1 Stakeholder Comment and Rationale Form AESO AUTHORITATIVE DOCUMENT PROCESS Stakeholder Consultation Draft Proposed New ISO Rules Section Version 2.0 Generating Unit Technical Requirements ( New ISO Rules Section Version 2.0 ) Date of Request for Comment [yyyy/mm/dd]: 2012/11/29 Period of Consultation [yyyy/mm/dd]: 2012/11/29 through 2012/12/14 Comments From: TransAlta Corporation Date [yyyy/mm/dd]: January 18, 2013 Contact: Bob Smith Phone: bob_smith@transalta.com Listed below is the summary description of changes for the proposed new, removed or amended sections of the ISO rules. Please refer back to the Letter of Notice under the Attachments to Letter of Notice section to view the actual proposed content changes to the ISO rules. Please place your comments / reasons for position underneath (if any). 1. ISO Rules Stakeholder Comments and/or Alternative Proposal AESO Replies (c) New Proposed New ISO Rules Section Version 2.0 sets out the minimum technical requirements for a legal owner connecting a generating unit to the transmission system. After considering stakeholder comments on proposed New ISO Rules Section 502.5, the AESO is proposing New ISO Rules Section Version 2.0, which includes the following key changes from proposed New ISO Rules Section 502.5: 1. Amended the language to improve clarity without any intended change to the technical requirements; Please refer the detailed comments below 1 TransAlta is unclear on how the new Section version 2.0 subsections 1, 2, and 6 adequately cover the previous Section version 1.0 subsection References to existing and new generating units have been removed to avoid confusion. Proposed New ISO Rules Section Version 2.0 applies to both new and existing generating units. This resulted in subsections 2 and 3 of proposed New ISO Rules Section being removed in its entirety from proposed New ISO Rules Section Version 2.0; 3. Subsection 6 has been removed to improve clarity although elements of Issued for Stakeholder Consultation: Page 1 of 6
2 subsection have been inserted into the appropriate relevant subsections; 4. Removed subsection 12.3 of proposed New ISO Rules Section so that this requirement can be more fully consulted on at some future time; 5. Amended subsection 15 to clarify what would be considered a simultaneous trip of multiple generating units and to allow for the trip of a combustion turbine to result in the trip of a steam turbine in combined cycle plants; 6. Removed the operating requirements and relocated these operating requirements into proposed New ISO Rules Section Generating Unit Operating Requirements ( New ISO Rules Section ) such that proposed New ISO Rules Section Version 2.0 now only contains technical requirements. Click here to access the Letter of Notice for proposed New ISO Rules Section 502.6; 7. Removed content related to the submission of modeling data to eliminate duplication with ISO OPP 1306 Reporting Equipment Changes;. 8. Removed appendices where the content was determined to be informational in nature; 9. Added an appendix relating to voltage-ride-through requirements for existing generating units; and 10. Removed the subsection referencing reactive power requirements for generating units with power purchase agreements. The AESO agreed with stakeholder comments that a single section referencing the requirements for all generating units was sufficient and improves clarity. The AESO is seeking comments from stakeholders with regard to the following matters: 1. In developing proposed New ISO Rules Section Version 2.0, the AESO did not intentionally change the intent of the technical requirements from proposed New ISO Rules Section If you disagree, please identify the specific requirement(s) where you believe the intent has changed. 2. Proposed New ISO Rules Section Version 2.0 remains consistent with the AESO s Generator and Load Interconnection Standard, except for the specific requirements added, which are only applicable to new generating Issued for Stakeholder Consultation: Page 2 of 6
3 units, and where the functional specification references ISO Rules Section 502.5, once effective, or if specific equipment is changed on planned basis. If you disagree please identify the specific requirements that are not consistent with the AESO s Generator and Load Interconnection Standard. 3. Are there any subsections where stakeholders feel that language does not clearly articulate the requirement for either the AESO or a market participant? If yes, please indicate the subsections and suggest language that would improve the clarity. (d) Other Stakeholders wishing to comment on specific provisions are requested to copy the provision into this area and provide comments. 2(1) The ISO must, in accordance and generally consistent with this section and any other applicable ISO rules, approve of a functional specification containing further details, work requirements, and specifications for the design, construction and operation of a generating unit connection project and any associated transmission system connection facilities. (2) The functional specification for the generating unit referred to in subsection 2(1) must be generally consistent with the provisions of this section 502.5, but may contain material variances the ISO approves of based upon its discrete analysis of any one (1) or more of the technical, economic, safety, operational and reliability requirements of the interconnected electric system related to the specific connection project. 5(2) The generating unit and any approved external reactive power resources must have the capability to operate in accordance with subsection 5(3) by both: 5(3) The reactive power capability of the generating unit must be in compliance with the following minimum requirements: (a) zero point nine (0.9) power factor, over-excited; and (b) zero point nine five (0.95) power factor, under-excited; based on the maximum authorized real power of the generating unit over the entire real power operating range, down to the applicable minimum gross real power. (4) The generating unit, subject to subsections 5(5), must not have limiters set to reduce the reactive power capability set out in subsection 5(3). Comment # 2: 2(1)(2) TransAlta recommends to reword section 2(2) to incorporate the need for the GFO to review and agree with any AESO analysis of issues that impact the GFO. 5(3)(4) TransAlta recommends to re-word section 5(4) to indicate the suitable application of limiters as per industry practice, to protect the generator based on the individual unit s design/condition/risk considerations. TransAlta submits that the reactive capability of the generator will need to be in line with industry standards as well as any specific OEM design considerations and capability curves that may be issued. Note that the OEM can issue specific design limitations and capability curves based on present day industry experience of generator failures and the subsequent studies of generator design. These studies have used modern analysis techniques to assess design deficiencies. Issued for Stakeholder Consultation: Page 3 of 6
4 (5) (5) The legal owner of a generating unit with the capability to meet the reactive power requirements of this subsection 5 but which has stability concerns must submit in writing to the ISO: (a) a request for approval of a proposed reduction in the reactive power capability requirement set out in subsection 5(3)(b) due to generating unit stability concerns; and (b) a detailed study in support of the request which is specific for the generating unit at its location and completed by a qualified professional engineer, demonstrating the reactive power capability set out in subsection 5(3)(b) should be reduced by a limiter because that reactive power capability will cause the generating unit to become unstable. (5) (5) TransAlta submits that, in addition to any reduction due to any stability concerns, provision shall be provided for any reduction in reactive power due to machine design considerations/revised manufacturer capability curves as a result of condition/risk considerations. (5) (7) The legal owner of a generating unit without the capability to meet the reactive power capability must submit to the ISO a request in writing for approval of the use of an external dynamic reactive power resource to compensate for the lack of capability such that the combined capability of the generating unit and external dynamic reactive power resource meets the requirements of subsection 5(3). (5) (7) TransAlta submits that any external dynamic reactive power resources should be designed and implemented by the AESO. (6)(2) The legal owner of a generating unit must determine the root mean square phase-to-phase voltage value at the high voltage side of the transmission system step-up transformer to be used as the one hundred percent (100%) voltage value to determine the voltage ride-through requirements for the generating unit. (3) A generating unit must be capable of meeting the following voltage ridethrough requirements: (a) continuous operation between ninety percent (90%) and one hundred and ten percent (110%) of the voltage value documented under subsection 6(2); and (b) not tripping or going off-line during or as a result of a voltage dip or posttransient voltage deviation resulting from a normally cleared disturbance on the transmission system on any phase or combination of phases at or beyond the point of connection as illustrated in Appendix 1. (4) The normal clearing time used in subsection 6(3)(b) must be based on the specific location where the generating unit is connected to the transmission system. (6-3) (a) TransAlta submits that the continuous operation capability of the generator is 95%-105% of the generator rated terminal voltage as per IEEE. Based on this, there may be concerns with the continuous operation of the generator for a voltage range of 90%- 110% at the HV side of the GSU and this will need to be studied. (6-3) (b) TransAlta submits that AESO requirements of the shaded region transient voltage no-trip zone of 625ms (Appendix 1) is not clear and contradicts the solid time curve. The shaded zone should be removed from the plot for clarity. Since checks will be needed to confirm a ride through capability, TransAlta requires time to study the implications of this requirement. (4) TransAlta suggests for AESO to identify the normal clearing time at the specific generating locations Issued for Stakeholder Consultation: Page 4 of 6
5 (7)(2) The legal owner of a generating unit must determine the root mean square phase-to-phase voltage value at the transmission system step-up transformer of the generating unit to be used as the one hundred percent (100%) voltage value to determine the voltage ride through requirements for the generating unit. (3) The legal owner of a new generating unit must ensure the generating unit is capable of meeting the following voltage ride-through requirements: (a) continuous operation between ninety percent (90%) and one hundred and ten percent (110%) of the voltage value documented under subsection 7(2); and (b) not tripping or going off-line during or as a result of a voltage dip or posttransient voltage deviation resulting from a normally cleared transmission system disturbance on any phase or combination of phases at or beyond the point of connection as illustrated in Appendix 2; and (c) the time that the voltage remains at zero point zero percent (0.0%) must be based on the normal clearing time for a three (3) phase fault at the specific location where the generating unit is connected to the transmission system. (4) The normal clearing time used in subsection 7(3)(b) must be based on the specific location where the generating unit is connected to the transmission system. (5) Notwithstanding any other provision of this subsection 7, a generating unit is not required to ride-through a transmission system fault that: (a) causes a forced outage of a radial transmission line connecting the generating unit to the transmission system; (b) occurs on the generating unit side of the point of connection, including the lower voltage network and the substation; or (c) results in a transfer trip or anti-islanding protection scheme to activate at the generating unit which will cause the generating unit to be disconnected from the transmission system. (8)(2)(c) be capable of manual set point adjustments to a percentage between ninety five percent (95%) and one hundred and five percent (105%) of the operating voltage value determined under subsection 6(1); and (7)(3) (a) TransAlta submits that the continuous operation capability of the generator is 95%-105% of the generator rated terminal voltage as per IEEE. Based on this, there may be concerns with the continuous operation of the generator for a voltage range of 90%- 110% at the HV side of the GSU and this will need to be studied. (7)(3) (b) AESO to clarify why voltage dip is down to 0 % instead of 15 %? (7)(3) (c) TransAlta suggests for AESO to identify the normal clearing time at the specific generating locations (7)(4) TransAlta suggests for AESO to identify the normal clearing time at the specific generating locations (7)(5) TransAlta recommends to add -- (d) which will cause the generating unit to be disconnected from the transmission system. (8)(2)(b) and (c) TransAlta submits that the AVR can only control voltage on the generator terminals and not on the HV side of the GSU transformer (8)(2)(c) Please note reference to Subsection (6)(1) is not correct. Issued for Stakeholder Consultation: Page 5 of 6
6 10(3) Notwithstanding subsection 11(1) and 11(2), a power system stabilizer is not required to be installed on a generating unit if the closed loop phase lag between the generating unit stator winding terminals voltage and the automatic voltage regulator 10(3) Please note that references of 11(1) and 11(2) should be 10(1) and 10(2). 11(2) The legal owner of a generating unit may subtract the amount of auxiliary and excitation system load in apparent power from the apparent power capability of the generating unit at the maximum authorized real power to determine the net real power and reactive power requirements of the transmission system step-up transformer referred to in subsection 11(1), but only if any of that auxiliary and excitation system load is connected between the generating unit stator winding terminals and the transmission system step-up transformer. 12(1)(a) Each generating unit must have auxiliary systems designed so that the failure of a single component will not result in the simultaneous tripping or shutdown of two (2) or more generating units; 11(2) AESO to include reference to IEEE C for GSU sizing methodology. 12(1) TransAlta suggests to add subject to normal operating conditions. Synchrophasor Measurement System 18(1) A new generating unit or an existing generating unit that undergoes a modification replacing the protection system must have a synchrophasor measurement system in compliance with the specifications contained in any related synchrophasor measurement system rule or standard. (3) The legal owner of the generating unit must design a system that is capable of downloading and retaining the recordings set out in subsection 18(2) for a period of one (1) calendar year from the date of the initial recording unless the ISO otherwise designates in the functional specification for the generating unit, 18(1) TransAlta submits that the modifications to protection systems are to be elaborated as replacement of the complete set of protection relays. Issued for Stakeholder Consultation: Page 6 of 6
Generating unit functional document submission form
Generating unit functional document submission form The below form must be completed and returned to generator.reports@aeso.ca. Supporting information to assist generating unit owners to complete this
More informationReactive Power Requirements and Financial Compensation. Addendum to Draft Final Proposal
Reactive Power Requirements and Financial Compensation July 21, 2016 Table of Contents 1. Introduction... 3 2. Changes to Proposal... 4 3. Plan for Stakeholder Engagement... 4 4.... 4 6. Next Steps...
More informationGuide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.
Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...
More informationFebruary 13, Docket No. ER ; ER Response to Request for Additional Information
California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 Re: California Independent System
More informationFunctional Specification Revision History
Functional Specification Revision History Revision Description of Revision Author Date B0 For comments Yale Zhou January 26, 2016 B1 Updated as per comments Yale Zhou February 1, 2016 Final issuance Yale
More informationA member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.
Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements
Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner
More informationLegal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:
Generating Facility Level 2 or 3 Interconnection Review (For Generating Facilities with Electric Nameplate Capacities no Larger than 20 MW) Instructions An Interconnection Customer who requests a Utah
More informationGeorgia Transmission Corporation Georgia Systems Operations Corporation
Georgia Transmission Corporation Georgia Systems Operations Corporation Reactive Power Requirements for Generating Facilities Interconnecting to the Georgia Integrated Transmission System with Georgia
More informationKey DRAFT OPERATING CODE 2 LEGAL TEXT
Key DRAFT OPERATING CODE 2 LEGAL TEXT 1) Blue Text From Grid Code 2) Black Text Changes / Additional words 3) Orange/ Brown text From RfG 4) Purple From HVDC Code 5) Green From DCC (not used in this document)
More informationINTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY
INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,
More informationGuidelines for connection of generators:
Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...
More informationPJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008
PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral
More informationAlberta Electric System Operator Saleski Transmission Project Needs Identification Document
Decision 2013-127 Alberta Electric System Operator Saleski Transmission Project Needs Identification Document ATCO Electric Ltd. Saleski 901S Substation and 144-kV Transmission Line 7L142 Facility Application
More informationStandard Authorization Request Form Regional Standard or Variance Texas Reliability Entity, Inc.
Standard Authorization Request Form Regional Standard or Variance Texas Reliability Entity, Inc. E-mail completed form to rsm@texasre.org Title of Proposed Regional Standard: BAL-001-TRE-1 SAR Requester
More informationGenerator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood
Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents
More informationNortheastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5
Columbia City, Indiana Page 1 of 5 SCHEDULE DG-2 LARGE POWER DISTRIBUTED GENERATION I. AVAILABILITY This Distributed Generation Rate is available to any member in good standing of Northeastern REMC (Northeastern)
More informationInterconnection Feasibility Study Report GIP-226-FEAS-R3
Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power
More informationAMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA
AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA AEP Texas (comprised of its Central and North Divisions
More informationDocument Requirements for Engineering Review- PV Systems v1.1 12/6/2018
Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Outlined below are the engineering documents and their associated minimum detail requirements for a Distributed Energy Resource (DER)
More informationGuideline for Parallel Grid Exit Point Connection 28/10/2010
Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND
More informationRULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)
- (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility
More informationPSNH INTERCONNECTION REQUEST
PSNH INTERCONNECTION REQUEST Send the completed Interconnection Request and required attachments to: Public Service of New Hampshire Attn: Michael Motta, Senior Engineer Supplemental Energy Sources P.
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less)
Section 466.APPENIX C Levels 2 to 4 Application Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less) Interconnection Customer Contact Information
More informationCHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.
25.211. Interconnection of On-Site Distributed Generation (DG). (a) (b) (c) Application. Unless the context indicates otherwise, this section and 25.212 of this title (relating to Technical Requirements
More informationPLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION
PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION Presentation by Engr. O. C. Akamnnonu Chief Executive Officer, Ikeja Electricity Distribution Company AGENDA WORK THROUGH
More informationGC0023 Protection Fault Clearance Time & Back-Up Protection
Stage 03: Report to Grid Code GC0023 Protection Fault Clearance Time & Back-Up Protection What stage is this document at? 01 02 03 Workgroup Report Industry Consultation Report to the This proposal seeks
More informationLouisville Gas and Electric Company
P.S.C. Electric No. 11, Original Sheet No. 57 APPLICABLE In all territory served. AVAILABILITY OF SERVICE Available to any customer-generator who owns and operates a generating facility located on Customer
More informationPage 1 of 5. 1 The Code Administrator will provide the paper reference following submission to National Grid.
Grid Code Review Panel Issue Assessment Proforma Operational Metering for Embedded Small Power Stations PP 11/35 1 A Panel Paper by John Lucas (ELEXON) & Steve Curtis (NGET) Summary Currently it is unclear
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)
Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less) Interconnection Customer Contact Information Name Alternative Contact Information (if different
More informationTRANSMISSION PLANNING CRITERIA
CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing
More informationAPPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION
APPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION Work Order No: File Reference: 16/2/1 This application form for the connection of small scale embedded generation is for small
More informationNet Metering Interconnection Requirements
Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland
More information18/10/2018. Mr Peter Adams General Manager, Wholesale Markets Australian Energy Regulator. By
ABN 70 250 995 390 180 Thomas Street, Sydney PO Box A1000 Sydney South NSW 1235 Australia T (02) 9284 3000 F (02) 9284 3456 18/10/2018 Mr Peter Adams General Manager, Wholesale Markets Australian Energy
More informationInterconnection Feasibility Study Report GIP-222-FEAS-R3
Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.
More informationImplementation Plan PRC Transmission Relay Loadability Project Phase II Relay Loadability
Implementation Plan PRC-023-3 Transmission Relay Loadability Project 2010-13.2 Phase II Relay Loadability Requested Approvals PRC-023-3 Transmission Relay Loadability Requested Retirements PRC-023-2 Transmission
More informationDistributed Generation Interconnection Policy
Distributed Generation Interconnection Policy 1 Introduction Carroll Electric Membership Corporation Distributed Generation Interconnection Policy Carroll Electric Membership Corporation (herein after
More informationConsumer Guidelines for Electric Power Generator Installation and Interconnection
Consumer Guidelines for Electric Power Generator Installation and Interconnection Habersham EMC seeks to provide its members and patrons with the best electric service possible, and at the lowest cost
More informationDER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.
Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations
More informationSummary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System
Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System This document is intended to be a general overview of PG&E s current technical
More informationUmatilla Electric Cooperative Net Metering Rules
Umatilla Electric Cooperative Net Metering Rules Version: July 2017 Umatilla Electric Cooperative NET METERING RULES Rule 0005 Scope and Applicability of Net Metering Facility Rules (1) Rule 0010 through
More informationEnquiry Form (Non-Registered Generator With Capacity less than 5 MW)
Connection Applicant (Embedded Generating Unit Owner/Proponent) Business name: ABN: Contact name: Address: Telephone number: E-mail address: Connection Applicant acting and working on behalf of the above
More informationSCHEDULE NO. ACG33 NET METERING SERVICE
Approved by Decision No.: 75408 Effective: January 19, 2016 Applicability Applicable to "Net Metering Facility" as defined below, or applicable Arizona Corporation Commission ("Cmnn1ission") Decision,
More informationCONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation
CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent
More informationXcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System
Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Adopted Based on State and Tariff Interconnection Rules Applicable to Northern States Power,
More informationXcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System
Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Adopted Based on State and Tariff Interconnection Rules Applicable to Northern States Power,
More informationNortheastern Rural Electric Membership Corporation Columbia City, Indiana
Page 1 of 5 SCHEDULE ADG - 1 AGGREGATED DISTRIBUTED GENERATION SERVICE I. AVAILABILITY This Aggregated Distributed Generation Schedule is available to any member in good standing of Northeastern REMC (Northeastern),
More informationSouthern California Edison Rule 21 Storage Charging Interconnection Load Process Guide. Version 1.1
Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide Version 1.1 October 21, 2016 1 Table of Contents: A. Application Processing Pages 3-4 B. Operational Modes Associated
More informationTransmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015
No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the
More informationCHAPTER 4 PROTECTION REQUIREMENTS
CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS 4.1 General Means of protection for automatic disconnection against phase and earth faults shall be provided on the customer main switch.
More informationGC108: EU Code: Emergency & Restoration: Black start testing requirement
Stage 01: Modification Proposal Grid Code GC108: EU Code: Emergency & Restoration: Black start testing requirement Purpose of Modification: This modification seeks to align the GB Grid Code with the European
More informationINTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS
INTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS TABLE OF CONTENTS Purpose and Scope...2 Authority...2 Applicability... 2 Intent.. 2 Maximum Connected Generation Allowed. 2 Definitions.
More informationPJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study
PJM Generator Interconnection R81 Emilie (Fords Mill) 100.9 MW Impact Study Re-Study August 2008 DMS # 498781 General Queue R81 Emilie (Fords Mills) is a Fairless Energy, LLC request to obtain an additional
More informationAccidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies
CIGRÉ-EPRI Grid of the Future Symposium 21, rue d Artois, F-75008 PARIS Boston, MA, October 20-22, 2013 http : //www.cigre.org Accidental Islanding of Distribution Systems with Multiple Distributed Generation
More informationMaryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)
Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less) Interconnection Customer Contact Information Name: Address: Alternative Contact Information
More informationWASHINGTON ELECTRIC COOPERATIVE, INC. NET METERING TARIFF POLICY BULLETIN NO. 38 NM
WASHINGTON ELECTRIC COOPERATIVE, INC. NET METERING TARIFF POLICY BULLETIN NO. 38 NM A. Application. The following tariff shall apply to members who: (1) take service under a rate within this electric service
More informationNORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM. Utility: Duke Energy Progress
NORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM ATTACHMENT 2 Utility: Duke Energy Progress Designated Utility Contact: Attention: Customer Owned Generation Mail Code ST13A E-Mail Address: Customerownedgeneration@duke-energy.com
More informationRULE STATIONARY GAS TURBINES Adopted (Amended , ) INDEX
RULE 413 - STATIONARY GAS TURBINES Adopted 04-06-95 (Amended 05-01-97, 03-24-05) INDEX 100 GENERAL 101 PURPOSE 102 APPLICABILITY 110 EXEMPTION - EMERGENCY STANDBY UNITS 111 EXEMPTION - REMOVAL FROM SERVICE
More informationDecember 13, This document was filed with the Board of Public Utilities on December 13, It is awaiting final approval by BPU staff.
JERSEY CENTRAL POWER & LIGHT UNIFORM TECHNICAL AND PROCEDURAL INTERCONNECTION REQUIREMENTS FOR NET METERING FACILITIES FOR INVERTER BASED WIND AND PHOTOVOLTAIC SYSTEMS OF 100 kw OR SMALLER for Atlantic
More informationKAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING
Third Revised Sheet 55a Cancels Second Revised Sheet 55a A. ELIGIBLE CUSTOMER-GENERATOR RULE NO. 17 NET ENERGY METERING Net energy metering is available to eligible customer-generators, defined as, permanent
More informationNet Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1
Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 01, 2017 1 Initial release Newfoundland
More informationMICHIGAN ELECTRIC UTILITY
MICHIGAN ELECTRIC UTILITY Generator Interconnection Requirements Category 4 Projects with Aggregate Generator Output Greater Than 550 kw or More, but Less Than or Equal to 2 MW August 3, 2009 Page 1 Introduction
More informationNoble County Rural Electric Membership Corporation
Albion, Indiana Page 1 of 5 SCHEDULE NB-1 RESIDENTIAL NET BILLING I. AVAILABILITY This Net Billing Rate is available to any residential member in good standing of Noble REMC (Noble) who owns and operates
More informationDISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase
PAGE 1 OF 7 USE: Requirements and guidelines for interconnection of single phase customer owned, (DR) Distributed Resource generation source, to NIPSCO s electric system, configured for. LATEST REVISION:
More informationDocument Requirements for Engineering Review PV Systems v1.0 6/9/2017
Document Requirements for Engineering Review PV Systems v1.0 6/9/2017 Outlined below are the documents and associated minimum details required for Engineering Review of Distributed Energy Resources Interconnection
More informationOC1 OC2 Phase 2 short term Proposals
GCRP 05/07 OC1 OC2 Phase 2 short term Proposals for GCRP on 19 May 2005 1 INTRODUCTION The OC1/OC2 Working Group discussions have focussed on two broad areas of work, namely, the framework documents which
More information3.0 Radial Distribution Systems
3.0 Radial Distribution Systems Radial distribution systems (RDS) are the most common design used by electric utilities, and are the least expensive to plan, construct, and maintain. They generally consist
More informationInformation Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program
Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program As part of our commitment to support renewable energy, Kissimmee Utility Authority
More informationMICHIGAN ELECTRIC UTILITY
MICHIGAN ELECTRIC UTILITY Generator Interconnection Requirements Category 3 Projects with Aggregate Generator Output Greater Than 150 kw, but Less Than or Equal to 550 kw August 3, 2009 Page 1 Introduction
More informationRATE 765 RENEWABLE FEED-IN TARIFF
NORTHERN INDIANA PUBLIC SERVICE COMPANY Original Sheet No. 104 TO WHOM AVAILABLE Sheet No. 1 of 12 This Rate Schedule is a voluntary offer available to any Customer that operates within the Company s service
More informationIssue 23 draft for Nuvve
Issue 23 draft for Nuvve Contents Introduction... 1 Issue Framing:... 2 Key Questions / Considerations... 2 Key Questions... 2 Key Considerations for IOUs:... 3 Background Knowledge... 4 Additional Details:...
More informationIndustry Recommendation Loss of Solar Resources during Transmission Disturbances due to Inverter Settings - II
Loss of Solar Resources during Transmission Disturbances due to Inverter Settings - II Initial Distribution: May 1, 2018 NERC has identified adverse characteristics of inverter-based resource performance
More informationGrid Stability Analysis for High Penetration Solar Photovoltaics
Grid Stability Analysis for High Penetration Solar Photovoltaics Ajit Kumar K Asst. Manager Solar Business Unit Larsen & Toubro Construction, Chennai Co Authors Dr. M. P. Selvan Asst. Professor Department
More informationEssential Reliability Services From PV Plants
Essential Reliability Services From PV Plants Mahesh Morjaria, Ph. D. VP, PV Systems Enabling a world powered by reliable, affordable solar electricity. Utility-Scale PV Plants Support Grid Stability &
More informationCo-location Informal Guidance Note. March 2018 Version 1.1
Co-location Informal Guidance Note March 2018 Version 1.1 Contents 1. Foreword...3 2. Purpose......4 3. Terminology.5 4. Co-location Guidance 6 5. Summary and Conclusion 9 Appendix 1 FAQs...10 1. Foreword
More informationApplication for Operation of & Net Metering for Member-Owned Generation Name: Mailing Address: City: County: State: Zip Code: _
Application for Operation of & Net Metering for Member-Owned Generation -------------- OWNER/APPLICANT INFORMATION Name: Mailing Address: City: County: State: Zip Code: _ Phone Number: Email Address:.Representative:
More informationGENERATING FACILITY INTERCONNECTION APPLICATION. Part 1 Introduction and Overview
Part 1 Introduction and Overview A. Applicability: This Generating Facility Interconnection Application (Application) is used to request the interconnection of a Generating Facility to Southern California
More informationReview of Reliability Must-Run and Capacity Procurement Mechanism BBB Issue Paper and Straw Proposal for Phase 1 Items
Review of Reliability Must-Run and Capacity Procurement Mechanism BBB Issue Paper and Straw Proposal for Phase 1 Items Stakeholder Meeting January 30, 2018 Keith Johnson Infrastructure and Regulatory Policy
More informationIf any further information is required for CHELCO to fulfill its reporting requirements, please let us know.
c o January 20, 2009 l'v1a rk Futrell Public Utility Supervisor Florida Public Service Commission 2540 Shumard Oak Boulevard Tallahassee, Florida 32399-0850 Dear Mr. Futrell, The documents accompanying
More informationHEARING STATEMENT - PALMERSTON NORTH CITY COUNCIL PLAN CHANGE 15A - RURAL ZONE (GENERAL ISSUES)
11111 TRANSPOWER Keeping Ihe energy flowing Sarah Shand Phone: 04 590 7434 Email: sarah.shand@transool.ler.co.nz Transpower House 96 The Terrace PO Box 1021 Wellington 6140 New Zealand p 6444957000 F 6444957]00
More informationThe Commonwealth of Massachusetts
The Commonwealth of Massachusetts DEPARTMENT OF PUBLIC UTILITIES D.P.U. 12-81-A January 18, 2013 Investigation by the Department of Public Utilities on its own Motion Commencing a Rulemaking pursuant to
More informationJournal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E
Integration of wind Power Plant on Electrical grid based on PSS/E S. Othman ; H. M. Mahmud 2 S. A. Kotb 3 and S. Sallam 2 Faculty of Engineering, Al-Azhar University, Cairo, Egypt. 2 Egyptian Electricity
More informationSP Distribution plc. and XXX
SP Distribution plc and XXX AGREEMENT FOR CONNECTION TO THE DISTRIBUTION SYSTEM (Where the customer has generating plant and uses the Distribution System for selling electricity or exporting energy) AGREEMENT
More informationISO Rules Part 300 System Reliability and Operations Division 304 Routine Operations Section Electric Motor Start Requirements
External Consultation Draft February 7, 2019 Applicability 1 Section 304.2 applies to: (a) the operator of an industrial complex that is: (i) in the Empress Area with an electric motor of a size twenty
More informationConnection of Power Generating Modules to DNO Distribution Networks in accordance with EREC G99
Connection of Power Generating Modules to DNO Distribution Networks in accordance with EREC G99 Version 1 August 2018 www.energynetworks.org 2 Introduction Connection of Power Generating Modules to DNO
More informationGUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM
GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM Page 1 of 19 Table of Contents 1.0 SCOPE...4 2.0 PURPOSE...4 3.0 LIMITATIONS...5 4.0 GENERAL INTERCONNECTION
More informationJemena Electricity Networks (Vic) Ltd
Jemena Electricity Networks (Vic) Ltd Embedded Generation - Technical Access Standards Embedded Generation - 5 MW or Greater ELE SP 0003 Public 1 October 2014 TABLE OF CONTENTS TABLE OF CONTENTS Abbreviations...
More informationEASTERN ILLINI ELECTRIC COOPERATIVE REGULATION NO. 26A
EASTERN ILLINI ELECTRIC COOPERATIVE REGULATION NO. 26A SUBJECT: Interconnection of and Service to Qualifying Facilities under Public Utility Regulatory Policies Act (PURPA) OBJECTIVE: To provide, through
More informationDRAFT PROPOSAL FOR STORAGE CONNECTION REQUIREMENTS
DRAFT PROPOSAL FOR STORAGE CONNECTION REQUIREMENTS January 2018 Contents 1 Introduction and background... 2 2 Definitions and applicability... 2 3 SPM categories types... 3 4 SPM Type A... 4 4.1 Frequency
More informationRULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES
RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES Last Revised Date: October 15, 2015 Contents Chapter 1 - Purpose and Scope 2 Chapter 2 - Application of Rules 2 Chapter 3 - Definitions
More informationHeber Light & Power Electric Service Rule No. 14 NET METERING SERVICE
Heber Light & Power Electric Service Rule No. 14 NET METERING SERVICE 1. Overview The Company offers Residential and Small General Service Customers net metering service that allows the Customer to use
More informationMs. Tracey Pennell Senior Counsel Newfoundland and Labrador Hydro P.O. Box St. John's, NL A1B 4K7
NEWFOUNDLAND AND LABRADOR BOARD OF COMMISSIONERS OF PUBLIC UTILITIES 120 Torbay Road, P.O. Box 21040, St. John's, Newfoundland and Labrador, Canada, AIA 5B2 E-mail: TraceyPennell@nlh.nl.ca 2017-01-27 Ms.
More informationWASHINGTON ELECTRIC COOPERATIVE, INC. NET METERING TARIFF POLICY BULLETIN NO. 38 NM
WASHINGTON ELECTRIC COOPERATIVE, INC. NET METERING TARIFF POLICY BULLETIN NO. 38 NM A. Application. The following tariff shall apply to members who: (1) take service under a rate within this electric service
More informationPROPOSAL FOR STORAGE CONNECTION REQUIREMENTS
PROPOSAL FOR STORAGE CONNECTION REQUIREMENTS Public consultation 15 March 23 April 2018 Contents 1 Introduction and background... 2 2 Definitions and applicability... 2 3 SPM categories types... 3 4 SPM
More informationLloyd s Register Type Approval System Test Specification Number GT04
Lloyd s Register Type Approval System Test Specification Number GT04 Gas Turbines Performance and test specifications for Gas Turbines to be used in Marine, Offshore and Industrial Applications 2004 Lloyd's
More informationAlberta Electric System Operator Needs Identification Document Application. Mowat 2033S Substation
Decision 21781-D01-2016 Alberta Electric System Operator Needs Identification Document Application Facility Applications September 7, 2016 Alberta Utilities Commission Decision 21781-D01-2016: Alberta
More informationMENARD ELECTRIC COOPERATIVE POLICY MANUAL. SECTION IV Operating Rules for Cooperative Members
49.1 INTERCONNECTION OF AND SERVICE TO QUALIFYING FACILITIES UNDER Objective To provide for the interconnection of and service to a Qualifying Facility in keeping with the provisions of the Public Utility
More informationDUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY
DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY Transmission Department Transmission Planning Duke Energy Progress TABLE OF CONTENTS I. SCOPE 3 II. TRANSMISSION PLANNING OBJECTIVES 3 III. TRANSMISSION
More informationMICHIGAN ELECTRIC UTILITY
MICHIGAN ELECTRIC UTILITY Generator Interconnection Requirements Category 5 Projects with Aggregate Generator Output Greater Than 2 MW August 3, 2009 Page 1 of 39 Introduction Category 5 Greater than 2MW
More informationESF on Fire Protection Proposed ESF on Fire Protection Engine attachment points applicable to Piston Engines EASA
ESF on Fire Protection Proposed ESF on Fire Protection Engine attachment points applicable to Piston Engines EASA UK CAA Comment: Paragraph (2) of the ESF should clarify whether the other features of the
More information