Tranquility. Large Vertical. Revised: 08 February, Submittal Data - S-I Units. Performance Data. Electrical Data. Unit Designation: Job Name:

Similar documents
Large Belt Drive (HBH/V) Series HBH HBV

Tranquility. Models TRH/V Revised: 18 July, Submittal Data - I-P Units. Performance Data. Electrical Data. Unit Designation: Job Name:

Tranquility Water-To-Water (TMW) Series

Residential Packaged Geothermal Heat Pump

Tranquility 16 (TR) Series Submittal Data

Tranquility 16 (TR) Series Submittal Data

Compact (HBH/V) Series HBH-HBV

Tranquility Compact (TC) Series Submittal Data

Tranquility Ducted Vertical Stack (TSL) Series Submittal Data

Tranquility 20 (TS) Series Submittal Data

Tranquility (TBW) Water-To-Water Series. WATER-TO-WATER SYSTEMS SIZES 036, 060, AND 120 [8.7, 13.5 and 26.9 kw]

TRANQUILITY 20 SINGLE-STAGE (TS) SERIES

Serenity GT Series. Two-Stage, R-410a Packaged Horizontal & Vertical Unit Specifi cations Catalog.

Heating and Air Conditioning

Engineering Data Submittal Manual

ENGINEERING DESIGN GUIDE

ARBOR BASE SERIES COMMERCIAL Geothermal/Water Source Heat Pumps Tons. Submittal Data English Language IP/Metric Units SD1201AZA 05/14

Heating and Air Conditioning

ComPACT. Commercial kw Water Source/Geothermal Heat Pump - 50Hz. Submittal Data English Language/IP Units SD1025AN 07/12

Geothermal Heat Pump Systems

ASTON SERIES COMPACT Commercial Ton Water Source/Geothermal Heat Pump. Submittal Data English Language/IP Units SD1022AGA 05/14

Heating and Air Conditioning

Engineering Data Submittal Manual

GT-PX SPLIT (50YDS) SERIES. Carrier Geothermal Heat Pump Systems GT-PXS 1. All Products Technical Guide:

RWT Series Water-to-Water Heat Pumps & Hydronic Air Handlers / A Coils: Engineering Data and Installation Manual

GT-PW (50YER) Water-to-Water Series. WATER-TO-WATER PURON SYSTEMS SIZES 036, 060, AND 120 [8.7, 13.5 and 26.9 kw]

HEAT CONTROLLER, INC. HC Series 1/2 to 5 Tons Commercial Water Source Heat Pumps

HEAT CONTROLLER, INC.

Engineering Data Submittal Manual

i Series Model SV Water Source Heat Pump 1/2 to 6 Ton

Tranquility 30 Digital (TE) Series Submittal Data

Product Data. S Two-stage scroll compressor S Variable speed ECM blower motor Control

i Series Model SV Water Source Heat Pump 1/2 to 6 Ton

Product Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm

Premier Split Specification Catalog

Tranquility Digital Split (TES/TEP/TAH/TAC) Series. TWO-STAGE INDOOR AND OUTDOOR SPLIT EARTHPURE SYSTEMS SIZES [

Product Data. S Single-stage scroll compressor S Multi-speed constant torque blower motor Control

Product Data. FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil

FMU4X, FMC4X FMU4Z, FMC4Z

48CWA2-00 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 48,000 BTUH

36CWA4-HW 4-Pipe Chilled & Hot Water Air Handler (120V) 4-Pipe Heat & Cool Fan Coil 36,000 BTUH

Product Data FFMA BASE SERIES FAN COIL SIZES 018 TO 037 FEATURES

24CWA4-HW 4-Pipe Chilled & Hot Water Air Handler (120V)

Tranquility 30 Digital (TE) Series Submittal Data

Product Data. S Two-stage scroll compressor S Used with variable speed fan coil or furnace coil Control

MHWW-24-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 24,000 BTUH. Rev. 1.3

Product Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES

Product Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO

ARBOR BASE SERIES COMMERCIAL Geothermal/Water Source Heat Pumps Tons. Submittal Data English Language IP/Metric Units SD1201AZB 03/16

Engineering Data Submittal Manual

CFM (L/s) Min Max 450 (212) 600 (283) 750 (354) Dimensions H x W x D in. (mm) 675 (319) 36 1/2 x 20 1/2 x (425)

Operating Net Capacity BTU/h. Input BTU/h Efficiency. lbs (kg) PGR524040KGP* 23, ,000/26, /8 x 47 x 31-7/16

500RO11. Outdoor Split Geothermal Heat Pump 2-6 ton (dual capacity) Submittal Data English Language/IP Units SD2504SN 04/17

Product Data. Features/Benefits. Omnizone 50XCA06-14 Air-Cooled Indoor Self-Contained Systems with Puron Refrigerant (R-410A) 5 to 12 Nominal Tons

Product Data. CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) FMA4P1800AL 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

CFM (L/s) Dimensions. Filter Size Ship Wt. HxWxDin.(mm) 1800Aǂ 1-1/2 18, (212) 675 (319) 36-1/2 x 20-1/2 x (45) FMA4P (928 x 521 x 381)

Product Data. S Two-stage scroll compressor S Used with variable speed fan coil or furnace coil Control

CFFWA Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 12,000-60,000 BTUH

CFM (L/s) Dimensions. Filter Size in. Ship Wt. H x W x D in. (mm) 1800A 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

Heating and Air Conditioning

DIMENSION AND SELECTION GUIDE

Precision Cooling For Business-Critical Continuity. Liebert CW. System Design Manual kW, 50 & 60Hz

Heating and Air Conditioning

Q6SP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.

MH1WC4W-08-1-B Chilled/Hot Water 1-Way Cassette Fan Coil

Product Data. Features/Benefits. OMNIZONE 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems with PURON Refrigerant (R-410A)

CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) 1800Aǂ 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

ENGINEERING SPECIFICATIONS:

GV Series High Efficiency Geothermal/Water Source Packaged Step-Capacity Heat Pump R-410A

BAC / BHC Product Specifications

GT-PB (50YF) Digital Packaged Series TWO-STAGE DIGITAL HORIZONTAL AND VERTICAL PURON. SYSTEMS SIZES [ kw]

PCB COMMERCIAL SERIES

CDI series. Engineering Submittal Sheet. Model SM Residential Geothermal Heat Pump. Standard Features. Overview and Certifications

Tranquility 20 (TS) Series. SINGLE-STAGE HORIZONTAL, VERTICAL, AND DOWNFLOW EARTHPURE SYSTEMS SIZES [ kw]

PHR5. Product Specifications

DIRECT EXPANSION COMMERCIAL PACKAGED AIR HANDLING UNITS, 6 25 TONS

Product Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES

GPC14H 2- to 5-Ton Packaged Air Conditioner Up to 14 SEER

Product Data FF1E LEGACY LINE FAN COIL SIZES 018 THRU 037 FEATURES

Specification Manual

CDI series. Engineering Submittal Sheet. Model SM Residential Geothermal Heat Pump. Standard Features. Overview and Certifications

BAC / BHC SERIES 6 to 20 Ton Air Handlers

NXW 10 TO 50 TON. Commercial Reversible Chiller - 60 Hz. Submittal Data English Language IP/Metric Units SD2502WN 06/14

BAC / BHC SERIES 6 to 20 Ton Air Handlers

Product Data PH3Z 13 SEER SINGLE -PACKAGED HEAT PUMP SYSTEM WITH R -22 REFRIGERANT SINGLE AND THREE PHASE 2-5 NOMINAL TONS ( )

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

DIRECT EXPANSION COMMERCIAL PACKAGED AIR HANDLING UNITS, 6 25 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Specification Manual Ground Source Heat Pumps Northern Geo LLC 75 West Veum Appleton, MN

Product Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES

ARBOR COMPACT SERIES COMMERCIAL Geothermal/Water Source Heat Pumps Tons. Submittal Data English Language IP/Metric Units SD1201AZ 08/18

Product Data. 40RUA 18.3 to 59.2 kw Direct Expansion Packaged Air---Handling Units 50 Hz

GPC14H. 2- to 5-Ton Packaged Air Conditioner 14 SEER. Cooling Capacity: 24,000-57,500 BTU/H

Tons BTU/h S.E.E.R* E.E.R** HSPF

SINGLE PACKAGE AIR CONDITIONING WATER COOLED

WE MAKE INDOOR AIR BETTER

EQUIPMENT TECHNICAL SUBMITTAL FOR APPROVAL DATE SUBMITTED APPROVED AS NOTED: NOT APPROVED PLEASE RESUBMIT

ENGINEERING SPECIFICATIONS

GT Series High Efficiency Geothermal/Water Source Step-Capacity Heat Pump R-410A

R410A TECHNICAL MANUAL. Inverter Single Split Series Air Conditioner. FTK-J, FTXN-J Series. Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2

Transcription:

Tranquility Large Vertical (TLV) Series Submittal Data Models TLV08-300 50Hz - HFC-10A English Language/S-I Units Submittal Data - S-I Units Unit Designation: Job Name: Architect: Engineer: Contractor: Performance Data Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp: C Entering Water Temp (Clg): C Entering Air Temp (Clg): C Entering Water Temp (Htg): C Entering Air Temp (Htg): C Airflow: l/s Fan Speed or Motor/RPM/Turns: Operating Weight: (kg) Electrical Data Power Supply: Volts Phase Hz Minimum Circuit Ampacity: Maximum Overcurrent Protection: ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at +1-05-75-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com. *LC810* LC810

Table of Contents *Page Number Unit Features 3 Selection Procedure TLV Series Nomenclature 5 Performance Data - AHRI/ASHRAE/ISO 13256-1 6 Performance Data Selection Notes 7 Performance Data - TLV08 8 Performance Data - TLV096 9 Performance Data - TLV120 10 Performance Data - TLV150 11 Performance Data - TLV168 12 Performance Data - TLV192 13 Performance Data - TLV20 1 Performance Data - TLV300 15 TLV Performance Data Correction Tables 16 Antifreeze Correction Table 16 Blower Performance Data - TLV08 - Standard Unit 17 Blower Performance Data - TLV096 - Standard Unit 18 Blower Performance Data - TLV120 - Standard Unit 19 Blower Performance Data - TLV150 - Standard Unit 21 Blower Performance Data - TLV168 - Standard Unit 23 Blower Performance Data - TLV192 - Standard Unit 2 Blower Performance Data - TLV20 - Standard Unit 25 Blower Performance Data - TLV300 - Standard Unit 27 TLV Physical Data 29 TLV08-150 Dimensional Data 30 TLV168-300 Dimensional Data 31 TLV Electrical Data Standard 32 TLV Electrical Data Dual Point Power 32 TLV Series Wiring Diagram Matrix 33 Typical Wiring Diagrams 3 Tranquility Large Vertical (TLV) Series 50Hz Engineering Specifications 36 Revision History *Document page number is shown next to part number (e.g. LC810-3 = page 3). Since not all pages are typically used in the submittals process, the page number in the lower right corner can still be used (page of ). LC810-2

The Tranquility large VERTICAL (TLV) Series The award winning Tranquility Large Vertical (TLV) Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does the Tranquility Large Vertical (TLV) Series exceed ASHRAE 90.1 efficiencies, but it also uses EarthPure (HFC-10A) zero ozone depletion refrigerant, making it an extremely environmentally-friendly option. Tranquility Large Series is eligible for additional LEED (Leadership in Energy and Environmental Design) points because of the green technology design. Unit Features Vertical sizes 08 (2.6 ) through 300 (87.9 ) Unit configuration can be ordered with, or converted to front or back return and top, front, or back discharge. Field conversion uses all existing parts including panels and belts Electrical box can be field converted to be on front or back of unit Electric power can enter from any side of unit Water and drain can be connected to either side Dual refrigeration circuits (TLV168, 192, 20, 300) Exceeds ASHRAE 90.1 efficiencies TXV metering device Extended range (-6.7 to 8.9 C operation) Microprocessor controls standard (optional DXM and/or DDC controls) LonWorks, BACnet, Modbus and Johnson N2 compatibility options for DDC controls Unit Performance Sentinel performance monitoring system Belt drive blowers with high efficiency motors and multiple pulley adjustment 25, 50, or 100 mm Full Filter Rack with bottom access options include Hot gas bypass Dual point power Coated air coil Internal motorized valve Internal secondary pump UltraQuiet Extended range insulation Cupro-nickel water coil Stainless steel drain pan LC810-3

Selection Procedure Legend and Glossary of Abbreviations l/s = airflow or water flow, liters per second COP = coefficient of performance, W/W DB = dry bulb temperature, C EAT = entering air temperature, C (dry bulb/wet bulb) EER = energy efficiency ratio = Watt output/watt input FPT = female pipe thread (U.S) MPT = male pipe thread (U.S) ESP = external static pressure, kpa EWT = entering water temperature, C HE = total heat of extraction, HC = air heating capacity, HR = total heat of rejection, LAT = leaving air temperature, C LC = latent cooling capacity, LWT = leaving water temperature, C S/T = sensible to total cooling ratio SC = sensible cooling capacity, TC = total cooling capacity, WB = wet bulb temperature, C WPD = waterside pressure drop (kpa) T = temperature difference, C = kilowatt = 1000 Watts kpa = kilopaskel = 1000 Paskels m/s = meters per second LC810 -

TLV Series Nomenclature MODEL TYPE TL = TRANQUILITY LARGE COMMERCIAL CONFIGURATION V = VERTICAL 1 2 3 5 6 7 8 9 10 11 12 13 1 15 T L V 0 9 6 A U F 1 A C B T S SPECIAL OPTIONS S = STANDARD A = DUAL POINT POWER B = HOT GAS BYPASS C = DUAL POINT POWER + HOT GAS BYPASS CONTROLS F = CXM G = DXM CE APPROVED H = CXM w/ LON EUROPE J = DXM w/ LON T = CXM w/ MPC {U = DXM w/ MPC UNIT SIZE 08 096 120 150 168 192 20 300 REVISION LEVEL A = CURRENT VOLTAGE U = 380-20/50/3 - R10A CABINET INSULATION / FILTER RACK OPTION RANGE ULTRA QUIET 1 FILTER RACK 2 FILTER RACK FILTER RACK 1 A B 2 C D 3 E F G H OPTION A C J N U T W S AIR FLOW OPTIONS BF = BACK RETURN / FRONT SUPPLY BT = BACK RETURN / TOP SUPPLY FB = FRONT RETURN / BACK SUPPLY FT = FRONT RETURN / TOP SUPPLY YF = BACK RETURN / FRONT SUPPLY + SS DRAIN PAN YT = BACK RETURN / TOP SUPPLY + SS DRAIN PAN ZB = FRONT RETURN / BACK SUPPLY + SS DRAIN PAN ZT = FRONT RETURN / TOP SUPPLY + SS DRAIN PAN HEAT EXCHANGER / MOTORIZED VALVE OPTIONS COPPER WATER COIL CUPRONICKEL WATER COIL BLOWER DRIVE PACKAGE A = STANDARD RPM & STANDARD MOTOR B = LOW & RPM & STANDARD MOTOR C = HIGH RPM & STANDARD MOTOR E = HIGH RPM & LARGE MOTOR N COATED AIR COIL COATED AIR COIL MTRZD VALVE ( WATER OUT ) LC810-5

Performance Data AHRI/ASHRAE/ISO 13256-1 AHRI/ASHRAE/ISO 13256-1. Metric (S-I) Units Model Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump Cooling 30ºC Heating 20ºC Cooling 15ºC Heating 10ºC Cooling 25ºC Heating 0ºC Capacity EER W/W Capacity COP Capacity EER W/W Capacity COP Capacity EER W/W Capacity COP TLV08 22.01.9 26.88 5.3 23.68 6.7 22.13.7 22.10 5.3 17.53.0 TLV096 2.97.8 31.01 5.2 27.52 6.6 25.21.6 25.15 5.1 19.3 3.8 TLV120 31.65.8 38.19 5.3 35.96 6.7 30.8.6 31.77 5.1 2.1 3.9 TLV150 0.06.5 8.65 5.1 5.93 6. 39.92.5 0.71.9 30.78 3.8 TLV168.02.9 53.75 5.3 7.36 6.7.26.7.20 5.3 35.05.0 TLV192 9.9.8 62.02 5.2 55.0 6.6 50.1.6 50.29 5.1 38.69 3.8 TLV20 63.31.8 76.38 5.3 71.92 6.7 60.96.6 63.5 5.1 8.83 3.9 TLV300 80.13.5 97.31 5.1 91.85 6. 79.8.5 81.2.9 61.55 3.8 Cooling capacities based upon 27 C DB, 19 C WB entering air temperature. Heating capacities based upon 20 C DB, 15 C WB entering air temperature. All ratings based upon operation at lower voltage of dual voltage rated models. All TLV08 ratings at 1321 l/s with sheave settings at 3.5 turns open. All TLV096 ratings at 1510 l/s with sheave settings at 3.5 turns open. All TLV120 ratings at 1888 l/s with sheave settings at 3.5 turns open. LC810-6

Performance Data Selection Notes For operation in the shaded area when water is used in lieu of an antifreeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 5 C when the JW3 jumper is not clipped (see example below). This is due to the potential of the refrigerant temperature being as low as 0 C with 5 C LWT, which may lead to a nuisance cutout due to the activation of the Low Temperature Protection. JW3 should never be clipped for standard range equipment or systems without antifreeze. Example: At 10 C EWT (Entering Water Temperature) and 0.63 l/s (minimum flow rate), a TLV096 unit has a HE of 18.7. To calculate LWT, rearrange the formula for HE as follows: HE = TD x Flow x.18 where HE = Heat of Extraction (); TD = temperature difference (EWT - LWT); and Flow = Water Flow Rate in l/s EER W/W HC KW HEATING - EAT 20 C PI KW HE KW LAT ºC COP 18.05 5.5 12.51 33.3 3.3 6.9 19.31 5.62 13.69 3.5 3. 8 7.2 20.20 5.68 1.52 35.3 3.6 7. 20.70 5.71 1.99 35.7 3.6 6. 22.1 5.80 16.3 37.0 3.8 6.8 23.27 5.87 17.1 38.1.0 7.0 23.91 5.90 18.00 38.7.0 9 2.69 5.95 18.7 39..1 26.0 6.03 20.00 0.6 6.08 20.71 1 TD = HE / (l/s x.18) TD = 18.7 / (0.63 x.18) TD = 7.1 C LWT = EWT - TD LWT = 10-7.1 = 2.9 C In this example, LWT is below 5 C. Antifreeze will be required. LC810-7

Performance Data TLV08 991 l/s Nominal Airflow Heating & Cooling Performance capacities shown in EWT C WATER / BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C FLOW l/s PD kpa TC SC S/T Ratio PI -5 1.10 8.98 Operation Not Recommended 15.53.8 11.0 31.9 3.5 0 5 10 15 20 25 30 35 0 5 HR EER W/W 0.55 11.65 21.59 1.0 0.67 3.23 2.81 6.7 16.57.57 12.00 32.8 3.6 0.83 26.68 20.50 13.58 0.66 2.98 23.8 6.9 17.28.63 12.65 33. 3.7 1.10 5.09 19.86 13.12 0.66 2.86 22.72 6.9 17.67.66 13.01 33.8 3.8 0.55 10.36 22.6 15.26 0.67 3.59 26.23 6.3 18.93.77 1.16 3.9.0 0.83 2.23 22.07 1.77 0.67 3.36 25.3 6.6 19.86.85 15.01 35.7.1 1.10 1.19 21.68 1.6 0.67 3.25 2.92 6.7 20.37.89 15.8 36.2.2 0.55 9.62 22.97 15.63 0.68 3.89 26.86 5.9 21.12.96 16.16 36.9.3 0.83 22.66 22.79 15.38 0.68 3.66 26.5 6.2 22.22 5.05 17.17 37.8. 1.10 38.87 22.59 15.20 0.67 3.55 26.1 6. 22.83 5.10 17.73 38..5 0.55 6.51 22.75 15.62 0.69.18 26.93 5. 23.38 5.15 18.22 38.9.5 0.83 17.5 22.86 15.56 0.68 3.95 26.81 5.8 2.63 5.26 19.37 0.0.7 1.10 31.65 22.83 15.8 0.68 3.83 26.66 6.0 25.31 5.32 20.00 0.6.8 0.55 5.99 22.25 15.50 0.70.53 26.78.9 25.99 5.38 20.61 1.2.8 0.83 16.5 22.63 15.60 0.69.29 26.91 5.3 27.37 5.50 21.87 2. 5.0 1.10 30.11 22.75 15.61 0.69.17 26.92 5.5 28.11 5.57 22.55 3.1 5.1 0.55 5.8 21.6 15.28 0.71.87 26.50. 28.26 5.58 22.68 3.2 5.1 0.83 15.36 22.17 15.7 0.70.61 26.78.8 29.69 5.71 23.98.5 5.2 1.10 28.57 22.0 15.5 0.69.8 26.89 5.0 30.3 5.78 2.65 5.1 5.3 0.55 5.16 20.7 1.92 0.72 5.27 26.02 3.9 30.56 5.79 2.76 5.3 5.3 0.83 1.83 21.0 15.18 0.71.99 26.38.3 31.93 5.93 26.01 6.5 5. 1.10 27.82 21.70 15.29 0.70.85 26.55.5 32.61 6.00 26.61 7.1 5. 0.55.8 19.76 1.52 0.7 5.71 25.7 3.5 0.83 1.31 20.6 1.81 0.72 5.39 25.85 3.8 1.10 27.08 20.91 1.9 0.71 5.2 26.0.0 0.55.52 18.7 1.1 0.75 6.21 2.96 3.0 0.83 13.78 19.5 1.1 0.7 5.86 25.30 3.3 1.10 26.33 19.69 1.50 0.7 5.69 25.9 3.5 Operation Not Recommended 0.83 13.26 18.39 1.01 0.76 6.1 2.80 2.9 1.10 25.58 18.73 1.1 0.75 6.22 2.95 3.0 HC PI HE LAT ºC Operation Not Recommended COP *WPD Adder for Motorized Water Valve TLV 08 Cv=37 MOPD = 150 PD Flow kpa 0.55 0.55 0.83 1.2 1.10 2.21 Interpolation is permissible; extrapolation is not. All entering air conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. AHRI/ISO certified conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. Table does not reflect fan or pump power corrections for AHRI/ISO conditions. All performance data is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below C EWT is based upon a 15% methanol antifreeze solution. Operation below 16 C EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. Gray shaded area refers to calculations required to determine if heating water flow is sufficient for non-antifreeze systems. LC810-8

Performance Data TLV096 1133 l/s Nominal Airflow Heating & Cooling Performance capacities shown in EWT C WATER / BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C FLOW l/s PD kpa TC SC S/T Ratio PI HR EER W/W -5 1.26 9.8 Operation Not Recommended 18.05 5.5 12.51 33.3 3.3 0 5 10 15 20 25 30 35 0 5 0.63 10.5 28.56 19.36 0.68.12 32.68 6.9 19.31 5.62 13.69 3.5 3. 0.95 25.7 28.55 19.39 0.68 3.9 32.8 7.2 20.20 5.68 1.52 35.3 3.6 1.26 5.3 28.6 19.38 0.68 3.86 32.32 7. 20.70 5.71 1.99 35.7 3.6 0.63 9.3 28.30 19.19 0.68.3 32.73 6. 22.1 5.80 16.3 37.0 3.8 0.95 23.3 28.53 19.33 0.68.20 32.73 6.8 23.27 5.87 17.1 38.1.0 1.26 0.9 28.58 19.37 0.68.10 32.67 7.0 23.91 5.90 18.00 38.7.0 0.63 8.5 27.85 18.97 0.68.75 32.60 5.9 2.69 5.95 18.7 39..1 0.95 21.8 28.26 19.17 0.68.7 32.7 6.3 26.0 6.03 20.00 0.6.3 1.26 38.6 28.1 19.25 0.68.35 32.76 6.5 26.78 6.08 20.71 1.3. 0.63 7.2 27.18 18.68 0.69 5.12 32.30 5.3 27.32 6.11 21.21 1.8.5 0.95 18.7 27.7 18.92 0.68.81 32.55 5.8 28.85 6.20 22.6 3.2.7 1.26 33.5 27.98 19.03 0.68.66 32.6 6.0 29.69 6.25 23.3.0.7 0.63 6.6 26.22 18.27 0.70 5.62 31.83.7 30.36 6.29 2.06.6.8 0.95 17.8 26.93 18.57 0.69 5.26 32.18 5.1 32.06 6.0 25.66 6.1 5.0 1.26 32.1 27.25 18.70 0.69 5.09 32.33 5. 32.97 6.6 26.52 7.0 5.1 0.63 5.9 25.19 17.86 0.71 6.12 31.31.1 33.02 6.6 26.56 7.0 5.1 0.95 16.8 26.01 18.19 0.70 5.72 31.73.5 3.81 6.58 28.23 8.6 5.3 1.26 30.7 26.39 18.35 0.70 5.53 31.92.8 35.75 6.6 29.11 9.5 5. 0.63 5. 23.95 17.37 0.73 6.72 30.68 3.6 35.75 6.6 29.11 9.5 5. 0.95 16.0 2.86 17.73 0.71 6.28 31.1.0 37.5 6.77 30.77 51.1 5.5 1.26 29.7 25.29 17.90 0.71 6.07 31.36.2 38.6 6.8 31.62 51.9 5.6 0.63.8 22.65 16.86 0.7 7.37 30.03 3.1 0.95 15.3 23.62 17.2 0.73 6.89 30.51 3. 1.26 28.7 2.23 17.3 0.72 6.66 30.75 3.6 0.63.3 21.27 16.31 0.77 8.09 29.35 2.6 0.95 1.5 22.27 16.71 0.75 7.57 29.8 2.9 1.26 27.7 22.61 16.85 0.7 7.31 30.08 3.1 Operation Not Recommended 0.95 13.7 20.79 16.12 0.78 8.3 29.13 2.5 1.26 26.7 21.30 16.33 0.77 8.07 29.37 2.6 HC PI HE LAT ºC Operation Not Recommended COP *WPD Adder for Motorized Water Valve TLV 096 Cv=37 MOPD = 150 PD Flow kpa 0.63 0.76 0.95 1.65 1.26 2.90 Interpolation is permissible; extrapolation is not. All entering air conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. AHRI/ISO certified conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. Table does not reflect fan or pump power corrections for AHRI/ISO conditions. All performance data is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below C EWT is based upon a 15% methanol antifreeze solution. Operation below 16 C EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. Gray shaded area refers to calculations required to determine if heating water flow is sufficient for non-antifreeze systems. LC810-9

Performance Data TLV120 116 l/s Nominal Airflow Heating & Cooling Performance capacities shown in EWT C WATER / BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C FLOW l/s PD kpa TC SC S/T Ratio PI HR EER W/W -5 1.58 9.69 Operation Not Recommended 21.82 6.2 15.0 31.6 3. 0 5 10 15 20 25 30 35 0 5 0.79 10.25 36.96 2.10 0.65 5.20 2.16 7.1 23.16 6.51 16.66 32.5 3.6 1.18 25.8 37.52 2.1 0.6.98 2.50 7.5 2.08 6.57 17.50 33.1 3.7 1.58 5.83 37.73 2.08 0.6.88 2.60 7.7 2.58 6.61 17.97 33. 3.7 0.79 9.13 35.99 23.82 0.66 5.53 1.51 6.5 26.26 6.7 19.52 3. 3.9 1.18 23.9 36.77 2.06 0.65 5.27 2.05 7.0 27.5 6.81 20.6 35.2.0 1.58 1.97 37.11 2.13 0.65 5.16 2.27 7.2 28.11 6.85 21.26 35.6.1 0.79 8.2 3.96 23.1 0.67 5.8 0.80 6.0 29.16 6.95 22.21 36.3.2 1.18 21.1 35.89 23.78 0.66 5.56 1.5 6.5 30.60 7.0 23.57 37.2.3 1.58 39.81 36.32 23.9 0.66 5.3 1.75 6.7 31.1 7.09 2.32 37.7. 0.79 6.28 33.76 22.85 0.68 6.20 39.96 5. 32. 7.17 25.26 38..5 1.18 18.21 3.79 23.31 0.67 5.89 0.68 5.9 3.13 7.28 26.86 39..7 1.58 3.30 35.28 23.52 0.67 5.75 1.03 6.1 35.07 7.33 27.7 0.0.8 0.79 5.72 32.21 22.11 0.69 6.68 38.88.8 36.37 7. 28.93 0.9.9 1.18 17.16 33.31 22.62 0.68 6.33 39.6 5.3 38.3 7.57 30.77 2.1 5.1 1.58 32.71 33.85 22.87 0.68 6.17 0.02 5.5 39.3 7.6 31.78 2.8 5.2 0.79 5.15 30.71 21.2 0.70 7.16 37.87.3 39.76 7.67 32.09 3.0 5.2 1.18 16.11 31.82 21.93 0.69 6.78 38.61.7 1.93 7.83 3.10. 5. 1.58 31.12 32.38 22.19 0.69 6.60 38.98.9 3.11 7.92 35.19 5.1 5. 0.79.88 29.0 20.69 0.71 7.75 36.79 3.7 3.98 8.03 35.95 5.6 5.5 1.18 15.6 30.15 21.19 0.70 7.33 37.8.1.99 7.83 37.17 6.5 5.7 1.58 30.22 30.71 21.5 0.70 7.13 37.85.3 5.55 7.7 37.82 6.9 5.9 0.79.61 27.9 20.06 0.73 8.39 35.88 3.3 1.18 15.17 28.56 20.50 0.72 7.93 36.50 3.6 1.58 29.33 29.29 20.7 0.71 7.71 36.83 3.8 0.79.3 26.03 19.53 0.75 9.11 35.1 2.9 1.18 1.70 27.0 19.89 0.7 8.61 35.65 3.1 1.58 28. 27.0 20.03 0.73 8.37 35.93 3.3 Operation Not Recommended 1.18 1.23 25.52 19.36 0.76 9.0 3.92 2.7 1.58 27.5 26.01 19.52 0.75 9.13 35.1 2.8 HC PI HE LAT ºC Operation Not Recommended COP *WPD Adder for Motorized Water Valve TLV 120 Cv=37 MOPD = 150 PD Flow kpa 0.79 1.10 1.18 2.55 1.58.55 Interpolation is permissible; extrapolation is not. All entering air conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. AHRI/ISO certified conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. Table does not reflect fan or pump power corrections for AHRI/ISO conditions. All performance data is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below C EWT is based upon a 15% methanol antifreeze solution. Operation below 16 C EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. Gray shaded area refers to calculations required to determine if heating water flow is sufficient for non-antifreeze systems. LC810-10

Performance Data TLV150 1770 l/s Nominal Airflow Heating & Cooling Performance capacities shown in EWT C WATER / BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C FLOW l/s PD kpa TC SC S/T Ratio PI HR EER W/W -5 2.00 58.50 Operation Not Recommended 28.12 8.52 19.60 31.8 3.3 0 5 10 15 20 25 30 35 0 5 1.00 13.27 5.62 32.0 0.71 6.91 52.53 6.6 29.99 8.69 21.30 32.7 3.5 1.7 30.25 5.3 33.90 0.75 6.58 52.01 6.9 31.19 8.79 22.0 33.3 3.5 2.00 53.80 5.12 3.78 0.77 6.39 51.51 7.1 31.93 8.86 23.08 33.7 3.6 1.00 11.36 5.13 30.57 0.68 7.38 52.50 6.1 3.13 9.03 25.10 3.8 3.8 1.7 27.17 5.5 31.80 0.70 7.03 52.58 6.5 35.66 9.1 26.51 35.6 3.9 2.00 9.10 5.61 32.57 0.71 6.85 52.5 6.7 36.60 9.21 27.38 36.1.0 1.00 10.8.19 29.27 0.66 7.79 51.98 5.7 37.90 9.31 28.59 36.7.1 1.7 25.50 5.01 30.28 0.67 7.3 52. 6.1 39.71 9.3 30.27 37.6.2 2.00 6. 5.3 30.91 0.68 7.2 52.58 6.3 0.81 9.51 31.30 38.2.3 1.00 8.13 2.82 28.2 0.66 8.2 51.06 5.2 1.96 9.61 32.35 38.8. 1.7 20.98 3.91 29.06 0.66 7.86 51.77 5.6.0 9.76 3.28 39.8.5 2.00 39.27.3 29.59 0.67 7.66 52.09 5.8 5.30 9.85 35.5 0.5.6 1.00 7. 0.99 27.21 0.66 8.83 9.82.6 6.7 9.98 36.76 1.2.7 1.7 19.81 2.28 27.87 0.66 8.2 50.71 5.0 9.07 10.15 38.91 2..8 2.00 37.67 2.96 28.29 0.66 8.20 51.16 5.2 50.7 10.26 0.21 3.1.9 1.00 6.75 39.15 26.0 0.67 9. 8.59.1 50.8 10.30 0.5 3.2.9 1.7 18.65 0.5 26.97 0.67 8.99 9.53.5 53.32 10.50 2.82.5 5.1 2.00 36.06 1.30 27.32 0.66 8.75 50.0.7 5.79 10.63.15 5.2 5.2 1.00 6.0 37.08 25.61 0.69 10.18 7.26 3.6 55.06 10.66.0 5. 5.2 1.7 18.0 38.8 26.12 0.68 9.68 8.16.0 57.60 10.91 6.69 6.6 5.3 2.00 35.05 39.27 26.2 0.67 9.2 8.68.2 59.05 11.07 7.98 7.3 5.3 1.00 6.06 35.10 2.89 0.71 10.98 6.09 3.2 1.7 17. 36. 25.37 0.70 10.3 6.87 3.5 2.00 3.05 37.5 25.65 0.68 10.1 7.35 3.7 1.00 5.71 33.27 2.21 0.73 11.90 5.16 2.8 1.7 16.83 3.7 2.66 0.72 11.27 5.75 3.1 2.00 33.0 3.97 2.8 0.71 10.95 6.1 3.2 Operation Not Recommended 1.7 16.23 32.62 23.96 0.73 12.28.90 2.7 2.00 32.03 33.2 2.20 0.73 11.91 5.15 2.8 HC PI HE LAT ºC Operation Not Recommended COP *WPD Adder for Motorized Water Valve TLV 150 Cv=57 MOPD = 150 Flow PD kpa 1.00 0.76 1.7 1.65 2.00 3.03 Interpolation is permissible; extrapolation is not. All entering air conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. AHRI/ISO certified conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. Table does not reflect fan or pump power corrections for AHRI/ISO conditions. All performance data is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below C EWT is based upon a 15% methanol antifreeze solution. Operation below 16 C EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. Gray shaded area refers to calculations required to determine if heating water flow is sufficient for non-antifreeze systems. LC810-11

Performance Data TLV168 1882 l/s Nominal (Rated) Airflow Performance capacities shown in EWT C WATER / BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C FLOW l/s PD kpa TC SC S/T Ratio PI HR EER W/W -5 2.21 55.11 Operation Not Recommended 31.06 8.97 22.09 31.9 3.5 0 5 10 15 20 25 30 35 0 5 1.10 13.11 3.17 28.79 0.67 6.5 9.62 6.7 33.1 9.1 2.00 32.8 3.6 1.66 30.02 0.99 27.17 0.66 5.96 6.96 6.9 3.56 9.26 25.30 33. 3.7 2.21 50.72 39.72 26.25 0.66 5.72 5.5 6.9 35.35 9.33 26.02 33.8 3.8 1.10 11.65 5.27 30.51 0.67 7.19 52.6 6.3 37.87 9.55 28.32 3.9.0 1.66 27.25.1 29.5 0.67 6.72 50.86 6.6 39.71 9.70 30.01 35.7.1 2.21 6.3 3.35 28.92 0.67 6.9 9.85 6.7 0.7 9.78 30.96 36.2.2 1.10 10.83 5.9 31.26 0.68 7.78 53.72 5.9 2.23 9.92 32.31 36.9.3 1.66 25.9 5.57 30.77 0.68 7.33 52.90 6.2. 10.10 3.3 37.8. 2.21 3.73 5.18 30.0 0.67 7.10 52.28 6. 5.65 10.20 35.5 38..5 1.10 7.32 5.50 31.25 0.69 8.36 53.86 5. 6.75 10.31 36.5 38.9.5 1.66 19.73 5.72 31.12 0.68 7.89 53.61 5.8 9.26 10.52 38.7 0.0.7 2.21 35.61 5.66 30.95 0.68 7.67 53.33 6.0 50.63 10.63 0.00 0.6.8 1.10 6.7.51 31.00 0.70 9.06 53.56.9 51.98 10.76 1.22 1.2.8 1.66 18.50 5.25 31.19 0.69 8.57 53.82 5.3 5.7 11.00 3.7 2. 5.0 2.21 33.87 5.50 31.21 0.69 8.3 53.8 5.5 56.22 11.13 5.09 3.1 5.1 1.10 6.16 3.27 30.55 0.71 9.7 53.01. 56.53 11.16 5.37 3.2 5.1 1.66 17.28.35 30.9 0.70 9.22 53.57.8 59.38 11.2 7.96.5 5.2 2.21 32.1.80 31.08 0.69 8.97 53.77 5.0 60.86 11.56 9.30 5.1 5.3 1.10 5.81 1.9 29.8 0.72 10.5 52.03 3.9 61.11 11.58 9.53 5.3 5.3 1.66 16.69 2.79 30.36 0.71 9.97 52.77.3 63.87 11.85 52.01 6.5 5. 2.21 31.30 3.0 30.59 0.70 9.70 53.10.5 65.22 12.00 53.23 7.1 5. 1.10 5.5 39.51 29.05 0.7 11.2 50.93 3.5 1.66 16.10 0.91 29.61 0.72 10.79 51.70 3.8 2.21 30.6 1.81 29.88 0.71 10.9 52.09.0 1.10 5.09 37.9 28.27 0.75 12.3 9.91 3.0 1.66 15.51 38.89 28.81 0.7 11.72 50.61 3.3 2.21 29.62 39.37 29.00 0.7 11.38 50.98 3.5 Operation Not Recommended 1.66 1.91 36.77 28.02 0.76 12.83 9.60 2.9 2.21 28.78 37.7 28.27 0.75 12. 9.91 3.0 HC PI HE LAT ºC Operation Not Recommended COP *WPD Adder for Motorized Water Valve TLV 168 Cv=37 MOPD = 150 PD Flow kpa 1.10 0.55 1.66 1.2 2.21 2.21 Interpolation is permissible; extrapolation is not. All entering air conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. AHRI/ISO certified conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. Table does not reflect fan or pump power corrections for AHRI/ISO conditions. All performance data is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below C EWT is based upon a 15% methanol antifreeze solution. Operation below 16 C EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. Gray shaded area refers to calculations required to determine if heating water flow is sufficient for non-antifreeze systems. LC810-12

Performance Data TLV192 2265 l/s Nominal Airflow Heating & Cooling Performance capacities shown in EWT C WATER / BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C FLOW l/s PD kpa TC SC S/T Ratio PI HR EER W/W -5 2.52 77.75 Operation Not Recommended 3.61 10.35 2.25 31.5 3.3 0 5 10 15 20 25 30 35 0 5 1.26 20.65 7.66 31.70 0.67 6.71 5.37 7.1 37.15 10.56 26.59 32.5 3.5 1.89.2 2.92 28. 0.66 5.62 8.53 7.6 38.81 10.71 28.10 33.1 3.6 2.52 71.32 0.32 26.67 0.66 5.07 5.39 7.9 39.72 10.79 28.9 33.5 3.7 1.26 18.7 52.39 3.96 0.67 8.12 60.51 6.5 2.67 11.07 31.60 3.6 3.9 1.89 39.71 50.03 33.30 0.67 7.31 57.3 6.8.77 11.2 33.53 35..0 2.52 6.90 8.2 32.19 0.66 6.86 55.29 7.1 5.93 11.3 3.59 35.9.1 1.26 17.10 53.83 36.00 0.67 8.98 62.80 6.0 7.67 11.52 36.15 36.5.1 1.89 37.25 53.07 35.0 0.67 8.3 61.1 6. 50.15 11.72 38.3 37.5.3 2.52 61.60 52.29 3.8 0.67 7.98 60.27 6.6 51.53 11.83 39.70 38.0. 1.26 13.3 53. 35.88 0.67 9.6 63.08 5.5 52.91 12.00 0.91 38.6. 1.89 30.80 53.77 35.96 0.67 9.09 62.86 5.9 55.78 12.23 3.5 39.7.6 2.52 52.78 53.62 35.81 0.67 8.80 62.2 6.1 57.36 12.36 5.00 0.3.6 1.26 12.9 51.90 35.10 0.68 10.3 62.25 5.0 59.06 12.56 6.50 0.9.7 1.89 29.13 53.08 35.68 0.67 9.85 62.93 5. 62.33 12.8 9.9 2.2.9 2.52 50.5 53.8 35.86 0.67 9.59 63.07 5.6 6.12 12.99 51.13 2.9.9 1.26 11.5 9.80 3.06 0.68 10.99 60.79.5 6.50 13.0 51.6 3.1.9 1.89 27.7 51.39 3.8 0.68 10.9 61.88.9 68.07 13.36 5.71. 5.1 2.52 8.13 52.09 35.19 0.68 10.2 62.33 5.1 70.00 13.5 56.6 5.2 5.2 1.26 11.13 7.19 32.88 0.70 11.78 58.97.0 70.25 13.56 56.68 5.3 5.2 1.89 26.68 8.95 33.69 0.69 11.22 60.16. 7.05 13.9 60.11 6.7 5.3 2.52 7.13 9.81 3.10 0.68 10.95 60.76.5 76.07 1.15 61.92 7.5 5. 1.26 10.71.7 31.91 0.71 12.72 57.6 3.5 1.89 25.89 6.2 32.57 0.70 12.0 58.6 3.9 2.52 6.1 7.59 32.96 0.69 11.73 59.0.1 1.26 10.30 2.68 31.35 0.73 13.92 56.60 3.1 1.89 25.10.06 31.68 0.72 13.06 57.12 3. 2.52 5.1.59 31.86 0.71 12.68 57.53 3.5 Operation Not Recommended 1.89 2.32 2.11 31.32 0.7 1.3 56.53 2.9 2.52.15 2.67 31.35 0.73 13.9 56.61 3.1 HC PI HE LAT ºC Operation Not Recommended COP *WPD Adder for Motorized Water Valve TLV 192 Cv=37 MOPD = 150 PD Flow kpa 1.26 0.76 1.89 1.65 2.52 2.90 Interpolation is permissible; extrapolation is not. All entering air conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. AHRI/ISO certified conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. Table does not reflect fan or pump power corrections for AHRI/ISO conditions. All performance data is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below C EWT is based upon a 15% methanol antifreeze solution. Operation below 16 C EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. Gray shaded area refers to calculations required to determine if heating water flow is sufficient for non-antifreeze systems. LC810-13

Performance Data TLV20 2832 l/s Nominal Airflow Heating & Cooling EWT C Performance capacities shown in WATER / BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C FLOW l/s PD kpa TC SC S/T Ratio PI HR EER W/W -5 3.15 55.90 Operation Not Recommended 3.6 12.8 30.80 31.6 3. 0 5 10 15 20 25 30 35 0 5 1.58 11.53 73.91 8.21 0.65 10.0 8.31 7.1 6.33 13.01 33.31 32.5 3.6 2.37 29.07 75.0 8.28 0.6 9.96 85.00 7.5 8.15 13.15 35.00 33.1 3.7 3.15 51.55 75.6 8.16 0.6 9.75 85.21 7.7 9.17 13.22 35.95 33. 3.7 1.58 10.27 71.97 7.6 0.66 11.05 83.02 6.5 52.52 13.7 39.05 3. 3.9 2.37 26.3 73.55 8.13 0.65 10.55 8.10 7.0 5.90 13.63 1.28 35.2.0 3.15 7.21 7.23 8.26 0.65 10.31 8.5 7.2 56.23 13.71 2.52 35.6.1 1.58 9.7 69.92 6.81 0.67 11.68 81.60 6.0 58.33 13.90.3 36.3.2 2.37 2.09 71.79 7.57 0.66 11.12 82.91 6.5 61.21 1.08 7.13 37.2.3 3.15.78 72.65 7.87 0.66 10.86 83.51 6.7 62.81 1.17 8.6 37.7. 1.58 7.07 67.51 5.71 0.68 12.0 79.91 5. 6.87 1.35 50.53 38..5 2.37 20.9 69.57 6.63 0.67 11.79 81.36 5.9 68.26 1.55 53.71 39..7 3.15 38.58 70.56 7.0 0.67 11.50 82.05 6.1 70.1 1.67 55.7 0.0.8 1.58 6.3 6.2.23 0.69 13.35 77.77.8 72.7 1.89 57.86 0.9.9 2.37 19.30 66.62 5.25 0.68 12.67 79.29 5.3 76.69 15.1 61.5 2.1 5.1 3.15 36.80 67.70 5.7 0.68 12.3 80.0 5.5 78.85 15.29 63.56 2.8 5.2 1.58 5.79 61.2 2.83 0.70 1.32 75.7.3 79.52 15.3 6.18 3.0 5.2 2.37 18.12 63.6 3.87 0.69 13.57 77.21.7 83.86 15.66 68.21. 5. 3.15 35.01 6.75.39 0.69 13.21 77.96.9 86.22 15.8 70.38 5.1 5. 1.58 5.9 58.08 1.39 0.71 15.50 73.58 3.7 87.95 16.05 71.90 5.6 5.5 2.37 17.59 60.30 2.37 0.70 1.67 7.96.1 89.98 15.65 7.33 6.5 5.7 3.15 3.00 61.3 2.89 0.70 1.27 75.69.3 91.11 15.7 75.6 6.9 5.9 1.58 5.19 5.98 0.12 0.73 16.78 71.76 3.3 2.37 17.06 57.12 1.01 0.72 15.87 72.99 3.6 3.15 33.00 58.59 1.8 0.71 15.3 73.66 3.8 1.58.88 52.06 39.05 0.75 18.23 70.29 2.9 2.37 16.5 5.07 39.78 0.7 17.22 71.29 3.1 3.15 31.99 5.79 0.05 0.73 16.7 71.87 3.3 Operation Not Recommended 2.37 16.01 51.05 38.73 0.76 18.80 69.85 2.7 3.15 30.98 52.02 39.0 0.75 18.26 70.28 2.8 HC PI HE LAT ºC Operation Not Recommended COP *WPD Adder for Motorized Water Valve TLV 20 Cv=37 MOPD = 150 PD Flow kpa 1.58 1.10 2.37 2.55 3.15.55 Interpolation is permissible; extrapolation is not. All entering air conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. AHRI/ISO certified conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. Table does not reflect fan or pump power corrections for AHRI/ISO conditions. All performance data is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below C EWT is based upon a 15% methanol antifreeze solution. Operation below 16 C EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. Gray shaded area refers to calculations required to determine if heating water flow is sufficient for non-antifreeze systems. LC810-1

Performance Data TLV300 350 l/s Nominal (Rated) Airflow Performance capacities shown in EWT C WATER / BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C FLOW l/s PD kpa TC SC S/T Ratio PI HR EER W/W -5.00 65.99 Operation Not Recommended 56.2 17.03 39.20 31.8 3.3 0 5 10 15 20 25 30 35 0 5 2.00 1.97 91.23 6.80 0.71 13.83 105.06 6.6 59.99 17.38 2.61 32.7 3.5 2.9 3.12 90.87 67.80 0.75 13.15 10.02 6.9 62.39 17.59.80 33.3 3.5.00 60.68 90.2 69.57 0.77 12.78 103.02 7.1 63.86 17.71 6.15 33.7 3.6 2.00 12.82 90.25 61.13 0.68 1.76 105.01 6.1 68.26 18.06 50.20 3.8 3.8 2.9 30.65 91.09 63.61 0.70 1.07 105.16 6.5 71.32 18.29 53.03 35.6 3.9.00 55.38 91.22 65.1 0.71 13.69 10.91 6.7 73.19 18.2 5.77 36.1.0 2.00 11.82 88.38 58.5 0.66 15.59 103.97 5.7 75.80 18.61 57.18 36.7.1 2.9 28.76 90.02 60.55 0.67 1.87 10.89 6.1 79.1 18.87 60.5 37.6.2.00 52.38 90.67 61.83 0.68 1.8 105.15 6.3 81.63 19.02 62.60 38.2.3 2.00 9.17 85.6 56.9 0.66 16.8 102.13 5.2 83.93 19.23 6.70 38.8. 2.9 23.67 87.82 58.13 0.66 15.73 103.55 5.6 88.07 19.52 68.55 39.8.5.00.30 88.86 59.17 0.67 15.32 10.17 5.8 90.59 19.70 70.89 0.5.6 2.00 8.39 81.98 5.2 0.66 17.67 99.6.6 93.7 19.96 73.51 1.2.7 2.9 22.35 8.57 55.75 0.66 16.8 101.1 5.0 98.1 20.31 77.83 2..8.00 2.9 85.92 56.57 0.66 16.0 102.32 5.2 100.9 20.52 80.1 3.1.9 2.00 7.61 78.31 52.80 0.67 18.87 97.18.1 101.68 20.60 81.09 3.2.9 2.9 21.03 81.08 53.95 0.67 17.98 99.06.5 106.65 21.01 85.6.5 5.1.00 0.68 82.59 5.65 0.66 17.50 100.09.7 109.57 21.27 88.30 5.2 5.2 2.00 7.22 7.16 51.21 0.69 20.35 9.52 3.6 110.12 21.32 88.80 5. 5.2 2.9 20.35 76.96 52.2 0.68 19.36 96.32.0 115.20 21.82 93.38 6.6 5.3.00 39.5 78.5 52.85 0.67 18.83 97.37.2 118.11 22.1 95.96 7.3 5.3 2.00 6.83 70.21 9.78 0.71 21.97 92.18 3.2 2.9 19.67 72.88 50.7 0.70 20.86 93.7 3.5.00 38.0 7.89 51.30 0.68 20.27 9.70 3.7 2.00 6. 66.53 8.2 0.73 23.79 90.32 2.8 2.9 18.99 68.9 9.32 0.72 22.55 91.9 3.1.00 37.27 69.95 9.68 0.71 21.89 92.28 3.2 Operation Not Recommended 2.9 18.31 65.2 7.93 0.73 2.56 89.80 2.7.00 36.13 66.9 8.1 0.73 23.82 90.30 2.8 HC PI HE LAT ºC Operation Not Recommended COP *WPD Adder for Motorized Water Valve TLV 300 Cv=57 MOPD = 150 PD Flow kpa 2.00 0.76 2.9 1.65.00 3.03 Interpolation is permissible; extrapolation is not. All entering air conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. AHRI/ISO certified conditions are 27 C DB and 19 C WB in cooling and 20 C DB in heating. Table does not reflect fan or pump power corrections for AHRI/ISO conditions. All performance data is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below C EWT is based upon a 15% methanol antifreeze solution. Operation below 16 C EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. Gray shaded area refers to calculations required to determine if heating water flow is sufficient for non-antifreeze systems. LC810-15

TLV Performance Data Correction Tables Air Flow Correction Table Percentage of Rated Airflow Total Capacity Sensible Capacity Cooling Power Heat of Rejection Heating Capacity Heating Power Heat of Extraction 75% 0.957 0.868 0.9 0.95 0.960 1.05 0.938 81% 0.970 0.901 0.957 0.967 0.971 1.027 0.956 88% 0.982 0.90 0.971 0.980 0.983 1.015 0.97 9% 0.991 0.970 0.985 0.990 0.991 1.007 0.987 100% 1.000 1.000 1.000 1.000 1.000 1.000 1.000 106% 1.002 1.025 1.013 1.00 1.006 0.999 1.009 113% 1.00 1.050 1.026 1.009 1.013 0.998 1.019 119% 1.008 1.073 1.02 1.015 1.021 0.997 1.028 125% 1.013 1.095 1.058 1.022 1.029 0.996 1.038 Entering Air Correction Table Entering Air DB ºC Heating Capacity Power Heat of Extraction 10.0 1.03 0.83 1.087 12.8 1.027 0.877 1.068 15.6 1.022 0.916 1.051 18.3 1.010 0.957 1.025 20.0 1.00 0.982 1.010 21.1 1.000 1.000 1.000 23.9 0.991 1.05 0.976 26.7 0.982 1.101 0.98 Entering Air WB C Total Capacity Sensible Cooling Capacity Multiplier - Entering Air WB C 18.3 21.1 23.9 26.7 27.0 29. 32.2 35.0 Power Heat of Rejection 12.8 0.953 0.909 * * * * * * * 0.988 0.960 15.6 0.95 0.760 0.810 1.076 1.209 1.233 * * * 0.991 0.962 18.3 0.975 0.6 0.872 1.089 1.115 1.238 * * 0.995 0.979 19.0 0.988 0.59 0.818 1.036 1.06 1.198 * * 0.998 0.990 19. 1.000 0.568 0.782 1.000 1.027 1.16 1.350 1.21 1.000 1.000 21.1 1.05 0.67 0.86 0.889 1.03 1.295 1.21 1.009 1.037 23.9 1.122 0.638 0.658 0.806 1.076 1.29 1.025 1.103 * = Sensible capacity equals total capacity AHRI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 27 C DB/19 C WB, and Heating - 20 C DB/15 C WB entering air temperature. Antifreeze Correction Table Antifreeze Type Cooling Heating WPD Antifreeze EWT 32 C EWT -1 C Corr. Fct. % EWT 30 C Total Cap Sens Cap Power Htg Cap Power Water 0 1.000 1.000 1.000 1.000 5 0.995 0.995 1.003 0.989 0.997 1.070 Propylene Glycol 15 0.986 0.986 1.009 0.968 0.990 1.210 25 0.978 0.978 1.01 0.97 0.983 1.360 5 0.997 0.997 1.002 0.989 0.997 1.070 Methanol 15 0.990 0.990 1.007 0.968 0.990 1.160 25 0.982 0.982 1.012 0.99 0.98 1.220 5 0.998 0.998 1.002 0.981 0.99 1.10 Ethanol 15 0.99 0.99 1.005 0.9 0.983 1.300 25 0.986 0.986 1.009 0.917 0.97 1.360 5 0.998 0.998 1.002 0.993 0.998 1.00 Ethylene Glycol 15 0.99 0.99 1.00 0.980 0.99 1.120 25 0.988 0.988 1.008 0.966 0.990 1.200 LC810-16

Blower Performance Data TLV08 - Standard Unit All Data is Wet Coil Airflow l/s 755.2 802. 89.6 896.8 9.0 991.2 1038. 1085.6 1132.8 1180.0 1227.2 127. 1321.6 1368.8 116.0 Airflow (l/s) at External Static Pressure (Pa) Pa 0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 B 0.12 0.15 0.13 0.19 0.22 0.2 0.26 0.30 0.31 0.33 0.37 0.39 Sheave/Mtr B B A A A A C C C C C C RPM 388 37 82 527 56 599 630 663 690 716 7 767 Turns Open 3.5 1.5 5 3.5 2.5 1.5 5.5.5 3.5 2.5 2 1 B 0.13 0.16 0.15 0.20 0.2 0.25 0.28 0.32 0.3 0.36 0.0 0.2 Sheave/Mtr B B A A A A C C C C C C RPM 392 0 85 529 566 601 633 666 693 720 77 771 Turns Open 3 1.5 5 3.5 2 1.5 5.5.5 3 2.5 2 1 B 0.1 0.17 0.17 0.22 0.25 0.27 0.29 0.33 0.36 0.38 0.2 Sheave/Mtr B B A A A A C C C C C RPM 395 88 530 568 603 636 668 697 723 751 Turns Open 2.5 1 5 3.5 2 1 5 3 2 1.5 B 0.15 0.18 0.19 0.23 0.27 0.28 0.31 0.35 0.38 0.1 0.5 Sheave/Mtr B B A A A C C C C C C RPM 399 7 91 532 571 606 639 671 700 727 75 Turns Open 2.5 1.5 3 2 5.5 5 3 2 1.5 B 0.11 0.16 0.19 0.21 0.25 0.28 0.30 0.33 0.37 0.0 0.3 0.7 Sheave/Mtr B B A A A A C C C C C C RPM 352 03 50 93 53 573 608 61 673 703 730 757 Turns Open.5 2.5 5.5.5 3 2 5.5.5 2.5 2 1.5 B 0.12 0.18 0.22 0.25 0.28 0.31 0.33 0.37 0.0 0. 0.8 0.52 Sheave/Mtr B B A A A A C C C C C C RPM 362 10 57 99 537 577 612 67 678 710 737 76 Turns Open.5 2 5.5.5 3 1.5 5.5.5 3.5 2.5 1.5 1 B 0.17 0.21 0.2 0.25 0.29 0.33 0.37 0.0 0. 0.8 0.52 0.55 Sheave/Mtr B B A A A A C C C C C C RPM 375 2 67 507 58 58 621 653 68 716 73 772 Turns Open 2 5 2.5 1.5 5.5 3.5 2.5 1.5 1 B 0.18 0.22 0.25 0.29 0.33 0.37 0.0 0. 0.8 0.52 0.55 Sheave/Mtr B B A A A A C C C C C RPM 387 35 76 518 555 590 627 659 692 721 751 Turns Open 3.5 1.5 5 2.5 1.5 5 3 2 1.5 B 0.18 0.22 0.25 0.29 0.33 0.37 0.0 0. 0.8 0.52 0.55 0.59 Sheave/Mtr B B B A A A A C C C C C RPM 353 03 6 85 527 563 600 633 665 697 726 756 Turns Open..5 3 1.5.5 3.5 2.5 1 5 3 2 1.5 B 0.21 0.23 0.25 0.29 0.33 0.37 0.0 0. 0.8 0.55 0.59 0.63 Sheave/Mtr B B B A A A A C C C C C RPM 362 11 52 95 532 567 60 636 670 700 729 759 Turns Open 2.5 1.5 3.5 2 1.5 3 2 1 B 0.22 0.25 0.32 0.36 0.0 0.3 0.7 0.51 0.55 0.58 0.62 0.66 Sheave/Mtr B B A A A A C C C C C C RPM 377 20 60 500 536 570 606 638 671 701 729 759 Turns Open 3.5 2 5.5 3 2 5.5.5 3.5 2.5 2 1 B 0.25 0.28 0.32 0.36 0.0 0. 0.8 0.52 0.55 0.59 0.63 0.67 Sheave/Mtr B B A A A A C C C C C C RPM 381 23 63 50 539 576 609 61 67 703 73 762 Turns Open 3.5 2 5.5 3 1.5 5.5.5 3.5 2.5 1.5 1 B 0.25 0.29 0.33 0.37 0.0 0.8 0.52 0.55 0.59 0.63 0.67 0.70 Sheave/Mtr B B A A A A C C C C C C RPM 390 31 7 510 55 581 613 67 677 706 737 76 Turns Open 3 1.5 5 3.5 2.5 1.5 5.5 3.5 2.5 1.5 1 B 0.29 0.33 0.37 0.0 0. 0.8 0.55 0.59 0.63 0.67 0.70 0.78 Sheave/Mtr B B A A A A C C C C C E RPM 399 0 81 517 551 586 618 651 681 710 70 767 Turns Open 2.5 1.5 5 3.5 2 1 5 3 2 1.5 1 B 0.32 0.37 0.0 0. 0.8 0.52 0.55 0.63 0.67 0.70 0.78 0.82 Sheave/Mtr B B A A A A C C C C E E RPM 12 55 92 526 563 595 628 658 687 718 75 77 Turns Open 2.5 1.5 3 2 1 5 3 2 1.5 1 A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, E = High Static/Large Motor. Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speeds require field selection. For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units. LC810-17

Blower Performance Data TLV096 - Standard Unit All Data is Wet Coil Airflow l/s 89.6 896.8 9.0 991.2 1038. 1085.6 1132.8 1180.0 1227.2 127. 1321.6 1368.8 116.0 163.2 1510. 1557.6 160.8 1652.0 Pa Airflow (l/s) at External Static Pressure (Pa) 0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 B 0.10 0.1 0.17 0.17 0.22 0.25 0.27 0.29 0.33 0.36 0.38 0.2 Sheave/Mtr B B A A A A A C C C C C RPM 33 395 88 530 568 603 636 668 697 723 751 Turns Open 5 3 6 5 3.5 2.5 1.5 5 3 2.5 1.5 B 0.11 0.15 0.18 0.19 0.23 0.27 0.28 0.31 0.35 0.38 0.1 0.5 Sheave/Mtr B B A A A A A C C C C C RPM 38 399 7 91 532 571 606 639 671 700 727 75 Turns Open.5 3 6 5 3.5 2 1.5 5 3 2.5 1.5 B 0.11 0.16 0.19 0.21 0.25 0.28 0.30 0.33 0.37 0.0 0.3 0.7 Sheave/Mtr B B A A A A A C C C C C RPM 352 03 50 93 53 573 608 61 673 703 730 757 Turns Open.5 3 5.5.5 3 2 1 5 2.5 2 1.5 B 0.12 0.18 0.22 0.25 0.28 0.31 0.33 0.37 0.0 0. 0.8 0.52 Sheave/Mtr B B A A A A A C C C C C RPM 362 10 57 99 537 577 612 67 678 710 737 76 Turns Open 2.5 5.5.5 3 2 1.5 3.5 2.5 2 1 B 0.17 0.21 0.2 0.25 0.29 0.33 0.37 0.0 0. 0.8 0.52 0.55 Sheave/Mtr B B A A A A A C C C C C RPM 375 2 67 507 58 58 621 653 68 716 73 772 Turns Open 2 5.5 3 1.5 1.5 3.5 2.5 2 1 B 0.16 0.18 0.22 0.25 0.29 0.33 0.37 0.0 0. 0.8 0.52 0.55 Sheave/Mtr B B A A A A A C C C C C RPM 339 387 35 76 518 555 590 627 659 692 721 751 Turns Open 5 3.5 6 5 2.5 1.5 5.5.5 3 2.5 1.5 B 0.18 0.22 0.25 0.29 0.33 0.37 0.0 0. 0.8 0.52 0.55 0.59 Sheave/Mtr B B A A A A A C C C C C RPM 353 03 6 85 527 563 600 633 665 697 726 756 Turns Open.5 3 6 5 3.5 2.5 1.5 5.5 3 2 1.5 B 0.21 0.23 0.25 0.29 0.33 0.37 0.0 0. 0.8 0.55 0.59 0.63 Sheave/Mtr B B A A A A A C C C C C RPM 362 11 52 95 532 567 60 636 670 700 729 759 Turns Open.0 2.5 5.5.5 3.5 2 1 5 3 2 1 B 0.22 0.25 0.32 0.36 0.0 0.3 0.7 0.51 0.55 0.58 0.62 0.66 Sheave/Mtr B B A A A A A C C C C C RPM 377 20 60 500 536 570 606 638 671 701 729 759 Turns Open 3.5 2 5.5.5 3 2 1 5 3.5 2.5 2 1 B 0.25 0.28 0.32 0.36 0.0 0. 0.8 0.52 0.55 0.59 0.63 0.67 Sheave/Mtr B B A A A A A C C C C C RPM 381 23 63 50 539 576 609 61 67 703 73 762 Turns Open 3.5 2 5 3 1.5 1 5 3.5 2.5 2 1 B 0.25 0.29 0.33 0.37 0.0 0.8 0.52 0.55 0.59 0.63 0.67 Sheave/Mtr B B A A A A A C C C C RPM 390 31 7 510 55 581 613 67 677 706 737 Turns Open 3 2 5 3 1.5 1.5 3.5 2.5 2 B 0.29 0.33 0.37 0.0 0. 0.8 0.55 0.59 0.63 0.67 0.70 Sheave/Mtr B A A A A A C C C C C RPM 399 0 81 517 551 586 618 651 681 710 70 Turns Open 3 6.5 3.5 2.5 1.5 5.5.5 3 2.5 1.5 B 0.32 0.37 0.0 0. 0.8 0.52 0.55 0.63 0.67 0.70 0.78 Sheave/Mtr B A A A A A C C C C C RPM 12 55 92 526 563 595 628 658 687 718 75 Turns Open 2.5 5.5.5 3.5 2 1 5 3 2 1.5 B 0.33 0.0 0. 0.8 0.52 0.55 0.63 0.67 0.70 0.7 0.78 Sheave/Mtr B A A A A A C C C C C RPM 21 59 99 533 569 600 633 663 691 722 79 Turns Open 2 5.5 3 2 1 5 3 2 1.5 B 0.37 0.0 0.8 0.52 0.55 0.63 0.67 0.70 0.7 0.78 0.85 Sheave/Mtr A A A A A A C C C C C RPM 1 78 513 59 581 61 6 672 703 730 759 Turns Open 6 5 2.5 1.5 1.5 3.5 2.5 2 1.5 B 0.0 0.8 0.52 0.55 0.62 0.67 0.70 0.7 0.78 0.85 0.92 Sheave/Mtr A A A A A C C C C C C RPM 56 95 529 561 595 625 656 685 712 71 767 Turns Open 5.5.5 3.5 2 1 5.5 3 2.5 2 1 B 0.7 0.52 0.55 0.59 0.63 0.70 0.7 0.78 0.85 0.89 0.93 Sheave/Mtr A A A A A C C C C C C RPM 71 506 539 57 60 633 66 692 721 77 773 Turns Open 5.5 3 1.5 1 5 3 2 1.5 1 B 0.8 0.55 0.59 0.63 0.70 0.7 0.78 0.85 0.92 0.96 Sheave/Mtr A A A A C C C C C C RPM 86 520 555 586 615 67 67 70 730 756 Turns Open 5 3.5 2.5 1 5.5.5 3 2 1.5 A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor. Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speeds require field selection. For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units. LC810-18

Blower Performance Data TLV120 - Standard Unit All Data is Wet Coil Airflow l/s 1085.6 1132.8 1180.0 1227.2 127. 1321.6 1368.8 116.0 163.2 1510. 1557.6 160.8 1652.0 1699.2 176. 1793.6 180.8 Pa Airflow (l/s) at External Static Pressure (Pa) 0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 B 0.18 0.19 0.22 0.27 0.30 0.3 0.37 0.2 0.5 0.8 0.52 0.55 0.60 0.63 Sheave/Mtr B B B A A A A A A C C C C C RPM 376 23 66 503 53 580 616 69 682 712 72 770 797 822 Turns Open 6.5 3 6 5 3 2 1 5.5.5 3 2.5 B 0.19 0.22 0.27 0.30 0.3 0.37 0.2 0.5 0.52 0.52 0.57 0.60 0.67 0.70 Sheave/Mtr B B B A A A A A C C C C C C RPM 395 39 81 517 555 592 626 659 691 722 751 779 805 831 Turns Open 5.5 2.5 5.5.5 3.5 2.5 1.5 6 5.5.5 3.5 3 2 B 0.22 0.25 0.30 0.33 0.37 0.0 0.5 0.8 0.55 0.60 0.63 0.67 0.70 0.75 Sheave/Mtr B B B A A A A A C C C C C C RPM 12 55 96 530 567 603 637 669 701 730 759 787 813 839 Turns Open 5 3 1.5 5.5 3 2 1 6 5 3.5 2.5 1.5 B 0.22 0.25 0.30 0.33 0.37 0.0 0.5 0.8 0.55 0.60 0.63 0.67 0.70 0.75 0.78 Sheave/Mtr B B B A A A A A A C C C C C C RPM 385 30 71 506 5 579 61 67 679 710 739 768 795 822 87 Turns Open 6 2.5 6 5 3.5 2.5 1.5 1 5.5.5 3 2 1.5 B 0.25 0.30 0.33 0.37 0.0 0.5 0.8 0.55 0.60 0.63 0.67 0.70 0.75 0.78 0.82 Sheave/Mtr B B B A A A A A C C C C C C C RPM 03 6 86 520 556 591 625 657 689 719 78 776 803 830 855 Turns Open 5 3.5 2 5.5.5 3.5 2.5 1 6 5.5.5 3.5 3 2 1 B 0.25 0.30 0.33 0.37 0.0 0.5 0.8 0.52 0.60 0.63 0.67 0.70 0.75 0.78 0.82 0.90 Sheave/Mtr B B B A A A A A A C C C C C C C RPM 377 21 62 501 53 569 603 636 668 698 728 757 785 812 838 860 Turns Open 6.5 3 6 5 3 2 1 6 5 3.5 2.5 1.5 1 B 0.30 0.33 0.37 0.0 0.5 0.8 0.52 0.55 0.63 0.67 0.70 0.75 0.78 0.85 0.90 0.93 Sheave/Mtr B B B A A A A A A C C C C C C C RPM 395 38 78 515 57 582 615 67 678 708 737 765 793 819 85 868 Turns Open 5.5 2.5 6.5 3.5 2.5 1.5 1 5.5 5 3 2.5 1.5 0.5 B 0.33 0.37 0.0 0. 0.8 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.89 0.93 1.00 Sheave/Mtr B B B A A A A A C C C C C C C C RPM 1 53 91 529 563 595 626 659 689 717 75 77 801 826 851 877 Turns Open.5 3.5 2 5.5.5 3.5 2.5 1.5 6 5.5.5 3.5 3 2 1 0.5 B 0.37 0.0 0. 0.8 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.89 0.93 1.00 1.08 Sheave/Mtr B B A A A A A A C C C C C C C C RPM 31 69 50 52 575 607 637 670 699 726 75 783 809 83 859 88 Turns Open 3 6 5 3 2 1 6 5.5 3.5 2.5 2 1 0.5 B 0.0 0. 0.8 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.93 0.96 1.00 1.08 1.1 Sheave/Mtr B B A A A A A A C C C C C C C C RPM 8 85 520 556 588 619 69 680 708 736 765 791 817 81 868 891 Turns Open 3.5 2 5.5.5 3.5 2.5 1.5 1 5.5 5 3 2.5 1.5 0.5 0 B 0. 0.8 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.93 0.96 1.00 1.08 1.11 1.15 Sheave/Mtr B B A A A A A C C C C C C C C C RPM 6 500 537 570 601 631 662 691 718 75 77 799 82 89 875 898 Turns Open 3 1.5 5 3 2 1.5 6 5.5.5 3 2 1.5 0.5 0 B 0.8 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.93 0.96 1.00 1.08 1.11 1.15 Sheave/Mtr B A A A A A A C C C C C C C C RPM 80 515 551 583 613 62 67 701 728 75 783 808 833 857 882 Turns Open 2.5 6.5 3.5 3 2 1 6 5.5 3.5 2.5 2 1 0 B 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.93 0.96 1.00 1.08 1.15 1.19 1.23 Sheave/Mtr B A A A A A C C C C C C C C C RPM 96 530 565 596 625 65 68 711 738 766 792 816 81 867 890 Turns Open 2 5.5 3.5 2.5 1.5 6 5.5.5 3 2.5 1.5 1 0 B 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.93 1.00 1.0 1.08 1.15 1.19 1.23 1.30 Sheave/Mtr A A A A A A C C C C C C C C C RPM 511 5 578 608 637 668 695 722 78 776 800 825 89 87 897 Turns Open 6 5 3.5 3 2 1 6 5.5 3.5 3 2 1.5 0.5 0 B 0.63 0.67 0.70 0.78 0.85 0.89 0.93 1.00 1.0 1.08 1.15 1.23 1.26 1.30 Sheave/Mtr A A A A A A C C C C C C C C RPM 526 561 592 621 69 679 706 732 758 785 809 833 857 882 Turns Open 5.5.5 3.5 2.5 1.5 1 5.5 5 3.5 2.5 2 1 0.5 B 0.67 0.70 0.78 0.82 0.85 0.93 1.00 1.0 1.08 1.15 1.23 1.26 1.30 1.38 Sheave/Mtr A A A A A C C C C C C C C C RPM 5 575 605 633 661 691 717 72 767 79 818 82 867 890 Turns Open 5 3 2 1 6 5.5.5 3 2 1.5 0.5 0 B 0.70 0.78 0.85 0.89 0.93 1.00 1.08 1.11 1.15 1.23 1.30 1.3 1.38 1.5 Sheave/Mtr A A A A A C C C C C C C C E RPM 555 589 618 66 676 702 728 753 779 803 827 850 875 898 Turns Open.5 3.5 2.5 1.5 6 6 5 3.5 2.5 2 1 0.5 0 A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, E = High Static/Large Motor. Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speeds require field selection. For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units. Table Continued on Next Page LC810-19

Blower Performance Data TLV120 - Standard Unit Table Continued from Previous Page All Data is Wet Coil Airflow l/s 1888.0 1935.2 1982. 2029.6 2076.8 212.0 Pa Airflow (l/s) at External Static Pressure (Pa) 0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 B 0.78 0.82 0.85 0.93 1.00 1.08 1.11 1.15 1.23 1.30 1.3 1.38 1.50 1.53 Sheave/Mtr A A A A C C C C C C C C E E RPM 572 601 630 657 686 712 737 762 789 812 836 859 883 905 Turns Open 3 2 1 6 5.5.5 3 2.5 1.5 1 0 0 B 0.85 0.89 0.93 1.00 1.08 1.11 1.15 1.23 1.30 1.38 1.1 1.50 1.53 Sheave/Mtr A A A A C C C C C C C E E RPM 589 617 65 672 700 726 751 775 801 82 87 872 89 Turns Open 3.5 2.5 1.5 1 6 5.5 3.5 2.5 2 1 0.5 0 B 0.93 0.96 1.00 1.08 1.15 1.19 1.23 1.30 1.38 1.50 1.53 1.56 Sheave/Mtr A A A C C C C C C E E E RPM 605 633 660 689 71 739 763 790 813 836 858 882 Turns Open 3 2 1 6 5.5.5 3 2 1.5 1 0.5 B 0.96 1.00 1.08 1.15 1.23 1.26 1.30 1.38 1.50 1.53 1.60 1.68 Sheave/Mtr A A A C C C C C E E E E RPM 621 69 675 703 728 752 776 802 827 87 869 893 Turns Open 2.5 1.5 1 6 5 3.5 2.5 2 1.5 1 0 B 1.00 1.08 1.15 1.23 1.30 1.38 1.1 1.50 1.53 1.60 1.68 1.75 Sheave/Mtr A A C C C C C E C E E E RPM 637 66 690 717 72 766 791 81 836 858 882 90 Turns Open 2 1 6 5.5.5 3 2 2 1 0.5 0 B 1.11 1.15 1.23 1.30 1.38 1.5 1.53 1.56 1.60 1.68 1.75 Sheave/Mtr A A C C C C E E C E E RPM 653 679 707 731 755 779 80 826 88 870 893 Turns Open 1.5 1 5.5 5 3.5 3 2 1.5 1 0 A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, E = High Static/Large Motor. Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speeds require field selection. For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units. LC810-20

Blower Performance Data TLV150 - Standard Unit All Data is Wet Coil Airflow l/s 1321.6 1368.8 116.0 163.2 1510. 1557.6 160.8 1652.0 1699.2 176. 1793.6 180.8 1888.0 1935.2 Pa Airflow (l/s) at External Static Pressure (Pa) 0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 B 0.3 0.37 0.2 0.9 0.52 0.57 0.6 0.72 0.79 0.87 0.9 Sheave/Mtr B B A A A A A A C C C RPM 533 572 606 60 676 712 76 783 821 859 901 Turns Open 5.5 6 5 3 2 1 5.5.5 3 B 0.37 0.2 0.5 0.52 0.57 0.60 0.67 0.75 0.81 0.90 0.97 Sheave/Mtr B B A A A A A A C C C RPM 5 582 619 652 686 719 75 789 823 860 902 Turns Open 5 5.5.5 3.5 2.5 1.5 1 5.5 3 B 0.37 0.2 0.5 0.52 0.57 0.60 0.67 0.75 0.79 0.82 0.9 1.02 Sheave/Mtr B B B A A A A A C C C C RPM 521 558 595 628 663 697 728 762 796 828 863 903 Turns Open 6.5 3.5 5.5.5 3.5 2.5 1.5 6 5 3 B 0.2 0.5 0.52 0.55 0.60 0.6 0.72 0.78 0.82 0.90 0.97 1.05 Sheave/Mtr B B A A A A A A C C C C RPM 536 572 608 60 67 705 737 769 799 832 866 90 Turns Open 5.5 6 5 3 2 1 6 5 3 B 0.5 0.9 0.55 0.60 0.67 0.70 0.75 0.85 0.90 0.97 1.05 1.12 Sheave/Mtr B B A A A A A A C C C C RPM 58 585 618 652 685 715 77 778 807 836 868 905 Turns Open 5 3.5 5.5.5 3.5 2.5 1.5 1 5.5 5 3.5 3 B 0.5 0.8 0.52 0.60 0.6 0.70 0.78 0.82 0.90 0.93 1.00 1.08 1.15 Sheave/Mtr B B A A A A A A A C C C C RPM 522 562 599 631 66 69 725 756 78 815 85 87 906 Turns Open 6.5 6 5.5 3 2.5 1.5 1 5.5.5 3.5 3 B 0.8 0.52 0.57 0.63 0.67 0.75 0.82 0.85 0.93 1.00 1.08 1.15 1.20 Sheave/Mtr B B A A A A A A C C C C C RPM 537 576 612 63 676 705 736 763 793 823 850 880 908 Turns Open 5.5 5.5 5 3 2 1 6 5.5 3.5 2.5 B 0.52 0.57 0.60 0.67 0.75 0.78 0.85 0.93 1.00 1.05 1.12 1.20 1.23 Sheave/Mtr B B A A A A A A C C C C C RPM 551 589 622 655 685 716 76 776 802 829 858 886 913 Turns Open 5 3.5 5.5.5 3.5 2.5 2 1 6 5 3 2.5 B 0.52 0.55 0.60 0.67 0.75 0.78 0.85 0.93 0.97 1.05 1.08 1.15 1.23 1.30 Sheave/Mtr B B A A A A A A C C C C C C RPM 526 565 600 63 665 696 727 75 783 809 837 865 891 919 Turns Open 6.5 6 5 3 2 1.5 6 5.5.5 3 2.5 B 0.55 0.63 0.67 0.70 0.78 0.85 0.93 0.97 1.00 1.08 1.15 1.23 1.30 1.38 Sheave/Mtr B B A A A A A A C C C C C C RPM 51 579 613 67 677 707 737 76 793 818 86 871 898 926 Turns Open 5.5 5.5.5 3 2 1.5 6 5.5.5 3.5 3 2 B 0.55 0.63 0.67 0.70 0.78 0.85 0.93 0.96 1.00 1.08 1.15 1.23 1.30 1.38 1.5 Sheave/Mtr B B B A A A A A A C C C C C C RPM 519 55 591 626 659 688 718 76 77 802 829 855 879 905 931 Turns Open 6 5 3.5 5.5.5 3.5 2.5 2 1 5.5 5.5 3.5 2.5 2 B 0.59 0.63 0.70 0.78 0.85 0.89 0.93 1.00 1.08 1.15 1.23 1.30 1.38 1.5 1.52 Sheave/Mtr B B A A A A A A A C C C C C C RPM 531 569 605 639 669 702 729 757 785 811 838 862 887 913 938 Turns Open 5.5.5 6 5 3 2.5 1.5 1 5.5 5 3.5 2.5 2 B 0.63 0.70 0.78 0.85 0.89 0.93 1.00 1.08 1.15 1.23 1.26 1.30 1.38 1.5 1.53 Sheave/Mtr B B A A A A A A C C C C C C C RPM 55 582 618 651 683 710 739 767 79 821 85 870 895 920 95 Turns Open 5 5.5.5 3 2 1.5 6 5.5.5 3 2.5 2 B 0.63 0.70 0.78 0.82 0.85 0.93 1.00 1.08 1.15 1.23 1.26 1.30 1.38 1.5 1.53 1.60 Sheave/Mtr B B B A A A A A A C C C C C C C RPM 523 560 596 631 661 692 722 750 778 80 831 85 879 90 928 951 Turns Open 6.5 3.5 5.5.5 3.5 2.5 1.5 1 6 5.5 3.5 3 2 1.5 A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, E = High Static/Large Motor. Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speeds require field selection. For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units. Table Continued on Next Page LC810-21