Guidelines for connection of generators:

Similar documents
Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Jemena Electricity Networks (Vic) Ltd

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Technical Requirements for Renewable Energy Power System

PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION

TRANSMISSION PLANNING CRITERIA

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

APPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION

Louisville Gas and Electric Company

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

Large Embedded Generation User Guide A

Switchgear and Distribution Systems for Engineers and Technicians

Electric Networks/Ina Lehto Updated Original 12/2011

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

Small Electrical Systems (Microgrids)

Copyright 2003 Advanced Power Technologies, Inc.

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Enquiry Form (Non-Registered Generator With Capacity less than 5 MW)

Small Generator Interconnection Program Interconnection Technical Requirements

Net +Plus Connection Code

Standards, Procedures and Policies for Grid Connection

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001

GUIDELINES FOR GRID INTERCONNECTION OF SMALL POWER PROJECTS IN TANZANIA

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Company Directive STANDARD TECHNIQUE: SD4O/1. Standard HV Connection Arrangements

100 MW Wind Generation Project

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 CHARACTER OF SERVICE

Renewable Generation Electrical Infrastructure and Grid Connection Services Provided by Power Systems Project and Consultancy Services (PCS) Ltd

On_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines.

Interconnection Feasibility Study Report GIP-226-FEAS-R3

Net Metering Interconnection Requirements

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Overview of State Distributed Generation Interconnection Rules

3.7 Areas where increasing levels of DER potentially affects operation of the system under Emergency Conditions

Major Customer Connections. Preliminary Enquiry Form Embedded Generation > 30 kw

Unit Protection System for Pumped-Storage Power Stations

CHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.

Proposed New ISO Rules Section Version 2.0 Generating Unit Technical Requirements ( New ISO Rules Section Version 2.

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

Comments on the Solar Alliance Proposal for Changes to New Jersey Interconnection Rules

NS194B Guidelines for Rotating Machines Connected to the Ausgrid Network. October 2014

Generator Interconnection System Impact Study For

Appendix A2: Technical Requirements for Distributed Generators > 10 kw to be Connected to Kitchener-Wilmot Hydro Inc. s Distribution System

Emerald Reactive Support Alternative Solution Expressions of interest

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.

SUBSTATION INTERLOCKING SCHEMES

Exemptions currently in force

List of exemptions from compliance with the Technical Rules granted by Western Power after 1 July 2007

Customer Guidelines for Low Voltage Connected. Embedded Generation

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011

RULES & REGULATIONS FOR RENEWABLE GENERATION SYSTEMS 2. SUMMARY OF APPLICATION AND INTERCONNECTION PROCESS

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS

AGN Alternator Ratings and Overload

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

GUIDELINES FOR OPERATING, METERING AND PROTECTIVE RELAYING FOR. NET METERED SYSTEMS UP TO 50 kw AND BELOW 750 VOLTS

POWER SYSTEM OPERATING INCIDENT REPORT: TRIP OF 837 TARONG MT. ENGLAND 275 KV LINE AND MT. ENGLAND NO KV BUSBAR ON 30 OCTOBER 2011

New Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities

Key elements of the AS3000 Wiring standards and some of the recent changes.

Northeastern Rural Electric Membership Corporation Columbia City, Indiana

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010

DISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase

APPLICATION ELECTRICITY SERVICES. APPLICATION FOR THE CONNECTION OF SMALL SCALE EMBEDDED GENERATION Page 1

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5

AGN 041 Alternator Operating Speed

PHILIPPINE DISTRIBUTION CODE 2017 EDITION

CHAPTER 4 PROTECTION REQUIREMENTS

Western Power s list of exemptions from compliance from Technical Rules granted after 1 July 2007.

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA

Technical Guidance for Customer Export Limiting Schemes

Effective discrimination of protective devices

STATE OF NORTH DAKOTA DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS TABLE OF CONTENTS

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

GENERATING FACILITY INTERCONNECTION APPLICATION. Part 1 Introduction and Overview

POWER SYSTEM OPERATING INCIDENT REPORT LIGHTNING STRIKES IN TASMANIA AND PACIFIC ALUMINIUM POTLINE LOAD REDUCTIONS 21 MARCH 2013

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw

Unified requirements for systems with voltages above 1 kv up to 15 kv

Grid Stability Analysis for High Penetration Solar Photovoltaics

Title Electrical Technical Maintenance Coding System. Reference Number PMP 01 (RIC Standard: EP SP)

AS/NZS AS/NZS

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Transformer Protection

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010

Technical Requirements for Export Limiting Schemes

National Distributed Energy Resources Grid Connection Guidelines. Technical Guidelines for Basic Micro EG Connections

SNZ TR 6120:2014. New Zealand Technical Report. Low voltage supply earthing systems SNZ TR 6120:2014

Transcription:

Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14

Contents 1 INTRODUCTION... 3 1.1 WHO THE GUIDELINES APPLY TO... 3 1.2 QUALIFIER... 3 2 WESTERN POWER POLICY... 3 3 APPROVALS REQUIRED... 3 3.1 WESTERN POWER... 3 3.2 OTHER APPROVALS... 3 4 KEY TECHNICAL ISSUES... 4 4.1 SYSTEM ISSUES... 4 4.2 CONNECTION ISSUES... 4 5 REQUIREMENTS OF THE WESTERN POWER S TECHNICAL RULES... 5 5.1 APPLICABLE CLAUSES... 5 6 INITIAL ASSESSMENT OF IMPACT OF A GENERATOR ON THE DISTRIBUTION SYSTEM... 7 7 REQUIREMENTS OF CLAUSE 3.6 OF THE TECHNICAL RULES... 7 7.1 3.6.3 INFORMATION TO BE PROVIDED BY THE GENERATOR... 7 7.2 3.6.10 PROTECTION... 8 7.2.1 Islanding protection... 8 7.3 3.6.11 COMMISSIONING AND TESTING... 13 7.4 3.6.12 TECHNICAL MATTERS TO BE COORDINATED... 13 7.5 5.3 POWER SYSTEM OPERATION CO ORDINATION RESPONSIBILITIES... 13 APPENDIX 1 ADDITIONAL REFERENCE DOCUMENTS... 14 A.1 AUSTRALIAN AND INTERNATIONAL STANDARDS... 14 EDM 32419002 / DM 13529244 Page 2 of 14

1 Introduction 1.1 Who the guidelines apply to This document is intended to assist Users planning to connect small generators to the Western Power Network (WPN). It addresses planning, design, compliance and operational issues. It provides detailed explanation of the requirements of section 3.6 of the Technical Rules applicable to all generator types up to 10 MW (except approved AS/NZS 4777 compliant inverter connected generating units rated up to 10 kva single phase and up to 30 kva three phase in respect of which section 3.7 applies). This document complements another document Detailed customer connection schedules for small generator installations and both documents are available from the Western Power internet site. The approved Technical Rules are available from Economic Regulation Authority (ERA) internet sites. 1.2 Qualifier This document is a guideline and does not diminish, alter or replace any requirements. If an inconsistency should arise, the Technical Rules document shall prevail. 2 Western Power policy Western Power will provide a connection to the distribution network for any generator in this category, provided that: a) the safety of Western Power operational personnel, other customers, contractors and the general public is not put at risk; b) the integrity of other customers plant and equipment is not put at risk; c) reliability and quality of supply to other customers is not adversely affected; and d) the proposed plant meets the requirements of the Technical Rules. 3 Approvals required 3.1 Western Power All exporting and non-exporting generators seeking a connection to the Western Power s network (WPN) must make a formal application for network access in accordance with Western Power policies and procedures. 3.2 Other approvals It is the responsibility of the generators to meet all registration requirements, environmental and safety codes, and to seek approval from any relevant bodies including but not limited to: Economic Regulation Authority (ERA), Energy Safety, applicable local government, Environmental protection Authority (EPA) and various other applicable Australian Standards. EDM 32419002 / DM 13529244 Page 3 of 14

4 Key technical issues Promotion of renewable sources of energy is likely to result in an increasing amount of distribution connected generation in the WPN, both intermittent and non-intermittent. Of initial concern to Western Power in evaluating applications will be the impact of proposed generators on other users and on the system in the vicinity of the point of connection. However, the collective impact of all distribution connected generators is also important and will be assessed. 4.1 System issues As the penetration of distributed generation increases it will become increasingly important that a power system disturbance does not result in the disconnection of multiple small generators, which would compound and magnify the effect of the disturbance. This could eventually have significant impact on the control of system frequency in the WPN, which being a small isolated system, is more vulnerable to frequency excursions than larger systems and those with interconnection and support from neighbouring systems. Protecting the system from the disturbance that disconnection of multiple small generators in sympathy with a large transmission connected generator would create, carrying an increased amount of spinning reserve thus increasing the cost of system operation. Consequently Section 3.6 of the Technical Rules also addresses the fault ride through (FRT) capability, rotor angle stability and the frequency performance of distribution connected generators. 4.2 Connection issues Issues that arise when connecting generators to the distribution system and which are addressed by Section 3.6 of the Technical Rules are: a) Network operators must be confident of the status of embedded generation when performing switching and maintenance. Depending on the degree of risk posed by facilities, this will require varying combinations of automatic protections, interlocks, inter-tripping, and remote indication, control and interlocking from the network control centre. b) Embedded generators exporting to the network may create switching hazards for network operators by causing switch ratings to be exceeded. c) Embedded generation is not common in the network at present and distribution switchgear is generally not equipped with synchronizing and back-feed facilities. d) Inadvertent islanding of an embedded generator on to a part of the distribution network may create operator safety and quality of supply problems. The generator protection may be unable to detect certain network faults. Inadvertent reclosing of a switch on to an undetected island may result in severe customer plant damage. e) An embedded generator may substantially increase distribution network fault levels and thermal loadings so that plant ratings may be exceeded in the network and at other customer facilities. f) The connection and disconnection of a generator will cause disturbing voltage transients and step voltage changes to the extent that the voltage limits at the point of connection and at other customer connections on the same feeder may be exceeded. EDM 32419002 / DM 13529244 Page 4 of 14

g) Inverter connected and wind generation will contribute to network harmonics and flicker at other customer installations. h) Distribution connected generators are generally more likely to become unstable during power system disturbances than transmission connected generators because of low inertia, higher interconnecting impedances and slower distribution system fault clearing times, thereby amplifying the disturbance and slowing the restoration. In the assessment of an application for embedded generator access, the main issues Western Power will cover are: i) risks to the safety of public, operating personnel and plant; j) the proportion of time the generator will remain connected and implications for protection and operational safety; k) the performance of proposed protection systems and compliance with relevant standards; l) protection against islanding of a generator with parts of the local distribution system; m) visibility to maintenance staff and control centre operators of generating plant status and requirements for isolation and remote control; n) short circuit currents, plant and switchgear ratings; o) local voltage rise and voltage transients caused by the generator; p) network thermal loadings; q) levels of harmonics and flicker; r) generator instability and the likely consequences. In terms of the collective effect of small generators on overall system security, the main issues Western Power will consider are: s) generator fault ride through capability; t) generator under and over frequency performance, including islanding. 5 Requirements of the Western Power s Technical Rules 5.1 Applicable clauses While other parts of the Technical Rules document can apply to small generators, the requirements for embedded generators are found primarily in Section 3.6 Requirements for connection of small generators to the distribution network. Table 3.4 of section 3.6 provides references to the applicable clauses of section 3.3 Requirements for connection of generators. To further assist Users, sections of the Technical Rules (other than 3.6) that may be of significance to an embedded generator facility are listed in Table 1 below. Table 1 - Clauses of WPN Technical Rules applicable to distribution connected generators Clause Requirement Notes on content 1 General 2.2 Power system performance standards Standards for voltage, frequency, harmonics, flicker etc to the extent required by clause 3.6.8. EDM 32419002 / DM 13529244 Page 5 of 14

2.3 Obligation of the Network Service Provider in relation to power system performance 2.5.5 Planning criteria: High Voltage Distribution System 2.5.6 Planning criteria: Low Voltage Distribution System NSP study of system performance with proposed connections may determine particular User performance requirements and network augmentations. Relates to standards of reliability of the network. Relates to standards of reliability of the network. Obligation to connect underground. 2.5.7 Fault limits Relates to permissible User contribution to fault current at point of connection. 2.5.8 Maximum fault currents 2.7 Design and construction standards 2.8 Distribution conductor or cable selection 2.9 Transmission and Distribution system protection 3.2.3 User s power quality monitoring equipment 3.3 Requirements for connection of generators 3.4 Requirements for connection of loads 3.5 User s protection requirements 3.7 Requirements for connection of energy systems to low voltage distribution system via inverters 4.1 Inspection and testing 4.2 Commissioning of User s equipment 4.3 Disconnection and reconnection 5.1 System operation and coordination: Design and construction standards for fault current withstand. Obligation of the NSP (and hence User) to comply with recognised standards. Obligation of the NSP to accommodate forecast load growth in selection of conductor or cable size. Includes reference to requirement for independence of islanding protection types. Possible requirement for the User to accommodate NSP power quality monitoring and recording equipment. Additional parts thereof referred to in Table 3.5 of clause 3.6. Where the facility subject of the access application includes an associated load. The qualifier of clause 3.5.1(a) applies to the islanding protection for all small power stations under clause 3.6. Whereas clause 3.7 only covers installations up to 30 kva in accordance with AS 4777, the requirements nevertheless apply in principle to larger inverter-connected energy systems otherwise covered by clause 3.6. All aspects of rights, requirements and obligations related to testing and commissioning of an installation. The requirements of clause 4.2 form part of the commissioning requirements for distribution connected generators. Defines circumstances under which the NSP will exercise right to disconnect. Relevant for power stations of all sizes. Relates to roles of market operations and EDM 32419002 / DM 13529244 Page 6 of 14

Application 5.3 System operation coordination responsibilities & obligations 5.7 Power system security operation and coordination 5.8 Operation and maintenance planning 5.9 Power system operating procedures 5.10 Power system operation support 5.11 Nomenclature standards Attachment 10 Distribution system connected generators up to 10MW Attachment 12 Testing and commissioning of small power stations network operations. Defines both NSP and User obligations. Relates to the obligations of the User to advise the NSP and NSP management of supply shortfall events, including requirement to reduce loads. For power stations exporting more than 1MW. Requirement for User to follow procedures and rules. Relates to remote control and monitoring, standards and protocols. Information to be supplied with application for connection. Testing and commissioning requirements for connection to the distribution system. 6 Initial assessment of impact of a generator on the distribution system While a formal Western Power response to an application for access will usually require load-flow, fault level, and in some cases, harmonic and dynamic studies, it is usually possible to conduct an approximate initial assessment of the extent to which a proposed installation would impact the local power system. Sections that follow provide methods for quick assessment (where feasible) of the extent to which a proposed installation might affect the integrity of the network and operational safety. 7 Requirements of Clause 3.6 of the Technical Rules The following section clarifies some of the requirements of the clause 3.6 of the Technical Rules for the embedded generators. 7.1 3.6.3 Information to be provided by the Generator The application form for connection of a distribution generator is available on-line from Western Power: http://www.westernpower.com.au/maincontent/connectionsupgrades/newconnections/gen erators.html EDM 32419002 / DM 13529244 Page 7 of 14

This document is based on Attachment 10 of the Technical Rules. The application form assumes that no transient stability studies will be required. Should such studies be required, Western Power will request additional information similar to that specified for transmission connected generators including models for dynamic simulation. 7.2 3.6.10 Protection Protection requirements for small generators are defined by clause 3.6.10. The Technical Rules requires duplication of the islanding protection. This duplication is not required for bumpless transfer generators, as per clause 3.6.10.1(l) for rapid bumpless transfer and clause 3.6.10.3(b) for gradual bumpless transfer. To provide guidance in what Western Power may require for individual applications Table 2 shows an interpretation of these protection requirements. 7.2.1 Islanding protection Following network switching both manual and automatic, there is the possibility that an embedded generator will become islanded with a section of the Western Power network. This constitutes a hazard with implications for operator safety, quality of supply, protection incompatibility, and potential damage to the embedded generators through out of synchronism switching. Required islanding protection would normally detect this situation and disconnect the embedded generator. It is important that the islanding protection operates within the specified 2 seconds to avoid out-of-synchronism operation of a recloser and thus avoid damage to the generator. Where sustained parallel operation is the mode of the generating unit, a specialist loss of mains protection function must be included in each of two independent protection schemes. Generating units designed for gradual bumpless transfer must be protected with at least one type of loss of mains protection. The protection functions used must be selected and set to enable them to detect the islanding condition. Where there is no export of power into the network and the aggregate rating is less than 150kVA, both independent islanding protection schemes can be in the form of a directional power function that will operate for power export. Directional overcurrent relays may also be used for this purpose. There is the possibility that, should the residual network load approximately match the generator export at the time, the loss of mains protection would not detect the abnormal situation. In these circumstances, when Western Power believes that rate of change of frequency and voltage vector shift will not adequately safeguard from islanding, then, Western Power may also specify remote control and/or interlocking so that, for example, the operation of a zone substation circuit breaker also trips the connection to the generator. EDM 32419002 / DM 13529244 Page 8 of 14

Table 2: Summary of protection requirements for inverter coupled generating units between 30kVA and 10 MVA Protection required for distribution system (see all Notes below) Distribution HV connected Permanent parallel operation Occasional parallel operation Distribution LV connected Type Technical Rules 2016 Clause(s) No export Export up to 1 MVA Aggregate capacity kva > 1 MVA Under / over voltage & frequency 3.6.10.1(f) & 3.6.10.3 Overcurrent 3.6.10.1 (f) Loss of one or more phases 3.6.10.1(h) Directional power (export) 3.6.10.1(h) & (i) Directional overcurrent 3.6.10.1(h) & (i) Rate of change of frequency 3.6.10.3 Voltage vector shift 3.6.10.3 Neutral voltage displacement see Note 8 3.6.10.1(g) Earth fault 3.6.10.1(g) Sensitive earth fault 3.6.10.1(g) Disconnection by timer Pole slipping 3.6.10.1(k) see Note 3 3.6.10.2 a/r a/r a/r a/r EDM 32419002 / DM 13529244 Page 9 of 14

Notes: 1. The symbol indicates required protection. 2. Loss of a protection supply must immediately trip all switches that depend on that supply for operation of their protection. 3. Term a/r means as required, will be determined as per clause 3.6.10.2 4. Requirements are determined by the Technical Rules. This table is for guidance only. 5. Protection functions shaded light green are alternatives for export limiting. Directional power (export) protection monitors power in the export direction not to exceed the export limit: a) directional/reverse power protection is not required under cl. 3.6.10.1(i) where an approved inverter has an agreed connection at its name plate capacity b) if an inverter is capable of exceeding the agreed export limit (at all), then directional/reverse power protection is required. c) reverse power protection is set and tested with settings taking account of the pickup current in sensing devices. No more sensing allowance can be made other than that required for reliable operation of the protection relay in preventing exported power. 6. Protection functions shaded blue are alternatives for loss of mains protection. 7. Protection functions shaded yellow are alternatives for earth fault protection. The use of overcurrent earth fault protection or neutral voltage displacement depends on the type of the earthing arrangement in the installation (earthed/unearthed). For example, the earth fault overcurrent protection is required in earthed systems. 8. NVD exemption may apply for eligible LV connected inverters rated at greater than 30 kva and not more than 1 MVA. EDM 32419002 / DM 13529244 Page 10 of 14

Table 3 Summary of protection requirements for small generating units up to 10 MVA (no inverter) Protection required for distribution system Type Under / over voltage & frequency (see all Notes below) Technical Rules 2016 Clause(s) 3.6.10.1(f) & 3.6.10.3 Permanent parallel operation Occasional parallel operation HV connected No export Export LV connected Aggregate capacity kva 150 >150 Short term test parallel HV connected LV connected Aggregate capacity above 1 MVA Rapid ( 1s) Bumpless Transfer Gradual ( 60s) Overcurrent 3.6.10.1 (f) Loss of one or more phases Directional power (export) Directional overcurrent Rate of change of frequency Voltage vector shift Neutral voltage displacement 3.6.10.1(h) 3.6.10.1(h) & (i) 3.6.10.1(h) & (i) 3.6.10.1(h) 3.6.10.3 3.6.10.1(h) 3.6.10.3 3.6.10.1(g) Earth fault 3.6.10.1(g) Sensitive earth fault 3.6.10.1(g) Disconnection by timer 3.6.10.1(k) Pole slipping see Note 3 3.6.10.2 a/r a/r a/r a/r a/r a/r a/r EDM 32419002 / DM 13529244 Page 11 of 14

Notes: 1. The symbol indicates required protection. 2. Loss of a protection supply must immediately trip all switches that depend on that supply for operation of their protection. 3. Term a/r means as required, will be determined as per clause 3.6.10.2 4. Requirements are determined by the Technical Rules. This table is for guidance only. 5. Protection functions shaded light green are alternatives for export limiting. Directional power (export) protection monitors power in the export direction not to exceed the export limit: a) directional/reverse power protection is not required under cl. 3.6.10.1(i) where an approved inverter has an agreed connection at its name plate capacity b) if an inverter is capable of exceeding the agreed export limit (at all), then directional/reverse power protection is required. c) reverse power protection is set and tested with settings taking account of the pickup current in sensing devices. No more sensing allowance can be made other than that required for reliable operation of the protection relay in preventing exported power. 6. Protection functions shaded blue are alternatives for loss of mains protection. 7. Protection functions shaded yellow are alternatives for earth fault protection. The use of overcurrent earth fault protection or neutral voltage displacement depends on the type of the earthing arrangement in the installation (earthed/unearthed). For example, the earth fault overcurrent protection is required in earthed systems. EDM 32419002 / DM 13529244 Page 12 of 14

7.3 3.6.11 Commissioning and testing As stated, requirements for embedded generators are listed in Attachment 12. Western Power document Detailed customer connection schedules for small generator installations, Schedule C Part 1 Commissioning, and Part 2 Approval to Operate, are templates based on Attachment 12. 7.4 3.6.12 Technical matters to be coordinated Matters to be coordinated include the general design of the User s facility in accordance with good engineering practice and relevant standards. Some of these issues are beyond the scope of this document. However of particular importance will be the vector grouping and tap range of the connecting transformer and the load and fault ratings of other primary plant such as circuit breakers and switches. These will be the most costly items in terms of the viability of connecting to the network. 7.5 5.3 Power system operation co-ordination responsibilities The title of this section explains well its purpose. Relevant clauses from this section of the Rules are listed in Table 1 of this document. Obligations of the user in relation to operation and coordination are summarised in Western Power template document Detailed customer connection schedules for small generator installations, Schedule B Part 1 Operating Procedures and Part 2 Remote control monitoring and communications. EDM 32419002 / DM 13529244 Page 13 of 14

Appendix 1 - Additional Reference Documents A.1 Australian and international standards AS 3010 (2005) Electrical installations Generating sets AS 1359 (1997) AS/NZS 3000 AS/NZS 4777 AS 1940 General requirements for rotating electrical machines SAA Wiring Rules - in particular sections relating to earthing, clearances and hazardous areas Grid Connection of Energy Systems via Inverters Storage and handling of flammable and combustible liquids AS 60947.6.2 (2004) Automatic transfer switches IEC 60255 Protective relays series of standards EDM 32419002 / DM 13529244 Page 14 of 14