CC3060 TYPE 12 CC3060 13 lbs 9,300 0.3 1 x 6 30 x 8-3/4 x 4 Efficiency: 68.8 Watts / C T based on average internal cabinet temperature. 2. CC3060 Rated cooling: 2,725 Watts mounted to an uninsulated 72 x 36 x 24 Cabinet CC3060 TYPE 12 CCS-PBD-7.2.2-883343-A
CC3260 TYPE 12 CC3260 13 lbs 8,600 0.3 1 x 6 13-7/8 x 12 x 7-7/8 Efficiency: 62.7 Watts / C T based on average internal cabinet temperature. Side View 2. CC3260 Rated cooling: 2,508 Watts mounted to an uninsulated 24 x 24 x 16 Cabinet CC3260 TYPE 12 CCS-PBD-7.2.2-883344-A
CC2060 TYPE 12 CC2060 9 lbs 3,350 0.2 1 x 4 22-1/2 x 6-1/4 x 4 Efficiency: 24.5 Watts / C T based on average internal cabinet temperature. 2. CC2060 Rated cooling: 980 Watts mounted to an uninsulated 24 x 24 x 16 Cabinet CC2060 TYPE 12 CCS-PBD-7.2.2-883342-A
CC6360 TYPE 12 CC6360 32 lbs 21,800 0.9 3 x 6 29 x 13-7/8 x 7-7/8 Efficiency: 159.7 Watts / C T based on average internal cabinet temperature. 2. CC6360 Rated cooling: 6,388 Watts mounted to an uninsulated 72 x 36 x 24 Cabinet CC6360 TYPE 12 CCS-PBD-7.2.2-883345-A
CC6361P & CC6362P* TYPE 4 or 4X Model Weight BTU / hr at 115 volts AC Size (H x W x D) CC6361 / 6362* 32 lbs 21,800* 0.9 3 x 6 29 x 13-7/8 x 7-7/8 Efficiency: 159.7 Watts / C T based on average internal cabinet temperature. 1. UL Listed for TYPE 4 or 4X environments. 2. CC6361P Rated cooling: 6,389 Watts mounted to an uninsulated 72 x 36 x 24 Cabinet *3. CC6362P HAS ALL TYPE 304 OR UNLESS SPECIFIED 316 STAINLESS STEEL WATER LINES THROUGHOUT UNIT. Unit gives approx. 2% less thermal performance. (approx. 6,260 Watts or 21,400 BTU/hr.) 4. Designed for surface mounting on the outside of cabinet. 5. TYPE 4 housing is aluminum housing (color is black). 6. TYPE 4X housing is type 304 or 316 stainless steel. 7. External water inlet and outlet connections. 8. Equipped with mounting gasket to maintain air tight seal. 9. Pressure tested to assure water tight seal. 10. Available with AC (115 & 230V) and DC (12, 24, & 48V) fans. DC version includes 11. Vertical mounting only. 12. Coolant water pressure: Pressure tested to 100 psi. Safe working pressure is 60 psi. 13. Recommended coolant flow rate (gallons per minute): 1 GPM 14. For design, quote, and sizing assistance: call (866) 936-6736. CC6361P & CC6362P* TYPE 4 or 4X CCS-PBD-7.2.2-883338-A
CC9000 & CC9000P * AIR-TO-WATER FLUSH MOUNT MODEL @ 40 C T Current Draw Fan Dimensions-Inches CC9000 79 lbs 57,000 2.4 8 x 6 70-1/2 x 23-3/4 x 8 Efficiency : 417.0 Watts / C T based on average internal cabinet temperature. SEE HOW CABINET COOLERS WORK CLICK HERE >> 1. RATED COOLING: 16,680 WATTS (MOUNTED TO AN UNINSULATED 72 x 36 x 24 CABINET WITH 2 GPM OF WATER AT 20 C, 40 C AMBIENT AIR AND 60 C CABINET AIR TEMPERATURE). 2. DESIGNED FOR SURFACE MOUNTING ON THE OUTSIDE OF CABINET. 3. ALUMINUM HOUSING (COLOR IS BLACK) OR STAINLESS STEEL. 4. EXTERNAL WATER INLET & OUTLET CONNECTIONS. 5. EQUIPPED WITH MOUNTING GASKET TO MAINTAIN AIR TIGHT SEAL. * 6. P UNIT IS PRESSURE TESTED TO ASSURE WATER TIGHT SEAL. 7. AVAILABLE WITH 115VAC, 230VAC, AND 12VDC, 24VDC, 48VDC FANS. 8. VERTICAL MOUNTING ONLY. 9. COOLANT WATER PRESSURE: THIS UNIT IS PRESSURE TESTED TO 100 PSI. SAFE WORKING PRESSURE IS 60 PSI. 10. RECOMMENDED COOLANT FLOW RATE (GALLONS PER MINUTE): 2 GPM 11. FOR DESIGN, QUOTE, AND SIZING ASSISTANCE : CALL (866) 936-6736. (650) 322-9500 CC9000 & CC9000P* CCS-PBD-7.2.2-883322-A