VERTICAL FAN COILS The FCVC is designed for concealed, wall mounted installations with flexible heating/ cooling loads and minimal duct requirements. With a variety of options, such as fiber free insulation, these units are durable, easily accessible, energy efficient, and quiet. Designed with the most highly demanded features & performance characteristics requested by engineers Optional PSC motor speed controller Heating and cooling coils, 1 to 4 rows in 2 and 4 pipe configurations Removable fan and motor deck for easy servicing Ideal for hotels, motels, condominiums and commercial applications www.priceindustries.com for additional product information, including product videos and brochures.
Features Model FCVC 1 duct collar allows quick field connection of ductwork Model Concealed 1 to 4 rows of heating and cooling coils in 2 and 4 pipe configurations up to 5 rows total Insulated with ½ thick fiberglass insulation (std). Foil faced fiberglass and foam insulation available as options FCVC Factory assembled, vertical blow-through fan coils designed for concealed ducted installations furred into walls. Suitable for projects such as hotels, condominiums, nursing homes and general commercial applications. Concealed (FCVC) 20 gauge galvanized steel casing Easily removable 1 thick MERV 3 throw away filter FAN COILS & BER COILS PERFORMANCE Standard Features: AHRI 440 certified and labelled. ETL-Listed. Constructed in compliance with ANSI/UL Standard 1995. Constructed from 20 gauge galvanized steel. Insulated with 1 / 2 in. thick, minimum 1 1 / 2 lb density fiberglass insulation, which meets NFPA 90A and UL 181. 1 in. discharge flange for duct connection. Water coils with copper tubes and aluminum fins certified in accordance with the current edition of AHRI Standard 410. Coil manual air vent included. Three speed permanent split capacitor (PSC) motor. 115, 208/240, 277V motors available. Double Width double Inlet (DWDI) direct driven blowers. Single point power connection. Single wall galvanized steel drain pan externally insulated with foam. 1 in. thick MERV 3 throw-away filter. Optional Features 1 through 4 row coils available for 2 pipe systems. 3 and 4 rows cooling coils with 1 or 2 row heating coils for 4 pipe system applications (reheat available, 5 rows max). LH or RH entry pipe connections. Coil circuiting options to optimize performance. Quick connect motor wire harness. Factory mounted disconnect switch and motor fusing. Energy efficient ECMs with 3 speed or full modulating control. Drain pan options: Single wall drain pan manufactured in 20 gauge 304 Stainless Steel, externally insulated Drain pan safety overflow connection (secondary drain). Insulation options: 5 / 8 in. thick Foil Faced fiberglass FB 1 / 2 in. thick Fiber Free Foam, FF50 3 speed fan relay board Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. F1-23
Dimensional Data Concealed (FCVC) Water Coil Connections & Air Vents FAN COILS & BER COILS Auxiliary Drain Pa w/ 3/4" (19) NPT Conn. Throwaway Filter B (Mtg. Holes) w/ 3 /4" (19) NPT Conn. 7 (178) 1 (25) D 25.8 (655) 24.8 (630) 18.1 (460) Typ. Control Enclosure (Optional) 5.5 (139) Return Air Opening 10 (255) 4.7 (120) C A 5.3 (135) LH configuration shown. Handing determined by looking at inlet Size Nom. [L/S] A in. [mm] B in. [mm] C in. [mm] D in. [mm] # of Blowers Motors [HP] 02 200 [94] 24 [610] 22.5 [572] 21 [534] 18 [457] 1 1/30 1/8 03 300 [142] 32 [813] 30.5 [775] 29 [737] 26 [660] 1 1/30 1/8 04 400 [189] 32 [813] 30.5 [775] 29 [737] 26 [660] 2 1/10 1/8 06 600 [283] 43 [1093] 41.5 [1055] 40 [1016] 37 [940] 2 1/10 1/8 08 800 [378] 48 [1220] 46.5 [1182] 45 [1143] 42 [1067] 2 1/10 1/4 10 1000 [472] 58 [1474] 56.5 [1436] 55 [1397] 52 [1321] 4 1/10 (x2) 1/8 (x2) 12 1200 [566] 68 [1728] 66.5 [1690] 65 [1651] 62 [1575] 4 1/10 (x2) 1/4 (x2) PSC ECM F1-24 All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.
Fan Performance Curves - PSC Option Model FCVC - Size 02 Model FCVC - Size 03 0 50 100 150 200 250 300 350 Model FCVC - Size 03 04 0 50 100 150 200 250 300 350 400 Model FCVC - Size 06 FAN COILS & BER COILS PERFORMANCE 0 100 200 300 400 500 600 0 100 200 300 400 500 600 700 800 1. Fan performance curves are for units with 4 row coils. Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. F1-25
Fan Performance Curves - PSC Option Model FCVC - Size 08 Model FCVC - Size 10 FAN COILS & BER COILS Model FCVC - Size 12 0 100 200 300 400 500 600 700 800 900 0 200 400 600 800 1000 1200 0 200 400 600 800 1000 1200 1400 1. Fan performance curves are for units with 4 row coils. F1-26 All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.
Fan Performance Curves - ECM Option Model FCVC - Size 02 Model FCVC - Size 03 0 50 100 150 200 250 300 Model FCVC - Size 04 Model FCVC - Size 06 0 50 100 150 200 250 300 350 400 FAN COILS & BER COILS PERFORMANCE 0 100 200 300 400 500 600 0 100 200 300 400 500 600 700 1. Fan performance curves are for units with 4 row coils. Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. F1-27
Fan Performance Curves - ECM Option Model FCVC - Size 08 Model FCVC - Size 10 FAN COILS & BER COILS 0 100 200 300 400 500 600 700 800 900 Model FCVC - Size 12 0 200 400 600 800 1000 1200 0 200 400 600 800 1000 1200 1400 1. Fan performance curves are for units with 4 row coils. F1-28 All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.
Non-Ducted Sound Data FCVC Unit Size 02 03 04 06 08 10 12 Fan Speed Sound Power Levels, Lw, db, re 10-12 Watts Octave Band (Hz) 2 3 4 5 6 7 8 High 58 60 58 55 49 43 38 Medium 54 55 54 50 43 36 31 Low 50 50 48 42 35 26 26 High 59 62 59 55 54 48 40 Medium 53 55 52 48 48 35 29 Low 48 48 45 42 40 26 26 High 61 63 60 58 52 45 39 Medium 58 61 58 55 49 40 33 Low 53 55 53 48 40 29 27 High 61 63 61 57 53 46 42 Medium 56 59 57 53 48 41 41 Low 49 52 49 43 37 27 27 High 63 65 62 59 55 51 45 Medium 56 59 56 52 49 40 32 Low 49 51 48 43 38 26 26 High 63 66 64 61 55 48 41 Medium 61 63 61 58 52 44 36 Low 55 58 56 52 45 35 28 High 65 66 64 61 55 48 42 Medium 61 63 61 57 51 43 35 Low 54 56 54 49 41 31 27 FAN COILS & BER COILS PERFORMANCE 1. Sound data obtained in accordance with the latest edition of AHRI standard 350. 2. Sound levels are expressed in decibels, db RE 1 x 10-12 watts. 3. Total sound power level data based on FCVC with 115/1/60 volt motor, 4 row coils, 0.0 in. ESP. AHRI Certified Standard Ratings Unit Type FCVC Unit Size 02 03 Rows Coil FPI Dry Flow () Cooling Capacity QT (Btu/h) QS (Btu/h) Flow (gpm) Water WPD (ft w.g.) Power Input (Watts) 16 260 7000 5000 1.56 1.0 60 320 7300 5600 1.62 0.6 68 04 450 10700 8300 2.35 1.0 132 06 3 610 14100 11200 3.07 1.2 144 12 08 650 19400 13100 4.41 8.7 147 10 900 22500 17700 5.09 2.3 270 12 1060 21200 17500 4.80 1.4 300 02 03 16 270 7500 4800 1.68 1.4 62 300 8500 6300 1.88 0.5 65 04 420 11900 8800 2.63 0.9 134 06 4 520 17700 13400 3.88 2.0 136 12 08 620 23700 15700 5.24 5.7 137 10 860 26800 19700 5.97 3.5 250 12 1030 29200 20500 6.46 2.7 300 1. Ratings based on 80 F DB and 67 F WB EAT, 45 F EWT, 10 F temperature rise, high fan speed. Motor type is PSC and motor voltage is 115/1/60. Air flow under dry coil conditions with external static pressure. 2. For all application ratings, please contact your local Price representative Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. F1-29