OFS 400A FIBER OPTIC INTERCONNECT Instruction Sheet UNIT (FOIU) Comcode INSTALLATION

Similar documents
OFS LSS1U-864/ Instruction Sheet Fiber Optic Comcode: Splice Shelf Installation

LSS1U-144/7 FIBER OPTIC SPLICE SHELF INSTALLATION GENERAL CUSTOMER SERVICES REFERENCES TOOLS REQUIRED

OFS Fitel LST1U-072/7 and LSTLW Instruction Sheet (LaserWave) Fiber Optic Comcode: Termination Shelf Installation

INSTALLATION INSTRUCTIONS

This instruction sheet covers the installation of the Fiber Optic 200A Interconnection Unit, which includes LaserWave Applications.

Fiber Splice Panel Rack Mount User Manual

Opticom Rack Mount Fiber Enclosures

Environmental Distribution Center (EDC-06P-NH)

8400 Series Fiber Distribution System

OFE-CLS-Type Outside Plant (OSP) Fiber Optic Closures Instructions

Pretium Wall-Mountable Housing (PWH-02P/-04P/- 06P/-12P and FZB-02P-JB)

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Fiber optic splice closure

3000SC Fiber Optic Splice Closure

FOSC-100 B/H FOSC-100 B2/H

Splice Trays. features and benefits. specifications. A LANscape. Solutions Product. Splice Capacity

FL2000 Termination/Splice Panels User Manual

FIBER CONNECTOR SAFETY WARNINGS

FOSC-400D5 INSTALLATION INSTRUCTION. Fibre Optic Splice Closure with integrated organiser system

SYSTIMAX G2 4U Fixed Rear Access Combination Shelf Instructions

Fiber Connector Shelf (CCS)

FOSC-400A4 INSTALLATION INSTRUCTION

Universal Splice Tray Installation Instructions

COYOTE 28" GLC (Ground Level Closure) Complete Assembly Installation

COYOTE 9.5" x 19" (292 mm x 509 mm) Cross-Connect Dome Closure

MARCH COYOTE 9.5 x 19 (292 mm x 509 mm) Terminal Dome Closure Kits

Instructions for Use - Opt-X 1000i Enclosure

Mini-OTE 400. Mini-OTE 400. Content 1 General 1.1 General product information 1.2 Cable types 1.3 Symbols in this guide.

PanView iq (PViQ) Fiber Tray

COYOTE LCC (Low Count Closure)

FIST-GSS2 FIST-GSS3. Fist Generic Splicing Shelf. Contents. 1 Introduction. 2 General. 3 Installation of the shelf. 5 Termination of the pigtails

Driver/Left Rear Inner Support Bracket. (2) Front Bracket Arms

Instructions for Use - Opt-X Ultra Enclosure Directives Enceintes Opt-X Ultra MC Instrucciones de Uso Caja Opt-X Ultra MR

COYOTE STP (Service Termination Point)

Be sure to read and completely understand this procedure before applying product. Be sure to select the proper PREFORMED product before application.

COYOTE CLOSURE ADOBE SERIES FOR UNDERGROUND, AERIAL, AND BURIED SPLICES 6.0" x 22" 8.5" x 22" (152.4 mm x mm mm x 558.

INSTRUCTIONS INSTRUCCIONES CONSIGNES

INSTALLATION INSTRUCTIONS

CS Fiber Optic Splice Case. Instruction

12-Inch Hybrid Fiber Access Terminal Installation Instructions

FIST-GMS2. FIST Generic Mixed Shelf MK2. Contents. 1 Introduction. 5 Termination of the pigtails. 2 General. 6 Splicing + fiber storage

Multilink s Family of Wall Mount Enclosures

FIST-GSS2. Fist Generic Splicing Shelf MK2. Contents. 1 Introduction. 2 General. 3 Installation of the shelf. 5 Termination of the pigtails

COYOTE STP (Service Termination Point)

INSTALLATION INSTRUCTIONS PART # 9B048803SS/9B048803A SIDE BAR FOR FORD ESCAPE 2013

IBER DISTRIBUTION FRAME (FDF) FOR EXCHANGE SIZE 900MM x 2200MM x 300 MM

JANUARY 2015 NOMENCLATURE. TOOLS REQUIRED 3/8" & 7/16" Can wrench or socket 1/4 Nut driver or screwdriver Snips Fiber optic cable opening tools

COYOTE Dome Closure 6.5" x 22" Kits. COYOTE Dome Closure 6.5" x 22" for Buffer Tube Applications. Includes: (2) Grommets, (1) Buffer

3M Fiber Dome Closure FDC 10

COYOTE Terminal Dome Closure 6.5" x 22"

COYOTE 9.5" x 19" (292 mm x 509 mm) Dome Closure

INSTALLATION INSTRUCTIONS

CONTENTS. This Product is Certified by CANADIAN STANDARDS ASSOCIATION and Bears the Mark:

SYSTIMAX 360 ipatch G2 Fiber Ultra High Density (UHD) Shelf, LC InstaPATCH Distribution Panel Instructions

PLEASE READ THIS INSTRUCTIONS CAREFULLY, BEFORE YOU START INSTALLATION

INSTRUCTIONS INSTRUCCIONES CONSIGNES

FIST-FPS. Front Patching Shelf. Contents. 1 Introduction. 3 Installation of the shelf. 2 General. 1 Introduction

Assembly Instructions

Fiber Optic Splice Module

SYSTIMAX SMB-4-3/4, SMB-8-1/2 Shelf-Mounted Cable Bracket Kits and 1000G2-XCPB Expanded Cable Protector Kit

INSTALLATION INSTRUCTIONS

HP BladeSystem c7000 Carrier-Grade Options Installation Guide

COYOTE Dome Cross-Connect Closure 6-1/2" x 22"

FIST-GPS2-J. 19 2HU Splicing, Patching and Storage shelf. 5 Fiber routing. 1 Introduction. Contents. 2 General. 6 Storage. 3 Installation of the shelf

COYOTE Dome Closure 9.5" x 28" with Transition Tray for High Density Splice Applications

Swing-Out Style Fiber Distribution Units

LPC Series Fiber Panel 12/24 Fiber Rack-Mount Enclosure Installation Instructions

SPACESAVER EC-300 A ELECTRICS

Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF and ZDF

INSTALLATION INSTRUCTIONS

Section 1 COYOTE Closure Series

SJOF-BS604A Fiber Optic Splice Closure User Manual Rev.0

Panduit PreConfigured ZDF48-RA Industrial Distribution Frame (IDF) Installation Instructions

Adjustable Light Kits E-Z-Go TXT All Models Installation Instructions

Patching & Splicing Shelf. 4.2 Side cable termination directly on the shelf using cable termination plate. IFC cable/break-out cable

INSTALLATION INSTRUCTIONS

WAVETRAX USER MANUAL

SYSTIMAX 360 ipatch G2 High Density Sliding Fiber Shelf Instructions

and Original Series Pickup Lift Mounting Instructions Fullsize Chevy & GMC Trucks: 1500 & 2500 LD HD & 3500HD BOLT-ON GUSSET

OPTICAL FIBER CLOSURE

A. Preparing the charge harness. Start by removing the plastic covers by the battery terminal.

JEEVES. JEEVES Installation Manual. Installation Manual The Easiest Do-It-Yourself Dumbwaiter on the Market

SYSTIMAX 360 ipatch G2 Fiber Ultra High Density (UHD) Shelf, MPO Distribution Panel Instructions

Features: Use the selection chart below to choose the Splice Case and splice tray organizer which meet the requirements for your application.

LEXUS GS 350/450h ILLUMINATED DOOR SILLS Preparation

Backside License Plate Mount for Jeep JK Wrangler

NOVO LIGHTED MIRROR. Installation Instructions

Replacing the T320 Cooling System Components. Replacing a T320 Fan Tray. Removing a T320 Front Fan Tray

1-3/8 Designer Metals Telescoping Traversing Rod Installation Instructions

MY F150 SuperCab 1. Tools Required. Page 1 of 12 9L3J-19A014-BA Copyright Ford 2013 FoMoCo

Installation Instructions Supertop for Truck

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

INSTALLATION INSTRUCTIONS FOR DSP9600/9100 WHEEL BALANCER

LEXUS GX TOWING HITCH Preparation

INSTALLATION INSTRUCTIONS

Section 3 FIBERLIGN Closure Series

SPC-P Smart Power Connection with Temperature Monitoring Transmitter Pipe Mounted Installation Instructions

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Transcription:

OFS 400A FIBER OPTIC INTERCONNECT 636-299-109-01 Instruction Sheet UNIT (FOIU) Comcode 846 586 212 INSTALLATION This instruction sheet covers the 400A1 (106266901) and 400A2 (106414170) Fiber Optic Interconnect Unit (FOIU). The 400A2 unit comes equipped with two locks. The 400A1 unit does not come equipped with locks but is provided with knockouts so that locks can be installed. It is recommended that up to five 400A units be mounted in one column (Figure 1). The top of the first unit should be no more than 68 inches (1727 mm) above the floor. Space allocated for the installation of the 400A units should be 55 inches (1397 mm) high by as wide as required. 17" (432 mm) 6th 2nd 7th Top of column from floor 68" (1727 mm) 3rd Space allocated 8th 55" (1397 mm) 4th 9th 5th 10th 34" (864 mm) Bottom of column from floor 13" (330 mm) Floor Figure 1 Recommended Mounting Configuration Issue 7 April 2002 2002 Fitel USA Corp Page 1 of 16 All rights Reserved Printed in USA

Instruction Sheet STEP 1 INSTALL 400A Units The mounting holes in the 400A unit are designed for easy installation with the top two mounting holes being keyholes. This allows the location of mounting screws to be marked, screws to be installed, and the 400A unit to be hung on the screws to be tightened down. 1. Position the 400A unit in upper left corner space allocated for installation. 2. Mark location of top mounting screws (Figure 2). 3. Remove 400A unit from wall. 4. Install two No. 8 wood screws or similar hardware for type of wall on which unit is being mounted. Note: Install the screws only halfway. 5. Hang the unit on the two mounting screws. 6. Install the two bottom mounting screws. 7. Tighten all four screws. 8. Repeat Steps 1 through 7 for other units to be mounted. Top mounting holes Keyholes Screws Bottom mounting holes Figure 2 Mounting Holes Page 2 of 16 Issue 7 April 2002

STEP 2 INSTALL 400A PARTS INSIDE OF UNIT Install the following parts inside the 400A unit, before routing the cable inside the box. Items to be install are as follows: Identification and notice decals Cable strain relief grommets (two provided) 12A1 or 12A2 cable clamps (must be ordered separately and installed two at a time) 1000-type panels (ST, SC, FC/DF, LC etc.) (must be ordered separately) Couplers or buildouts (must be ordered separately). 1. Install the provided identification and notice decals (Figure 3). 2. Remove the appropriate number of knockouts for cable entry. Note: For cross-connect applications, cables are routed into the 400A unit on the left side. For interconnect applications, cables are routed on either side of the unit. 3. Install the cable strain relief grommets in the openings made by removing the knockouts (Figure 4). Note: Grommets fit smaller knockouts only. 4. Remove the appropriate cable clamp bracket from the 400A unit. 5. Install two 12A1 or 12A2 cable clamps (Figure 6). Note: The 12A-type cable clamps should be ordered and installed in pairs. See instruction sheet for applicable cable clamp. 6. Reinstall the cable clamp bracket with two 12A-type cable clamps (Figure 5). 7. Install couplers in 1000-type panels (Figure 6). 8. Mount individual identification decals on the panels and write the identification number of each coupler on the decals. 9. When the couplers have been installed, position and secure the panels onto the 400A bulk-head unit (Figure 7). Note: The bulk-head unit partially slides in and out of the 400A unit allowing easy access to the couplers (Figure 5). The bulk-head will not slide out of the track completely. Issue 7 April 2002 Page 3 of 16

Instruction Sheet STEP 2 INSTALL 400A PARTS INSIDE OF UNIT (Continued) Left door Right door Identification label Notice label Identification label Notice label Figure 3 Decal Installation Top cap Top of 400A unit Bottom nut Figure 4 Cable Strain Relief Grommet Page 4 of 16 Issue 7 April 2002

STEP 2 INSTALL 400A PARTS INSIDE OF UNIT (Continued) Cable strain relief grommets Couplers Black rubber grommets 2" (51 mm) fiber rings Cable tie-down brackets 12A-type cable clamps Fiber rings Track for bulk-head unit Bulk-head unit Black rubber grommets Figure 5 Parts Locations Fastener 1000-type panel Couplers Figure 6 Coupler Installation (ST-Type Shown) Issue 7 April 2002 Page 5 of 16

Instruction Sheet STEP 2 INSTALL 400A PARTS INSIDE OF UNIT (Continued) Couplers 1000-type panel Fasteners Bulk-head unit Figure 7 Bulk-Head Unit Page 6 of 16 Issue 7 April 2002

STEP 3 ROUTE AND PREPARE CABLE INSIDE OF UNIT Whether a cable is routed from the top or bottom of the 400A unit, a strain relief grommet should be installed in the first unit that the cable enters. The cable can then be clamped inside the individual unit. If a cable is to be routed from the first unit to a consecutive unit, the proper knockouts between the units must be removed. 1. Route cable through the cable strain relief grommet into the 400A unit (Figure 8). 2. Measure 60 inches (1524 mm) from the end of the cable back to the 12A-type cable clamp. 3. Mark and remove the sheath from the cable. 4. Attach the cable to a 12A-type cable clamp. 5. Tighten the top cap of the cable strain relief grommet. 6. Complete fiber termination by routing the fibers through protective tubing and installing the appropriate connectors on the individual fibers. 7. Repeat Steps 1 through 6 for all cables routed into the 400A unit. Top cap of cable strain relief grommet Cable 12A-type cable clamp 60" (1524 mm) 60" (1524 mm) R Lightpack Core Tube Fiber Unit tube splitter Unit tube Heat shrink Buffer tubes Connector Core tube 32" (813 mm) 27" (686 mm) Figure 8 Cable Preparation Issue 7 April 2002 Page 7 of 16

Instruction Sheet STEP 4 TERMINATE FIBERS AND STORE FIBER SLACK After cable has been routed inside the 400A unit and connectors installed, the fibers may be terminated to the bulk-head unit. 1. Pull bulk-head unit out until it stops (Figure 9). 2. Terminate connectors to couplers on bulk-head unit. 3. Starting from the connector end of the fiber, store fiber slack inside the fiber rings. 4. When all fiber has been stored, slide bulk-head unit to the back of the 400A unit. 5. Close the 400A unit doors by first closing the left door and then closing the right door. 6. Turn plastic tabs to secure doors. Cable Fiber rings Fiber slack Connectors and couplers 12A-type cable clamp Figure 9 Cable Slack Storage Page 8 of 16 Issue 7 April 2002

STEP 5 TERMINATE AND ROUTE JUMPERS The jumpers are located on the right side of the 400A unit and can be routed to the next unit through the black grommets. 1. Pull bulk-head unit out until it stops (Figure 10). 2. Terminate jumpers to couplers on bulk-head unit. 3. Slide bulk-head unit to the back of the 400A unit. 4. Prepare black grommets by using a utility knife to cut grommets along dotted lines. 5. Route jumpers through black grommets and terminate in the desired unit. 6. Store the jumper slack in the fiber rings. 7. Close the 400A unit doors by first closing the left door and then closing the right door. 8. Turn plastic tabs to secure doors. Connectors 2 and couplers Fiber rings Jumper slack 6 1 3 Bulk-head unit 4 Cut along dashed line Black 5 rubber grommets Figure 10 Jumper Slack Storage Issue 7 April 2002 Page 9 of 16

Instruction Sheet STEP 6 INTERCONNECTION APPLICATION The 400A unit will accommodate interconnection of OSP cables to building cables. 1. Remove knockout for cable entry from the right side of the 400A unit (Figure 11). 2. Install cable strain relief grommet in the knockout opening. 3. Route the building cable through the grommet. 4. Tie wrap the cable to the top tie down bracket and tighten top cap of cable strain relief grommet. 5. Measure 40 inches (1016 mm) from the end of the cable back to the tie down bracket. 6. Remove 38 inches (965 mm) of jacket from the cable. 7. Install a connector on each fiber and terminate the connectors to the couplers on the bulk-head unit. 8. Starting from the connector end of the fiber, store fiber slack inside the fiber rings. 9. When all fiber has been stored, close the 400A unit doors by first closing the left door and then closing the right door. 10. Turn plastic tabs to secure doors. OSP cable Top cap of cable strain relief grommet Building cable 12A-type cable clamp Cable tie 38" (965 mm) 60" (1524 mm) Fibers Fibers Figure 11 Interconnection Cabling Page 10 of 16 Issue 7 April 2002

D-181706 FIBER OPTIC MECHANICAL/ROTARY SPLICE ADAPTER KIT AND D-181707 FIBER OPTIC FUSION SPLICE ADAPTER KIT FOR 400A UNIT INSTALLATION STEP 1 VERIFY APPLICABLE KIT MATERIALS Holder with four mounting screws Splice tray Adapter tray White PVC tubing Mechanical organizer and cover (D-181706 kit) Fusion organizer and cover (D-181707 kit) STEP 2 REMOVE METAL BRACKETS AND PLASTIC RINGS Note: If the 400A unit does not contain the six plastic split rings or metal bracket, go to Step 3. 1. Remove and discard the six plastic split rings. 2. Remove and discard the two metal brackets. Left door Metal 2 bracket Plastic split rings 1 Partial left view of 400A unit 1 1/2 Metal bracket 2 Plastic split rings 1 Issue 7 April 2002 Page 11 of 16

Instruction Sheet STEP 3 INSTALL HOLDER 1. Locate the holder and four mounting screws. 2. Position the holder in the 400A unit and secure with the four mounting screws. Holder 1 Mounting screws 2 Partial left view of 400A unit 1 1/2 Mounting screws 2 STEP 4 INSTALL SPLICE TRAY 1. Locate the splice tray and note the mounting tabs on upper and lower left edge of the tray. Note: The upper mounting tab is spring-loaded. 2. Insert the lower tab of the tray into the lowest hole of the holder s bottom mounting flange. 3. Press down on the tray s upper spring-loaded tab and insert it into the lowest hole on the holder s top mounting flange. Holder Splice tray Lowest hole in the holder's top mounting flange Tray's upper spring-loaded mounting tab Tray's lower mounting tab Lowest hole in the holder's bottom mounting flange Page 12 of 16 Issue 7 April 2002

STEP 5 PREPARE AND INSTALL CABLE 1. Prepare the end of the lightguide cable. Note: Allow for 60 inches (1524 mm) of cable fiber slack and leave ½ inch (13 mm) of inner tubing from the cable sheath. 2. Install the lightguide cable in the 12A-type clamp and ground the cable, if required. 3. Cut a length of the white PVC tubing long enough to reach from the cable end to 1 inch (25 mm) inside the splice tray s entry slot. 4. Insert a maximum of 12 fibers into the cut length of PVC tubing and slide the tubing up over the fibers to the butt of the cable. 5. Place the PVC tubing into the splice tray s entry slot. Note: The tubing must extend 1 inch (25 mm) into the entry slot. 6. Install splice organizer onto the splice tray by inserting the organizer under the tray s two outer mounting tabs, then gently pressing the opposite side of the organizer under the tray s inner mounting tab. 2 Ground wire Lightguide cable 1 Inner 6 mounting tab 2 12A-type clamp Outer 6 mounting tabs 4 Lightguide cable butt 3 White PVC tubing Splice organizer 6 5 Fiber entry slot Issue 7 April 2002 Page 13 of 16

Instruction Sheet STEP 6 STORE FIBER SLACK 1. Splice the fiber pigtails and cable fibers. 2. Store the completed splices in the splice organizer and install the organizer cover. 3. Starting at the PVC end of the cable fiber, wrap the fiber around the lower storage cylinder of the splice tray in a counterclockwise direction. 4. Starting at the splice end of the pigtails, store two slack loops around the upper storage cylinder of the splice tray in a counterclockwise direction. 5. If a second splice tray is to be added to the 400A unit, repeat Steps 4 through 6. 1 4 Fiber pigtails Upper storage cylinder 4 2 Splice organizer Cable fibers 1 3 Lower storage cylinder 3 Page 14 of 16 Issue 7 April 2002

STEP 7 INSTALL ADAPTER TRAY 1. Locate the adapter tray and note the mounting tabs on upper and lower left edge of the tray. Note: The upper mounting tab is spring-loaded. 2. Route all pigtail fibers through the adapter tray s left opening. 3. Insert the lower tab of the adapter tray into the lowest hole of the holder s bottom mounting flange. 4. Press down on the tray s upper spring-loaded tab and insert it into the lowest hole on the holder s top mounting flange. Adapter tray 1 Lowest hole in the holder's top mounting flange 4 Tray's upper spring-loaded mounting tab Left 2 opening Note: Organizer cover is shown removed for clarity Lowest hole in the holder's bottom mounting flange Tray's lower mounting tab 3 Issue 7 April 2002 Page 15 of 16

Instruction Sheet STEP 8 STORE PIGTAIL FIBER SLACK 1. Store the pigtail fiber slack around the adapter tray s storage cylinder in a counterclockwise direction. Adapter tray 1 storage cylinder Adapter tray Pigtails 1 Note: Organizer cover is shown removed for clarity Pigtail connector plugs STEP 9 INSTALL CONNECTOR PANELS AND CONNECT PIGTAIL CONNECTOR PLUGS 1. Install connectors on the connector panel in only the first three positions. 2. Install 1000-type connector panels into 400A unit. Note: Make sure the connectors are toward the front of the 400A unit. 3. Connect the pigtail connector plugs to the connector panels. 1000-type connector panel 2 Connectors 1 2 Toward front of 400A unit Pigtail connector plug 3 Note: Organizer cover is shown removed for clarity Page 16 of 16 Issue 7 April 2002