ASPIRO & GUARDIAN BATTERY MANAGEMENT WITH ACC EXTENDED CONTROLLER

Similar documents
DIN-Rail DC UPS. Powers Loads and Charges Back-Up Battery, Ideal for Automation and Wireless System Transmitter Applications

User Manual Solar Charge Controller 3KW

INTRODUCTION. Specifications. Operating voltage range:

Ag Features. Multi-Stage Charging. Solar Panel or DC Input. Maximum Power Point Tracking (MPPT) Very Low Power Consumption

GEPA. ARG-24 Series Battery Charger & Battery Group. User Guide

Silvertel. Ag Features. Multi-Stage Charging. Battery Reversal Protection. Reduced Power Consumption. Wide DC or AC Input Voltage Range

Battery Care the new Battery Charger Philosophy Battery Charger and Battery Tester. Charge & Testing. Integrated Electronic Solutions

Using Apollo Solar Remote Monitoring Software

Ion Technologies SUMPRO Battery Back-Up

MKN-DSP SERIES - THREE PHASE

Innovative Circuit Technology Ltd.

OPTI-Solar SC MPPT Series

User Manual. Solar Charge Controller 3KW

Integrated Inverter/Battery Monitoring System (IBMS)

SOLAR SMART. 12/24V 20Amp MPPT Solar Charge controller with Ethernet

Cellwatch Battery Monitoring Systems

Service Manual BLACK DIAMOND SERVICE MANUAL. V.160 November

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

BIGLA30-T/BIELA14-T Event Codes Quick Reference EXPLANATION CORRECTIVE ACTION PARTS TO CARRY ON SERVICE CALL

RUTLAND HRDi CHARGE REGULATOR INSTALLATION AND OPERATION

Sonnenschein Lithium HC (High Current)

SmartON / SmartON+ Installation and Use Manual

CBI All in One DC UPS Power Solutions

User Manual 1.5KVA-3KVA INVERTER / CHARGER. Version: 1.1

Industrial Chargers and

Pulsar EXtreme CLA 1500C

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)

PV Charge Controller SBC-7108 / 7112 / 7120

All In one uninterruptible power supply solutions

User manual. Solar Hybrid 1-5KVA. Uninterruptible Power Supply / Charger

Special Specification 6058 Battery Back-Up System for Signal Cabinets

World Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants

User Manual 5KVA/5KW INVERTER / CHARGER. Version: 1.3

LDX-U20 is a microprocessor controlled DC-UPS rated 20 A usable in 12 V or 24 V systems.

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Quick Start Instructions For

User Manual. Hybrid PV Inverter. Version: 2.1

Solar Hybrid Inverter SP Brilliant Series

Intelligent Solar Charge Controller. User's Manual. Please read this manual carefully before you use this product

Est Battery Data Logger BDL3000

BBC-3140 USER MANUAL DC-DC CHARGER / BATTERY EQUALIZER / VOLTAGE REDUCER

SNMP dedicated to ORVALDI Solar Infini

INVERTEK WINDTAR MPPT SERIES

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

MiG2 TIME SWITCHES. 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

SINAMICS GM150 IGCT version

.3 Section Waste Management and Disposal.

CRAGG RAILCHARGER Instruction Manual for 20SMC-12V 20SMC-24V 40SMC-12V 40SMC-24V 60SMC-12V 80SMC-12V

AME. Rectifier - Battery charger. Industrial applications: Key features:

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

UP100AC INSTRUCTION MANUAL

Intelligent Digital Balance Charger

Operating Instructions CHARGERY C650. Microprocessor controlled high performance rapid charger for LiPo battery packs with cell balancer.

TRIPS AND FAULT FINDING

PowerSTAR PS-2024-D. Maximum Power Point Tracking Solar Regulator. w w w. r o c s o l i d. c o m. a u. Contents

INSTALLATION INFORMATION

Aurora Single Phase Emergency Lighting Inverters

Rover Series. Rover 20A 40A Maximum Power Point Tracking Solar Charge Controller

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

CONTENTS TABLE OF CONTENTS... 1 INTRODUCTION... 2 SEC 1 - SPECIFICATIONS... 3 SEC 2 - DESCRIPTION... 5 SEC 3 - OPERATING INSTRUCTIONS...

Lithium battery charging

SENTINEL BATTERY MONITORING

World Class Charging Systems. TEBETRON expert. Intelligent charging systems for traction batteries

Stand-Alone-Systems POWERFUL TECHNOLOGY

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

SMPPT. Solar Charge Controller with Maximum Power Point Tracking. Installation & Operation Manual

Pulsar Evolution 1500 / 1500 Rack 1100 / 1100 Rack 800 / 800 Rack 500 Rack

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Modbus Register Map:Galaxy VM (3: kVA 400/480V)

ML Maximum Power Point Tracking (MPPT) Series ML2420-ML2430-ML2440 Solar Charge and Discharge Controller

I t n e t l e l l i l g i e g n e t n So S l o a l r a Ch C a h r a g r e g Co C n o t n r t o r l o l l e l r U e s r e s Man an al

400W Solar Charger Maximum Power Point Tracker

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

PowerValue 11/31 T kva

EVO SERIES BATTERY CHARGER SERIES BATTERY CHARGER

HYDRUS ULTRASONIC METER

MPPT Controller PVTS Series User Manual. User Manual. 800W-4000W Hybrid solar inverter. Version: 1.4

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual

CONGRATULATIONS ON YOUR PURCHASE OF YOUR THUNDER SOLAR REGULATOR!

STAND- ALONE -SYSTEMS

RELIABLE SOLUTIONS in POWER ELECTRONICS. Power Management Instruments RDAT SERIES BATTERY CHARGER / DC RECTIFIER PMI / GESS / KARMET GROUP COMPANIES

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets

User Manual 1KVA-5KVA INVERTER / CHARGER

All specifications and figures are subject to change without notice. Printed in China Instruction Manual

Illuminator Series CR NEMA 3R

User Manual 1KVA-5KVA (PF1) INVERTER / CHARGER. Version: 1.0

Solar inverter with MPPT AX II - M series: 4 / 5 kva, AX II - P series: 3 kva. With integrated star point grounding* according to VDE AR-E 2510-

Solar Hybrid Inverter SP Efecto Series

Silvertel. Ag Features. Multi-Stage Charging. Battery Reversal Protection. Reduced Power Consumption. Wide DC or AC Input Voltage Range

HERMES power supply - short description -

Uninterruptible Power System

:43 1/13 Victron & BYD B-Box

PREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J.

DIESEL Engine Fire Pump Controllers Features

Maximum Power Point Tracking (MPPT) KA1224MPPT20A KA1224MPPT40A. Solar Charge Controller. User Manual 20A

Sola 3000 Guide Specifications

Models. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery

SC-Max 48V series. User Manual. Solar Charge Controller 30A

User Manual V1.1 OptiFlex 1100 / OptiFlex 2000

Transcription:

DESCRIPTION Battery management is implemented in the Aspiro and Guardian DC Power Systems using the ACC Extended (ACX) controller. ASPIRO & GUARDIAN BATTERY MANAGEMENT WITH ACC EXTENDED CONTROLLER The main benefit of integrating battery management into the controller and it s associated interconnection boards is that it does not require any additional hardware other than associate wiring. MONITORING FUNCTIONALITY Know the Health of your system 24/7. Real time cell voltages are displayed or cell voltages from a previous discharge. User can remotely monitor and store battery telemetry data reducing trips to site and increasing uptime. Automatic or on-demand battery testing (over the internet) ensures batteries are functioning properly and provides battery health statistics back to a NOC without affecting the existing system loads. INTELLIGENT MANAGEMENT Battery Disconnection Boost Charging Battery Testing Temperature Compensation Charging Battery Current Limiting Enhanced Monitoring and Data Logging Symmetry Measurement Load Shedding Powcom Battery Symmetry Screen Powcom Test Data Screen www.unipowerco.com NORTH AMERICA CALL: +1-954-905-1071 LATIN AMERICA CALL: +1-954-905-1078 EUROPE CALL: +44 1903 768200

ASPIRO & GUARDIAN BATTERY MANAGEMENT - 2 Available Functions Battery Disconnection Boost Charging Battery Tests Temperature Compensation Charging Battery Current Limiting Enhanced Battery Monitoring Symmetry Measurement Load Shedding (PLD) Allows voltage controlled disconnection of batteries. Manual time controlled or automatic boost charging with adjustable time and voltage levels. Automatic or manual testing of batteries up to six times per year with a 10 test memory. Variables include test duration and end voltage. Battery discontinuance test to ensure battery connection. Allows continuous adjustment of output voltage according to battery temperature. Features include adjustable compensation factor and separate thresholds for high temperature alarms. Limits the maximum current flowing into the batteries during charging. Monthly logging of essential battery parameters including temperature, temperature hours, current, charging voltage and symmetry voltage, Data logged for 5 years. Battery alarms are also logged. Optional tool that measures batteries for early detection of thermal runaway. Optional feature that allows voltage or time controlled disconnection of non-essential load. Each Aspiro and Guardian system supports batteries as follow: Aspiro 1U: 1 string Aspiro 2U: 2 strings Guardian 2U: 2 strings Guardian 3U: 3 strings Guardian 5/6U: 6 strings Guardian Central: Varies according to the number of cabinets deployed. ACC Front Panel Display Icons The controller displays several icons at the top of LCD screen two of which are specifically related to the batteries, the Battery icon at the top left and the Graph icon at second left. - +

ASPIRO & GUARDIAN BATTERY MANAGEMENT - 3 Battery Icon - + The battery icon displays the battery charge status in 20% increments. To predict the remaining capacity, immediate load current and voltage are also taken into account. During battery charging the icon pulses. Once the battery is fully charged only the rightmost segment blinks. When starting the system for the first time it takes some time before the battery icon is fully operational and displays correctly. The battery capacity must be set correctly (Adjust Limits Battery settings Battery Capacity). If the Battery capacity is set to 0 (zero) the icon is not shown. Graph Icon Boost Test The graph icons indicate charging mode as either Boost or Test. The graph showing an up-going curve is the Boost icon, while Test is indicated with a down-going curve on the graph. Battery Disconnection The battery disconnection function disconnects the battery from the load at the end of the discharge cycle and before any damage to the batteries can occur. This is achieved by the controller monitoring the bus voltage when the system is running on batteries and opening the Low Voltage Disconnect contactor at a predefined voltage according to the battery manufacturer s recommendations. Boost Charging The boost charging function defines the parameters that are to be used during a boost charging cycle. The following parameters can be set: Boost time (Hours) Boost interval (Weeks) Boost factor (-) Boost t1 (V) Boost t2 (V) Autoboost Enable (On/Off)

ASPIRO & GUARDIAN BATTERY MANAGEMENT - 4 Boost charging can be activated by three methods: 1. Manual boost charging - can be activated manually by selecting U2, boost charger voltage setting, via the controller front panel, WEB interface (Select/Adjust U1-U4 Reference U2) or via PowCom software (Adjust limits window). Return to float charge manually by choosing U1, float charger voltage setting, or automatically, after a pre-set time. 2. Periodic boost charging - after a pre-set period boost charging will be automatically activated for a pre-set time. The interval and boost time should be programmed (for example 4 hours every 3rd week). 3. Automatic boost charging - referring to the following graph, when the battery voltage drops below LEVEL t1 during a mains failure, timer t1 is started. When the mains is restored, timer t1 is stopped and the system starts automatic boost charging for time t2 = k x t1 (k is an adjustable constant). Timer t2 starts counting when the battery voltage reaches LEVEL t2, see Figure 11. Voltage (V) Level t2 U1 (Float Charge) Level t1 t1 Mains Interrupt Mains Returns t2=k x t1 Time (hours) The following values are adjustable for boost charging: Boost voltage 40-60 V Boost time 0-200 hrs Boost interval 3-16 weeks Boost factor 1.0-16 Boost t1 40-60 V Boost t2 40-60 V Automatic boost Enable/Disable Note that not all battery types support boost charging, so this facility should not be used if this is the case.

ASPIRO & GUARDIAN BATTERY MANAGEMENT - 5 Battery Test and Short Interval Battery Test The following limits and parameters for Battery Test and Short Interval Battery Test can be set in the controller: Test end voltage (V) Test end Ah (Ah) Test duration (Min) Time of test (-) Number of tests per year (-) Short interval Enable (On/Off) Short interval period (Days) Short interval length (Min) Short interval deviation (%) The following menu items are available: Battery Test Battery test is used for checking the condition and capacity of installed batteries. The test can be activated Manually or Automatically. Manual Start-up Battery testing is activated manually by selecting U3, test voltage setting, via the controller front panel, web interface (Select/ Adjust U1-U4 Reference U3) or via PowCom software in the Adjust Limits window. Automatic Start-up Battery test can be also activated automatically 1-6 times a year via the controller front panel, web interface (Adjust Limits Battery Test No. of tests per Year) or via PowCom software in the Adjust Limits window (Auto Test). The test date is calculated from the installation date of the system defined in PowCom software (Supervision Set installation data). The day-time (24-hour format) of the battery test is set in Time for Test. Test Performance Once the battery test starts, the rectifier voltage decreases to a pre-set value U3 and is stopped when the set value is reached. Reasons for the test stopping could be: battery voltage reaches the End voltage [V] battery test reaches the Test duration time [min]. discharged capacity reaches the set Ah limit value. Battery voltage, battery current and Ah are logged during the test. The recommended minimum duration of the test is 5 minutes.

ASPIRO & GUARDIAN BATTERY MANAGEMENT - 6 Upon completion the test will have either PASSED or FAILED. PASS The battery parameters meet requirements and the voltage reference is set back to U1 when: FAIL the battery voltage is higher then set End Voltage b. test [V] after expiration of Batt. test time [min]. the battery voltage is higher then set End Voltage b. test [V] after discharged capacity reaches the set value [Ah]. The test is interrupted and the battery is considered as faulty when: the set voltage value [V] is reached before time [min]. the set voltage value [V] is reached before Ah limit for test [Ah]. the symmetry limit is exceeded. SYMMETRY FAULT alarm is activated, battery test is ended and BATTERY FAILURE alarm is generated. The battery failure alarm is indicated and further automatically activated battery tests will not be performed while the battery failure alarm is active. Voltage reference is set to U1 again. Parameter Settings The parameter settings feature allows a partial discharge of the batteries (approximately 30-40% of their capacity) in order to test the batteries for errors. The settings should be done according to the battery manufacturer s requirements. The following setting can be used as an example for standard value-regulated lead batteries: U3 = 1.9V/cell End voltage = 1.94V/cell Time = 40% of expected backup time Ah = 40% of nominal battery capacity. Parameters that can be set or adjusted in the battery test: Battery test voltage U3: 0-100V (Check Rectifier datasheet for min. voltage.) Symmetry limit: 0.0-4.0V Test end voltage: 0-100V Test duration: 0-20 hours Ah limit: 0-50,000Ah Time of test: 0-23 (0=midnight) No of test/year: 0-6

ASPIRO & GUARDIAN BATTERY MANAGEMENT - 7 Short interval battery test This is used to test for a permanent break or interruption in the battery strings when more than one shunt with extension board is used. Once this test is Enabled, it is performed in the time interval set in the Short interval period. The system voltage is decreased to U3 for the time duration set in Short interval length and the current through all used shunts is measured. If the current deviation through the shunts exceeds the value set in the Short interval deviation or if one of the currents is equal to 0 (zero), a Battery Failure alarm is generated. The test can be Enabled via the controller front panel, web interface (Adjust limits Battery test Short Interval Enable On/Off) or in one of two ways via PowCom software: 1. (Supervision Set parameters Battery settings toggle Short interval Battery Test) or 2. (Utilities Config Wizard Battery settings window toggle Short interval Battery Test). Temperature Compensation Temperature compensation adjusts the float depending on battery temperature. This feature is recommended if the battery temperature is expected to vary more than ±5 C from ambient temperature. The temperature coefficient for lead acid batteries is typically -3 to -5 millivolts/ C per cell. Correct use of battery temperature compensation increases battery life. Setting of the following parameters for temperature compensation is available through the front panel, web interface or via PowCom software: Enable temperature compensation (On/Off) Compensation factor (V/10 C) Turn temperature compensation On/Off. When the battery temperature is higher or lower than 20 C, temperature compensation regulates the set float or boost battery voltage based on battery temperature and temperature compensation factor. (This value can be changed to 25 C.) If the temperature rises by 10 degrees, the voltage decreases according to the adjusted compensation factor, if the temperature drops the voltage is adjusted correspondingly. If the temperature changes by 1 degree, the voltage changes by 1/10 of the compensation factor. Example: A system includes 4 x 12V battery blocks - 6 cells in each battery block. The value of 1 cell defined in the battery datasheet is 2.28V/20 C, 2.24V/30 C. The difference between values at 20 C and 30 C is 0.04V/cell.

ASPIRO & GUARDIAN BATTERY MANAGEMENT - 8 6 x 0.04V = 0.24V/10 C - 6 cells in each battery block. The compensation factor value is set for a full battery string which in this case contains 4 x 12V battery blocks. So, the correct compensation factor is: 4 x 0.24V = 0.96V/10 C. Battery Current Limit This function limits the maximum current flowing into the batteries during charging. (It does not limit discharge current!) The minimum charging current is 5A. The maximum charging current value can be set via PowCom software to 1000A, via the controller front display or web interface it can be higher. This menu allows settings for: Battery current limit Enable (On/Off) Battery current limit (A) The charging current limit for lead-acid batteries is usually 0.1 of rated capacity. (Check the battery datasheet in case a different value is required.) If the current limit is not required or batteries are not installed, keep the function disabled. However, non-limited charge current or improper setting may shorten battery life, so it is generally recommended to set this parameter according to the specifications of the batteries being used. Enhanced Battery Monitoring This function provides monthly logging of essential battery parameters including: Temperature Temperature hours Current Charging voltage Symmetry voltage The following battery related alarms are also logged: Load/Battery disconnection - This alarm is generated when the system voltage drops below a preset limit for more than 30s. Battery failure - This alarm occurs when either a Battery test or a Short interval Battery Test Fails. High battery temperature - This alarm occurs when the battery temperature exceeds a preset limit.

ASPIRO & GUARDIAN BATTERY MANAGEMENT - 9 Symmetry fault - This alarm is generated when the voltage between battery blocks differs from a preset limit. This value is calculated from the system voltage based on the battery settings, number of batteries and battery type. Battery fuse failure - This alarm occurs when a battery circuit breaker is switched Off and the system voltage is 0.65V higher than the battery voltage. PLD/PLD2/PLD3 Disconnection - These alarms occur either when the system voltage drops below the associated set limits, or when the time reaches a preset value. Temp. probe failure - This alarm always appears when: The temperature probe is disconnected and temperature compensation is enabled. Battery temperature is above +80 C or below -20 C, temperature compensation can be enabled or disabled. (If disabled and temperature is below -40 C the alarm does not appear.) Battery temperature is 10 C higher than the temperature of the controller s internal temperature sensor. Battery temperature is 30 C lower than the temperature of the controller s internal temperature sensor. This alarm does not appear when: The temperature probe is disconnected and temperature compensation is disabled. Temperature compensation is disabled and the temperature drops below -40 C. Battery is discharging - This alarm appears when the battery is discharging with current higher than 2% of the current rating of the shunt and the system voltage drops 1V below the voltage reference (U1 or U2). Low battery temperature - This alarm is activated when the battery temperature drops below a preset temperature. Data and alarms are logged for 5 years. This function requires that a microsd data card is fitted. Symmetry Measurement Symmetry measurement is used to a battery string is faulty. The ACC Extended controller supports 2 block (single wire) and 4 block (three wire) symmetry measurement as shown below: 2 block measurement 4 block measurement

ASPIRO & GUARDIAN BATTERY MANAGEMENT - 10 The total number of symmetry measurements that can be supported with the standard controller interface card is 12 (2 block measurement) or 4 (4 block measurement). The following shows how connections for up to 4 battery strings are made to the extension interface board: Note that larger systems such as Guardian Central may have additional battery cabinets which require additional exrension interface boards. Load Shedding Load shedding is a method that can be used to extend system run time when operating on batteries. Systems incorporating load shedding include between one and three additional Voltage Disconnect contactors known as PLD contactors. Non-critical loads are connected through these PLD contactors so that they can be disconnected as the battery discharges at an earlier point than the battery LVD disconnects. Note that in some system configurations load shedding is essential so as to ensure that the system bus current carrying capacity is not exceeded as current increases for a given load as the voltage drops. 2016 UNIPOWER LLC This document is believed to be correct at time of publication and UNIPOWER LLC accepts no responsibility for consequences from printing errors or inaccuracies. All specifications subject to change without notice. battery_maganement-an-revc-0616.indd