Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)

Similar documents
A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

A. Submit manufacturer's literature and technical data before starting work.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Low Voltage Automatic Transfer Switch Systems

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

University of Houston Master Construction Specifications Insert Project Name

ASCO Low Voltage Automatic Transfer Switch Systems

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

University of Houston Master Construction Specifications Insert Project Name

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

Design considerations for generator set mounted paralleling breakers

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

E-12 Low-voltage Switchboard

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers

MEDIUM-VOLTAGE SWITCHGEAR

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

BGE STRATEGIC CUSTOMER ENGINEERING

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

BUSWAY Low Voltage (Pow-R-Flex)

SECTION PANELBOARDS

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

E-12 Low-voltage Switchboard

Critical Power Switchboards. Selection and Application Guide

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

Horizontal Circuit Switchers

Horizontal Circuit Switchers

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

7. SERVICES OVER 600 VOLTS

Unified requirements for systems with voltages above 1 kv up to 15 kv

MaxSG Low Voltage Switchgear

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

POWERFUL LINEUP. Paralleling Generator Sets

WARREN COUNTY, N.Y. M/E REFERENCE

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Quick Start Guide TS 910 & TS 920

Recommended Procedures

Electromagnetic Industries LLP

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

Alternator protection, part 1: Understanding code requirements

Power System Solutions (PSS)

SECTION MOTOR CONTROL

CENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

GE 8000-Line Motor Control Centers

A. This section includes unit capacitors for power factor correction.

Magnum IEC Low Voltage Air Circuit Breakers

Application Note RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS

A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less.

2009 North American Power Quality Interest Group Workshop Title: Power Quality of Emergency Stand-by Systems

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECONDS CAN COST MILLIONS

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Standby Power Systems

Quick Start Guide TS 910

Bypass/Isolation Switches RTS-03 SERIES

MP7650 CONTROLLER. Lake-Shore-Electric.com MP7650 Controller STANDARD FEATURES 1.0 INTRODUCTION

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Rex Healthcare Medium Voltage System Presentation APEC 2015 March 15-19, 2015

Design Standard. Purpose: Design Standard:

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

Design Standards NEMA

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw

Optimizing Emergency Power Systems for Health Care Applications

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations

DMX 3 -I 2500 switch disconnectors

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

TYPES DS II AND DSL II METAL ENCLOSED LOW VOLTAGE POWER CIRCUIT BREAKERS

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

Chapter 6 Generator-Voltage System

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Figure 1. Single-phase pad-mounted voltage regulator. STANDARD FEATURES

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

SECTION DC POWER SUPPLY/BATTERY CHARGER

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

Paralleling Equipment

Switchgear. Low Voltage

Zone Selective Interlocking

Bypass/Isolation Switches RTS-30 SERIES

SECTION LOW VOLTAGE SWITCHBOARDS - Spectra Bolt-On

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

SECTION 16311A INTEGRATED UNIT SUBSTATIONS (IUS) SECONDARY LESS THAN 1000 V

SECTION 16426B. RELATED SECTIONS Section 16671A Transient Voltage Surge Suppression Section Microprocessor-Based Metering Equipment

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System

Powerware Master Modbus

Transcription:

2101 Commonwealth Blvd, Suite B Ann Arbor, MI 48105-5759 www.med.umich.edu/facilities/plan/ 263010-H: SUPPLEMENTAL PARALLELING GEAR (16315-H) Related Sections Basis Guideline: N/A For an explanation of the use of these guidelines, see Design Guidelines for UMHHC Facilities General Paralleling gear shall be installed in all locations were multiple generators are being installed under current project, and/or will be installed in the future. In all instances this paralleling gear will be installed in a separate room from the generators, and shall meet the following requirements. The paralleling gear shall have capability to be expanded for its building s projected growth. Generator plant shall ideally be designed with N+1 configuration loss of one generator still supports all emergency loads. Allow physical space so gear can be expanded by at least one section in both directions. Ends of bus bar are to be prepped for future expansion. The first generator shall be to be online, serving the Life safety and Critical Loads within 10 seconds of the loss of power. Configure gear to have the largest available generator start first. Ideally, all generators controlled by the paralleling gear are the same size, fuel type, and pitch. As noted above paralleling gear shall be in a separate room from the generators. Rooms or vaults for paralleling gear shall be adequately ventilated for equipment cooling. Provide rear access to all paralleling gear sections. Do not have sprinkler heads mounted directly above units. Do not install duct work and/or piping above the electrical gear. Do not run piping and/or duct in electrical that does not serve the room. Provide red acrylic mimic bus affixed with machine screws showing entire one-line of gear. Manual paralleling controls located at paralleling gear should always be present to support/back-up the automatic controls. Provide provisions to rotate the generators if N+1 scheme is used. Construct paralleling gear to be phased X-Y-Z (or A-B-C) from top to bottom, front to back and left to right when viewed from the front. All buses, bonding jumpers, and termination lugs shall be silver plated copper and shall be connected using at least two bolted (or more for higher currents) connectors at each bus joint, and/or at all insulators. Bolted connections shall use hex head bolts and split lock washers made of stainless steel or grade 5 steel with yellow zinc dichromate finish. Bus bars shall be silver plated copper before final assembly, including neutral and ground buses. The NEMA specified minimum (current carrying) cross sectional area of the bus should not be compromised by the holes needed to make connection. Each section of the paralleling gear shall be of metal clad construction. All lugs within the parallel gear shall be of the long barrel two hole (minimum) type, mechanical lugs shall not be accepted. Page 1 of 5

Power Limitations Size and brace the bus amperage and AIC rating of the paralleling gear and all breakers to support the ultimate number of generators to meet the scope of work, plus an addition of a future expansion generator of the same size. Automatic Transfer Switches serving essential loads shall not have non-essential loads. Size the paralleling gear in such a way that the bus is capable of handling all planned generators running at 100% capacity plus one possible future generator running at 100%. Incoming Section Requirements Provide generator connections in dedicated sections. (i.e. only one generator per section of paralleling gear.) Provide silver plated copper bus bar connection for generator connections. Provide each generator section with voltmeter (600V scale), ampere meter (4-1/2, 1% accuracy, scale as required), frequency meter (55 65 Hz scale), Wattmeter (scale as required), and synchroscope for each generator connection. All meters are to be analog type (definite preference), 1% accuracy, and with a scale length of approximately 4-1/2. Ampere meters and voltmeters to have four position phase selector switch. These provisions are to be made for future generator incoming sections. When the future generator is added the section, all provisions shall be in place so only the trip unit is to be put in place. Distribution Section Requirements Provide 20% spare (10% spare and 10% spaces) positions in the gear being provided for future loads. Provide a minimum of one spare breaker for each breaker size installed. All sections designated as spaces are to be identically prepped and bussed as occupied breakers. Feeder breakers shall be: 1. Individually mounted, draw out, mechanically operated, stored energy type, quick-make and quick-break air circuit breakers. a. Unless noted otherwise, the breakers shall be manually 'charged'. b. Electrically operated (electrically charged) breakers shall be supplied where called for on the drawings. Each electrically operated breaker shall be powered by a dedicated, charging motor. 2. Breakers shall be equipped with removable arcing contacts and operation counters. 3. Breakers shall be rated for 100 percent continuous duty, with frame and trip (sensor) ratings as shown on the drawings. Sensor size (and design application) will typically be 75%, or more, of the frame size 4. Breakers shall be capable of being manually racked into three positions; connected, test and disconnected. The breaker frames shall be grounded in all positions. 5. The compartment front doors shall be closable in all breaker positions and shall permit breaker operation with door open or closed. The doors shall be capable of being opened without tripping breakers in the connected position. 6. A breaker shall be tripped open and the stored energy in the breaker mechanism shall be discharged as the breaker is moved from one position to another. 7. Breaker compartments shall be dead-front. Shutters shall close automatically as a breaker is racked out of the 'connected' position. Control contacts shall be 'made' when breaker is in test or connected positions. 8. Breakers shall have a minimum of two spare Form C", isolated contacts brought out to an accessible terminal strip in the compartment. The contacts shall be rated 120 volts, 10 amperes, 60 Hz. Page 2 of 5

9. Each breaker shall be equipped with three-phase and one neutral current sensor, and a microprocessor-based trip unit. 10. Where shown on the drawings, breakers shall be equipped with a flux transfer shunt-trip. The flux transfer shunt trip wiring shall be terminated on an accessible terminal strip in the compartment. 11. Breakers shall be capable of being padlocked in the open position. 12. Breakers shall not be less than 10% of the rated bus. Each breaker shall be equipped with RMS sensing trip units as noted below. 1. Solid-state trip units shall be true RMS sensing, with trip ratings adjustable by removable rating plugs. The trip units shall be magnitude and time adjustable, and shall include a local indication of the cause of a trip. The trip units shall be rated as shown on the drawings. 2. The trip units shall coordinate with the primary fuses, main breaker and largest downstream feeder breakers. 3. The trip units shall allow adjustment without breaker trips and routine testing without removing the breakers from service. 4. The trip units (sensors) shall be rated for 100 percent continuous duty. 5. Trip units shall provide the following ranges and functions as a minimum. See drawings for specific requirements that vary from this configuration: a. Long time (L) current settings of at least 50-100 percent of the current sensor rating, divided into seven or more steps, and time delays of at least 2-22 seconds, at 600 percent of the long time current setting, divided into seven or more steps. b. Short time (S) current settings of at least 250-1000 percent of the long time current setting, divided into seven or more steps, and time delays of at least.1-.5 seconds, divided into seven or more steps, to include "flat response" and "I2T response" characteristics. c. Instantaneous (I) (with off position) settings of at least 200-1000 percent of current sensor rating. d. Ground fault (G) current settings of 25-100% of current sensor rating, with a 1200 ampere maximum, divided in seven or more steps, with ground fault time delay settings of at least.1-.5 seconds, divided into five or more steps, to include "flat response" and "I2T response" characteristics. e. Provide ground fault warnings, not trips, for all breakers. Avoid providing unnecessary ground fault protection that may cause nuisance outages. f. All trips 6. Power for operating the solid state trip unit shall be obtained from within the circuit breaker assembly itself, or it shall be provided by a separate control circuit connected to the secondary bus ahead of the main breaker. The solid state trip units shall have nonvolatile memory to maintain all settings, trip indications and fault data during a power outage. Batteries to maintain the memory are not acceptable. The system shall be capable of initiating manual or automatic load testing with specified load bank. If normal utility power fails during a load test, the generator paralleling control system shall open the trip unit providing power to the load bank and initiate emergency procedures. The A/E shall design the over current protective system so the paralleling gear trip units are coordinated with the down stream fuses and down stream devices to minimize the disruption from any given fault, to as small an area as possible. The A/E shall also prepare, and/or approve the settings for the over current protective system to insure proper selectivity and coordination. The contractor shall provide test reports showing that the over current system has been set and tested, before the system is commissioned Bus bars shall be braced for the calculated short circuit current. Provide an analog voltmeter with selector switch, and an ammeter with selector switch. Selector switches shall have also off position. Page 3 of 5

Engine Generator Set Monitoring and Control The generators, automatic transfer switches, and paralleling switchgear shall operate as a complete and integrated system to provide the necessary power to the building s electrical distribution in the event of normal utility source failure. Note: Systems that use paralleling controls that are mounted on the engine generator are not acceptable. The system shall be capable of manually adding and shedding loads from the paralleling gear in the event that the interface or automatic controls are lost. Paralleling switchgear shall have a "Bus Optimization" program that will automatically add loads if there is sufficient capacity in the generator system with all or one of the generators running. Bus Optimization is to be activated or deactivated via a hardwired toggle switch located on the paralleling control panel. When Bus Optimization is active a hard-wired LED light and the touch screen shall indicate that the feature is working and automatically controlling loads. Bus optimization will add loads automatically based upon a table of KW values associated with the next priority load, including start up requirements to be added, and determine if there is sufficient head room to add that load. Once the new load is added and after a field adjustable stabilization time delay, a new demand KW reading shall be taken and the next priority load evaluated to see if it can be added without overloading the bus. The program shall compare the peak of the start-up for each load and update the tables only if the value goes up. When the bus has been loaded to a level such that the next load would exceed 90% of bus capacity, a hard wired light and a warning in the control touch screen will activate to alert the operator that the next load is expected to overload the generator system. The system will continuously monitor the generator demand and evaluate if the next load can be added to the bus. If the building demand decreases and the next load can be added without overloading the system beyond 90%, then the load will be added. This evaluation process will continue and safely add as many loads as possible automatically to the generating system. The number of priorities is not to be limited by the number of generators. Priorities, other than Critical and Life Safety, shall be determined by loads that required to be grouped together in order to function, such as dampers with air handlers. The amount of time to add all of the Equipment loads shall be less than one minute from time of outage. In the event a generator fails, or increase in building load, or there is a bus under-frequency, the lowest priority load or loads will be shed to keep the remaining higher priority loads running. The system must be designed to prevent stalling or failing of the remaining generator(s). Priority one (Life Safety and Critical) non shed-able loads must be maintained in any bus optimization system design. The system shall be designed to interface with the existing or planned Eaton power monitoring system within the building. Provide one point of connection for Ethernet communication. Identify the number of free channels required by the power monitoring system and verify capacity of software. Power monitoring to include the following: 1. Each Automatic Transfer Switch to report position, load, available normal and emergency power, kw load. 2. Position of each generator trip unit, general alarm, and ground alarm. 3. All generator information to complete a Joint Commissions Report and any additional generator information retrieved by paralleling gear for proper control. 4. General paralleling gear alarm. Provide remote access to alarm screen that gives the duplicated information that is provided on the interface that is located at the local control screen. Page 4 of 5

Digital and Manual Control Provide a Master Control and Monitoring Panel, with a touch screen interface, which displays the position and load of each trip unit and ATS. Also, display the power provided by each generator and total load of system. The Master Controller shall have redundant processors. It shall be designed in such a way that the paralleling gear will not fail upon the loss of one processor. The interface shall allow designated personnel to set priority levels to loads and shall display the status and value of each priority as it is loaded and shed. Provide the ability to bring on all generators on line manually at the paralleling gear. Page 5 of 5