SVX-Series Solenoid Actuated Diesel Engine Air Shut Down Valves (Energised to Run, Hazardous Area Types without Manual Override)

Similar documents
Solenoid Actuated Diesel Engine Air Shut Down Valves

SVX-Series Solenoid Actuated Diesel Engine Air Shut Down Valves (Energised to Run Types for Non-Hazardous Areas)

SVX-Series Solenoid Actuated Diesel Engine Air Shut Down Valves (Energised to Stop Types)

SVX-Series Diesel Engine Shut Down Valves (Solenoid Latched Types with Manual Start Override/Emergency Stop)

SVX-Series Solenoid Actuated Diesel Air Shut Down Valves

MVX-Series Diesel Engine Air Shut Down Valves

Diesel Engine Shutdown Valves

HVX-Series Diesel Engine Shut Down Valves (Oil Pressure Latched Types with Manual Start Override/Emergency Stop)

Diesel Engine Shutdown Valve

Diesel Engine Shutdown System

D-Series Automatic Engine Overspeed Shut Down Valves (Bendix Types)

Automatic Fuel Shut Down Valves

D200 Spindle Type Automatic Engine Overspeed Air Intake Shut Down Valve (including Manual, Oil and Air Pressure Shut Down Control options)

D-Series Automatic Engine Overspeed Shut Down Valves (Mini Range)

MPX-Series Diesel Engine Shut Down Valves (Manual Reset / Air Pressure and Manual Closure Options)

SELECTION, APPLICATION AND MAINTENANCE

FS2 Valves. Solenoid Powered to Close / Auto Reset Butterfly Valves

FS3 Valves. Solenoid Powered to Open / Spring to Close (failsafe)

Flameproof Alternator

Flameproof Alternator

Self-Exciting Flameproof Alternator

Flameproof Alternator

SELECTION, APPLICATION AND MAINTENANCE

D-Series Automatic Engine Overspeed Shut Down Valves (Bendix Types)

E Series. Automatic Engine Overspeed Shut Down Valves

SELECTION, APPLICATION AND MAINTENANCE

E-M Series. Combined Manual and Automatic Engine Overspeed Shut Down Valves

by AMOT World class diesel engine safety solutions Automatic Engine Overspeed Shut Down Valves - D Series

Diesel Engine Air Intake Shutoff Valves

RODADEACO. Diesel Engine Air Intake Shutoff Valves. Model RDB3 Compact Butterfly Valve. by AMOT. Overview. Typical Applications

Flameproof Alternators

System Selection Guide

by AMOT World class diesel engine safety solutions Product Selection Guide

Model 4418F. Overview. Typical applications. Key features and benefits. Accreditations. Starting air/gas valve Vented fuel gas valve

Pressure and Temperature Switches

Intake Air Shut-off Valve

PH2 C50219A AIR INTAKE SHUT-OFF VALVE. T800 KENWORTH / ISX ENGINE WITH POWERGUARD SMART OVERSPEED LIMITER

PH1 AIR INTAKE EMERGENCY SHUT-OFF VALVE PULL CABLE ACTUATION.

Diesel Engine Safety Solutions. Automatic Engine Overspeed Shut Down Valves - D Series

AIR INTAKE EMERGENCY SHUT-OFF VALVE C50203 AIR INTAKE SHUT-OFF VALVES APPLICATION DODGE 5.9L CUMMINS.

C50254A PH3 AIR INTAKE SHUT-OFF VALVE DODGE 6.7L CUMMINS WITH POWERGUARD SMART OVERSPEED LIMITER

AIR INTAKE EMERGENCY SHUT-OFF VALVE PH2 C50204 AIR INTAKE SHUT-OFF VALVE DODGE 6.7L CUMMINS.

SERIES 2000 GAS SAFETY SHUT OFF VALVE

PH2 POWERHALT AIR INTAKE SHUT-OFF VALVE C50201A ½ DODGE 6.7L CUMMINS C50202A DODGE 6.

E1186X Breather Kit. For Yanmar L48N Engines

Model 4418F. Overview. Typical applications. Key features and benefits. Accreditations. Starting air/gas valve Vented fuel gas valve

PH3 AIR INTAKE EMERGENCY SHUT-OFF VALVE WITH POWERGUARD SMART OVERSPEED LIMITER. Generic PH3 Truck Shut-Off Valve Kit.

World class manufacturer of safety solutions SYSTEM SELECTION GUIDE. Safety solutions for vehicles and machines working in petrochemical plants

PH2 AIR INTAKE EMERGENCY SHUT-OFF VALVES. APPLICATION C ½ DODGE 6.7L CUMMINS C DODGE 6.

Pilot Operated 2-Way Gas Valves

Pneumatic Indicating Relay

AIR INTAKE EMERGENCY SHUT-OFF VALVE C50207 AIR INTAKE SHUT-OFF VALVES APPLICATION FORD 6.7L POWERSTROKE.

Black Teknigas. Powerseat Eco Gas Safety Shut-Off Valve. Technical, Installation and Maintenance Details. WattsIndustries.co.uk

ELECTRIC ACTUATOR MOD. VB015 MAINTENANCE AND INSTALLATION INSTRUCTIONS OF VALBIA ELECTRIC ACTUATORS

Series 500. Liquid Level Transmitters. Instruction Manual

2-Way Temperature Sensing Valves

Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black

Service Manual for Battery Control Center

Type 2511/12. Type Type 2030 Cable plug. ASI cable plug. Dosing control. General technical data Orifice Type 6518

II 2GD. xxxx. Westlock 2200 Series Quantum - ATEX certified Installation & Operating Instructions

Installation Instructions. Standard Gate Valves

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

abc INSTALLATION, OPERATION, & MAINTENANCE MANUAL ADDENDA 210 MKII LOW TEMPERATURE CELL SAMPLER

Metal Particle Detector

Thermostatic Valve. Filterstat - Model FJA. Typical applications. Key features and benefits. Mixing Diverting

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

Series 810: 2 Way Angle Body Valves: 1/4 to 3 NPT

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

2/2 Pressure operated valves

Quarter turn actuators Index

Installation, Operating & Maintenance Instructions. Norbro J-Switch FM 00707

Metal Particle Detector

ATB Series - Integral Throttle Body Actuators

High pressure valves. 80 to 350 bar

ay Manifold Mounted KHP3K

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions

Operating, Installation and Maintenance Instructions

INSTALLATION AND MAINTENANCE

Electric Fuel Pump FPM

3-Way Temperature Control Valve

ABV21i and ABV40i Air Actuated Boiler Blowdown Valves

LNG Screw Down Non-Return Valve Installation, Operation and Maintenance Manual

EXPLOSION PROOF DIRECTIONAL CONTROL VALVE TYPE ED6 SERIE 5X CENELEC STANDARD & ATEX DIRECTIVE

Model J. Thermostatic Control Valves. Typical applications. Key benefits. Key features. Accreditations available

The enginewithintegrated water cooling

XS VALVE WITH SA05 / SA-X05 ELECTRIC ACTUATOR. Model/Ref:

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

P0441-EVAP PURGE SYSTEM PERFO... P0441-EVAP PURGE SYSTEM PERFORMANCE

2 way ball valve S4 with pneumatic actuator

3- and 4-Way Ball Valves KH3/KH4

D-26. Combination Air Valve for Wastewater. Description. Applications. Operation. Main Features

Installation, Operation. IOM 1540 Rev. 1. Page 1 of

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

2/2-way Solenoid Valve with servo diaphragm

OCTOPUS SELECTION & INSTALLATION GUIDE Rev. C CRA SERIES CONTINUOUS RUNNING PUMPSET

Operating Instructions. Valves Atkomatic Series ATEX and Series ATEX Series Series

DEEP SEA ELECTRONICS PLC

Thermostatic Control Valve

NEOTECHA NEOSEAL BUTTERFLY VALVE INSTALLATION AND MAINTENANCE INSTRUCTIONS

Transcription:

SVX-Series Solenoid Actuated Diesel Engine Air Shut Down Valves (Energised to Run, Hazardous Area Types without Manual Override) Selection, Application and Maintenance Valve Numbers SVX-320 SVX-330 SVX-520 SVX-530 SVX-820 SVX-830 CE239 (8) 0509 SVX

DESCRIPTION A range of 12 and 24 volt EExe solenoid operated diesel engine air intake closure valves based on the standard Chalwyn slimfit 3, 5 and 8 butterfly valves. These products are available in basic flange mounted form, but can also be supplied fitted with hose adaptors. These valves are designed to fail safe in that if electrical power is lost for any reason the valve will revert to the closed condition. Valve bodies and discs are all manufactured from corrosion resistant hard anodised aluminium with a PTFE coating. Spindles and mechanisms are manufactured from 316 stainless steel. The Chalwyn 12 volt solenoid type SSX-102 built into the hazardous area valves type SVX-320, SVX-520 and SVX-820 is marked as follows: CHALWYN LTD., Poole, ENGLAND TYPE SSX-102 EEx e II T4 (Tamb = -30 c to +50 c) 0518 11 2 G D IP66 SIRA99ATEX3186X SERIAL NO. xxxxx 12 VOLTS, HOLD 1.1A PULL 46A The Chalwyn 24 volt solenoid type SSX-201 built into the hazardous area valves type SVX-330, SVX-530 and SVX-830 is marked as follows: CHALWYN LTD., Poole, ENGLAND TYPE SSX-201 EEx e II T4 (Tamb = -30 c to +50 c) 0518 11 2 G D IP66 SIRA99ATEX3186X SERIAL NO. xxxxx 24 VOLTS, HOLD 0.5A PULL 25A IMPORTANT NOTES: SOLENOID TYPES SSX-102 AND SSX-201 Araldite epoxy adhesive and an elastomeric cable seal are used in the construction of these solenoids. The characteristics of these materials with regard to attack by aggressive substances shall be taken into account when installing or using the product in a hazardous area. Solenoids SSX-102 and SSX-201 must not be mounted or installed in such a way that the effective ambient temperature exceeds 50 c. 2 svx solenoid actuated Diesel8Engine Shutdown

Typical Valve Arrangement: B Alternative Cable Gland Position Cable Gland Optional Hose Adapter Range C 1 C 2 (Min) C 2 (Max) D A Main Dimensions (mm) Valve Type Nominal Bore Dia. A B C 1 C 2 (min & max) D SVX-320 SVX-330 SVX-520 SVX-530 SVX-820 SVX-830 76 (3 ) 127 (5 ) 203 (8 ) 161.0 217.0 317.5 111.5 167.5 257.0 37.5 45.5 56.0 82.5 to 112.5 102.0 to 157.5 136.5 to 185.5 121.5 125.5 130.5 For optional hose adaptor range see page 4. 3 SVX solenoid actuated Diesel Engine Shutdown

SELECTION This range of valves is suitable for operation in T4, Zone 1, Gas Group IIB or in Zone 21 hazardous areas. All valves in this range have separate connections for pull and hold coils. The power supply must therefore be arranged with a suitable timer circuit to switch between the pull and hold connections. Determine the size and position of the SVX valve to be installed. Within the various constraints imposed by the application, the valve should be as generously sized as possible. Check that the valve can be installed such that the electrical cable may be routed away without risk of damage. The standard cable gland entry point is shown on page 3. An alternative end entry position is available if specified. If the valve is to be fitted into a hose as opposed to flange mounted, suitable hose adaptors should be selected from the table below and ordered with the valve. Hose Adaptor Options 76mm (3 ) Bore Valves Adaptor To Suit Hose Bore Part Number mm (inches) HAX-320 38 ( 1 1 / 2 ) HAX-322 44.5 (1 3 / 4 ) HAX-301 51 (2) HAX-302 54 (2 1 / 8 ) HAX-303 57 (2 1 / 4 ) HAX-304 60 (2 3 / 8 ) HAX-305 63.5 (2 1 / 2 ) HAX-306 67 (2 5 / 8 ) HAX-307 70 (2 3 / 4 ) HAX-308 73 (2 7 / 8 ) HAX-309 76 (3) HAX-312 82.5 (3 1 / 4 ) HAX-314 89 (3 1 / 2 ) HAX-319 102 (4) 127mm (5 ) Bore Valves Adaptor To Suit Hose Bore Part Number mm (inches) HAX-501 89 (3 1 / 2 ) HAX-502 92 (3 5 / 8 ) HAX-503 95 (3 3 / 4 ) HAX-504 98 (3 7 / 8 ) HAX-505 102 (4) HAX-506 105 (4 1 / 8 ) HAX-507 108 (4 1 / 4 ) HAX-508 111 (4 3 / 8 ) HAX-509 114 (4 1 / 2 ) HAX-510 117.5 (4 5 / 8 ) HAX-511 121 (4 3 / 4 ) HAX-512 124 (4 7 / 8 ) HAX-513 127 (5) HAX-518 140 (5 1 / 2 ) HAX-523 152 (6) 203mm (8 ) Bore Valves Adaptor To Suit Hose Bore Part Number mm (inches) HAX-807 178 (7) HAX-808 203 (8) 4 SVX solenoid actuated Diesel Engine Shutdown

INSTALLATION (MECHANICAL) 1. In the case of a naturally aspirated engine, the Chalwyn SVX shut down valve should generally be fitted as close to the engine air intake manifold as possible. If an air intake flame trap is also fitted, the SVX valve must be installed upstream (air cleaner side) of the flame trap. 2. If the engine is turbocharged, it may be necessary to fit the valve upstream of the turbocharger in order to avoid temperatures in excess of the maximum permitted for the solenoid (see page 2). Again if an air intake flametrap is also fitted the valve must be installed upstream of the flametrap. 3. Where more than one SVX valve is installed on an engine, as in the case of an engine with multiple intake pipes, the shut down valve control system must be arranged to ensure all valves close simultaneously. 4. This valve may be installed either horizontally or vertically. 5. If hose adaptors are used, the mating hose should be of a reinforced type, provide adequate support for the valve and prevent excessive vibration. If necessary, additional support brackets mounted from the engine should be considered. 6. Particular care must be taken to ensure the integrity of the intake pipework between the Chalwyn valve and intake manifold. Ideally metal pipework should be used and any gaps kept as short as possible, (taking into account any relative movement) and closed by reinforced hose. 7. Any engine crankcase breather connections into the intake system between the SVX valve and engine, or any internal crankcase breather arrangement venting directly into the engine intake ports must be sealed and replaced by an external breather system venting either to atmosphere or to the intake system upstream of the shut down valve. External breather system kits for various engine types are available from Chalwyn. INSTALLATION (ELECTRICAL) The diagram shows a typical Chalwyn wiring arrangement for the solenoids. It is IMPORTANT that the start key switch for the engine is wired such that between starting attempts it is not necessary to de-energise the solenoid. The starting instructions for the operative must clearly state that the key switch should not be returned to the solenoid de-energised position whilst attempting to start. If this requirement cannot be complied with, or if the engine is an unattended unit fitted with an automatic start arrangement, the control system providing the power to the solenoid must be designed to restrict the number of times the pull coil is energised to a maximum of 6 times per 30 minutes followed by a 30 minute rest before repeating the cycle. Supply voltage: 12 vdc. (SVX-320, SVX-520 and SVX-820) or 24vdc (SVX-330, SVX-530 and SVX- 830 Pull current at 23 C : 46 amps (12 volt types) or 25 amps (24 volt types). Hold current at 23 C : 1.1 amps (12 volt types) or 0.5 amps (24 volt types). Pull coil: Must not be powered for more than 0.5 seconds continuously. A suitable timer circuit must be incorporated to achieve this. NOTE: The control system must include a back-up safety device which de-energises the pull coil if it is energised for more than 14 seconds continuously. D+ D+ THERMAL CIRCUIT BREAKER THERMAL CIRCUIT BREAKER CONTROL BOARD 2 1 + 12V 50A 5 3 + 12V 50A 2 1 5 3 D- D- AIR INT VALVE SO FUEL VA EXample of a TYPICAL SOLENOID OPERATING CIRCUIT The blue wire is the common return and must be connected to the negative terminal of the supply. The yellow/green wire is the pull coil supply. The brown wire is the hold coil supply. The outer braiding of the supply cable should be earthed at the supply end. The solenoid may be earthed using the earth tag of the cable gland. NOTES: a) Suitable cable glanding must be used at the supply end of the cable. b) The length of the supply cable should not be increased from that supplied. HOLD PULL 0V HOLD PULL 0V 5 svx solenoid actuated Diesel Engine Shutdown

OPERATION When powered the solenoid holds the air intake shut down valve in the open (engine run) condition. On loss of power the spring within the shut down valve assembly moves the valve to the closed (engine stop) position, i.e. failure of power supply gives a fail safe (engine stopped) condition. MAINTENANCE WEEKLY: Visually check the valve, solenoid, cable and cable gland for damage or deterioration. Withdraw from service if significant damage or deterioration is observed. NOTE: Chalwyn hazardous area solenoids are sealed units. The cable gland must not be loosened or removed. If a service problem occurs, the valve should be returned to Chalwyn for repair. MONTHLY: Check that the fasteners locating the shut down valve and any associated intake system or support bracket fasteners are securely tightened. Check that any flexible hoses in the engine intake between the SVX valve and engine are free from damage and suitable for further service. Run engine, preferably at low idle. Use shut down control system emergency stop to close the intake shut down valve. The engine should stop within a few seconds. If not, check there are no leaks in the engine air intake system between the SVX valve and engine. If this does not resolve the problem remove the SVX valve to return to Chalwyn for investigation. 6 SVX solenoid actuated Diesel Engine Shutdown

NOTES: 7 SVX solenoid actuated Diesel Engine Shutdown ValvesCE239 (8)

Chalwyn by AMOT www.chalwyn.com A division of Roper Industries Limited UK Western Way Bury St Edmunds Suffolk, IP33 3SZ Tel: +44 (0)1284 715739 Fax: +44 (0)1284 715747 USA 8824 Fallbrook Drive Houston TX 77064 Tel: +1 281 940 1800 Fax: +1 713 559 9419 Canada 3230 97 Street Edmonton Alberta, T6N 1K4 Tel: +1 780 465 4429 Fax: +1 780 469 6275 Chalwyn reserves the right to update this PRODUCT specification without prior notice.