Digital-Flo TM Boiler Water/Water Plate & Frame Heat Exchanger

Similar documents
PT-516 Pumping Trap Installation and Maintenance

V400D VERIS Verabar (Double Rod) Installation and Maintenance Manual

V500 and V510 VERIS Verabar Installation and Maintenance Manual

V200D VERIS Verabar (Double Rod) Installation and Maintenance Manual

V150 VERIS Verabar Installation and Maintenance Manual

Armstrong Steam Filters (ASF)

CV Control Valves Installation and Operation Manual

StormPro BA Series Sump Pump

Operating Instructions for PAC800 Battery Charger

Digital-Flo TM Digital Instantaneous Steam/Water Plate & Frame Heat Exchanger Product Manual

10 Year Limited Warranty

Dual Flow Manifold Systems Instruction Manual

Power. On Your Terms.

HALLMARK INDUSTRIES INC

Armstrong Double Duty 6 Steam Trap/Pump Combination Installation and Maintenance

Dual/Triple Manifold Water Filtration Systems Instruction Manual

HR-20P Pneumatically Controlled Pressure Regulator

QUICK START GUIDE OWNER S MANUAL AL50 SERIES SAND FILTRATION TECHNOLOGY PLEASE CALL DO NOT RETURN TO STORE

APCO ASR-400/450 SEWAGE AIR RELEASE VALVES

APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES

TALCO FIRE SYSTEMS. LSF Start-Up Instructions. 1) IMPORTANT: Inspect the unit for damage. Report any damage to the freight carrier immediately.

READ THIS MANUAL CAREFULLY BEFORE USING THE PUMP

SUNC3000 / Item #40885

StormPro BCV400 Sewage Ejector Pump

Scale Feeder Manifold Water Filtration System Instruction Manual

Manufacturing Facility is ISO9001:2000. Welded Steel Pipe Conform to ASTM A53. Threads Conform to ASME B1.20.1

OWNER S MANUAL SELF-PRIMING PORTABLE UTILITY PUMP

OPERATION MANUAL Variable Speed Pump Controller Dated: 06/04/2013 Pump Down Application. Document No.: LMSII_V100_OM Page 1 of 8 Model-V100 LMS II

LUBRICATOR GUN INSTRUCTIONS-PARTS LIST. 10,000 psi (700 bar) Maximum Delivery Pressure. Detachable-type

Full Flow Drinking Water System Model: 3MFF100

See Installation Guide

PARTS AND INSTALLATION MANUAL

Model BP6150. Triplex Ceramic Plunger Pump Operating Instructions/ Manual

Read this entire manual before operation begins.

SUNC1200 / ITEM #40882 SUBMERSIBLE UTILITY PUMP OPERATIONS MANUAL

G8 Portable Fuel Transfer Pump Owner s Manual

Straight-Bore Clutch LSCC-32, 44, 54

Operators Manual. Model 3370 Air Cooled Recirculator rev.8/98

SUPER PUMP OUT SYSTEM

STAINLESS STEEL FORGED FITTINGS 3000lb 304/304L & 316/316L Forged Stainless Steel Fittings Product Specifications

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Blue Air. Commercial Refrigeration Inc. Installation & Operation Manual Chef Bases

ESE Series Cast Iron Sewage Pumps

IMPORTANT SAFETY INSTRUCTIONS

Installation Instructions / Warranty

MetroPrime 22MPC Self-Priming Centrifugal Pump

Installation, Operation and Maintenance Manual

JET METER INSTRUCTIONS

DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

PreSoak System (NonFoaming) DU PS1-HP DU PS6-HP

Reach ins, Freeezers & Refrigerators Installation & Operation Manual

MaxLite StaxMax LED Flood Lights

Water Jetter Units DU JT50 / DU JT100

FOR TECHNICAL ASSISTANCE

Model GX Series. Consumer Pump. Triplex Plunger Pump Operating Instructions/ Repair Instructions Manual

FOR TECHNICAL ASSISTANCE

Ion Technologies SHR-HR Submersible Sewage Pump Single Seal, Single Phase, & Three Phase Power

PRYCO, INC. P. O. BOX 108 Mechanicsburg, IL OPERATIONS AND MAINTENANCE MANUAL For PUMP SETS

Model GXR Series. Consumer Pump. Triplex Plunger Pump Operating Instructions/ Repair Instructions Manual

Pro Shot Grease Dispense Valve

DRAIN WATER TEMPERING KIT

Installation Instructions / Warranty

Service Guide JATCO Environmental Protection Tank Model J-7000

INSTALLATION INSTRUCTION & OWNER S MANUAL

P SERIES PUMPS. 18mm Versions Nickle-Aluminum Bronze Models: P , P , P , P , P , P , P

Blue Air. Commercial Refrigeration Inc. Installation & Operation Manual Glass Door Countertop Refrigerator

Model GXR Series. Consumer Pump. Triplex Plunger Pump Operating Instructions/ Repair Instructions Manual

GC-1. Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY

Installation Instructions / Warranty

Operator's Manual. Models (¾") (1") (1½ ) (2 ) (3") (4") (6") (8")

Installation & Operation Manual Chef Base

Model GP5128. Triplex Ceramic Plunger Pump Operating Instructions / Manual

Model GXR Series. Consumer Pump. Triplex Plunger Pump Operating Instructions/ Repair Instructions Manual

Model GP Triplex Ceramic Plunger Pump Operating Instructions/ Manual

Wash Prep Systems featuring CAT PUMPS DUPM623 DUPM820 / DUPM820-TS DUPM820D / DUPM820D-TS DUPM1010. Owner s Manual #

Series: PFUEG 1/12HP, 5000 RPM, 60 Hz Utility Pumps

OWNER S MANUAL SUBMERSIBLE UTILITY PUMP

PowerFLO 7800 Series 12 Volt DC Motor-Driven Diaphragm Pumps

Single-Valve Powerstation

PENBERTHY MODELS GL AND GH GAS OPERATED JET PUMPS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

PACKING LIST DESCRIPTION MODEL NUMBER - PANEL HOUSING HAND SHOWER HOSE HAND SHOWER FLEXIBLE HOSES 16" LONG WITH 1/2" FEMALE 88

Harley Davidson FL Touring Current Xtreme

Owner s Manual Nitrate Series Salt Based Filter System

STOP CITY PRESSURE BOOSTER PUMP INSTRUCTION MANUAL

ProFlo FatBoy

PVI 1800/PVI Residential/Commercial Grid-Tied Photovoltaic Inverter WARRANTY MANUAL. Subject to Change REV , Solectria Renewables

Installation, Operation and Maintenance Manual for Pressure/Vacuum Relief Valves (Spring Loaded)

Models GP5132, GP5136, GP5142 & GP5145. Triplex Ceramic Plunger Pump Operating Instructions / Manual

Operators Manual. Recirculating Chiller /06/08

Type Flexair Pneumatic Pressure Control Valves

INSTALLATION INSTRUCTIONS, PARTS LIST AND CONFIGURATION GUIDE FOR THE CARBONATOR. Large Model No

Read this entire manual before operation begins.

HIGH VOLTAGE DIGITAL AMMETER

DeZURIK 2 20" BOS BUTTERFLY VALVES

Aqua Ultraviolet Sunami Series Pumps 1/3HP, 3/4HP, 3HP, 4HP, 5HP

DeZURIK 24 and Larger BHP High Performance Butterfly Valves WITH (FB) FYRE-BLOCK SEAT

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT.

PolyStat Immersion Circulators

MODEL VG08001 CONTENT PACKING LIST / TOOLS NEEDED PANEL DIMENSIONS FITTINGS / TECHNICAL DATA WALL/CORNER INSTALLATION CARE AND TROUBLE SHOOTING

Dual Port Manifold Water Filtration Systems Instruction Manual

Transcription:

Digital-Flo TM Boiler Plate & Frame Heat Exchanger Installation, Operation, and Maintenance Manual 221 Armstrong Blvd., Three Rivers, Michigan, 49093 - USA Ph. (269) 279-3602 Toll Free (888) HOT-HOSE (468-4673) Fax (269) 279-3130 Keep this manual with heat exchanger for future reference.

Armstrong Contents Safety...1 General Description...2 Specifications...4 Operational Specifications..............................4 Technical Specifications................................. 4 Materials of Construction................................5 Dimensions................................................... 6 Installation...7 General Information....................................... 7 Typical Installation.........................................8 Commissioning..............................................9 Periodic Maintenance... 10 Troubleshooting... 11 Parts Lists... 14 Limited Warranty and Remedy... 16 Notes... 17 221 Armstrong Blvd., Three Rivers, Michigan, 49093 - USA Ph. (269) 279-3602 Toll Free (888) HOT-HOSE (468-4673) Fax (269) 279-3130

Safety Icon Legend If instructions are not followed: injury or death and property damage are imminent injury or death and property damage are possible potential property damage, expensive repairs, and/or voiding the warranty may result Read this manual. It contains important information. Installation must comply with all applicable federal, state, and local sanitary, construction, plumbing and regulatory codes. Service must be performed by a qualified person. Burn hazard Components and piping may be hot. Skin exposure to 140 F (60 C) water for only five seconds may cause a second degree burn. Improper installation, start-up, operation, maintenance, or service may void the warranty. Page 1 of 18

General Description Note: In this manual "DF" stands for "Digital Flo" and is the brand designation. "PHE" stands for "Plate Heat Exchanger" as distinct from a tube and shell type. The Digital-Flo Boiler Plate and Frame Heat Exchanger uses digital technology to monitor water temperature (inlet hot and inlet cold/system return), eliminating the need for the following components: Boiler Water Control Valve PID Controller High Temperature Limit Thermostat High Temperature Limit Controller Cold Water Injection Valve Internal Circulating Pump Compressed Air Requirement The secondary (sometimes called domestic) side of all units is equipped with a safety shut-off valve. Units are shipped pre-piped and pressure tested. All Digital-Flo units may be integrated into Building Automation Systems or LANs. Among the available options: Boiler water greater than 160 F units optimized for 180 F (82.2 C) in and 150 F (65.6 C) out. Boiler water less than 160 F units optimized for 150 F (65.6 C) in and 115 F (46.1 C) out. Standard Components: DRV40, DRV50, or DRV80 digital recirculating valve Heat exchanger module (ASME stamped) Thermometers Check valves Inlet strainer(s) Isolation valves Safety shut-off valves Note: Because the Digital-Flo is customizable, there may be components that are not addressed in this IOM. Armstrong reserves the right to make design or specification changes without notification. Page 2 of 18

Typical Layout Heat exchanger module Relief valve Safety shut off Outlet thermometer Mixed water outlet Isolation valve Recirculation return Strainer Strainer Return thermometer Cold water inlet DRV Inlet thermometer Strainer Clean-in-place port Isolation valve Page 3 of 18 Typical Layout

Specifications Operational Specifications Parameter Specification Maximum Boiler Water Temperature Maximum Boiler Water Pressure Minimum Inlet Supply Water Temperature Digital Recirculating Valve (DRV) Set Point Range Minimum Recirculation Loop Temperature Loss Minimum Recirculation Pump Flow Rate Minimum System Draw Off Primary Side Secondary Side 250 F (121 C) 150 psi (10 bar) 34 F (1 C) 81 158 F (29 70 C) 2 F (1 C) 5 GPM (DRV40) / 10 GPM (DRV50/DRV80) 0 GPM Minimum Distance to First Outlet 49 ft (15 m) Maximum Water Pressure Maximum Operating Pressure Drop Power Supply Supply Fuse/Circuit Breaker Protection Rating Signal Cable Fittings Battery Duty Cycle 150 psi (10 bar) 7 psi (0.5 bar) 120/240 VAC 50 60 Hz 10 A 3 A IPX4 3/8" SOW and cord grips 2 x CR - P2 6V Continuously Rated Technical Specifications Deciphering a Model Number "W" indicates a water-towater heat exchanger. Digits show DRV model. "BS" is present only if unit is equipped with brain scan. "DF" means Digital-Flo. Digits show the secondary side flow capacity. DF120WEDW80BS "E" indicates a < 160 F model (no "E" is > 160 F). "DW" indicates a double-wall model (single wall has no indicator). Page 4 of 18 Technical Specifications

Primary Side Data Capacity (GPM [LPM] @ 150 to 115 F [65.6 to 46.1 C]) < 160 F Models > 160 F Models Connections* Capacity (GPM [LPM] @ 180 to 150 F [82.2 to 65.6 C]) Connections* 44 (166.6) 2 (51) 51 (193.1) 1 ¼ (32) 101 (382.3) 2 (51) 119 (450.5) 2 (51) 188 (711.7) 2.5 (64) flg (4 [102] flg DW) 221 (836.6) 2 (51) 260 (984.2) 3 (76) flg (4 [102] flg DW) 306 (1158.3) 4 (102) flg 347 (1313.5) 4 (102) flg 407 (1540.7) 4 (102) flg Secondary Side Data Capacity Connections* (GPM [LPM] @ 40 140 F [4.4 60 C]) In/Out Recirc DRV 15 (56.8) 1 (25) 1 (25) 1 ½ (38) 35 (132.5) 1 ½ (38) 1 (25) 1 ½ (38) 65 (246.1) 2 (51) 1 ½ (38) 3 (76) 90 (340.7) 3 (76) flg 2 (51) 3 (76) 120 (454.3) 3 (76) flg 2 (51) 3 (76) * All connections are shown in inches (mm) and are NPT unless shown as flanged ("flg"). Materials of Construction Component Material Primary Side PHE Plates PHE Frame Gasket DRV Pipework Fittings 316 Stainless Steel Carbon Steel Painted Acrylic Nitrile (FDA approved) Secondary Side 316L Stainless Steel Copper Type L Brass/Bronze (Lead Free) Page 5 of 18 Materials of Construction

Dimensions C A B Side View Top View Model Single Wall Dimensions in. (mm) A B C > 160 F Models DF15W40 25 (635) 40 (1016) DF15W40BS 27 (686) 68 (1727) DF35W40 25 (635) 50 (1270) DF35W40BS 27 (686) 76 (1930) DF65W50 25 (635) 65 (1651) DF65W50BS 27 (686) 94 (2388) DF90W80 34 (864) DF90W80BS 35 (889) 67 (1702) DF120W80 34 (864) 79 (2007) DF120W80BS 35 (889) < 160 F Models DF15WE40 25 (635) 56 (1422) DF15WE40BS 27 (686) 68 (1727) DF35WE40 25 (635) 62 (1575) DF35WE40BS 27 (686) 84 (2134) DF65WE50 29 (737) 65 (1651) DF65WE50BS 31 (787) 86 (2184) DF90WE80 34 (864) 61 (1549) DF90WE80BS 35 (889) 79 (2007) DF120WE80 34 (864) 62 (1575) DF120WE80BS 35 (889) 94 (2388) Model Double Wall Dimensions in. (mm) A B C > 160 F Models DF15WDW40 25 (635) 40 (1016) DF15WDW40BS 27 (686) 68 (1727) DF35WDW40 25 (635) 62 (1570) 76 (1930) DF35WDW40BS 27 (686) DF65WDW50 25 (635) 65 (1651) 94 (2388) DF65WDW50BS 27 (686) DF90WDW80 34 (864) 67 (1702) 79 (2007) DF90WDW80BS 35 (889) DF120WDW80 34 (864) 64 (1626) 94 (2388) DF120WDW80BS 35 (889) < 160 F Models DF15WEDW40 25 (635) 56 (1422) 68 (1727) DF15WEDW40BS 27 (686) DF35WEDW40 25 (635) 62 (1575) 84 (2134) DF35WEDW40BS 27 (686) DF65WEDW50 33 (838) 67 (1702) 106 (2692) DF65WEDW50BS 35 (889) DF90WEDW80 34 (864) DF90WEDW80BS 35 (889) 64 (1626) 94 (2388) DF120WEDW80 34 (864) DF120WEDW80BS 35 (889) Page 6 of 18 Dimensions

Installation General Information Locate adjacent to appropriate electrical service. Position with adequate space for service and maintenance. Installation must be performed by designated, qualified, and competent personnel, including a licensed electrician and plumber or pipe fitter. Follow all applicable codes. Requires primary and secondary side circulating pumps (not supplied). Always wear appropriate safety clothing and equipment. Isolate all water and condensate lines. Relieve residual pressure in system or connecting piping. Allow hot parts to cool before beginning work. Notes: Secondary loop is supplied with enable/disable temperature limit protection. A secondary system recirculation pump must be installed and be operational at all times on the inlet to the unit. Isolating valves should be fitted to primary side connections (not supplied). Page 7 of 18 General Information

Typical Installation 1 Connect boiler water supply pipe to exchanger inlet. Note: Boiler supply and return line size should match heat exchanger inlet. Boiler supply and return lines must not exceed operating parameters of heat exchanger. 4 Connect outlet to system. 5 Connect recirculation return pipe work. 3 Connect inlet cold water supply. 2 Connect boiler water return line to exchanger outlet. Page 8 of 18 Typical Installation

Commissioning 1 Confirm all plumbing, piping, and electrical connections. 2 Ensure that boiler water supply valve and all valves on heat exchanger are closed. 3 Open several fixtures in building to vent air from system. 4 Open isolation valves to flood secondary side of system. 5 Start secondary side recirculating pump. Isolation Valves 6 Confirm water circulation through heat exchanger. 7 Turn on power to DRV. Note: Water temperature is preset based on information provided to Armstrong. Secondary high side limit default is set 18 F (10 C) above setpoint. See DRV IOM for information on changing preset values. 8 Slowly open inlet boiler water supply valve. 9 Confirm display of system setpoint and secondary side delivery temperature on DRV. Note: Display will show "temp low" during start-up. Page 9 of 18 Commissioning

Periodic Maintenance Hot parts when unit is operating. Prior to performing any invasive procedure, turn off heat exchanger, allow to cool, and relieve pressure. Note: Maintenance information for the DRV is not shown here. See the separate IOM. Interval Six months Six months Six months Six months Six months As required Six months As required Task Check PHE temperatures and flow rates against standard specifications. Check plate pack tightening dimension of PHE and look for signs of leakage. Check condition of PHE nozzles and for signs of leakage. Wipe PHE frame painted parts. Check for damage. Touch up if required. Clean bolts and bars of PHE. Lightly coat threaded parts with molybdenum grease or a corrosion inhibitor. Do not allow grease or inhibitor to fall onto plate gaskets. Check and replace PHE gaskets. If PHE rollers are fitted to follower frame plate, lubricate bearings with light machine oil. Descale system (frequency depends on water quality) Page 10 of 18

Troubleshooting Components and water may be hot. Note: For problems exclusive to the DRV controller, see that IOM. Problem Probable Cause Correction Secondary side temperature low Secondary side temperature rises when there is no demand. Secondary side system temperature fluctuates > ± 5 F (2.8 C) Restriction on primary side Primary side pump not running Primary side water temperature too low Secondary side check valve failed Secondary side flow rate < 10 GPM (38 LPM) Return temperature is within 2 F (1.1 C) of set point Confirm that all isolation valves are fully open. Restart or troubleshoot pump (If pump is variable-speed, confirm that speed selection is correct for necessary flow and discharge pressure.) Confirm that temperature is set to design spec. Confirm that recirculation line is hot. If not, check for failed check valve (allows cold water to bypass heat exchanger). 1. Confirm that flow rate setting is > 10 GPM (38 LPM). 2. Check system for: Air locks Closed valves Pump failure Other similar causes Ensure temperature differential in circuit is 2 F (1.1 C). Check valve problem 1. Confirm that check valves were installed as designed. 2. Ensure proper function of valves. Water pressure problem 1. Ensure that supply pressure differential is 20 psi (1.4 bar). 2. Confirm that recirc pump is operating. Flow restriction DRV fault Unequal supply pressures on secondary side Secondary side flow restriction Excessive supply temperature differential DRV fault Primary side inlet temperature fluctuating Demand exceeds capacity of unit Check for: Air locks Closed valves Clogged filters Other restrictions See DRV IOM. Balance pressures. Check for: Air locks Closed valves Clogged filters Other restrictions Confirm that differentials between set point and hot and cold inlet supplies to DRV are 10 F (5.6 C). See DRV IOM. 1. Confirm that connections are as designed (no cross connections). 2. Confirm that bypass is not open. Reduce demand. Page 11 of 18

Problem Probable Cause Correction DRV displays any of following errors: Temp High 127 F Setpoint 120 F Temp Low 100 F Setpoint 120 F Temp High 130 F Error Temp DRV display and secondary side system temperature show constant difference Water supply problem System fault DRV fault Process error: System does not return to normal temperature within Disinfection Timeout period Process error: Disinfection process aborted Inaccurate outlet thermometer DRV fault Water to DRV must be 180 F (82.2 C). Turn off DRV for 10 seconds, then restart. See DRV IOM. See DRV IOM. See DRV IOM. Replace thermometer. See DRV IOM. Heater capacity reduced Scale build-up 1. If completely blocked, disassemble and clean (see heat exchanger module manufacturer s IOM). 2. If partially blocked, clean with suitable descalant through CIP connections. Secondary side system temperature not adjustable DRV has no display or no control High pitched noise from DRV Secondary side has low pump flow rate Return temperature is within 2 F (1.1 C) of set point 1. Reset circuit flow rate at recirc pump discharge. 2. Check for: Air locks Closed valves Clogged filters Pump failure Other similar issues Ensure temperature differential in circuit 2 F (1.1 C). Check valve problem 1. Confirm that check valves were installed as designed. 2. Ensure proper function of valves. Water pressure problem Flow restriction Unequal supply pressures on secondary side Excessive supply temperature differential DRV fault No power to DRV DRV fault Unequal supply pressures on secondary side Excessive supply temperature differential DRV fault Water leaking from DRV See DRV IOM. N/A Moisture visible in DRV cover See DRV IOM. N/A 1. Ensure that supply pressures are balanced. 2. Ensure that there is mixed return to exchanger. Check for: Air locks Closed valves Clogged filters Other restrictions Supply pressure differential must be 20 psi (1.4 bar). Confirm that differentials between set point and hot and cold inlet supplies to DRV are 10 F (5.6 C). See DRV IOM. Confirm or reestablish power. See DRV IOM. Supply pressure differential must be 20 psi (1.4 bar). Confirm that differentials between set point and hot and cold inlet supplies to DRV are 10 F (5.6 C). See DRV IOM. Page 12 of 18

Problem Probable Cause Correction Water leaking from plate and frame module N/A 1. Check plate pack tightening dimension (see heat exchanger module manufacturer's IOM). 2. Note serial number on PHE and call Armstrong. Page 13 of 18

Parts Lists A E F J Model PHE (A) Base (B) DF15W D44041 D46281 DF15WE D44042 D46281 D M O G I DF15W DW D44044 D46281 DF15WE DW D44045 D46281 DF35W D44047 D46282 L DF35WE D44048 D46283 H P DF35W DW D44050 D46282 DF35WE DW D44051 D46283 N DF65W D44053 D46285 DF65WE D44054 D46284 C DF65W DW D44056 D46285 O F DF65WE DW D44057 D46286 F H B M K Note: All dimensions shown as in. (mm). Ref. Description DF15 (all) DF35 (all) DF65 (all) No. Size No. Size No. Size C DRV* D41578 1 ½ (38) D41578 1 ½ (38) D40864 2 (51) D Safety Shut-Off Valve D40163 1 (25) D40164 1 ½ (38) D40165 2 (51) E* Pressure Relief Valve D32789 ¼ (6) D32789 ¼ (6) D32789 ¼ (6) F Inlet/Mixed Isolation Valve D30040 1 (25) (ball) D30019 1 ½ (38) (ball) D30037 2 (51) (ball) G Return Isolation Valve D30040 1 (25) (ball) D30040 1 (25) (ball) D30019 1 ½ (38) (ball) H Inlet/Hot Y-Strainer D30039 1 (25) D38922 1 ½ (38) D30036 2 (51) I Return Y-Strainer D30039 1 (25) D30039 1 (25) D38922 1 ½ (38) J Mixed Check Valve D30028 1 (25) (swing) D39479 1 ½ (38) (swing) D30024 2 (51) (swing) K Inlet Check Valve D30022 1 (25) (spring) D38888 1 ½ (38) (spring) D30026 2 (51) (spring) L Return Check Valve D30022 1 (25) (spring) D30022 1 (25) (spring) D38888 1 ½ (38) (spring) M Inlet/Mixed Thermometer D8931 ½ (13) D8969 ½ (13) D8969 ½ (13) N Return Thermometer D8931 ½ (13) D8931 ½ (13) D8969 ½ (13) O Inlet/Mixed Thermowell D22048 ¾ (19) D40277 ¾ (19) D40277 ¾ (19) P Return Thermowell D22048 ¾ (19) D22048 ¾ (19) D40277 ¾ (19) * See DRV IOM for parts * Oulet for Pressure Relief Valve should be piped to floor/drain to make sure invididual does not get sprayed with hot water. Standard cracking pressure is 165 psi. Page 14 of 18

E Model PHE (A) Base (B) DF90W D44059 D46287 A DF90WE D44060 D46287 F DF90W DW D44062 D46287 DF90WE DW D44063 D46287 DF120W D44065 D46287 H D G DF120WE D44066 D46288 DF120W DW D44068 D46288 BRAINSCAN OPTION ONLY J N I K DF120DW DW D44069 D46288 O M L F H J C N B L Ref. Description DF90 and 120 (all) No. Size C DRV* D41579 3 (76) D Safety Shut-Off Valve D40168 3 (76) flg E Pressure Relief Valve D32789 ¼ (6) F Inlet/Mixed Isolation Valve D8743 3 (76) flg G Return Isolation Valve D30037 2 (51) (ball) H Inlet/Hot Y-Strainer D39199 3 (76) flg (epoxy) I Return Y-Strainer D30036 2 (51) J Inlet/Hot Check Valve D8745 3 (76) flg (wafer) K Return Check Valve D30026 2 (51) (spring) L Inlet/Mixed Thermometer D8746 ½ (13) M Return Thermometer D8969 ½ (13) N Inlet/Mixed Thermowell D36848 ¾ (19) O Return Thermowell D40277 ¾ (19) *See DRV80 IOM for parts Note: All dimensions shown as in. (mm). Page 15 of 18

Limited Warranty and Remedy Armstrong Hot Water, Inc. ("Armstrong") warrants to the original user of those products supplied by it and used in the service and in the manner for which they are intended, that such products shall be free from defects in material and workmanship for a period of two (2) years from the date of installation, but not longer than 27 months from the date of shipment from the factory [unless a special warranty period applies, as listed below]. This warranty does not extend to any product that has been subject to misuse, neglect, or alteration after shipment from the Armstrong factory. Except as may be expressly provided in a written agreement between Armstrong and the user, which is signed by both parties, Armstrong DOES NOT MAKE ANY OTHER REPRESENTATIONS OR WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. The sole and exclusive remedy with respect to the above limited warranty or with respect to any other claim relating to the products or to defects or any condition or use of the products supplied by Armstrong, however caused, and whether such claim is based upon warranty, contract, negligence, strict liability, or any other basis or theory, is limited to Armstrong's repair or replacement of the part or product, excluding any labor or any other cost to remove or install said part or product, or, at Armstrong's option, to repayment of the purchase price. As a condition of enforcing any rights or remedies relating to Armstrong products, notice of any warranty or other claim relating to the products must be given in writing to Armstrong: (i) within 30 days of last day of the applicable warranty period, or (ii) within 30 days of the date of the manifestation of the condition or occurrence giving rise to the claim, whichever is earlier. IN NO EVENT SHALL ARMSTRONG BE LIABLE FOR SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING, BUT NOT LIMITED TO, LOSS OF USE OR PROFITS OR INTERRUPTION OF BUSINESS. The Limited Warranty and Remedy terms herein apply notwithstanding any contrary terms in any purchase order or form submitted or issued by any user, purchaser, or third party and all such contrary terms shall be deemed rejected by Armstrong. DRV warranty: products shall be free from defect in material and workmanship for a period of five (5) years from the date of shipment from the factory. This warranty does not extend to any product that has been subject to misuse, neglect, or alteration after shipment from the Armstrong factory. Except as may be expressly provided in a written agreement between Armstrong and the user, which is signed by both parties, Armstrong DOES NOT MAKE ANY OTHER REPRESENTATIONS OR WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. The sole and exclusive remedy with respect to the above limited warranty or with respect to any other claim relating to the products or to defects or any other condition or use of the products supplied by Armstrong, however caused, and whether such claim is based upon warranty, contract, negligence, strict liability, or any other basis or theory, is limited to Armstrong s repair or replacement of the part or product, excluding any labor or any cost to remove or install said part or product, or, at Armstrong s option, to repayment of the purchase price. As a condition of enforcing any rights or remedies relating to Armstrong products, notice of any warranty or other claim relating to the products must be given in writing to Armstrong: (i) within 30 days of last day of the appliance warranty period, or (ii) within 30 days of the date of the manifestation of the condition or occurrence giving rise to the claim, whichever is earlier. IN NO EVENT SHALL ARMSTRONG BE LIABLE FOR SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING, BUT NOT LIMITED TO, LOSS OF USE OR PROFITS OR INTERRUPTION OF BUSINESS. The Limited Warranty and Remedy terms herein apply notwithstanding any contrary terms in any purchase order or form submitted or issued by any user, purchaser, or third party and all such contrary terms shall be deemed rejected by Armstrong. Page 16 of 18

Notes Page 17 of 18