SMT-AZC INSTALLATION / OPERATION MANUAL

Similar documents
SMT-150 Installer Manual

ZoneTouch V2 Zone Control System Installation Manual

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output

Digital Room Thermostats with Touch Screen LCD

SE8300 Series Installation Guide 24 Vac Low Voltage

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data

ASSEMBLY INSTRUCTIONS ZONE MODULE 2 1 THERMOSTAT DESCRIPTION POWER SUPPLY AIRZONE CONTROLLER

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

SetPoint 501 and 501s Controllers Installation and Operation Manual

SLIMZONE CLASSIC /

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

BAPI-Stat 3 Room Sensor

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

Description. functions including single duct pressure dependent or pressure independent systems.

Combined Ventilation Controller RVWS-T-224HA

Safety & Installation Instructions

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor

RDG160TU Commercial Thermostat

1 Overview. 2 WPT Installation. WPT Installation Manual Document No , Rev 17. Wireless Pneumatic Thermostat- WPT-800 Series

R.A.D. Remote Activated Diffuser WIRELESS DIFFUSER CONTROL. 448 South Main Street / Verona, WI / (608)

Cooling mode. Temperature adjustment button. Override button. 24 VAC COM AN1 COM OPEN CLOSED T2/AN2 T2/COM T3 T3 COM SENSOR COM C-Over COM NSB

Installation, Service, and Troubleshooting Instructions

Installation and User Manual. with RAIN SENSOR.

Salt 1 Pocket Salinity Tester Instruction Manual

Deadband Wireless Pneumatic Thermostat- WPT-800-DB Series

A419ABG-3C Electronic Temperature Control

SE8300 Series Installation Guide 24 Vac Low Voltage

Water Specialist EE Control Valve Programming and Cover Drawing Manual

EXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE

EC20 Pocket Conductivity Tester Instruction Manual

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

ECscan30 Pocket Conductivity/TDS Tester Instruction Manual

ECscan20 Pocket Conductivity Tester Instruction Manual

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure

WPT Installation Manual. Wireless Pneumatic Thermostat- WPT-800 Series. 1. Overview. 1.1 Parts Included. 1.2 Prerequisites for Installation

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

Owner s Guide PROCOMP

RC-DO. Room controllers with display and manual forced ventilation function

PCT-3001 plus. Display LCD

TZT-701 Thermostat Installer Manual

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

KTM 690 TTV UPGRADE INSTRUCTIONS

T158 Series. Application. Digital, Three-Wire Floating/On-Off Thermostat/Controller General Instructions. Features

User Manual Solar Charge Controller 3KW

ALC-PRM-VFC. Ceiling Mounted Photocell. Product Guide. Overview. Features

User Manual JS-ICON. 624 ARCH Dimmer Rack. JOHNSON SYSTEMS INC. Spring

Owner s Guide APS596Z

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

SetPoint 150 Controller Installation Manual

TM-9100 Series Room Command Module

Advanced Outdoor Airflow Control, DCV Control and Alarm Solution for OA Applications Document Name: QG_EAC1100_A_R3A

Metasys Zoning Package Installation

DFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR

PHscan30S Pocket ph Meter Instruction Manual

- Data Brochure D 156. Difference Setpoint Control 156. Item 06/10

YCCS TE-6800 Series Temperature Sensors

USER GUIDE. Model RH10 Hygro Thermometer. Humidity and Temperature Meter

Digital Formaldehyde Meter

MT-1 Tracer Meter. RENOGY MT-1 Tracer Meter for Duo Battery Charge Controller E. Philadelphia St., Ontario CA

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual

PIR Ready VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications (Issue Date June 12, _R2)

Zonestar Installation Manual

EVG1200W/10A PHplus-R3

Installation and Maintenance Manual IM

SE7200 Series Installation Guide

Water Specialist EI Control Valve Programming and Cover Drawing Manual

SERVICE MANUAL STARTER 2100 Bench ph Meter STARTER 3100 Bench ph Meter STARTER 3100C Bench ph Meter

SERVICE MANUAL (DOMESTIC & INTERNATIONAL)

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

AUTOMATIC 12 WAY HEAT TREATMENT CONSOLE

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

GENERAL INFORMATION. H-1649, H-1650, H-1651 H-1653, H-1654 Easy-Count. uline.com. that may hurt accuracy:

ECscan40 Pocket Conductivity/TDS/Salinity Tester Instruction Manual

IRRIGATION CONTROLLER

DIFFERENTIAL THERMOSTAT

User manual Temperature Calibrator JOFRA CTC-140/320/650 A/B JOFRA CTC-1200 A Copyright 2005 AMETEK DENMARK A/S ( UK)

INSTALLATION AND OPERATION INSTRUCTION

Marin Control Digital

EC1 Pocket Conductivity Tester Instruction Manual

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

Liebert GXT MT+ User Manual VA Installer/User Guide

PowerView PV380-R2 Mechanical Configuration

Dusty / Dusty Ex. Low-Cost Broken Bag Detection. Operating Instructions. SWR engineering Messtechnik GmbH

DT304. Digital Temperature Logger INSTRUCTION MANUAL

MAGPOWR Spyder-Plus-S1 Tension Control

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

! WARNING To avoid risk of electrical shock, personal injury, or death, disconnect power to range before servicing, unless testing requires power.

USER GUIDE Digital Thermostat GUIDE D UTILISATION Thermostat digital Bedienungsanleitung Termostato digital 50-72

CA 180 Owner's Manual

ECL Apex 10. User Guide. ECL Apex 10 *087R9745* Installation and configuration. *vijem102*

EconoMi$er, Power Exhaust, and Sensor Installation Instructions

Instruction Manual MINI IRRIGATION CONTROLLER.

PC60 Premium Multi-Parameter Tester (ph/ec/tds/salinity/temp.) Instruction Manual. APERA INSTRUMENTS, LLC V6.4

SAX Electronic Valve Actuator

DPS/MPS/RAH/RPS/SWP Space Sensor

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

Farm Hand Vent Master 24

Transcription:

SMT-AZC INSTALLATION / OPERATION MANUAL 22o OFF VERSION 2.0 www.smarttemp.com

INTRODUCTION The SMT-AZC thermostat is designed to work with the Smart Temp 24Volt Zone Dampers TERMINAL DESIGNATIONS The SMT-AZC has dedicated screw terminals located on the subbase to facilitate ease of wiring to the actuator Please take time to read and understand this manual so that installation and testing is undertaken in an efficient and effective manner. Although great care has been taken in the preparation of this manual, Smart Temp takes no responsibility for errors or omissions contained herein. It is the responsibility of the installer to ensure that this thermostat and the equipment connected to it operate in a safe and efficient manner. Due to ongoing product improvement, Smart Temp reserves the right to change the specifications of the SMT-AZC without notice. All right reserved. Smart Temp Australia Pty Ltd Intellectual rights apply. SMT-AZC SUBBASE C R PO PC DS DS Y W A B DISASSEMBLY Insert a small coin in the release slot located on the bottom of the thermostat. Gently twist the coin to release the thermostat from the subbase. Avoid twisting the case, as this may stress the LCD and cause it to crack or bend the terminal pin connectors. C R PO PC DS DS Y W A B 24 Volt Common 24 Volt Hot Power Open Power Close Duct Sensor Duct Sensor Not Applicable in Aust Not Applicable in Aust Modbus Modbus

THERMOSTAT LOCATION The SMT-AZC should be installed in a location that represents the ambient space temperature. Do not install the thermostat in an area where drafts are present, near the floor, behind doors or on an external wall. Avoid placing the thermostat in areas where the air movement is limited, affected by direct sunlight or other areas not typical of the temperature in the space. Do not over-tighten the terminal screws. Check to see that all wires are landed correctly and dressed properly to prevent any shorts. SWITCH FUNCTIONS The SMT-AZC contains a set of dip switches numbered 1 through 8. Only dip switches 1, 2, 3 and 6 are active. MOUNTING THE SUBBASE When mounting the SMT-AZC, be aware that drafts may travel down wall cavities and enter the back of the thermostat through the control wire hole in the wall. It is important to seal the hole to prevent any drafts that might affect the internal temperature sensor. ON 1 2 3 4 5 6 7 8.......... C R PO PC DS DS Y W A B Pull the control wires through the large opening in the thermostat subbase then level and mount the subbase on the wall using the supplied anchors and screws. Do not over-tighten the mounting screws as the subbase may warp causing improper seating of the thermostat connecting pins to the terminal blocks. Use a properly sized screwdriver and land each wire to its dedicated terminal. Switch 1 - Switch 1 is used to lock the thermostat after setup is completed. When the thermostat is locked (ON position) a padlock icon will show on the LCD. When locked, only setpoint changes and status functions can be accessed by the user. Do not set Switch 1 in the ON position until all setup functions are completed. Switch 2 - Switch 2 is used to display the space temperature, duct temperature and setpoint in Celsius (ON position) or Fahrenheit (OFF position). Select Celsius or Fahrenheit before proceeding to the thermostat setup menu. Switch 3 - Switch 3 is used to select two-position (ON position) or fully modulating (OFF position) damper control to best suit the specific application requirement. Switch 6 - Must be ON for Australia

Model SZ-PS 24Vac Plug Pack Ducting From Heating / Cooling Equipment Damper To downstream vents Upstream Sensor Smart Temp Belimo LM24T Actuator 1 2 3 C R PO PC DS DS Y W A B 24Vac Damper Sensor Cool/Heat Modbus SMT-AZC Zone Control Thermostat SW 1= OFF SW 2 = ON SW 3 = OFF SW 4 = NA SW 5 = NA SW 6 = ON SW 7 = NA SW 8 = NA

KEY FUNCTIONS ATTACHING THERMOSTAT TO THE SUBBASE A B C D E F A = ON/OFF KEY - When the SMT-AZC is not locked, this key allows the thermostat to be turned ON or OFF. When in the OFF position, the damper is also driven closed. B = STATUS KEY - Pressing the STATUS key displays the UNIT number, ZONE number, DUCT temperature and DAMPER position. When attaching the thermostat to the subbase, first place the hinged access cover on by fitting the plastic molded pins into the grooves at the top of the thermostat. Carefully align the two standoffs located at the top of the thermostat with the slots in the top of the subbase. Allow the thermostat to swing downward and gently push until the connector pins are fully seated into the terminal blocks. SETUP C and D = UP and DOWN KEYS - These keys are used to increase or decrease the setpoint as well as change thermostat setup values. E = SETUP KEY - This key is used to toggle through the thermostat setup menu. F = ENTER KEY - This key is used to enter changes as well as exit the setup menu. FIGURE 1 Apply 24 Volts power to the thermostat. The LCD will momentarily display all icons. (Figure 1)

ENTERING THE SETUP MENU Press twice and hold the SETUP key until the word DAMPER appears on the LCD. (Figure 2) SETTING THE MAXIMUM DAMPER POSITION LCD will display the maximum damper position for heating and cooling. The factory default is 100% which means the damper can drive fully open with a call for heating or cooling. Position may be adjusted in 10% increments using the UP and DOWN keys. (Figure 4) FIGURE 2 SETTING THE MINIMUM DAMPER POSITION LCD will display the minimum damper position. The factory default is 10% which means the damper is driven 90% closed after a heating or cooling call is satisfied. Press the UP and DOWN keys to change the minimum damper position. Position may be adjusted in 10% increments. (Figure 3) FIGURE 4 SETTING A UNIT NUMBER LCD will display the word UNIT. The factory default is 00. This number can be used to assign the SMT-AZC to a particular HVAC unit. Use the UP and DOWN keys to assign a UNIT number from 00 to 99. (Figure 5) FIGURE 3 FIGURE 5

SETTING A ZONE NUMBER LCD will display the word ZONE. The factory default is 00. This number can be used to identify each SMT-AZC thermostat Network or when used in multiple stand-alone applications. Use the UP and DOWN keys to assign a ZONE number from 00 to 99. (Figure 6) SETTING THE COOLING LIMIT LCD will display the cooling limit. The factory default is 68 F. Press the UP and DOWN keys to change the cooling limit setting. It is strongly recommended that the limit not be set below the factory default setting. (Figure 8) LIMiT 20 o COOL FIGURE 8 FIGURE 6 SETTING THE HEATING LIMIT LCD will display the heating limit. The factory default is 24 C. Press the UP and DOWN keys to change the heating limit setting. It is strongly recommended that the limit not be set above the factory default setting. (Figure 7) SETTING THE ACTUATOR SPEED LCD will display the actuator speed. The factory default is 90 seconds which is the time it takes the actuator to drive the damper blade fully open or fully closed. This is a critical step in the SMT-AZC setup since the thermostat can be used with a variety of 24 Volt actuators. If you are unsure of the actuator speed, place the actuator in the fully closed position and then apply 24 Volts to common and normally open. The time it takes to drive the damper blade fully open equals the actuator speed setting. (Figure 9) LIMiT HEAT 24 o FIGURE 7 When using Smart Temp Model LMU-24T set speed to 45 Seconds FIGURE 9

SETTING THE MODBUS ADDRESS LCD will display the Modbus communications address. The factory default is 01. The SMT-AZC has integrated Modbus communications capability for remote monitoring and control. For more information on Modus Communications, contact Smart Temp at (03) 9763 0094 or info@smarttemp.com.au (Figure 10) TEMPERATURE CALIBRATION OFFSET LCD will display the temperature calibration offset. The factory default setting is 0. Typically, it is not necessary to adjust the temperature calibration offset as the SMT-AZC has been factory calibrated. If calibration is necessary, a high quality electronic digital thermometer must be used. Place the thermometer sensor probe next to the thermostat sensor and allow five minutes before comparing the temperature readings. Use the UP and DOWN keys to adjust the temperature calibration. The range is +/- 10 C. (Figure 11) FIGURE 10 FIGURE 11 SENSOR LOCATION

SAVING SETTINGS AND EXITING THE SETUP MENU Press the ENTER key and the SMT-AZC will save the setup menu settings and exit the program. The LCD will display the space temperature along with other normal operating functions. To review the thermostat settings, simply press and hold the SETUP key until the setup menu is displayed and then toggle through the settings. Press the ENTER key to exit the setup menu. Remove the thermostat from the subbase and set Switch 1 in the ON position to lock the thermostat which will prevent setup changes from being made. When the thermostat is locked, a padlock icon will be displayed on the LCD. (Figure 12) 22 o CHECKING THERMOSTAT STATUS POINTS After the thermostat is locked and operational, its status functions can be checked by pressing the STATUS key twice and toggling through the following status points: UNIT - Displays the HVAC unit number assigned to thermostat. ZONE - Displays the thermostat zone number. DUCT - Displays the duct temperature. DAMPER - Displays the damper position in one degree increments. (0% = fully closed and 100% = fully open) THERMOSTAT OPERATION The SMT-AZC is designed to provide accurate but simple temperature control for the user. When the thermostat is not calling, only the space temperature is displayed on the LCD along with the padlock icon that confirms the thermostat setup functions can not be changed. The user can use the UP and DOWN keys to change the thermostat setpoint within the setpoint limits and review the status points by pressing the STATUS key. (Figure 13) FIGURE 12 HELPFUL HINT If it is necessary to exit the setup menu before all setup functions are completed, simply press the ENTER key and all settings will be saved. To re-enter the setup menu, press and hold the SETUP key until the word DAMPER appears and then continue pressing the SETUP key to toggle through the functions to where you left off. 22 o FIGURE 13

CHANGING THE SETPOINT When the UP and DOWN keys are pressed, the thermostat will display the word SET. The setpoint then can be changed within the setpoint limits. (Figure 14) ADVANCED FUNCTIONS DAMPER POSITION OVERRIDE The SMT-AZC has a damper position override feature to assist in air balancing and bypass damper setup. With the thermostat unlocked, press twice and hold the SETUP key until the word DAMPER appears on the LCD. (Figure 15) 22o SET FIGURE 14 FIGURE 15

OVERRIDE TO OPEN Press the UP and DOWN keys until the word OPEN appears on the LCD and then press the ENTER key. The damper will drive open and remain in the open position until the override is cancelled. (Figure 16) CANCELLING THE DAMPER OVERRIDE In order for the SMT-AZC to control normal damper operation, the override must be cancelled. Press and hold the SETUP key until the word DAMPER OPEN or DAMPER CLOSE appears on the LCD. Use the UP or DOWN key until only the word DAMPER is displayed and then press the ENTER key. The thermostat will then resume normal operation. Figure 18) FIGURE 16 OVERRIDE TO CLOSE Press the UP and DOWN keys until the word CLOSED appears on the LCD and press the ENTER key. The damper will drive closed and remain in the closed position until the override is cancelled. (Figure 17) FIGURE 18 SMT-AZC SPECIFICATIONS FIGURE 17 Input Voltage 24 VAC 50/60 Hz Relay Rating 24 VAC @ 1Amp per relay Operating Temperature 23 F to 122 F Operating RH 0-95% (non-condensing) Size 4-7/16 W x 4-1/16 H x 7/8 D LCD Display Size 2-3/4 W x 1-7/8 H Temperature Sensor 10K NTC type 3 Accuracy +/- 1 F @ 77 F Display Resolution 1 F Control Range 36 F to 96 F Back Light Blue EL (Electro Luminescent) Back Light Life 3,000 hours to half brightness Communications Protocol Modbus Approvals FCC (Part 15) (Pending) C-tick Warranty 3 Years 06-1050-051410