TYPE 41LA MINING LED LUMINAIRE EXPLOSION PROOF LUMINAIRE WITH FLAMEPROOF PROTECTION (TYPE d)

Similar documents
TYPE NO. AS APPROPRIATE

Operating manual FP-2. Index

Zone 1 Linear Range - Installation Guide

User Manual. PBA428 Weighing platform

Floodlight Range Installation Guide

SAUTER TVO Version /2014 GB

Operating instructions

RoboSterz. Automatic Management of Steering Without Operator ITA. Mod. V.

Infratek 23DC-Source Tester

OPERATING INSTRUCTION

TriScroll TM 300 Series Dry Scroll Vacuum Pump

Powerflare Caution Light

Universal spotlight LED

800 Series Floodlight Luminaires (Ex n) ATEX Models 844, 854, and 864

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS High Wattage Floodlight Luminaires Industrial

N CX 5500 DAT Operating and Instruction manual

Protecta III GRP ATEX

INSTALLATION AND SERVICE INSTRUCTIONS FOR 2000 SERIES FLAMEPROOF XENON AND FLUORESCENT BEACONS

CONTENTS APM ELECTRONIC WEIGHING INDICATOR OPERATION MANUAL 1. INSTALLATION 2. SPECIFICATIONS 3. KEYBOARD LAYOUT AND DESCRIPTION 4.

P-1500/P-1700-manual from PMV

2000 Series Flameproof Xenon and Fluorescent Beacons Installation and Service Instructions

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Wellglass Luminaires ATEX & IECEx

KSEV97X. IT Libretto Istruzioni GB Instruction Manual. 11 FR Manuel d Instructions 20 DE Bedienungsanleitung 29 NL Gebruiksaanwijzing

SERIES 670E End-of-Line Deflagration Flame Arrester

Dumper 1001, 1501, 2001 OPERATOR S MANUAL

TM 60 TS 75 TS 100 Please read this user guide before using your operator. Please read carefully the security advises on the following pages!

INSTRUCTION MANUAL (ATEX / IECEx)

Curie - Recessed LED Luminaires Industrial

EVZ Series (Small body) Explosion protected luminaire Operating Instructions

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Evolution II & Evolution II LT (Low Temperature) Floodlight Luminaires ATEX & IECEx

Acclaim III Recessed Emergency Fluorescent Luminaires. ATEX INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Operating Instructions

F5 Feedback Unit F5/F5-EX. Easy to install

Dumper OPERATOR S MANUAL

Instructions for use L 2015

Operating Instructions

Operating Instructions School Balance

Operation instructions Platform/floor scales

Explosion protected terminal boxes type, GHG 72.

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SOLAS LED Luminaire ATEX & IECEx

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Evolution Floodlight (ATEX)

STERIPOWER stainless steel edition / white edition BEDIENUNGSANLEITUNG OPERATING MANUAL

Eclipse II - Wellglass Luminaires Industrial

Operating Instructions

INSTRUCTION MANUAL (ATEX / IECEx)

Position Limit Switches PLTA

RFID110-L1. For use in combination with charge controllers used in electric vehicle charging stations, wall boxes and street light charging points

FLOX. Gebrauchsanweisung Operating instructions Manuel d instructions Instruzioni d uso Instrucciones de uso Gebruiksaanwijzing

Clarius EP PLUS LED FLOODLIGHT Installation Guide

Instruction Manual. Ex-Time 40 / 50

Operating and maintenance instructions

Operating Instructions

RFID114. For use in combination with charge controllers used in electric vehicle charging stations, wall boxes or street light charging points.

Power Factor Correction

IIC wellglass luminaires for low energy, halogen and incandescent lamps flameproof

ToughPIX 2300XP Series INSTRUCTIONS FOR SAFE OPERATION

OPERATING INSTRUCTIONS

FLEXIBLE DISC COUPLING FOR API APPLICATIONS

General operation manual. induction cage-motors

INSTALLATION MANUAL XMT MAGNETOSTRICTIVE LEVEL PROBE

RI.15KI. L Rev. 04/03/02 MIKROCONTROLLER-STEUERUNG FÜR. Betriebsanleitung

LED Emergency Luminaires

Installation, Operating & Maintenance Instructions. Norbro J-Switch FM 00707

EdgeLED TM Range. Installation and Operating Instructions EdgeLED TM RANGE INSTALLATION NON-EMERGENCY LUMINAIRES PRE INSTALLATION

Crane fork KGM/KGA and KGQ/KGL

Limit Switch Type 4747

ILED Aquarius Illuminated Windsock. User Manual

GuaRdboX - Gd series IOM (Installation, Operation & Maintenance Manual) 0100-ENG rev.4

AEROSTAT HP-N-Ex Ionising Air Blower

INSTALLATION INSTRUCTIONS LED Canopy Retrofit Kit

VALIADIS S.A. HELLENIC MOTORS

Translation. Operating Instruction Electromechanical linear drive..com

Installation Instructions

Flameproof Level Sensor (Flameproof F/S FP)

Guidance to Installers of Viridian EV Charging Stations

IQL Helios Area-/Streetlight. User Manual

USER s MANUAL 1. GENERAL INFORMATION 2. PRODUCT IDENTIFICATION

Curie Elite IP65 Recessed Fluorescent Luminaires ATEX INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

LED Area Light. This is the fixture of choice for all of our dealerships. Contact Us:

Dimensions shown apply to both Stainless Steel and Mild Steel S1, SF*1 = 162, S2, SF*2, S2L, SF*2L = 170, S3, SF*3 = 250,

Type 0283, Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies

11mm Slot Label S1 = 162, S2 = 170, S3 = 250, S4 = 305, S5 = 330, S6 = 410, S7 = 490, S8 = 570, S9 = 650. Maximum Power Dissipation (Watts) T** T**

Self-Exciting Flameproof Alternator

ILED Dorado. User Manual

INSTRUCTION MANUAL WARNING

BR 31a Rack-and-pinion Actuator,

Sparkasse zu Lübeck (Sort code ) Acc.No

LED Area Light. scratch that. This is the fixture of choice for all of our dealerships. Contact Us:

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

VOLUMETRIC PUMPS. BOMBA ELIAS has developed the volumetric for clean water suitable for small flow rates and average height.

IBExU Institut für Sicherheitstechnik GmbH An-Institut der Technischen Universität Bergakademie Freiberg

WOLF ATEX TURBOLITE RANGE

QUBO DE EN FR IT ES NL RU PL LT LV SR CZ RO BG HU

Adam Equipment. User Manual (EN) Pricing Retail RAV Series Adam Equipment Co. Ltd.

PREFACE. Thank you for your purchase of the Böhler-AG Petrol Generator.

BLz03 TO 75/77. 50/60 Hz DUST PROTECTED TO EN INSTALLATION AND MAINTENANCE 'BLz' SERIES VIBRATORS ENGLISH

Protecta Ex na Fluorescent Luminaire

SPH214 Small Panel Handler

INSTALLATION INSTRUCTIONS MOONRING 1 LP1/MR1

HIGH VOLTAGE TEF 1060 HV ENCLOSURE WITH A-BLOCK SOLUTIONS USER MANUAL

Transcription:

Victor Products Ltd New York Way New York Industrial Park Newcastle upon Tyne NE27 0QF ENGLAND Tel : +44(0)191 2808000 Fax : +44(0)191 2808080 0518 Making Hazardous Environments Work TYPE 41LA MINING LED LUMINAIRE EXPLOSION PROOF LUMINAIRE WITH FLAMEPROOF PROTECTION (TYPE d) Certification number SIRA02ATEX1407X I M2 EExd I The ATEX certificate carries the ATEX group and category marking: - I M2 Where: I signifies suitability for use in mining and M2 signifies suitability for use in mines where it must be de-energised in the presence of an explosive atmosphere. Victor Products Ltd. Newcastle upon Tyne NE27 0QF U.K. TYPE 41LA LED LUMINAIRE. 190V - 277V 1X T8 18W 1500mm LED TUBE. SIRA APPROVAL No. SIRA02ATEX1407X I M2 EEx d I IP54-15 C TO +50 C AMBIENT DO NOT OPEN WHEN ENERGISED OR WHEN AN EXPLOSIVE GAS IS PRESENT. SERIAL No. 0518 STYLE No. TYPICAL LABEL 1753mm FIXINGS Ø11mm DIMENSIONS IMPORTANT 1. Read this leaflet carefully before commencing to install the luminaire and retain it for future reference. 2. Check the rating label to ensure that the luminaire is suitable for the supply provided. 3. The operating temperature range is 15 C to + 50 C 1

4. The LED lamp must be changed at the intervals recommended by the lamp manufacturer which is up to 50,000 hours. 5. Under NO circumstances should a luminaire be opened, even when isolated, when an explosive gas or dust environment is present. INSTALLATION a) Mounting The luminaire is supplied with mounting brackets as shown in the diagram on the front of this leaflet. The luminaire must be securely fastened to its supporting structure. Care must be taken not to put the luminaire under any distortion as this may over-stress the glass assembly or make it difficult to open during re-lamping. b) Cable entries Plug-in entries 2 pin type used on Type 41LA Roadway Luminaires will accept Plug or Cable Sealing Boxes which are suitably certified, for use with the interface to N.C.B. spec No. 691, see leaflet ML2. These entries can be blanked using Blanking Covers as shown on leaflet ML2. FITTING OR REPLACING LED TUBES 1. The lampglass assembly is secured by a single bolt fixing and this is undone to remove the lampglass. The lampglass will be jacked out by the bolt, but if the assembly sticks jar the main body slightly to free it. Allow the lampglass assembly to hang on the suspension cord.(fig 1&2) Fig.1 Fig.2 2

2. Undo the push-on terminals from the pins on the lamp support assembly Plate. Remove the lamp support assembly by turning the securing screw through a couple of turns and then rotate the assembly until the screw head clears the keyhole slot. Remove (See Figs 3 &4). Fig.3 Fig.4 3. To replace LED tube, push the pin into the supporting clips. These clips should be located on the lampglass. 4. Push the terminations onto the remote end cap lamp pins. 5. Replace the lamp Assembly into the lampglass assembly and ensure that the locating bracket is passed over the head of the screw remaining in the lampglass assembly. Rotate to allow the keyhole slot to engage behind the screw head. Fully tighten the screw.(fig.5) Fig.5 3

6. Push the remaining terminals onto their respective pins, taking care to ensure that they are fully engaged before re-closing the lampglass. 7. Grease the spigot and main fixing bolt with a non-setting grease (see note f on next sheet). 8. Re-locate the lampglass Assembly in the Main Body Housing. Slide the lampglass forward until the fixing bolt makes contact with the thread in the fixing bolt hole in the main body. Do not attempt to force the spigot of the lampglass Assembly into the bore of the body. If at all tight, remove and re-enter to give the correct alignment. 9. Engage the thread of the fixing screw and tighten to close the lampglass assembly. The lampglass assembly is finally located when the lampglass assembly is fully home with the sealing ring compressed. 10. A feature of the 41LA is that the complete overtube assembly can be removed from the mounting channel by removing a split pin from the end of the channel and at the suspension cord point. The overtube may then be slid out of the mounting channel and replaced. See drawing on the front sheet for dimensions required for this. MAINTENANCE AND INSPECTION. Frequency of inspection must be determined by the installer, but should be frequent enough to ensure that the luminaires continue to work in their designed manner. The more onerous the working conditions, the more frequent the inspection. The interval should never exceed two years. The following list indicates some of the points that should be given particular attention. Suitable repairs should be carried out if required:- a) Clean all flameproof paths using a non-metallic scraper and / or suitable noncorrosive cleaners and examine the flameproof paths for signs of damage. Replace damaged parts. b) Dirty lampglasses should be cleaned using a mild soap solution. c) Replace cracked or damaged lampglasses. d) Replace any missing fasteners with items of the correct type and quality. e) Fit new gaskets, lock-washers, etc as appropriate. 4

f) Grease all flamepaths and screw threads with a non-setting grease that does not contain an evaporating solvent and does not cause corrosion of the surfaces to which it is applied. g) Ensure that blind tapped holes are clear of dirt, etc that could prevent correct closure of joints. h) Do not over-tighten fasteners on re-assembly. i) Ensure all mountings are secure and not corroded, including the suspension cord. j) Faulty lamps should be changed. k) Check the paintwork and renovate as needed. Note: changes to surface finish, paint, etc. may affect the surface temperature classification. l) Check cable glands for tightness and check the luminaire is efficiently earthed. m) Check the resin joints for deterioration. If damaged, the assembly must be replaced in its entirety. Resined components cannot be repaired except by the manufacturer. n) Any mechanically damaged parts must be replaced. GENERAL All components that are replaced should be in accordance with the manufacturer s specification. Failure to use approved parts invalidates the certification and approval of the luminaire and may make it dangerous. NO modifications should be made to the luminaire without the knowledge and approval of the manufacturer. HEALTH AND SAFETY AT WORK etc. ACT 1974 In the United Kingdom all equipment must be installed, operated and disposed of (as required) within the legislative requirements of the Health and Safety at Work etc. Act 1974. Leaflet No. HSS L1 refers to the Company s obligation and is available on request. It is the responsibility of the user to select, install, operate and 5

maintain the equipment in accordance with the relevant legislation and appropriate code of practice. WEE Producers Identification No. WEE/EA 0073UQ Prices and design are subject to alteration without notice. All products are sold subject to our conditions of sale, copies of which are available on request. We reserve the right to change characteristics of our products. All data is for guidance only. 6

INTENTIONALLY BLANK 7

EC - Declaration of conformity CE Dèclaration De Conformitè EG - Konformitätserklärung TYPE 41LA MINING LUMINAIRE Certification number SIRA02ATEX1407X I M2 EExd I Victor Products Ltd New York Way New York Industrial Park Newcastle upon Tyne NE27 0QF ENGLAND Victor Products Ltd Hereby declare our sole responsibility that the product which is the subject of this declaration is in conformity with the following standards or normative documents. Erklären in alleiniger Verantwortung, daβ das Product auf das sich diese Erklärung bezieht, mit der/den folgenden Norm(en) oder normativen Dokumenten Ubereinstimmt. Déclarons de notre seule responsabilité, que le produit auquel cette déclaration se rapporte, est conforme aux norme(s) ou aux documents normatifs suivants. Number and date of standard Nr. Sowie Ausgabedatum der Norm No. Ainsi que date d emission des normes. EN 50014 (1998) EN 50018 (2000) This equipment has been reviewed against the requirements of EN60079-0: 2006 and EN60079-1: 2004, in respect of the differences from the standards to which this certificate was issued; none of these differences affect this equipment. Diese Ausrüstung ist gegen die Anforderungen von EN60079-0 wiederholt worden: 2006 und EN60079-1: 2004, in Bezug auf die Unterschiede von den Standards, zu denen diese Bescheinigung ausgestellt wurde; keine dieser Unterschiede beeinflussen diese Ausrüstung. Cet équipement a été passé en revue contre les conditions d'en60079-0 : 2006 et EN60079-1 : 2004, en ce qui concerne les différences des normes auxquelles ce certificat a été délivré ; aucune de ces différences n'affecte cet équipement. EN50082 (1992) EN55015 (1993) EN 60555-2 (1987) Directive description Bestimmungen der Richtlinie Prescription de la directive 94/9 EC : Equipment and protective systems intended for use in potentially explosive atmospheres. 94/9 EG: Geräte und Schutzsysteme zur bestimmungsgemäßen Verwendung in explosionsgefährdeten Bereichen 94/9 CE: Appareils et systèmes de protection destinés a êtré utilisés en atmosphères explosibles. 89/336 EEC: Electromagnetic Compatability 89/336 EWG: Elektromagnetische Verträglichkeit 89/336 CEE: Compatabilité électromagnétique Notified Body: SIRA Certiifcation Services (0518) Rake Lane Eccleston Chester CH4 9JN H. Davis Engineering & Quality Manager Mar 2007 Notification No. SIRA 02 ATEX M191 8

9