Technical Bulletin, Communicating with Auto-Adjust Turbo Meter Gas Flowmeters

Similar documents
MATRIX LLC LEVEL CONTROL PANEL

PQube 3 Modbus Interface

Circuit breaker wear monitoring function block description for railway application

CS 420RC. Solid De-icer Controller Configuration and Set-up Manual

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

9200 Revenue Meter. Model Certification Current Inputs. Complies with the accuracy requirements of the ANSI C Revenue Metering Standard

Issue 2.0 December EPAS Midi User Manual EPAS35

User Manual Solar Charge Controller 3KW

Explanation 1 Input External Switch 2 Input Hipot Safety Switch

Loadcell Tension Control

Rosemount 8750WA Magnetic Flowmeter System For Water and Wastewater Industries

INSTALLATION & OPERATION MANUAL

OVERVIEW OF CONTROLS

Part Number AEM 4-CH WIDEBAND UEGO CONTROLLER

ASPIRO & GUARDIAN BATTERY MANAGEMENT WITH ACC EXTENDED CONTROLLER

BERMAD Waterworks. Insertion Flow Meter Device (IFM)

Elite Power Solutions Automatic Battery Control (ABC) Operation Manual

CONTENTS TABLE OF CONTENTS... 1 INTRODUCTION... 2 SEC 1 - SPECIFICATIONS... 3 SEC 2 - DESCRIPTION... 5 SEC 3 - OPERATING INSTRUCTIONS...

Newcastle Weighing Services Pty Ltd

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS

Inlet Controller SB3500 USER'S MANUAL

Series 905-IV16(E) CAN/CANopen Input Modules Installation and Operating Manual

CS 430RC. Solid De-icer Controller Configuration and Set-up Manual

Nickel Cadmium and Nickel Hydride Battery Charging Applications Using the HT48R062

Automatic Genset Controller, AGC-4 Display readings Push-button functions Alarm handling Log list

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:

Setup Tabs. Basic Setup: Advanced Setup:

OUTPUT VOLTAGE 5V MAX.INPUT CURRENT 16.0A 12V 7.0A 12V 12V 24V 35.0A 28V 48V 12V 15V 24V 28V 23.0A 48V 12V 15V 24V 28V 48V 11.5A

80V 300Ah Lithium-ion Battery Pack Data Sheet

CPW Current Programmed Winder for the 890. Application Handbook. Copyright 2005 by Parker SSD Drives, Inc.

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0

Programming of different charge methods with the BaSyTec Battery Test System

USER MANUAL LOAD CELL (Expansion)

INSTRUMENTATIOIN - TSB # 20 Rev. #1- Digital Display Unit

GREASE CONTROL GUNS GREASE CONTROL GUNS Grease control gun Grease control gun with rigid stem and 3 jaw connector ( ).

EPAS Desktop Pro Software User Manual

INSTRUCTION MANUAL_1219_ENGLISH SUPER ELF X3. Operating Instructions for DORNIER looms. Robustness Reliability Quality Productivity Versatility

Mark II and Mark IIE Turbo-Meters

Cat Electronic Technician 2017A v1.0 Product Status Report 7/10/2017 9:49 AM

SA Series Tape Feeder

Project 2: Traffic and Queuing (updated 28 Feb 2006)

From. McCROMETER, INC WEST STETSON AVENUE HEMET, CA Phone (951) Toll Free (800) Fax (951)

CLASSIC MPPT CHARGE CONTROLLERS

SOLAR SMART. 12/24V 20Amp MPPT Solar Charge controller with Ethernet

TOUCH PLS TOUCHSCREEN PLS A NEW HORIZON IN PROGRAMMABLE LIMIT SWITCHES

SmartPak Welding Controller WK-MPS-16 Constant Current

Dispenser Communication Error Codes for units containing the DeLaRue SDD-1700 feeders only

Quick Setup Guide for IntelliAg Model YP Air Pro

ULTRASONIC FLOW SENSOR IFX-M4-01

Application Engineering Europe

Quick Setup Guide for IntelliAg Model YP40 20 Air Pro

5. OVERCURRENT RELEASE (OCR)

EM101 LOW FLOW MAGNETIC FLOWMETER INSTRUCTIONS

Yaskawa AC Drive L1000A Supplement to the L1000A Technical Manual No. SIEP C , SIEP C , and SIEP C

Adelaide Wind Power Project Turbine T05 (AD117) IEC Edition 3.0 Measurement Report

SAC SERIES CONTENTS TRIPLE-INTERVAL HIGH PRECISION COUNTING SCALE OPERATION MANUAL 1. INSTALLATION 2. SPECIFICATIONS

SURE-TRIP OEM RELACEMENT TRIP UNIT

Electronic Preset Delivery System Smith Meter AccuLoad III. Vapor Recovery. Vapor Recovery System. Overview

DRIVE STARTUP MANUAL. Magnetek HPV900-S2 Drive. PM Motor Installation

Solid State Electronic Pressure Switch with Integral LED Display Model PSD-10

Temperature Controller OVATION 214 User's Guide

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.

MAGPOWR Spyder-Plus-S1 Tension Control

FOLLOW THE ARROWS. Alspa MV1000 Variable speed drive TEL: INSTALLATION QUICK START PROGRAMMING. FIRMWARE VERSION: 1.

FVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description

Validation of Generation Meter Data in MV-90 xi

Features: Enhanced throttle response, excellent acceleration, linearity and driveability

DIGITAL FLOWMETER AND PRESSURE INDICATOR MODEL FPA400

Signet Pressure Transmitter

CHAPTER 3 LIFE-LIMITED COMPONENTS

Signet Temperature Transmitter

Caterpillar Electronic Technician 2012C v1.0 Product Status Report 11/23/2013 2:25 PM

Tracer VMA with AutoReg

FLY BY WIRE SETTINGS 31 August 2016

Model DE-3 Air Release Heads Parts List

Whizbang Jr. Installation Instructions

Section 55 Chapter 6

OnGuard Display Operating Instructions

F-2600 SERIES INLINE VORTEX FLOW METER

Errors with S1/S2/S3/S4 Safety cards

Traffic Impact Statement (TIS)

Rosemount 8750WB Magnetic Flowmeter System

Introduction. ShockWatch Impact Indicator Activation. Contents

QUANTUM LX CONTROL PANEL

Digital Room Thermostats with Touch Screen LCD

F-1500 SERIES INSERTION TURBINE FLOW METER

Accelerated Testing of Advanced Battery Technologies in PHEV Applications

CLA-VAL e-drive-34. User Manual. Motorised Pilots. CLA-VAL Europe LIN072UE - 04/16

EGT-100 Operations and Installation Manual

Technical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER

Operations Manual. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL

Model 1000 Vortex Meter

Diagnostic Trouble Code (DTC) List

DIRECT INJECTION FOAM PROPORTIONING SYSTEM MODELS: TFC100, TFC200, TFC300, TFC400


Model 2500 Horsepower Computer System User Manual

Service Manual BLACK DIAMOND SERVICE MANUAL. V.160 November

Turbo-Meters Mark-II and Auto-Adjust

DIGITAL PRESSURE AND FLOW INDICATOR MODEL FPA500

Transcription:

Last Updated: 19-June-2009 TB-000314B Technical Bulletin, Communicating with Auto-Adjust Turbo Meter Gas Flowmeters OMNI FLOW COMPUTERS, INC. 12620 West Airport Boulevard, Suite 100 Sugar Land, Texas 77478 United States of America Phone-281.240.6161 Fax: 281.240.6162 www.omniflow.com 52-0003-0005/Rev B Page 1 of 11

NOTE: User Manual Reference - This Technical Bulletin complements the information contained in the User Manual applicable to Revision 23.74/27.74+. Table of Contents Scope...3 Abstract...3 AAT Flowmeter Theory of Operation...3 OMNI Flow Computer Logic...3 Wiring Invensys Auto-Adjust (AAT) Turbine Flowmeter (SLOT SENSOR) Signals to E Type Combo Modules (OMNI 6000 and 30000)...5 Wiring Invensys Auto-Adjust (AAT) Turbine Flowmeter (BLADE TIP SENSOR) Signals to E Type Combo Modules (OMNI 6000 and 3000)...6 Flow Computer Configuration...6 Miscellaneous Configuration Meter Run Settings...6 Meter Run Setup Entries...7 Meter Run Data...8 Warning and Alarm Messages...8 Flow Computer es and Index Numbers...9 Figures Figure 1. Flow Computer Logic Flow Diagram for the AAT Gas Flowmeter...4 Figure 2. Slot Sensor Wiring...5 Figure 3. Blade Tip Sensor Wiring...6 52-0003-0005/Rev B Page 2 of 11

Scope This Technical Bulletin applies to firmware revisions 23.74+ and 27.74+ of OMNI 6000/OMNI 3000 Flow Computers, for gas flow metering systems. Abstract The Auto-Adjust (AAT) Turbo-Meter (Figure 1) generates a self-checking output that is derived from the ratio between the main and sensing rotor pulses. This output is referred to as Delta A. The self-checking feature indicates how much adjustment the meter is making, thereby warning the user of meter or flowconditioning problems. The OMNI Flow Computer totalizes the flowmeter pulse input signal received from the Auto-Adjust Turbo-Meter. AAT Flowmeter Theory of Operation The Auto-Adjust (AAT) Turbo-Meter was introduced in the early 1980's. This meter has larger bearings, rugged rotor shafts, and unique dual rotor, is similar to that for a single rotor turbine. However, the second rotor, or sensing rotor, is unique in that its speed reacts to changes that occur to the main rotor. The pulse signals from the two (2) rotors are fed into the flow computer where algorithms calculate an adjusted volume and a self-checking value called "Delta-A". The adjusted volume is based on original factory calibration accuracy and gives the ATT the ability to compensate for a number of conditions that could degrade the accuracy of a single rotor turbine meter. While the meter is operating, the Delta-A output detects shifts in accuracy that could go unnoticed in a single rotor turbine meter. The periodic Delta-A reading indicates that a shift in accuracy did occur. OMNI Flow Computer Logic NOTE: Gross Flow Rate Equation - Qv=(Pm/Km)-(Ps/Ks) *3600 Adjusted Volume Equation (Pm/Km) (Ps/Ks) *Time Pm: Main Rotor Pulses Ps: Sensing Rotor Pulses Km: Main Rotor Pulse Factor Ks: Sensing Rotor Pulse Factor The OMNI Flow Computer determines the actual flow rate from the live pulse frequency signal inputs, which has been assigned and configured. This calculation is done every 500 milliseconds using pulses read from the Main and Sensing rotors of an Auto-Adjust Turbo-Meter. By combining these pulses along with the unique pulse factors for each rotor in an adjusted volume (Cumulative Gross) equation, a gas measurement volume will be calculated. In addition to the adjusted volume equation, algorithms are included that provide corrections to the volume totalization for conditions of Leakage flow, Resonant No- Net flow, Severe flow pulsation or Non-Steady flow. Self-Checking (Delta-A) Calculation - This calculation is performed after 25,000 main rotor counts are accumulated or after a time interval of 512 seconds has elapsed, whichever occurs first. The equation for this calculation compares the speed ratio of the Main rotor and Sensing rotor with the average speed ratio determined at factory calibration. The average factory value is represented by the "A-bar" value in percent. The calculation difference in field operation from the A-bar value is the % Deviation or Delta-A reading. Warning Flags and Alarm Outputs - The logic and algorithms in this section compare error conditions and Delta-A values to limits that are fixed or operator selected. Warning flags, alarms, and messages are set depending upon which limits are exceeded. Un-Adjusted Volume Calculation - This section shows how the mechanical or Un-Adjusted volume is properly calculated using the pulses from the Main rotor only. This volume is to be used in the measurement totalization when pulses from the Sensing rotor are unavailable or when the gas flow rate is below the minimum for the Adjusted output. Volume Totalizer Increment - This section shows how the totalizer registers for both Adjusted and Un-Adjusted volumes are incremented after the calculation are performed each second. 52-0003-0005/Rev B Page 3 of 11

Figure 1. Flow Computer Logic Flow Diagram for the AAT Gas Flowmeter 52-0003-0005/Rev B Page 4 of 11

Wiring Invensys Auto-Adjust (AAT) Turbine Flowmeter (SLOT SENSOR) Signals to E Type Combo Modules (OMNI 6000 and 30000) Input Channels 3 and 4 of each E Type Combo Module are used to input signals for turbine or PD flowmeters (Figure 2). Both channels share a common signal return at the OMNI terminals. Input threshold can be jumpered for +1 or +3.5 volt. Input coupling can be AC or DC (refer to Chapter 2). Hysteresis is approximately 0.5 volt. Figure 2. Slot Sensor Wiring 52-0003-0005/Rev B Page 5 of 11

Wiring Invensys Auto-Adjust (AAT) Turbine Flowmeter (BLADE TIP SENSOR) Signals to E Type Combo Modules (OMNI 6000 and 3000) Input Channels 3 and 4 of each E Type Combo Module are used to input signals from turbine or PD flowmeters (Figure 3). Both channels share a common signal return at the OMNI terminals. Input threshold can be jumpered for +1 or +3.5 volt. Input coupling can be AC or DC (refer to Chapter 2). Hysteresis is approximately 0.5 volt. Flow Computer Configuration Figure 3. Blade Tip Sensor Wiring The flow computer configuration settings that are specific to the AAT flowmeter are entered in the miscellaneous configuration meter run menu and the meter run setup menu. You must enter the miscellaneous configuration meter run settings first and then proceed to the meter run setup entries. These configuration settings at this time can be entered via the OMNI Flow Computer s front panel keypad. Miscellaneous Configuration Meter Run Settings The following miscellaneous configuration meter run settings are required for each AAT gas flowmeter: Select Flowmeter Device Type - Enter [7] for each meter run that you want to select the AAT gas flowmeter as the device type. Flow I/O Point - Flowmeter pulse signals can only be assigned to the 3 rd and 4 th input channels of the E combo modules. Assign the Main Rotor pulse to the OMNI channel number that corresponds to the 3 rd input channel on an E-Combo module and the flow computer program will assume the Sensing Rotor Pulse signal is wired to the 4 th input channel of the same E-Combo module. 52-0003-0005/Rev B Page 6 of 11

Meter Run Setup Entries The following meter run setup entries are required for each AAT gas flowmeter: M.R. Factor -The Main Rotor (MR) Factor value (Pulses/MCF or /M 3 ) of an individual Auto-Adjust Turbine meter can be found on the METER FACTOR badge or on the factory calibration documents. S.R. Factor - The Sensing Rotor (SR) Factor value (Pulses/MCF or /M 3 ) of an individual Auto- Adjust Turbine meter can be found on the METER FACTOR badge or on the factory calibration documents. M.O. Factor - The Mechanical Output (MO) Factor value (Pulses/MCF or /M 3 ) of an individual Auto-Adjust Turbine meter can be found on the factory calibration curve for the meter. This value is determined mathematically from the mechanical output of the meter, change gears, internal gearing, and blades on the pulsar wheel. A_Bar % - The Average Relative Adjustment (A) value (%) of an individual Auto-Adjust Turbine meter can be found on the METER FACTOR badge or on the factory calibration documents. The purpose of the Adjusted volume calculation is to provide a measurement registration that is adjusted back to original factory calibration accuracy, compensating for meter changes or for abnormal flow conditions. These field or operating Delta_A values can be compared with those at factory calibration. BTSF - Blade Tip Sensor Factor (BTSF) for meter AlarmBand H % - Alarm band high limits %. The logic and algorithms in this section compare error conditions and Delta-A values to limits that are fixed or Operator selected. Delta_A above normal limits. AlarmBand L % - Alarm band low limits %. The logic and algorithms in this section compare error conditions and Delta-A values to limits that are fixed or Operator selected. Delta_A below normal limits. Warning Hi % - Alarm band high limits %. The logic and algorithms in this section compare error conditions and Delta-A values to limits that are fixed or Operator selected. Delta_A above normal operating limits. Warning Lo% - Alarm band low limits %. The logic and algorithms in this section compare error conditions and Delta-A values to limits that are fixed or Operator selected. Delta_A below normal operating limits. AutoAdj Set (Set1) - The adjusted volume calculation is done every 500mS cycle using pulses read from the Main and Sensing rotors of an Auto-Adjust Turbo-Meter. In addition to the adjusted volume equation, algorithms are included that provide corrections to the volume totalization for condition of Leakage flow, Resonant No-Net flow, Severe flow pulsation or Non-Steady flow. Set1 = 0; Enable the auto adjust volume calculation, self-checking, flags and alarms. Set1 = 1; Enable the auto adjust volume calculation, self-checking, disable flags and disable alarms. Set1 = 2; Enable the auto adjust volume calculation, disable self-checking, disable flags and disable alarms. Set1 = 3; Disable the auto adjust volume calculation, disable self-checking, disable flags and disable alarms. Un-Adj Set (Set2) - This section shows how the "Mechanical" or Un-Adjusted volume is properly calculated using the pulses from the Main rotor only. This volume is to be used in the measurement totalization when pulses from the Sensing rotor are unavailable or when the gas flow rate is below the minimum for the Adjusted output. Set2 = 0; Enable the UN-Adjusted volume calculation. Set2 = 1; Disable the UN-Adjusted volume calculation 52-0003-0005/Rev B Page 7 of 11

Meter Run Data To configure meter run setup on the flow computer LCD display, press [Prog] [Meter] [n] [Enter] on the OMNI front panel keypad (where n equals the meter run number, 1 to 4, you want to setup) when in the setup Mode. The following entries will display: METER RUN #1 Meter ID Select Product No. GC Stream # Flow Low Flow High G FullScal M FullScal Active Freq. M.R.Factor S.R.Factor M.O.Factor A_bar% BTSF AlarmBand H% Alarm Band L% Warning Hi % Warning Lo % AutoAdj Set Un-Adj Set Meter Factor Meter Model Meter Size Serial No. Select Trans Dens? Warning and Alarm Messages The following warning or alarm messages will be displayed when the alarm condition occurs: AAT ABN Warning AAT ABN Alarm Non-steady Flow Alarm Non-steady Flow Warning No Flow or No Pulses (Both) Leakage/Resonant No-Net Flow No Main Rotor Pulses No Sensing Rotor Pulses 52-0003-0005/Rev B Page 8 of 11

Flow Computer es and Index Numbers The Tables 1 thru 4 list the Modbus database addresses within the OMNI assigned to the Auto-Adjust Turbo metering feature. These tables are categorized per data type. Table 1. Meter Run Alarm & Status Points Real Time Data Description for Meter Run Number Description for Meter Run Number 1 2 3 4 1 2 3 4 AAT ABN Warning 2178 2278 2378 2478 System Status Word 3158 3258 3358 3458 AAT ABN Alarm 2179 2279 2379 2479 Non-Steady Flow Status 3159 3259 3359 3459 Non-steady Flow Alarm 2180 2280 2380 2480 Auto Adj. Abnormal Status 3160 3260 3360 3460 Non-steady Flow Warning 2181 2281 2381 2481 Auto Adjust Alarm Status 3161 3261 3361 3461 No Flow or No Pulses (Both) 2182 2282 2382 2482 Warning/alarm message #1 Leakage/Resonant No-Net Flow 2183 2283 2383 2483 Warning/alarm message #2 No Main Rotor Pulses 2184 2284 2384 2484 Warning/alarm message #3 No Sensing Rotor Pulses 2185 2285 2385 2485 Table 2. Meter Configuration & Setup Entry Data 4123 4223 4323 4423 4124 4224 4324 4424 4125 4225 4325 4425 Description for Meter Run Number Description for Meter Run Number 1 2 3 4 1 2 3 4 M.R. Factor 17501 17601 17701 17801 Auto Adjust Set (Set 1) 3156 3256 3356 3456 S.R. Factor 17502 17602 17702 17802 Un-Adjusted Set (Set 1) 3157 3257 3357 3457 M.O. Factor 17503 17603 17703 17803 A_Bar % 17504 17604 17704 17804 Blade Tip Sensor (BTSF) 17505 17605 17705 17805 Alarm Band High Limit % 17506 17606 17706 17806 Alarm Band Low Limit % 17507 17607 17707 17807 Warning Band High Limit % 17508 17608 17708 17808 Warning Band Low Limit % 17509 17609 17709 17809 52-0003-0005/Rev B Page 9 of 11

Table 3. 32-Bit Integer Data Description for Meter Run Number Description for Meter Run Number 1 2 3 4 1 2 3 4 Sensing Rotor Pulses (Batch) 5196 5296 5396 5496 Sensing Rotor Pulses (Daily) 5197 5297 5397 5497 Cumulative Un-Adjusted Total 5198 5298 5398 5498 Table 4. 32-Bit IEEE Floating Point Data Description for Meter Run Number Description for Meter Run Number 1 2 3 4 1 2 3 4 Previous Hour Average Delta A 8528 8628 8728 8828 Previous Day Average Delta A 8546 8646 8746 8846 Calculated Delta A 8569 8669 8769 8869 52-0003-0005/Rev B Page 10 of 11

DOCUMENT REVISION HISTORY DOCUMENT INITIAL RELEASE DATE... 14-March-2001 REVISION DATE PURPOSE / CHANGE REQUEST A 14-March-2001 Maintained on the web - Initial release B 19-June-2009 DCR 090208 52-0003-0005/Rev B Page 11 of 11