Apex 5000 Positioner

Similar documents
Mounting: The following instructions apply to rotary actuators only. Linear applications require special mounting and coupling (consult factory).

XL90 Series High-Performance Positioner

XL90 Series High-Performance Positioner

CONTROLS INC. Position Indicators. Valve Positioners

PMV P36C AND P41C POSITIONERS ACTUATORS

CENTAC Inlet and Bypass Valve Positioners

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

Type Type 1001 Transducers. I/P & E/P Transducers

Electro-Pneumatic Positioner Series 830/831-WP/EX. Operation & Maintenance Manual

Moniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners.

Installation and Operating Instructions Electro-Pneumatic Rotary Positioner SP-21. Description of Device. Part Number System

Electro-Pneumatic Linear Positioner Installation and Operation Instructions B GB

SP-20 Input. Installation and Operating Instructions Electro-Pneumatic Linear Positioner. Description of Device. Part Number System

Trouble Shooting Guide for V100 Positioner

Type 2000 Transducer Product Instructions

Type Installation, Operation and Maintenance Instructions. Ordering Information. Contents CA20 -

SINGLE-ACTING ACTUATORS FOR DOUBLE-ACTING & SERIES 65 POSITIONERS PNEUMATIC & ELECTRO-PNEUMATIC. The High Performance Company

ABB MEASUREMENT & ANALYTICS DATA SHEET. AV1 and AV2 Characterizable pneumatic and electro-pneumatic positioners

Valtek Beta Positioners for Control Valves

No. 1 GENERAL INFORMATION 3

CONTROLS. Bray Pneumatic Actuators & Accessories. Technical Manual. A Division of BRAY INTERNATIONAL, Inc.

Type Type I/P & E/P Transducers

Spring Cylinder Rotary Actuator

Double Acting & Spring Return. SERIES 92/93 Rack & Pinion PNEUMATIC ACTUATOR. The High Performance Company

Actuators & Positioners Pneumatic Actuators Series UP1/2/3/4/5/6

Electric Modulating Actuator Installation, Operation & Maintenance Manual

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

Operation and Maintenance Instructions Manual BOOSTER. Volume amplifier

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Control Valves Positioner

Control Valves Positioner

Fisher 2506 and 2516 Receiver/Controllers

Valve Positioners Series 760P/E Valve Positioners

Fisher 3570 Pneumatic Valve Positioners

Quarter Master Chief Series 92 Actuator

Product Specification

T-1001 TYPE 1001 I/P & E/P TRANSDUCERS

Fisher 546 Electro Pneumatic Transducer

FAIRCHILD T5220 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

3570 Series Pneumatic Valve Positioners

Features. Flexibility

Pneumatic Positioner RTX - Series USER S MANUAL. ROTEX P/P Ver. 0.1 Dated: MAY / 2009 REV 01: SEP/2010 Page 1 of 16

LIMIT SWITCH Axiom - AX

Type I/P & E/P Transducers

Fisher 4194S Differential Pressure Controllers

Series AV1 / 2 / 4 Characterizable pneumatic positioners

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

Fisher 657 Diaphragm Actuator Sizes and 87

Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual

12 Series Linear Electric Actuator Installation, Operation & Maintenance Manual

M9216 Series Electric Spring Return Actuators

DENISON HYDRAULICS open loop pump controls series P140 A-mod, P260 B-mod service information

Quarter Master Series 94 Actuator

Type 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information.

Fisher 3710 and 3720 Valve Positioners and 3722 Electro-Pneumatic Converter

Valve Positioners Series 760P/E Valve Positioners

Series AV1 / 2 / 3 / 4 Characterizable pneumatic positioners

Fisher 4194A, B, and C Differential Pressure Controllers1 1

Fisher 3610J and 3620J Positioners and 3622 Electro Pneumatic Converter

FAIRCHILD T5200 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

QB4 PRESSURE CONTROL VALVE INSTALLATION & MAINTENANCE INSTRUCTIONS

Actuators & Positioners Characterizable Pneumatic Positioners Series AV1/2/3

Fisher 3710 and 3720 Positioners and 3722 Electro-Pneumatic Converter

OIL FIELD ELECTRIC ACTUATOR INSTRUCTION MANUAL SPECIAL APPLICATIONS ACTUATORS Q 6.0.1

Series 60. New Smart Positioner. Compact design Convenient & powerful function Enhanced reliability

DENISON HYDRAULICS Premier Series. open circuit pump controls P16 B-mod, P09 A-mod. service information

GP1/GP2 INSTALLATION & MAINTENANCE INSTRUCTIONS

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

POSITIONERS and Controls for Complete Valve Automation

SMART VALVE POSITIONER 4 to 20 ma + HART Digital Communication. smar B87

Fisher 3710 and 3720 Positioners and 3722 Electro Pneumatic Converter

Pneumatic Actuator Accessories. Discrete, NEMA 4, Four-Way Air/Air Suffix A2 (For PAD3 & PKD2 actuators)

Title: Installation & Maintenance AP Pneumatic Positioner

FAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

DENISON HYDRAULICS Premier Series. open loop pump controls series P080. service information

V200 Positioner. V200 P Pneumatic Positioner. V200 E Electropneumatic Positioner. Housing Material: Cast aluminium with polyester coating

ABB Automation. Characterizable Pneumatic Positioners Series AV1/2/3/4. Series AV1/2/3/4 Pneumatic Positioners

Fisher i2p 100 Electro Pneumatic Transducer

Actuators & Positioners Models UP1/2/3/4/5/6/7. Universal Pneumatic Rotary Actuators

Accord Logix Series 1000 Digital Positioner

DeZURIK MODELS P41, P41D AND P42 PMV POSITIONERS

ANDCO Eagle Actuator Instruction Manual

Corrosion Resistant Pneumatic Positioners Model 4700P and 4700E

Electro-Pneumatic Positioner YT-1000 / 1050 SERIES

Installation Manual OPEN. For Corrosive Service. The ONYX integrates electronic sensors and pneumatic valving into a vapor tight enclosure.

Valtek XL Series High Performance Positioner. for Control Valves

Electric Actuators Maximum in-lbs

Milwaukee's Electric Actuator Installation, Operation & Maintenance Manual

The Series I/P Current to Pressure Transducer

INSTRUCTION AND MAINTENANCE MANUAL GC31 COMMANDAIRE POSITIONER

Electric Actuators Maximum in-lbs

Powers TM Controls EA 338 Electronic Actuator

2506 Series Multi-Trol Receiver/Controllers (Types 2506, 2516, 2516F)

Fisher 4194HS Differential Pressure Indicating Controllers

RTX1000 SERIES ELECTRO-PNEUMATIC POSITIONER

ECON ELECTRIC ACTUATOR Fig ELA60 Ex

Type 1051 and 1052 Size 33 Diaphragm Rotary Actuator

TZIM. Electropneumatic Analog Positioner 10/ EN

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

Instruction. MI June E69F Current-to-Pneumatic Signal Converter

Transcription:

Apex 5000 Positioner Principles of Operation: The Apex 5000 positioner causes rotation (or linear movement) of valve actuator in proportion to an input signal. This signal may take the form of pneumatic pressure (Model 5000) or electric current (Models 5100, 5200, 5300, 5400 and 5600). Supply pressure is directed to the actuator through a precision spool valve. As input pressure is varied, the balance beam shifts away from its neutral position. The spool also shifts and a differential pressure is created across the actuator causing rotation (of linear movement). Rotation is fed back through the positioner shaft and cam. Cam rotation causes rotation of both follower arm and feedback arm about their respective pivot pins. Rotation of feedback arm changes compression in the spring which forces the balance beam and spool back to their neutral positions. This shuts off the flow of air to the actuator and rotation stops. Installation: The Apex 5000 positioner can be installed on rotary and linear actuators. Actuators can be either double acting or spring return. Positioners can be set up for rotation in either direction (direct or reverse acting). Supply Air Requirements: Air pressure must be limited to 120 psi for supply and 50 psi for instrument signal to avoid damage to the positioner. Supply air must be clean, dry, and oil free instrument quality air in accordance with ISA S7.3 specifications (dew point >18 degrees below ambient temperature, particle size <5 microns, oil content <1ppm). Mounting: The following instructions apply to rotary actuators only. Linear applications require special mounting and coupling. 1. Mount bracket to actuator. Tighten bolts finger tight only at this time. 2. Install coupler (if required) on actuator shaft making sure it is centered. 3. Verify that orientation of actuator and coupler flats matches positioner shaft flats. If necessary, rotate the cam before installing positioner (see Cam Installation ). 4. Install positioner onto bracket. Make sure positioner shaft and coupler are engaged and centered. Tighten bolts finger tight only at this time. Pneumatic Connections: The supply and both output ports are female 1/4" NPT. The instrument port is female 1/8" NPT. All positioners are supplied with either gauges or pipe plugs in the gauge ports. All connections require usersupplied tubing fittings. Caution: Do not use Teflon tape as a pipe thread sealant. Use only a liquid or paste nonhardening pipe sealant on the threads. 5. Connect positioner ports 1 and 2 to actuator. Port 2 is always connected to the actuator port used to drive actuator away from its start or fail position (the factory cam setting is full clockwise at minimum input). Port 1 is connected to the opposite port or may be plugged for spring return actuators. Note: For fail counterclockwise applications, the cam must be flipped over so the R side is up (see Cam Installation ). 6. Connect supply air to the port marked S. 7. Connect instrument signal air to the port marked I for model 5000. For models 5100, 5200 or 5400, connect 4-20 ma and(-). For intrinsically safe applications (Model 5400 only), see Figure 1 for barrier requirements and schematics. The I/P is factory calibrated and should not require adjustment. See I/P Module Calibration if adjustments are necessary. 8. Stroke actuator/valve two or three times to align positioner, coupler and actuator. With 50% input (actuator/valve at 45 degrees), tighten all mounting bolts. Stroke actuator/valve again to verify there is no misalignment throughout stroke. Page 1 of 8

Cam Installation: Introduction: The standard cam features linear, 90 degree operation for full 3-15 psi input, 3-9 and 9-15 psi split ranges, and 3-15 psi 180 degree operation. The factory setting is 3-15 psi, 90 degrees, with D (direct) side up for full clockwise position at 3 psi. Caution: Be sure supply air pressure is removed and no pressure exists in actuator before adjusting cam. Cam Removal: With a wrench on the output shaft (if necessary), loosen and remove the jam nut. Remove pressure from feedback arm by pushing it away from cam. Remove cam. Cam Installation: 1. Be sure shaft is properly aligned with coupler or actuator. 2. Push feedback arm away from shaft to avoid pressure on cam. 3. Place cam over shaft. Make sure D is showing for direct acting or R is showing for reverse acting. 4. Align hole at start of desired range with bearing. 5. Tighten jam nut making sure cam does not rotate. Use a flat-bladed screwdriver to prevent cam rotation. Calibration: Caution: Cam pinch points may injure fingers. Be sure to avoid placing fingers and other objects in cam pinch points. Also avoid touching balance beam and spool while making adjustments as unpredictable cam rotation may result. Finally, maintain control of input signal while making adjustments. 1. Start with cover removed, supply air connected, and a 3 psi (4 ma) input signal. 2. Loosen jam nut on zero adjust screw. 3. Turn zero adjust screw to rotate actuator/valve to desired start or fail position. Loosening screw moves actuator/valve away from start or fail position towards end position. 4. Change input signal to 15 psi (20 ma). 5. Loosen span adjust lockscrew (larger screw on span adjust assembly). 6. Turn span adjust pinion to rotate actuator/valve to desired end position. Counterclockwise rotation moves slide towards cam which moves actuator/valve towards start or fail position. Retighten lockscrew to lock setting. 7. Repeat steps 3 through 7 as necessary. Note: The Apex 5000 positioner is designed so that span adjustment does not affect zero setting. However, zero setting may be affected slightly because of manufacturing tolerances and/or zero setting itself. 8. While holding zero knob to prevent rotation, tighten jam nut to lock setting. 9. Replace cover. Gain Adjustment: Introduction: The Apex 5000 positioner features an adjustable gain. This feature can be used to tune positioner performance to specific applications. The adjustment primarily affects sensitivity, but also may affect overshoot and speed (to a minor extent). For most applications, especially medium and large-sized actuators on valves with resistive closure members (ball and plug valves), the factory setting of maximum gain should be used for maximum sensitivity and quick response. For smaller actuators or actuators on low resistance closure members (butterfly valves and dampers) lower gain may improve performance by reducing overshoot. This also tends to reduce sensitivity. On applications using the low flow spool valve, the maximum gain setting is suggested. 1. Remove cover and loosen gain adjust lockscrew. 2. Move gain adjust assembly by holding the tab and pushing towards balance beam (to decrease gain) or away from balance beam (to increase gain). The triangle adjacent to adjustment assembly indicates effective ends of adjustment travel when lined up with fillet closest to tab. 3. Tighten lockscrew to lock setting and replace cover. 4. Important: Check positioner calibration after making gain adjustments. Page 2 of 8

Maintenance: The Apex 5000 positioner is designed for long life and trouble-free operation. The following steps should be followed every six months to assure proper operation. 1. Check air supply and associated filtration equipment. See Supply Air Requirements. 2. Make sure arms, bearings, and adjustment screws move freely. Caution: Moving parts to check freedom with supply pressure connected will cause rotation of cam. Be sure to keep fingers away from cam pinch points. If parts do not move freely, disassemble and lubricate with a light, instrument grade grease (Lubriplate MAG 1 or equivalent). 3. Check for smooth operation of the spool valve. If it sticks or feels gummy, remove it and clean both spool and valve bore with solvent. Make sure both parts are clean and dry before reinstalling. Do NOT apply grease to these parts. 4. Check for air leaks in air supply. 5. Refer to Troubleshooting sections if maintenance does not cure a problem. Troubleshooting: Problem Probable Cause/Solution Actuator/Valve won t stroke or 1. Positioner ports are connected to wrong sides of actuator. goes full stroke with no control: 2. Cam on wrong side (see Cam Installation ). 3. Stuck arm or spool valve (see Maintenance ). 4. Input section problem (see I/P Module Troubleshooting ). Calibration Shifts: 1. Loose mounting hardware. 2. Loose cam nut. 3. Loose lockscrews/nut. Excessive air consumption (other 1. Spool valve gasket leaking or loose screws. than normal exhaust of 10-30 scfh): 2. Air leak between positioner/actuator or within actuator. 3. If condition occurs at end of stroke only, calibration is incorrect. Oscillation or hunting: 1. Air leak between positioner/actuator or within actuator. 2. Oversized spool valve (decrease size). 3. Gain setting too high (see Gain Adjustment ). Sluggish or slow response: 1. Undersized spool valve (increase size or add volume boosters). 2. Gain setting too low (see Gain Adjustment ). 3. Tubing restriction (check supply between positioner/actuator). 4. Tubing too small (increase tubing size). I/P Module: General: All I/P Modules are factory calibrated and should not require adjustment. However, long-term storage or storage in temperature extremes may affect calibration. The factoryinstalled pressure gauge may be used for calibration, but accuracy is limited (+/- 3 percent). Ordering Information: The Apex 5000 Modular Positioning System (AMPS) allows easy field installation of four input options. Specify the following for changeover kits (Kits include modules, mounting hardware [if necessary], fasteners, and o-ring seals): KM50 - Change I/P Module input to 3-15 psi pneumatic input. KM51 - Change to Model 5100 I/P Module. KM52 - Change to Model 5200 I/P Module. KM53 - Change to Model 5300 I/P Module. KM54 - Change to Model 5400 I/P Module. KM56 - Change to Model 5600 I/P Module. Page 3 of 8

Electrical Specifications: Parameter Model 5100 Model 5200 Model 5300 Model 5400 Model 5600 Max. Voltage VDC 30 30 28 30 28 Min. Voltage VDC 6 5.5 5.5 5.5 5.5 Max. Current (ma) 50 125 93.3 125 93.3 C (Micro Farad) 1 1 1 1 1 L (Mili Henry) 1 1 1 1 1 Hazardous Locations Exp. Proof Exp. Proof Intrinsically Safe Intrinsically Safe CL l,ll, Div 1 EEx d llb+h2 CL l,ll Div 1 EEx ia llc T4 Non-incendive T6-40 to +40C Groups B-G CL l, Div 2 T5-40 to +75C Groups A-D T4-40 to 110C Agency Approval FM/CSA SCS FM/CSA SCS Class I, Division 2, Applications must be installed as specified in NEC Section 501-4 when barriers are not used. (Refer to ANSI/ISA RP12.6 for guidance on installation). Field Installation: All input options can be added/changed in the field without removing positioner cover. Figures 3 and 4 (5100 and 5200/5600 respectively) show mounting information and location of terminal connections. Caution: If I/P Module is installed in explosive atmosphere, disconnect power prior to removing cover to avoid personal injury. 1. Remove supply pressure and input signal connection. 2. Remove old I/P Module or pneumatic manifold and associated hardware. 3. Following applicable figure, install new I/P Module and associated hardware. Be sure o-rings are in place. 4. Make electrical and pneumatic connections. Do not use Teflon tape on supply connection fitting. Use only a liquid or paste non-hardening pipe sealant on the threads. 5. For intrinsically safe applications (Model 5400 only) refer to Figure 1 for barrier information and schematics. 6. All I/P Modules are factory calibrated and should not require adjustment. However, it is recommended that calibration be checked (see I/P Module Calibration ). 7. Install cover. Page 4 of 8

I/P Module Calibration: Caution: If I/P Module is installed in explosive atmosphere, disconnect power prior to removing cover to avoid personal injury. Figures 3 and 4 (5100, and 5200-5600 respectively) show the locations of zero and span adjustments. 1. Start with cover removed, supply pressure connected, and a 4 ma input signal. 2. Turn zero potentiometer (pot) until I/P Module gauge reads 3 psi. 3. Change input to 20 ma and turn span pot until I/P Module gauge reads 15 psi. 4. Zero and span adjustments are interactive, so repeat steps 1 thru 3 as necessary. 5. Replace cover. I/P Module Troubleshooting (Model 5100 only - consult factory for 5200 & 5400): Problem Probable Cause/Solution I/P Module does not build up full output pressure 1. Improper zero/span setting. regardless of input: 2. Low bias (see Bias Adjustment ). 3. Air leakage (check O-Rings & pneumatic diaphragm). 4. Low air supply. 5. Low regulator output (see Regulator Adjustment ). I/P Module does not build up any pressure (or does not build up over bias pressure): Circuit Board LED not lit: 1. Loose, shorted, or reversed signal connection. 2. Coil connection reversed. 3. Controller board not responding (replace board). Circuit Board LED lit: 1. Low bias pressure (see Bias Adjustment ). 2. Air leakage (check o-rings & pneumatic diaphragm). 3. Bad coil connection or bad coil. 4. Dirty or plugged I/P Module filter (clean or replace). I/P Module puts out excessive pressure at 4 ma: 1. Improper zero/span setting. 2. High bias (see Bias Adjustment ). I/P Module output fluctuates: 1. Air leakage (check o-rings & pneumatic diaphragm). 2. Zero or low bias pressure (see Bias Adjustment ). Bias Adjustment: With supply pressure connected and no input signal, the I/P Module should put out between 2 and 2 1/2 psi. If necessary, turn the bias adjust setscrew (CW to increase, item 20 figure 3). Regulator Adjustment: With supply pressure connected and input adjusted to 24 ma or 125 percent, the I/P Module pressure should be between 18 and 20 psi. If necessary, turn Electrical Output (Feedback) Options Base No. Add Cam Option Suffix Options - Description KMA A-Std. Linear Cam F - 4-20 ma Transmitter KMA B-30,45,60,90 G - 1K OHM Feedback Pot. KMA C-Characterized H - 10K OHM Feedback Pot. KMS D-60 for butterfly valve K - 2-SPDT Mechanical Sw. KMS M - 2-SPST Proximity Sw. KMS N - 2-SPDT Proximity Sw. the regulator setscrew (CW to increase, see figure 3). This adjustment may affect bias pressure, recheck bias pressure after making adjustment. Apex Modular Positioning System (AMPS) Options: The Apex 5000 positioner is also designed to accept modular output accessories. These bolt on easily and require no housing modification. The following is a list of part numbers to specify when ordering. Part Number KMFC KMBB KMBBFC Pneumatic Output Options Description Flow Control Module Block/Bleed Module (Manual Override + lock-out) Flow Control + Block/Bleed Modules Page 5 of 8

FIG. 2 Bill of Material Item Part # Description No. Req d 1 Housing 1 2 XA0092 Balance Beam Assembly 1 2A Hinge Spring 2B Feedback Spring 3 XM0121 Hinge Spring Block 1 4 XM0112 Hinge Spring Nut 1 5 X00462 6-32 x 7/8 FHS 2 6 XA0089 Spool Valve Assembly (HF) 1 (LF - XA0091; MF - XA0103) 7 X00452 Spool Valve Gasket 1 8 X00449 Spool Clip 1 9 101920 8-32 x 3/4 RHS 2 10 X00444 Signal Diaphragm 1 11 X00245 Diaphragm Washer 2 12 X00465 Seal Screw 1 13 X00428 Diaphragm Cover 1 14 105330 6-32 x 1/2 PHS 4 15 103603 O-Ring 2 16 XM0105 Manifold 1 17 X00257 8-32 x 5/8 PHS 4 N0. Item Part # Description Req d 18 X00461 8-32 x 1/4 PHS 1 19 XA0093 Gain Adjustment Asmbly. 1 20 XM0122 Gain Adjstmt. Slide Pin 1 21 XA0100 Zero Arm Assembly 1 21A Zero Adjustment Screw 21B Jam nut (1/4-28) 22 X00474 Washer 2 23 X00471 E-Clip 2 24 XA0090 Span Arm Assembly 1 24A Pinion 24B Lockscrew 25 XM0106 Shaft (Standard) 1 26 X00455 Snap Ring 1 26A X00625 Snap Ring 1 27 XM0077 Cam (Linear) 1 28 102476 Jam Nut (3/8 x 16) 1 29 X00359 Flat Rotor OPT 30 SPCF Flat Cover Assembly OPT 30A X00457 O-Ring 1 30B X00456 Cover Screw 4 30C X00454 Washer 4 31 SPCP Pharos Cover Assembly OPT 31D 102258 O-Ring 1 31E SXLROTOP Pharos Rotor 1 31F 104010 Pharos Dome 1 32 X00121 Pharos Adapter OPT 33 X00464 Vent Screen 1 34 X00463 Conduit Plug 1 Page 6 of 8

FIG. 3 Model 5100 I/P Transducer Bill of Material No. Item Part # Description Req d 1 Housing 1 2 X00486 O-Ring 1 3 XM0092 Filter/Regulator Spool 1 4 X00435 Filter 1 5 X00487 O-Ring 1 6 XM0093 Filter Cover 1 7 X00133 O-Ring 1 8 X00488 Spacer 1 9 X00120 Regulator 1 10 XM0114 Regulator Cover 1 11 101921 6-32 x 3/8 PHS 2 12 X00489 Coil Spacer 1 13 X00214 O-Ring 1 14 XA0016 Coil Assembly 1 15 X00054 Spider Diaphragm 1 No. Item Part # Description Req d 16 X00108 Washer 4 17 X00351 Bias Spring 1 18 XM0115 Coil Retainer 1 19 X00466 6-32 x 1/4 PHS 6 20 X00358 1/4-28 Set Screw 1 21 101263 O-Ring 1 22 XA0094 PCB Assembly 1 23 X00216 8-32 x 1/2 PHS 1 24 102304 8-32 x 1 1/4 PHS 4 25 103603 O-Ring 2 26 X00096 Gauge 1 27 X00491 O-Ring 1 28 XM0083 Cover 1 29 X00360 Cover Screw 4 Page 7 of 8

Model 5200-5600 I/P Transducer SPAN ADJ. TERMINAL BLOCK ZERO ADJ. OUTPUT GAUGE FIG. 4 Page 8 of 8