DEMCO DEMCO RESILIENT SEATED BUTTERFLY VALVE. Installation, Operation and Maintenance Manual D I S T R I B U T E D V A L V E S DEM-RSBV-IOM

Similar documents
DEMCO Resilient Seated Butterfly Valve

DEMCO Resilient-Seated Butterfly Valve

WKM Model MB DynaCentric High Performance Butterfly Valve

W-K-M Model MA-1 DynaCentric Butterfly Valve

RESILIENT SEATED CARTRIDGE STYLE BFV S

Installation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822

IOM Manual. IOM Manual. Series 76/77.

Fisher 9500 Butterfly Control Valve

Bray/Mckannalok Butterfly Valve Series 40/41/42/43/44/45 Installation Manual Technical Bulletin No Date: May 2004/Page 1 of 6

McCannalok HIGH PERFORMANCE BUTTERFLY VALVE OPERATION AND MAINTENANCE MANUAL. The High Performance Company

Wafer and Globe Style Silent Check Valve. Operation, Maintenance and Installation Manual

14 and Larger Wafer and Lug Style Dual Disc Check Valve. Operation, Maintenance and Installation Manual

Installation Operation Maintenance

2-12 Grooved End Dual Disc Check Valve. Operation, Maintenance and Installation Manual

VSI, LLC SERIES 2100 RESILIENT SEATED BUTTERFLY VALVES INSTALLATION, OPERATION AND MAINTENANCE MANUAL

YOUR GLOBAL FLOW CONTROL PARTNER. BRAY/MCCANNALOK EN High Performance Butterfly Valve Operation and Maintenance Manual

Bray/McCannalok High Performance Butterfly Valve Operation and Maintenance Manual

SLURRY KNIFE GATE VALVE

SWING CHECK VALVES SERIES 52-SC SERIES 600

ENGINEERING STANDARD

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING

Keystone Series GR resilient seated butterfly valves GRW/GRL Installation and operation manual

INSTALLATION, OPERATION, MAINTENANCE MANUAL FOR MANUALLY OPERATED STOP CHECK VALVE

Installation Operation Maintenance. LSSN Butterfly Valve AGA Approved 50MM - 150MM. QAD#IM6055.REVA

NYL Resilient Seated Butterfly Valves Operation and Maintenance Instructions

LC149 SERIES BUTTERFLY VALVE INSTALLATION, OPERATION, & MAINTENANCE

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING

Val-Matic 3"-24" Butterfly Valve With LSA Actuator and External Stops

740G Double Disc Check. Valve. Operation / Maintenance Manual. General Information 2. Installation/Operation 3

MK Series - High Performance Butterfly Valves Operation and Maintenance Instructions

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

A. This Section includes general duty valves common to several HVAC piping systems.

Newco / OIC / Cooper Forged Valves. Operation & Maintenance. Manual

DEMCO Model DM Gate Valves

Michigan State University Construction Standards. GENERAL-DUTY VALVES FOR PLUMBING PIPING Page

Crispin Valves Operating Guide. Crispin

CENTER LINE. INSTALLATION and MAINTENANCE INSTRUCTIONS RESILIENT SEAT BUTTERFLY VALVES MANUAL AND AUTOMATED

310 Wafer high performance butterfly valve 312 Lugged high performance butterfly valve

MODEL 5540 CONTENTS. Installation, Operation and Maintenance Instructions 1.0 GENERAL

Division 23 - HVAC Section Switzerland Beallsville K-12 GENERAL DUTY VALVES FOR HVAC PIPING

Series 820 AWWA Butterfly Valves

Double Offset High Performance Butterfly Valve

CompoSeal butterfly valves, wafer style Installation & Maintenance Instructions

Installation, Operation and Maintenance Manual. TOM WHEATLEY Piston Check Valve TOM WHEATLEY

Power-Seal High Performance Butterfly Valve: Series P1 Installation & Maintenance Manual

SECTION VALVES

Swing-Flex Check Valve

GT-200 GATE VALVES PN16, Screwed end

KEYSTONE SERIES GRF RESILIENT SEATED BUTTERFLY VALVES INSTALLATION AND OPERATION MANUAL

PNEUMATIC SLIDING VALVE

Butterfly Valves. watts.com

IMOI 2010 Rev 0

4 - Way Control 4 - Way Control 4 - Way Control with lock

NEECO INDUSTRIES INC. INSTRUCTION MANUAL 7 1/16 10K SLAB GATE BODY

The valves should be stored on a pallet or skid in a clean, dry warehouse. If the valves must be stored outside, the following apply:

INSTALLATION - MAINTENANCE MANUAL Severe Service Series M4 Ball Valve

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves

15100 VALVES. E. Section Building Automation and Control System Guidelines

KEYSTONE FIGURES 310/312 K-LOK BUTTERFLY VALVES

740G Double Disc Check Valve

DeZURIK 2 20" BOS BUTTERFLY VALVES

Installation, Operation, and Maintenance Manual GENERAL VALVE GENERAL VALVE TRUSEAL / IOM-GEN-TRUSEAL. Installation, Operation, and Maintenance Manual

Butterfly Valves. Jenkins Valves 254 Henry Street Brantford, Ontario N3T 5T7 Tel: Tel: Fax:

Fisher V250 Ball Valve

Gear Products Inc N. 161st E. Ave. Tulsa, OK Phone (918) Fax (918)

Swing-Flex Check Valve

Keystone Figures 310/312 K-LOK Butterfly Valves

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING

310 Wafer high performance butterfly valve 312 Lugged high performance butterfly valve

Series 800 AWWA Butterfly Valves

INSTRUCTIONS FOR INSTALLATION, START-UP, AND OPERATION

HIGH PRESSURE CONTROL VALVE R2L ACTUATOR

Series 2200/2220 Control Valve. Operation and Maintenance SCOPE OF MANUAL MAINTENANCE DESCRIPTION VALVE INSTALLATION

2-20 (50mm-500mm) SERIES 30/31 Wafer/Lug RESILIENT SEATED BUTTERFLY VALVES. The High Performance Company

DISCOVER VALVES. Standard Service Critical Application High Quality WKM DEMCO NEWCO NUTRON

DISCOVER VALVES. Standard Service Critical Application High Quality WKM DEMCO NEWCO NUTRON

Fisher POSI SEAL A31A Cryogenic High Performance Butterfly Valve

SAN ANTONIO WATER SYSTEM SPECIFICATIONS FOR RUBBER-SEATED BUTTERFLY VALVES 3 INCHES THROUGH 72 INCHES ANSI/AWWA C504 Class 150/250 December 2012

Hydraulic Motors Repair Instructions

INSTALLATION & MAINTENANCE MODEL mm

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

for ½" thru 2" 800 lb. Piston Lift Check Valves with Resilient Seat Option

KEYSTONE SERIES 320 BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

LARGE DIAMETER VALVES

Storage: The valves should be stored on a pallet or skid in a clean, dry location.

INSTRUCTION MANUAL. Anchor Darling 1878 Swing Check Valves. Installation Operation Maintenance. Sizes 1/2 through 2 FCD ADENIM

Ver Trunnion Ball Valve INSTALLATION, OPERATION AND MAINTENANCE MANUAL FBV/IOM/BA02

720G Wafer and 821G Globe Style Silent Check Valves

SECTION VALVES PART 1 - GENERAL

Transportation Valves

Val-Matic 3-72 Cam-Centric Plug Valve

POSI-SEAL Type A31A Cryogenic High Performance Butterfly Valve

SERIES 90/91 R PNEUMATIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

D I S T R I B U T E D V A L V E S. Super G Lubricated-Non-Lubricated Plug Valve TEXSTEAM

Installation, Operation, and Maintenance Manual

Installation, Operation and Maintenance Manual for the HE Series

DeZURIK 24" THRU 36" RESILIENT BUTTERFLY VALVES

Union County Vocational - Technical Schools Scotch Plains, New Jersey

KEYSTONE Figure 990/991 Butterfly valves Installation, operation and maintenance instructions

KEYSTONE OPTISEAL F14/16-15/17 AND BREWSEAL BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Transcription:

DEMCO RESILIENT SEATED BUTTERFLY VALVE DEMCO

TABLE OF CONTENTS DEMCO RESILIENT SEATED BUTTERFLY VALVE Bill of Materials... 1 Scope... 3 Nameplate Information... 3 Storage... 3 Installation... 4 End-of-Line Service... 4 Gaskets... 4 Flanges... 4 Disc/Pipe Clearance... 5 Flange Bolts... 5 Procedure... 6 Operation... 6 Trouble Shooting... 7 Cameron s Valves & Measurement Group Revised 10/07

Bill of Materials 22 24 7 4 14 24 23 2 3 1 6 23 7 Figure 1 - DEMCO 2" through 12" Resilient Seated Butterfly Valve DEMCO 2" through 12" Parts List ITEM REQ'D DESCRIPTION 1. 1 Body 2. 1 Seat 3. 1 Disc 4. 1 Upper Stem 6. 1 Lower Stem 7. 2 Spring Pin 14. 1 Retainer 22. 1 Top O-Ring 23. * Stem O-Ring 24. 2 Bearing * 4 Required for throttling valves only. 1

Bill of Materials 24 7 4 14 24 23 2 23 3 1 6 23 23 7 25 Figure 2 - DEMCO 14" through 36" Resilient Seated Butterfly Valve DEMCO 14" through 36" Parts List ITEM REQ'D DESCRIPTION 1. 1 Body 2. 1 Seat 3. 1 Disc 4. 1 Upper Stem 6. 1 Lower Stem 7. 2 Spring Pin 14. 1 Retainer** 23. * Stem O-Ring 24. 2 Upper Bearing 25. 1 Lower Bearing * 4 Required for throttling valves only. ** 24" - 36" Spacer. 2

Scope DEMCO Resilient Seated Butterfly Valves are an economical alternative to ball, gate or plug valves in many applications. They are light weight quarter turn devices with few parts. They are designed for bubble-tight sealing up to rated pressure and are capable of throttling service. They are easily adapted to automatic actuators. The DEMCO Resilient Seated Butterfly Valve is available in flangeless wafer design or single flange tapped lug configuration. Nameplate Information Valves & Measurement P/N Descr: 2 1 Rev. DEMCO Oklahoma City, OK, USA Body: Disc: 3 4 Stem: Seat: 6 5 WO: Figure 3 - DEMCO Resilient Seated Butterfly Valve Item Stamp 1 Product ID Number 2 Product Description 3 Body Material 4 Disc Material 5 Seat Material 6 Stem Material Storage DEMCO Resilient Seated Butterfly Valves are shipped in the partial open position to minimize permanent deformation of the resilient seat. The disc edge is contained within the flange faces of the valve to prevent damage to the sealing area (Figure 4). Caution: valves with fail open or closed actuators are shipped with the disc in the fail position and extra care should be given to prevent damage to the disc edges. Valves should be stored in a clean dry area away from extremes of heat. The resilient seat surfaces should be protected from sunlight and physical abuse. Figure 4 3

Installation Direction - DEMCO Resilient Seated Butterfly Valves are bidirectional and will operate in any position. Normally the valve is installed with the upper stem pointing upward (Figure 5). Elevated valves with gear operators and chainwheels should be installed with the upper stem pointing down (Figure 6) so the open-closed indicator is visible from the ground and the chain does not drag on the pipe. End-of-Line Service - DEMCO tapped lug butterfly valves are suitable for liquid service end-of-line applications with downstream piping removed (Figure 7). Only weld neck or socket weld flanges can be used for this service. Since the upstream pressure is excluded between the flange and the seat face by the exclusive DEMCO flange seal, there is no effective force to slide the seat downstream. Figure 5 Caution: The valves must not be opened or closed with the downstream piping removed as the seat might be shifted breaking the flange seal and allowing pressure to slide the seat downstream. Gaskets - Flange gaskets are not required nor recommended for use with positive shut-off DEMCO Resilient Seated Butterfly Valves. An integral flange seal is molded into the edge of the rubber seat eliminating the need for flange gaskets. Throttling Valves, only, utilize an o-ring stem seal that must be assisted with flange gaskets for a proper seal. Flanges - Steel ASME Class 150 (or MSS SP-44) weld neck, slip-on, threaded and socket weld as well as "stub end" type C flanges are suitable for use with 2" thru 24" DEMCO Resilient Seated Butterfly Valves. 30" and 36" DEMCO Resilient Seated Butterfly Valves fit between ASME 125/ASME 150 Series A Flanges (or MSS SP-44). Other flange types may be applicable also, but should be thoroughly checked to assure proper seal makeup. Plastic flanges are subject to damage at installation by over-tightening the bolting and may defect or "cup" resulting in flange leaks. Upstream Figure 6 Disc Figure 7 4

Disc/Pipe Clearance Before beginning installation, disc/pipe clearance should be checked to avoid the possibility of scraping the disc edge on the pipe ID and damaging the sealing surface. Minimum pipe ID requirements are given in Table 1. PIPE I.D. DISC CHORD Figure 8 Flange Bolts Recommended bolt and stud lengths for installation in ASME flanges are provided in Table 2. MSS flanges require longer bolts. Valve Bolt Wafer Body Lug Body Size Size Stud Screw Screw (in.) (in.) Qty. Length Length Qty. Length "A" (in.) "B" (in.) "B" (in.) 2" 5/8"- 11 4 5" N/A 8 1 1/2" 2 1/2" 5/8"- 11 4 5 1/2" N/A 8 1 1/2" 3" 5/8"- 11 4 5 1/2" N/A 8 1 1/2" 4" 5/8"- 11 8 5 3/4" N/A 16 1 3/4" 5" 3/4"- 10 8 6 1/2" N/A 16 1 3/4" 6" 3/4"- 10 8 6 1/2" N/A 16 2" 8" 3/4"- 10 8 7" N/A 16 2 1/4" 10" 7/8"- 9 12 7 1/2" N/A 24 2 1/4" 12" 7/8"- 9 12 8 1/4" N/A 24 2 1/2" 14" 1"- 8 12 8 1/4" N/A 24 2 1/2" 16" 1"- 8 16 10" N/A 32 3 1/4" 18" 1 1/8"- 7 16 10 1/2" N/A 32 3 1/2" 20" 1 1/8"- 7 20 11 3/4" N/A 40 4" 24" 1 1/4"- 7 20 12 1/2" N/A 40 4" 30" 1 1/4"- 7 * * * 56 5" 36" 1 1/2"- 6 ** ** ** *** *** Table 2 - Flange Bolt Size * - 24 Studs 1 1/4" - 7 x 15 1/2" ; 8 capscrews 1 1/4" - 7 x 5" ** - 28 Studs 1 1/2" - 6 x 18 1/2" ; 8 capscrews 1 1/2" - 6 x 5 1/2" *** - 56 Capscrews 1 1/2" - 6 x 6"; 8 capscrews 1 1/2" - 6 x 5 1/2" Valve Disc Swing Opens into: Size (in.) Size (in.) Std Pipe Sch 40 Sch 80 2" 1.467" X X X 2 1/2" 2.144" X X X 3" 2.743" X X X 4" 3.601" X X X 5" 4.582" X X X 6" 5.624" X X X 8" 7.428" X X X 10" 9.382" X X X 12" 11.35" X X X 14" 12.86" X X N/A 16" 14.72" X X N/A 18" 16.61" X X N/A 20" 18.53" X X N/A 24" 22.57" X X N/A 30" 28.67" X N/A N/A 36" 34.70" X N/A N/A Table 1 - Disc Clearance LUG BODY CAPSCREWS B WAFER BODY STUDS & HEX NUTS Figure 9 Figure 10 A 5

Procedure - The following procedure applies to new installation between standard ASME pipe flanges. When replacing a valve from an existing installation, clean flange faces and check for excessive corrosion or other damage to the sealing face of the flange. 1. Remove the valve from any packing material. Close the valve disc so that it is contained within the flange faces. It is not necessary to fully close the valve; the disc must be contained within the confines of the valve body so it will slip between the mating flanges without contact with the flanges. 2. When installing wafer body valves, install the lower flange bolts without tightening. Position the valve between the flanges, within the pocket formed by the flange bolts. (The OD of the wafer body is equal to the inside of the bolt circle of the Operation DEMCO Resilient Seated Butterfly Valves should never be operated without a handle or other means of controlling the disc. Caution: Failure to restrain the disc under flow conditions can result in the disc slamming closed and possible damage or broken parts. 2" through 12" DEMCO Resilient Seated Butterfly Valves have flats on the upper stem. 14" and larger valves have a single square key. Stem flats or the square key indicate valve position. When they are in line with the flow stream, the valve is open. When perpendicular, the valve is closed. Manually Operated - DEMCO Resilient Seated Butterfly Valves operate from fully open to fully closed by a 90 turn of the handle. The handle is marked with a flow arrow. When this arrow is in line with the pipe axis, the flanges, so the valves are self-centering). Install the remaining flange bolts. 3. Lug bodies have tapped holes coinciding with those in the flanges. They should be positioned between the flanges and the capscrews inserted through the flange holes into the threaded lug holes. 4. Tighten all bolts or capscrews in a crossover or star pattern to assure even sealing. Tighten sufficiently to assure metal-to-matal contact between the flange face and the metal butterfly valve body. No further tightening is required. 5. Carefully check disc clearance by placing the valve in the full open position. Any binding or scraping should be investigated and corrections made. valve is open (Figure 11). When perpendicular to the pipe, the valve is closed (Figure 12). Worm Gear Operated - Worm gear operators are recommended for valves larger than 6 inches. Clockwise rotation of the handwheel closes the butterfly valve. Counterclockwise rotation opens the valve. Gear operators are always mounted with the input shaft perpendicular to the pipe axis for handwheel clearance. Each operator has an arrow on the top of the gear, which indicates the "OPEN - CLOSED" position of the valve (Figure 13). Automatic Valves - Butterfly valves with their quarter turn operation are easily adapted to automatic actuators for remote operation. To prevent water hammer, actuators should close the valve slower than 6 to 8 seconds, open-to-close. Rapid closure causes water hammer which can break or otherwise damage valve parts. DEMCO DEMCO CLOSED OPEN CLOSED Figure 11 Valve shown OPEN Figure 12 Valve shown CLOSED Figure 13 Valve with Gear Operator 6

Troubleshooting Trouble Probable Cause Remedy The valve will not seal properly. The valve is hard to operate. The valve will not open. The valve is leaking around stem. The valve closes with line flow. Flange leaks. The seat and/or disc is worn or damaged. Foreign matter is present between seat and disc. Operator stops are not set properly. Build up of solids or roughness on edge of disc. Operator is not installed properly. Disc hits on side of pipe. Seat is damaged or worn. Disc is bent. Flange seal is leaking Handle or actuator does not provide proper restraint. Line flow too great. Flange seal surface on seat is damaged. Flange surfaces are damaged or corroded. Flange bore is too large. Replace worn parts.* Operate several times to wipe clean. Adjust stops to proper setting. Operate several times to wipe clean or disassemble valve and clean disc edge.* Reinstall operator in proper alignment with valve stem. Check for proper pipe clearance. Replace Seat.* Replace disc, stems and seat as required* Correct flange seal leak to prevent fluid from migrating behind seat and out stem. Restrain disc with handle or actuator. Choose larger valve or slow down flow. Replace seat.* Clean, repair or replace flanges. Replace with proper flanges. Clockwise rotation of Gear Operator handwheel opens valve. Open-Shut indicators do not coincide with valve disc position. Automatic actuator slams valve shut or open. Hard, soft or cracked seat damage is present. Gear operator has been rotated Rotate gear operator 90 on valve top to put 90 on valve top. input shaft perpendicular with pipe axis. Handwheel shaft aligns with pipe (should be perpendicular). Speed control valves missing or not adjusted. Heat or chemical damage to seat Install and/or adjust speed control valves. Replace elastomer seat with compatible material and/or correct offending fluid conditions. * Contact your Cameron representative for repair manual. 7

NOTES

NOTES

Contact your Cameron s Valves & Measurement group representative for a Repair Manual DEMCO 3250 Briarpark Drive, Suite 300 Houston, Texas 77042 USA Toll Free 800 323 9160 For the most current contact and location information go to: www.c-a-m.com Cameron s Valves & Measurement Group Revised 10/07