Standby Power Systems Considerations

Similar documents
Operator Manual. Transfer Switch. RSS100 and RSS Cummins Inc. All rights reserved. English

Optimizing Emergency Power Systems for Health Care Applications

Emergency Power Systems 101 An Overview of Emergency Power Systems. Craig Ayers, MHA, CHFM, CHSP, CPO

BUILDER S GUIDE TO AUTOMATIC HOME STANDBY GENERATORS

Questions Section: Do you have questions that aren't covered? Please contact us!

POWERING THE WAY Rental Power Planner. 877.YOUR.PWR ( ) holtcat.com. Your Business Powered Anywhere.

Standby Power Systems

Vigilant Automatic Transfer Switches

CHARGE TANK. Overview. Using The Charge Tank. User Guide

7kW. 7kW. CorePower System Residential Standby Generators Air-Cooled Gas Engine FEATURES. Power Rating Model (Composite Polymer) - 7 kw 60Hz

70 kw GENERAC STANDBY GENERATORS. Liquid-Cooled Engine Generator Sets FEATURES INCLUDES: Standby Power Rating Model QT070 (Bisque) - 70 kw 60Hz

Installation instructions for ATS panel Ref:ATS --/2 M2GC705 Issue

Quick Start Guide TS 910 & TS 920

Quick Start Guide TS 910

Diesel generator set QSX15 series engine

Diesel generator set QSK60 series engine

STATEMENT OF WORK. Sinnemahoning State Park Cameron County, Pennsylvania

MaxxForce DT, 9, 10 ( )

Protector Series ISO FEATURES. Standby Generators Liquid-Cooled Gas Engine INCLUDES:

Diesel generator set. QSB5 series engine Hz EPA Tier 3 emissions. Specification sheet. Description. Features

GENERAC GUARDIAN SERIES STANDBY GENERATORS

1P 120/240V, 3600 RPM,

STANDBY GENERATOR 25 kw LIQUID-COOLED GENERATOR SET INCLUDES FEATURES. Standby Power Rating Model HT kw 60Hz

HOME GENERATOR SYSTEMS STANDBY SOLUTI NS PRODUCTS. Home Comfort Home Generator Systems

22 kva GENERAC STANDBY GENERATORS ISO. Liquid-Cooled Engine Generator Sets FEATURES INCLUDES:

MAGNETIC MOTOR STARTERS

GENERAC GUARDIAN SERIES STANDBY GENERATORS

White Paper Load Banks for Power System Testing

Diesel generator set QSK60 series engine

Bypass Isolation Transfer Switches Amperes

Diesel generator set QSK50 series engine

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Owner s Manual. Series 165 Automatic Transfer Switches rated 100 and 200 amps, single phase, 240 V ac for automatic 2 wire start generators

STANDBY GENERATOR 130 kw LIQUID-COOLED GENERATOR SET INCLUDES FEATURES. Standby Power Rating Model HT kw 60Hz

Appendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies

Deutz Cummins Kohler IVECO Detroit Diesel MTU Volvo/Penta Perkins John Deere Mitsubishi

AP1000 European 7. Instrumentation and Controls Design Control Document

STANDBY GENERATOR 100 kw LIQUID-COOLED GENERATOR SET INCLUDES FEATURES. Standby Power Rating Model HT kw 60Hz

White Paper. Application of Resistive/Reactive Load Banks for kva Testing

GENERAC QUIETSOURCE SERIES STANDBY GENERATORS

Power Ratings. Standby SG kva / 160 kw. Prime and standby ratings based on 3-Phase voltages. Model number based on kw rating.

Standby Rated Generators. Standby SG kva / 28 kw. Prime PG kva / 22 kw

STANDBY GENERATOR 80 kw LIQUID-COOLED GENERATOR SET INCLUDES FEATURES. Standby Power Rating Model HT kw 60Hz

G50U MODEL STANDARD FEATURES GENERATOR RATINGS CONDITIONS OF SALE. General features :

Diesel generator set QSX15 series engine

Electrical Books Genset Ebooks Download

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

QT025A 2.4L 25 kw INDUSTRIAL SPARK-IGNITED GENERATOR SET EPA Certified Stationary Emergency

G100U MODEL STANDARD FEATURES GENERATOR RATINGS CONDITIONS OF SALE. General features :

Power Ratings. Standby SG kva / 240 kw. Prime PG kva / 192 kw

Te 803 Electronic Controller. Service, Operation & Technical Information Manual

GENERAC GUARDIAN SERIES STANDBY GENERATORS

GENERAC GUARDIAN SERIES STANDBY GENERATORS

N1387 Series Troubleshooting Guide for N Alternators

Diesel generator set 6BT5.9 series engine

Electric Motor Controls BOMA Pre-Quiz

Diesel generator set QSK60 series engine

GENERAC GUARDIAN SERIES STANDBY GENERATORS

DASSAULT AVIATION Proprietary Data

Spark-ignited generator set

NEC REQUIREMENTS FOR GENERATORS

Operator s Series 300 Generator Paralleling System

OCEAN COUNTY ARES EMERGENCY GENERATOR USE By WX2NJ. The following was taken from September and October Ocean County ARES Newsletters in 2012:

Spark-ignited generator set

Transfer switch OHPC open or delayed transition

Generator/VFD/Emergency Response Issues. Affordable Standby Power

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

G80U MODEL STANDARD FEATURES GENERATOR RATINGS CONDITIONS OF SALE. General features :

Backup Generation Application

Diesel generator set. 50 kw - 60 kw EPA emissions stationary Standby. Specification sheet. Description. Features

SPECIFICATIONS. Stationary Emergency Generator Specifications STATIONARY EMERGENCY GENERATOR COOLING SYSTEM FUEL SYSTEM ENGINE ELECTRICAL SYSTEM

GENERAC GUARDIAN SERIES STANDBY GENERATORS

Diesel generator set. 20 kw EPA emissions stationary Standby. Specification sheet. Description. Features

UK MANUFACTURED GENERATORS PS9P PS20P PERKINS 400 SERIES TECHNICAL DATA SHEET

Diesel generator set QSK23 series engine

ANG50P-6. Voltage Stand-by Power Stand-by Current Prime Power Prime Current. 480 / 277V 50kVA / 40kW 60.1 A 40kVA / 32kW 48.1 A

EMERGENCY GENERATOR SET

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

CUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)

Residential standby system RS12000

Residential standby system RS12000

design prefix 50 Hanover Road, Florham Park, New Jersey USA (ASCO), for service call (ASCO)

O & M Manual for A (480/600 Vac) ATC Position Contactor Based Transfer Switch

Diesel generator set QSK95 series engine

OTPC-SE Service entrance transfer switch open transition

Power Factor Correction

GENERAC QUIETSOURCE SERIES STANDBY GENERATORS

w.s e c.c o m.t w AUTOMATIC TRANSFER SWITCHES Instructions (MCCB TYPE) BREAKER & SWITCHGEAR SYSTEM

B CW POWER RELAY

Generator Set Specifications 100 ekw (125 kva)

As diesel fuel ages it degrades in 2 ways: particulate formation, and biological growth.

YOUR POWER PARTNER. Enclosed product is tested according to EU noise legislation 2000/14/EC. Voltage kva kw kva kw 400/ ,

Ex. 1-1 Nacelle Familiarization and Safety Discussion

SCAQMD Rule 1470 Impact on Diesel Generator Installations

CHPC Transfer switch closed transition

Diesel generator set QSK23 series engine

AGi20P 2.2 L 20 kw Perkins Powered Diesel Generator AURORA GENERATORS INCORPORATED AURORA STANDARD FEATURES STANDBY POWER RATING 20 KW, 20 KVA, 60 HZ.

Technical specification

Energetech LLC 7427 S. Main (P.O. Box 400) Midvale, Utah (801) Ph. (801) Fx.

Diesel generator set QSL9-G7 series engine

Transcription:

Standby Power Systems Considerations TVSFPE Chapter Meeting Ken Cockerham Nixon Power Services Company March 14, 2013

Radiator Basic Engine Generator Set Exhaust Outlet Turbo Charger Converts Mechanical Energy into Electrical Energy Engine Drives Alternator, Resulting in Electrical Power Output (AC) Air Intake Filter Control Panel 1800 RPM Engine Speed Gives 60 Hertz Electrical Output Engine Power Capability is Rated in Horsepower at 1800 RPM Engine Battery Skid Base Alternator Output Circuit Breaker(s) Sub Base Fuel Tank

Automatic Transfer Switches Utility Source Automatic Transfer Switch (ATS) Senses presence of both/either power sources ATS-Generator Control Wiring Starts & Stops Genset Transfers Load from One Source to the Other ATS Power to the Load

The System and How it Works

Normal Conditions Utility Source In Normal Condition Load is fed through the ATS from the Utility source ATS Continually Monitors the Presence of Utility Power ATS ATS-Generator Control Wiring Generator is in the Automatic Mode ready to start on command. The engine is being kept warm by a block heater and the starting battery is being kept refreshed by a battery charger. Load is Powered by Utility

Power Failure Utility Source X When Utility Fails senses failure Time delay TDES ATS sends start signal to generator controller Generator starts and comes up to speed, providing voltage to ATS. ATS No Power to the Load ATS-Generator Control Wiring senses availability of generator source and TDNE ATS Contactor transfers from Normal position to Emergency position The load is now powered by the generator

Power Failure Utility Source When Utility Fails senses failure X senses availability of generator source and TDNE Time delay TDES ATS sends start signal to generator controller Generator starts and comes up to speed, providing voltage to ATS. ATS No Power to the Load ATS-Generator Control Wiring ATS Contactor transfers from Normal position to Emergency position The load is now powered by the generator

Power Failure Utility Source When Utility Fails senses failure X senses availability of generator source and TDNE Time delay TDES ATS sends start signal to generator controller Generator starts and comes up to speed, providing voltage to ATS. ATS No Power to the Load ATS-Generator Control Wiring ATS Contactor transfers from Normal position to Emergency position The load is now powered by the generator

Power Failure Utility Source When Utility Fails senses failure X senses availability of generator source and TDNE Time delay TDES ATS sends start signal to generator controller Generator starts and comes up to speed, providing voltage to ATS. ATS No Power to the Load ATS-Generator Control Wiring ATS Contactor transfers from Normal position to Emergency position The load is now powered by the generator

Power Failure Utility Source When Utility Fails senses failure X senses availability of generator source and TDNE Time delay TDES ATS sends start signal to generator controller Generator starts and comes up to speed, providing voltage to ATS. ATS No Power to the Load ATS-Generator Control Wiring ATS Contactor transfers from Normal position to Emergency position The load is now powered by the generator

Power Failure Utility Source When Utility Fails senses failure X senses availability of generator source and TDNE Time delay TDES ATS sends start signal to generator controller Generator starts and comes up to speed, providing voltage to ATS. ATS Load is Powered by Generator ATS-Generator Control Wiring ATS Contactor transfers from Normal position to Emergency position The load is now powered by the generator

Return to Normal Utility Source When Utility Returns senses availability of utility Time delay TDEN ATS Contactor transfers from Emergency position to Normal position causing a momentary blink in power to the load. ATS Load is Powered by Generator ATS-Generator Control Wiring The load is now powered by the utility Time delay TDES ATS sends shutdown signal to generator controller. Engine stays running in cooldown mode Time delay TDEC The engine stops and the generator is ready for the next outage

Return to Normal Utility Source When Utility Returns senses availability of utility Time delay TDEN ATS Contactor transfers from Emergency position to Normal position causing a momentary blink in power to the load. ATS Load is Powered by Generator ATS-Generator Control Wiring The load is now powered by the utility Time delay TDES ATS sends shutdown signal to generator controller. Engine stays running in cooldown mode Time delay TDEC The engine stops and the generator is ready for the next outage

Return to Normal Utility Source When Utility Returns senses availability of utility Time delay TDEN ATS Contactor transfers from Emergency position to Normal position causing a momentary blink in power to the load. ATS Load is Powered by Utility ATS-Generator Control Wiring The load is now powered by the utility Time delay TDES ATS sends shutdown signal to generator controller. Engine stays running in cooldown mode Time delay TDEC The engine stops and the generator is ready for the next outage

Return to Normal Utility Source When Utility Returns senses availability of utility Time delay TDEN ATS Contactor transfers from Emergency position to Normal position causing a momentary blink in power to the load. ATS Load is Powered by Utility ATS-Generator Control Wiring The load is now powered by the utility Time delay TDES ATS sends shutdown signal to generator controller. Engine stays running in cooldown mode Time delay TDEC The engine stops and the generator is ready for the next outage

Return to Normal Utility Source The load is now powered by the utility When Utility Returns senses availability of utility Time delay TDEN ATS Contactor transfers from Emergency position to Normal position causing a momentary blink in power to the load. ATS Load is Powered by Utility ATS-Generator Control Wiring Time delay TDES ATS sends shutdown signal to generator controller. Engine stays running in cooldown mode until time delay TDEC times out The engine stops and the generator is ready for the next outage

Return to Normal Utility Source The load is now powered by the utility When Utility Returns senses availability of utility Time delay TDEN ATS Contactor transfers from Emergency position to Normal position causing a momentary blink in power to the load. ATS Load is Powered by Utility ATS-Generator Control Wiring Time delay TDES ATS sends shutdown signal to generator controller. Engine stays running in cooldown mode until time delay TDEC The engine stops and the generator is ready for the next outage

Return to Normal Utility Source The load is now powered by the utility When Utility Returns senses availability of utility Time delay TDEN ATS Contactor transfers from Emergency position to Normal position causing a momentary blink in power to the load. ATS Load is Powered by Utility ATS-Generator Control Wiring Time delay TDES ATS sends shutdown signal to generator controller. Engine stays running in cooldown mode until time delay TDEC times out The engine stops and the generator is ready for the next outage

Bypass Isolation ATS For Critical Facilities Allows ATS to be de-energized and/or removed for service while maintaining power continuity Allows for manual transfer from Normal to Emergency while in bypass mode (NFPA 110, 6.4.4)

Bypass Isolation ATS Interlocked To Generator Set Interlocked To Utility To Load Normal Operation

Bypass Isolation ATS Interlocked To Generator Set Interlocked To Utility To Load Emergency Operation

Bypass Isolation ATS Interlocked To Generator Set Interlocked To Utility To Load Bypass to Utility Operation

Bypass Isolation ATS Interlocked To Generator Set Interlocked To Utility To Load Bypass to Generator Operation

Test Exercise Modes Scheduled - No Load Scheduled Loaded Unscheduled No Load Unscheduled Loaded NFPA 110, Standard for Emergency and Standby Power Systems (2013 Edition) Scheduled is defined as through a programmed exerciser clock

Questions Fuel Q: How important is fuel testing for gasoline or diesel generators? How often should the fuel be changed out? Does it need to be treated with Sta-bil or some type of fuel treatment? A1: Fuel testing diesel is very important for reliability and for engine life. A2: We do not recommend gasoline as a standby generation fuel. Period. A3: Fuel polishing and additives are available. Their need is identified by testing fuel samples. Q: What are some of the key elements (water, mold, bacteria, etc.) that should be looked for on a fuel test that would drive one to require that the fuel tank be emptied, cleaned out, and replaced with fresh fuel? A: The annual fuel sample analysis we recommend checks for 24 Elemental Metals, Pensky- Marten Flash Point, Water, Sediment, Bacteria, Fungi, and Mold. Others are available, but this meets ASTM standards per NFPA 110, 8.3.8. In severe cases, fuel is normally removed, tank cleaned, filters replaced, fuel treated and returned (not replaced), fuel train flushed, and engine run under load.

Questions General System Testing Q: How important is the testing of the automatic transfer switch on a monthly basis? A: Very important. The ATS is usually the SPF in the system. The closer you can simulate actual outage, the more confidence you can have in the systems reliability. Q: Does the ATS have to be switched under load? A: Great question. It s very difficult to switch the ATS except when it is under load. The contactor mechanism can be manually articulated from one position to another with an operating handle when it isn t under load, but the very definition of switching implies transferring load from one source to another. Ergo, if the requirement is to switch the ATS, it is under load.

Questions General System Testing (cont.) Q: There always seem to be a lot of discussion about ATS that are provided with a bypass. Can an ATS be placed in the bypass mode during periodic testing such as monthly or it is required to be tested in the normal mode? A: NFPA 110 requires the ATS be operated monthly (8.4.6) and immediately following acceptance test or repairs (8.3.2.1). The short answer to the question is No. The test of the ATS must occur at the ATS, not the BIS section of a bypass isolation transfer switch. Certainly the generator set can be run under load with the BIS/ATS in the bypass mode. This may be desirable when only the generator set is to be tested. Q: Can the exhaust gas temperature just be measured with a pyrometer at the surface of the exhaust pipe/muffler? A: NFPA 110 does not specify how the measurement is taken. My personal recommendation is by using an IR gun. It s important to measure the temperature downstream of the turbocharger, and to measure when the unit is under load and up to temperature.

Questions Load Testing Q: How important is periodic load testing of a generator? Is 30% good enough or should a more substantial load be place on the unit? A: Recommend 100% rated load test bi-annually on diesels. For diesel engine sets, NFPA 110 (8.4.2)(2) requires monthly 30 minute test at minimum of 30% standby nameplate rating, whereas it doesn t specify a minimum load for spark ignited engine sets (8.4.2.4). Q: Can the load test be just the supplied load? If so, is there a minimum % of the name plate rating that the service load should meet? A: As long as there is sufficient available load to meet the requirements of NFPA 110 (8.4.2) facility load is only ok.

Questions Load Testing (cont.) Q: Are there significant hazards with using a portable load bank to test with? Do you recommend a permanent disconnect for the load bank or can it just be connected to the generator terminals? A1: Yes. Electrical hazards associated with ground laid cable, trip hazards, intense heat rejected from the load banks. Portable load bank operations are best left to professionals. Additionally, if stationary generator is to be disconnected from facility load while it is being load banked, a temporary portable generator would need to be connected in its place in anticipation of an unforeseen utility outage. A2: A permanent load bank connection point with its own breaker is desirable and in some cases essential. NFPA 110 (8.4.2.2) and (8.4.2.4.2) requires that the load bank be automatically replaced with the emergency loads (ie disconnected from the load bank and generator power transferred to connected facility load) in the event that utility fails while the generator is in a load bank test.

Questions Load Testing (cont.) Q: When can a permanent test bank be added to a generator? Does the permanent bank have to be from the manufacturer of the gen set? Are there generic permanent test banks? A1: A permanent load bank can be added to the system after the fact. It is preferred that it be designed in, specified, and procured along with the new generator set and other EPSS equipment. A2: The load bank does not necessarily come from the generator set provider, but there are many obvious advantages to procuring it along with the generator set. There are a number of American companies that manufacture and sell load banks. Controls interface after the fact may prove difficult when purchased from multiple sources. Q: Can you install just one load rod that will provide a 50% load and call it good enough or do you incremental loads? A: NFPA 110 (8.4.2.3) requires 75% (of nameplate kw rating) load for 1 hour if (8.4.2) is not met.

Questions General System Testing (cont.) Q: The code (Section 8.4.2) discusses the manufacturers recommend exhaust gas temperatures for the monthly test. Is there a magical temperature that all generators should be tested to or if there a different exhaust gas temperature for every model/brand? Can the exhaust gas temperature be determined with a non-contact IR temperature scanner on the exhaust pipe? A: Sorry, there is no magical temperature. Each is specified on the manufacturers data sheet included with the operation and service literature. Diesel exhaust is typically in the 950 F range. Spark ignited exhaust (natural gas or LP) is typically in the 1200 F range. How should a generator be started when conducting a monthly, annual, or tri-annual test that requires the generator to be tested under loaded conditions? A: NFPA 110 (8.4.3) Test should be initiated using test switch on ATS or by opening the utility breaker to simulate an outage. Also, (8.4.4) load test is to include complete cold starts.

Questions - General Q: What is the minimum recommended load for a generator? A: For diesel, 30% of nameplate rating. For spark ignited, there really is no minimum recommendation. Q: generators are generally rated in watts or kw s and the measurement of load would most likely be in amps. Voltage and amps are easy to understand and determine. We need help with how one would determine the efficiency factor for a particular generator or can it be assume that all generators have an efficiency factor of.92 or whatever the number may be? Just trying to figure out how to determine if a particular generator is loaded to at least 30% of it rated capacity. A: Modern generator sets are designed and rated for a load power factor (PF) of 0.8. The alternator is overbuilt enough that it will supply rated true power (kw) even at 0.8 (inductive) load power factor. This means that when powering inductive loads the generator can sustain 125% of the amp rating it would have at full load with unity power factor (PF=1.0, pure resistive load). The load s PF can be measured with a PF meter. Once PF is known the follow calculations can be made: Single Phase Apparent Power (KVA)=volts X amps/1000 Three Phase Apparent Power (KVA)=volts X amps X 1.73/1000 True Power (kw) = Apparent Power (KVA) X PF

Notes

Notes