground Braid Leg Figure 21 13.5 Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring and exposed shield wires (Figure 22). NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed. 1 (38 mm) Semi-Con Shield Wires Constant Force Spring Two Half-Lapped Layers of Electrical Grade Vinyl Tape Scotch Mastic Strip 2230 Vinyl Tape Marker Figure 22 16 78-8119-6018-2 Rev C

14.0 Install Lug or Connector 14.1 Check to insure 3M Cold Shrink QT-III Silicone Rubber Termination assembly fits over the selected lug or connector. If lug or connector (Figure 23) will not fit through the termination core, clean the insulation (per Step 15.0) and slide termination on cable before installing lug or connector. DO NOT REMOVE CORE AT THIS TIME. Clearance Figure 23 NOTE: Refer to pages 19-21 for 3M connector and lug crimping information. Connector/Lug NOTE: For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Immediately insert conductor into lug or connector barrel as far as it will go. 14.2 Position connector or lug and crimp according to manufacturer's directions. Remove excess oxide inhibitor and sharp crimp flashings following crimping. 15.0 Clean Cable Insulation and Lug or Connector Barrel Using Standard Practice 15.1 Wipe the cable insulation with one of the solvent saturated pads from the 3M Cable Cleaning Preparation Kit CC-2. DO NOT ALLOW SOLVENT TO TOUCH SEMI-CON INSULATION SHIELD! 15.2 If abrasive must be used: a. Use on insulation only. DO NOT USE ABRASIVE ON SEMI-CON INSULATION SHIELD! b. Use only aluminum oxide abrasive; grit 120 or finer, included in the 3M Cable Cleaning Preparation Kit CC-2. c. Be careful not to reduce the cable insulation diameter below that allowed by the kit. 78-8119-6018-2 Rev C 17

16.0 Install Termination 16.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 24). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 24). NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. DO NOT PUSH OR PULL ON THE TERMINATION ASSEMBLY WHILE UNWINDING THE CORE. Counter-Clockwise Vinyl Tape Marker NOTE: The material being removed at this step is mixed polymers and can be recycled with waste. Figure 24 16.2 Connect ground braid to system ground according to standard practice Correct Installation of Termination on UniShield Shielded Cable Vinyl Tape Marker Ridge at End of High-K Tube Ridge at End of Cable Insulation Shield (Semi-Con) Semi-Con Insulation Shield Stress Controlling Compound Cable Insulation Conductor Environmental Top Seal High-K Stress Relief Tube 18 78-8119-6018-2 Rev C

Tooling Index 30014 thru 30045 One hole Lug and Crimping Information for 3M Scotchlok Copper Lugs 31036 thru 31068 One hole-long barrel 31145 thru 31178 Two hole long barrel Cable Size AWG/ kcmil Stud Size (in.) 3M Scotchlok Copper Lug Number Crimping Tool-Die Sets (Minimum Number Of Crimps) Burndy Corporation MD6 MY29 Y34A Y35, Y39, Y45*, Y46* Thomas & Betts Corporation TBM 5 TBM 8 TBM 15 Square D Co. Anderson Div. VC63, VC6FT** 6 10 1/4 5/16 30014 30015 30016 6AWG U5CRT Blue Blue 4 10 1/4 3/8 30018 30019 30021 W161 4AWG A4CR U4CRT Grey Grey 2 1/4 5/16 3/8 30022 30023 30024 W162 2AWG A2CR U2CRT Brown Brown 33 1 5/16 3/8 30027 30028 1AWG A1CR U1CRT Green Green 37 1/0 5/16 3/8 30031 30032 W163 1/0 A25R U25RT Pink Pink 42H 2/0 3/8 3/8 30036 31036 W241 W241 2/0 2/0 A26R A26R U26RT U26RT Black Black Black Black 45 45 3/0 30041 31041 W243 W243 3/0 3/0 A27R A27R U27RT U27RT Orange Orange Orange Orange 50 50 4/0 30045 31045 31145 BG BG(4) BG(4) 4/0 4/0 4/0 A28R U28RT U28RT U28RT Purple Purple Purple Purple Purple Purple 54H 54H 54H 250 31049 31149 W166(4) 250 A29R U29RT Yellow Yellow 62 300 31053 31153 A30R U30RT White 66 350 31056 31156 A31R U31RT Red(4) 71H(4) 400 31060 31160 A32R U32RT Blue(4) 76H(4) 500 5/8 31066 31067 31166 A34R U34RT Brown(4) 87H(4) 600 31068 31168 U36RT Green(4) 94H(4) 750 31172 1000 31178 Y39, Y45, Y46 U39RT(5) Y45: S44RT(6) Y46: P44RT(6) 106H(4) 125H(4) * Y45 and Y46 accept all Y35 dies ( U series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter. ** Anderson VC63 and VC6FT require no die set. 78-8119-6018-2 Rev C 19

Tooling Index Lug and Crimping Information for 3M Scotchlok Copper/Aluminum Lugs 40016 thru 40079 One hole 40132 thru 40178 Two hole Cable Size AWG/ kcmil Stud Size (in.) 3M Scotchlok Lug Number Burndy Corporation MD6 MY29 Y34A Crimping Tool-Die Sets (Minimum Number Of Crimps) Thomas & Betts Corporation Square D Co. Anderson Div. Y35, Y39, Y45*, Y46* Y1000** TBM 5 TBM 8 TBM 12 TBM 15 VC63** VC6FT** ITT Blackburn Co. Kearny Nat l Div. VC8C** OD58 TYPE O 6 5/16 40016 W161 6AWG A6CAB U6CABT Grey Grey 29 BY19 J 4 5/16 40020 W162 4AWG A4CAB U4CABT Green Green 37 BY53 P 2 3/8 40024 40025 W163 W163 2AWG 2AWG A2CAB A2CAB U2CABT U2CABT Pink Pink Pink Pink 42H 42H BY23 BY23 1 3/8 40028 40029 W163 W163 1AWG 1AWG A1CAR A1CAR U1CART U1CART Gold Gold Gold Gold 45 45 BY23 BY23 1/0 3/8 3/8 40032 40033 40132 W241 W241 W241 1/0 1/0 1/0 A25AR A25AR A25AR U25ART U25ART U25ART Tan Tan Tan Tan Tan Tan 50 50 50 BY25 BY25 BY25 5/81 5/81 5/81 2/0 40037 40137 BG(4) BG(4) 2/0 2/0 A26AR A26AR U26ART U26ART Olive Olive Olive Olive 54H 54H BY31C BY31C 5/81 5/81 3/0 40041 40141 W166(4) W166(4) 3/0 3/0 A27AR A27AR U27ART U27ART Ruby Ruby Ruby Ruby 60 60 737 737 4/0 5/8 40045 40046 40145 W660(4) W660(4) W660(4) 4/0 4/0 4/0 A28AR A28AR A28AR U28ART U28ART U28ART White(4) White(4) White(4) 66(4) 66(4) 66(4) BY35C(4) BY35C(4) BY35C(4) 840(4) 840(4) 840(4) 250 5/8 40049 40050 40149 W249 W249 W249 A29AR A29AR A29AR U29ART U29ART U29ART 71H(4) 71H(4) 71H(4) 71H 71H 71H 300 40053 40153 A30AR A30AR U30ART U30ART 76H(4) 76H(4) 76H 76H 350 5/8 40056 40057 40156 U31ART U31ART U31ART 87H(4) 87H(4) 87H(4) 87H 87H 87H 400 40160 U32ART(4) 94H(4) 94H(4) 500 5/8 40067 40166 U34ART(4) U34ART(4) 106H(4) 106H(4) 106H 106H 600 40170 U36ART(4) 115H 750 5/8 40073 40172 U39ART(4) U39ART(4) 125H(4) 125H(4) 1000 5/8 40079 40178 S44ART(4) S44ART(4) 140H(4) 140H(4) * Y45 and Y46 accept all Y35 dies ( U series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter. ** Anderson VC63, VC6FT, VC8C and Burndy Y1000 require no die set. 20 78-8119-6018-2 Rev C

Tooling Index Crimping Information for 3M Stem Connectors Copper/Aluminum Conductor Size Crimping Table For 3M Stem Type Connector AWG & kcmil 3M Connector Recommended Crimping Tools Number Stranded Solid Manufacturer Mech. Tool Die (Minimum No. Crimps) Hydraulic 2, 1 4 1/0 2/0 3/0 4/0 1, 1/0 2 2/0 3/0 4/0 SC0001 SC0002 SC0010 SC0020 SC0030 SC0040 Die (Minimum No. Crimps) Burndy MD6 BG(4), W243(4) Y35, Y39, Y45* U25ART, U243 Kearny 051, 052 5/81 (4) 12, 20, 40, Ton 5/81(4) T & B TBM 5 Tan T & B TBM 8 Olive TBM 15 50 Anderson VC6 Burndy MD6 W669(0) 840(5) Y35, Y39, Y45* U28ART Kearny 051, 052 840(5) WH1, WH2 840 T & B TBM 8 White(4) TBM 15 66H Anderson VC6 * Y45 and Y46 accept all Y35 dies ( U series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter. ** Anderson VC6 is dieless and does not require a die set. 78-8119-6018-2 Rev C 21

3M, Scotch and Scotchlok are trademarks of 3M Company. UniShield is a registered trademark of General Cable Technologies Corporation. Important Notice All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M's current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M. Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture at the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted. 3 Electrical Markets Division 6801 River Place Blvd. Austin, TX 78726-9000 800.245.3573 Fax 800.245.0329 www.3m.com/electrical Please Recycle. Printed in USA. 3M 2013. All Rights Reserved. 78-8119-6018-2 Rev C