CALEFFI. Ball shut-off valve fitted for integrated flow rate measuring sensor. 111 series 01234/13 GB. (kpa) (mm w.g.) G (m 3 /h)

Similar documents
CALEFFI. Direct supply unit for heating systems. 165 series 01237/17 GB. replaces dp 01237/15 GB. Function

CALEFFI. Pre-assembled distribution manifolds for. heating and air-conditioning systems. 663 series 01065/18 GB. replaces dp 01065/06 GB.

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/14 GB

CALEFFI. Modulating temperature regulating unit with distribution kit for primary circuit. 171 series 01153/15 GB. replaces 01153/07 GB

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/18 GB. replaces 01260/14 GB

CALEFFI. Motorised temperature regulating unit for heating and air conditioning systems WYP UPM series 01254/17 GB

ACCREDITED. brass EN CW617N brass EN CW614N brass EN CW614N, chrome plated PTFE PSU EPDM

CALEFFI. Composite manifolds specifically designed for radiant panel systems. 670 series 01126/18 GB. replaces dp 01126/11 GB.

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Product range. Technical specifications. Characteristic components

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Important Product range Technical specifications

CALEFFI. Pre-assembled distribution manifold for radiant panel systems S1 series 01144/11 GB. Replaces 01144/07 GB.

CALEFFI. Manifolds in composite specifically designed for radiant panel systems. 670 series 01126/05 GB. Function

COMPONENTS FOR SOLAR THERMAL SYSTEMS

COMPONENTS FOR SOLAR THERMAL SYSTEMS

CALEFFI. Pre-assembled distribution manifolds for radiant panel systems. series 663 & /05 NA. Function

CALEFFI. Pressure independent control valve (PICV) 145 series 01262/14 GB B 51

CALEFFI. Motorised ball zone valves with 3-contact control BY series 01131/18 GB. replaces 01131/11 GB

Pre-assembled distribution manifolds for radiant panel systems

CALEFFI. Solar pump stations 01166/14 NA. 278 and 279 series 01264/16 NA

CALEFFI. Hydraulic separator-manifold SEPCOLL. 559 series 01084/16 GB. replaces dp 01084/13 GB

Safety cap. Measuring probe. Seal. Operating principle. Advantages of balanced circuits. Balanced circuits have the following principal benefits:

548 hydraulic separator

THERMOSETTER Recirculation thermal balancing valve

CALEFFI. Motorised ball valve for central heating systems. 638 series 01196/18 GB. replaces dp 01196/12 GB

FLOW RATE STATIC BALANCING Valves for radiators

CALEFFI. QuickSetter Balancing Valve with flow meter. Installation Tip

Positive displacement batch controller

CALEFFI. HydroMixer motorized temperature mixing unit. 167 series 01239/13 NA. Function

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Operating principle Application diagram. Regulator-actuator Wiring diagrams

CT3202.0_01 EN February 2018

Connection and regulation kit for HVAC terminal units

Pressure Independent Control Valve

Portable pressure calibrator, Wally Box III Model CPH7600

TECHNICAL CATALOGUE BALL VALVES: PARIS

LAUDA Integral. Process thermostats for professional external thermostating across a wide temperature range from -90 up to 320 C

l The Battery Tester is designed for measuring the l AC four-terminal method to measure the internal

Multivariable Vortex Flow Meter

Vortex Flow Meter Model DVH

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions

DKD/CP DN PVC-U. Direct action pneumatically actuated 2-way diaphragm valve

Armstrong In-Line and Insertion Vortex Flow Meters

CALEFFI. FLOWCAL Automatic flow balancing valve with polymer cartridge. 121 series 01141/11 NA. Function

TECHNICAL CATALOGUE GAS BALL VALVES: BERLIN

User manual MTS-32. QUI-1013 Version 1.5 January

Model 322 Automated Thermocouple Calibrator Operating Instructions. Product Description. Practical Instrument Electronics

Multivariable Vortex Flow Meter

Vortex Flowmeter Model DVE

CALEFFI. Mixing valves and actuators series 01169/17 GB. replaces dp 01169/09. Function

Technical Datasheet. HM U Series. Turbine Flow Meters. for lubricating liquids

Art.918C Pre-assembled manifold with flow meters, air

MD x230V. Grundfos Pump GRUNDFOS DATA BOOKLET

Paddle-wheel flow controller for On/Off control

VORTEX FLOW METTER DVH. Despriction. Advantages of the DVH Vortex Flow Meter

DLRO 10 and DLRO 10X. Digital Microhmmeter. DLRO 10 and DLRO 10X Digital Microhmmeter. NEW interchangeable test lead terminations

TECHNICAL CATALOGUE DISTRIBUTION MANIFOLDS

DVH. Vortex Flowmeter. Measuring range: Nm³/h. Accuracy: ± 0,7% of reading (liquids) ± 1% of reading (gases and steam) p max

Productinformatie BAFA.NL BAFA.NL A.U.K. MÜLLER GMBH & CO. KG

F-2600 SERIES INLINE VORTEX FLOW METER

DM-TR. series 10 RADIAL DRIVEN TOOL SYSTEM WITH DIRECT MOTOR TURRETS (PATENTED) TECHNICAL INFORMATION I.T ISSUED 09-11

TECHNICAL CATALOGUE BALL VALVES: VIENNA

Preassembled manifolds with flow meter, series CPRFL

F-2500 SERIES VORTEX METER

TECHNICAL CATALOGUE BALL VALVES: VIENNA

PNEUMATICALLY ACTUATED 2-WAY

Model 422 Automated Thermocouple Calibrator Operating Instructions. Product Description

RUTLAND HRDi CHARGE REGULATOR INSTALLATION AND OPERATION

SINGLE MANIFOLDS TECHNICAL DATA SHEET10/ ENG

Features PNEUMAT IC VALVES. Pneumatic valves Vip - Pneumatic coaxial valve GENERAL FEATURES CONTROL MEDIA OPERATING MEDIA

Installation, commissioning and servicing instructions

Technote. Frese OPTIMA - Pressure independent control & balancing valve. Application. Features. Benefits.

Fluidic Oscillation Compact Heat Meter

Vortex Flowmeters VFM 3100 F-T VFM 3100 W-T

Compact Static Heat Meter of High-Tech Composite

WAY MOTORISED COMPACT ZONE VALVES

Compressed Air-Supply Meter

MVD, MV, MKV, MKL, 2161C, MXV Series

AV 23 Balancing valves SETTER Inline

User Manual Version: 1.4

VersaFlow Vortex 100 Vortex Flow Meter Specifications

MD x400V. Grundfos pump GRUNDFOS DATA BOOKLET

TECHNICAL CATALOGUE BALL VALVES: IDEAL

230V 60Hz LINE FUSES AM CLASS:

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features.

FE DN PVC-U. Butterfly valve

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

485 - NC NO/DA DN

Servotronic Digital 615 Series

STAINLESS STEEL MANIFOLDS FOR RADIANT SYSTEMS CREATION AND DIFFUSION OF THE STAINLESS STEEL MANIFOLD USE DIAGRAMS OF STAINLESS STEEL MANIFOLDS

Ballorex Vario. Description. Versions. Benefits. Applications. Balancing

SonoMeter 30 Energy Meters

display on the wall or in a panel away from the inline sensor SE30 for easy meter reading.

NEW: quality. DuoSolar. DuoSolar. ARMAFLEX DUOSOLAR the easy-to-install pre-insulated tubing system for reducing the energy loss.

Paddle-wheel flow controller for On/Off control

SAI GM Series Piston Hydraulic Motor Crankshaft Design Radial Piston Motors

Table of Contents 2.0 COOLFLEX CLX. 2.0 Table of Contents

Series 8000 Vortex Flow Meter

VPA Series and VAP Actuator

Components for central heating

Sentronic PLUS 614 Series

PIECAL 322 Automated Thermocouple Calibrator Operating Instructions. Product Description

Transcription:

Ball shut-off valve fitted for integrated flow rate measuring sensor series ACCREDITED CALEFFI 034/3 GB ISO 900 FM 654 ISO 900 No. 0003 Function The valve allows to shut the circuit off and is fitted for the installation of the integrated flow rate measuring sensor. In addition to the accuracy and simplicity of regulation, this system features very low head losses and does not obstruct the medium flow. The shut-off valve consists of a ball valve, that can be adjusted using the cap, and a control lever. The cap in composite material was designed to assure a perfect hydraulic seal, thanks to the positioning lugs and seal ring. The series shut-off valve can only be fitted with the 0 series geothermal manifold. PATENT PENDING Product range series Shut-off valve sizes DN 5 (Ø 5), DN 3 (Ø 3), DN 40 (Ø 40) Code 00/3 Insulation for shut-off valves Code 3000 Flow rate electronic measuring station with Vortex effect Code 00 Flow rate integrated measuring sensor with Vortex effect Code 00 series Control lever for shut-off valves Technical specifications Hydraulic characteristics Materials Body: Cap: Seal ring: brass EN 65 CW67N PA66G30 stainless steel (mm w.g.) (kpa) Performance Medium: water, glycol solutions, saline solutions Max. percentage of glycol: 50% Max. working pressure: System test pressure: Working temperature range: Ambient temperature range: 6 bar 0 bar -0 40 C -0 60 C Connections: - to manifold: with captive nut 4 p.,5 TR - to pipe: DN 5, DN 3, DN 40 Vortex-effect sensor Accuracy of flow rate reading: ±0% Dimensions with cap with sensor G (m 3 /h) Insulation Material: closed cell expanded PE-X Thickness: 0 mm Density: - inner part: 30 kg/m 3 - outer part: 80 kg/m 3 Thermal conductivity (DIN 56): - at 0 C: 0,038 W/(m K) - at 40 C: 0,045 W/(m K) Coefficient of resistance to water vapour (DIN 565): > 300 Working temperature range: 0 00 C Reaction to fire (DIN 40): class B Code Mass (kg)

Operation Shut-off The control knob () opens and closes the ball valve. The knob must be positioned parallel to the chamfers () of the cap, and aligned with the slots, so as to correctly guide the cap. Balancing with the Vortex sensor has many advantages: The measurement and regulation system does not remain installed in the system but can be removed, after the balancing operation are concluded, and can be kept by the installer. During normal operation, the shut-off valve has no moving parts subject to wear over time and head losses are negligible. The measuring device is not affected by changes in temperature, pressure or viscosity. When the control knob is in the vertical position, the ball is open and the medium is flowing (A). When the lever is in the horizontal position the ball is closed: the seats ensure a tight seal and impede the medium flow (B). A B Measurement principle The flow rate metering devices, based on the vortex precession (Vortex effect), work according to the Karman principle. When a fluid in movement hits an obstacle (normally called a stocky object), vortices take origin and separate from both sides, rotating in the opposite direction. Each vortex generates a localized low pressure. Variations in pressure are picked up by the sensor and converted into electrical pulses. Analysis electronics are used to process and analyse the metering device pulses and translate them into a numerical flow rate value. Using the Vortex-effect sensor The shut-off valve is fitted for the installation of the integrated flow rate measuring sensor with Vortex effect. The sensor is mounted on a composite material body, similar to the cap and can be fitted instead of the latter during flow rate measuring and balancing phase. The ball was in fact designed to accommodate the sensor. Shut-off valve with cap. Shut-off valve with Vortex-effect sensor: ball in open position. The circuit can be balanced.

Construction details To fit the cap correctly to the valve body, line up the two lugs () on the cap with the slots (). When opening the ball, the lugs slide under the seal guide and avoid the cap to be extracted when the ball is open. The cap has a special shape to assure perfect union with the ball and to prevent any obstructions within the useful flow section. Insulation The balancing valve can be combined with the closed cell expanded PE-X insulation ( series) which provides perfect thermal insulation and is particularly useful for limiting heat loss in geothermal installations. To facilitate maintenance and circuit shut-off, the insulation is equipped with a velcro closing thus avoiding the usual glueing. The clip (3), inserted after the cap or sensor are in position, anchors the unit securely to the valve body. The clip is firmly restrained in its seat and subsequently the correct position is assured by a spacer (4). Connection to geothermal pipe The geothermal circuit pipe can be connected straight to the shut-off valve via the polyethylene pipe fitting. These fittings are extremely practical as they do not have to be disassembled when joining pipes and are not affected by frost, hence any deformations are absorbed by the pipe itself. 3 4 In horizontal installations, liquid above the ball could impede the correct positioning of the sensor in the valve body. For this reason, the valve body is equipped with a cock on the rear (5) to discharge the fluid, contained inside the ball, when this is in the closed position. Flexible installation The versatility of the shut-off valve and flow rate measurement system means it can be installed both vertically, anchored to a wall, or horizontally in an outdoor well, for example. 5

Circuit balancing To swap the cap with the sensor it is necessary to:. Close the valve with the knob.. Remove the lock, the clip and extract the cap. 6. This operation must be repeated on subsequent branches to obtain the desired flow rate. 6 3. Insert the flow rate sensor and secure it with the clip and the lock. 4. Reopen the valve with the knob. 3 4 While measuring the flow rate, the sensor creates no significant head losses and therefore causes no significant changes in the actual flow rate. After balancing, disconnect the electronic meter and put the shut-off valves back into their standard operating condition as follows: 7. Close the valve with the knob. 8. Remove the lock, the clip and extract the sensor. 5. After carrying out these operations on all the outlets, it is possible to connect the electronic measurer to the sensor for the first branch and measure the corresponding flow rate. Flow rate regulation is performed by using the special knob to control the shut-off valve on the return manifold in correspondence with the same circuit, until the instrument indicates the design setting. 7 8 5 9. Fit the cap back in and secure it with the clip and the lock. 0. Reopen the valve with the knob. Repeat the above operations for all circuits. 9 0

Electronic flow rate meter The 30 series electronic flow rate measuring station was designed to be easily set up and allow the flow rate to be quickly read. The flow rate measuring station measures the instantaneous flow rate inside a pipe: in particular, the device was designed to work with series sensors. The electronic measuring station calculates the average medium speed using the Von Karman effect that the sensor creates in the flow. It is also programmed with data regarding the flowing surface of the medium and conversion factors needed to be able to calculate the instantaneous flow rate. Technical specifications Measuring device Display: alphanumeric with white backlighting Minimum flow rate: 300 l/h Maximum flow rate: 400 l/h Maximum error: ±0% Units of measurement available: l/h, l/min, GPM Liquids used: water, glycol solutions (up to 50%) saline solutions Electric supply: internal 9 V NiMh battery User interface ) Display showing flow rate ) ON/OFF button 3) Light 4) Menu button 5) Battery button 6) Sensor connection socket 7) Battery charger connection socket The device has an LCD display showing flow rate during measurement, configuration menus and other information needed for the correct use. To switch on the measuring station, just press and hold the ON button until words appear on the display. To switch the device off, just press and hold the ON button until all words on the display disappear. If no keys are pressed for 4 minutes, the device automatically switches off even if the sensor is still connected: this prolongs the life of the internal battery. Pressing the Light button switches on or off the display ➅ backlighting, enabling it to be used in dark places with no lighting. The backlighting is switched off automatically after minute to prolong battery life. ➀ Pressing the button allows to enter and browse the configuration menu. On exiting the menu page, it Light Menu returns to the measurement display. ➂ ➃ Battery Pressing the button from the ➁ ➄ measurement screen shows the status of the device s internal battery. To go back to the Cod. 3000 IP 44 measurement screen, press the button again. ➆ Battery charge Electric supply: 30 V~50 Hz Output: 8 V (dc) Max. current consumption by the device in charge (8 V): 50 ma Maximum power output of the supply unit: 6 W Connection: audio jack 3,5 mm Dimensions B C The battery charge is expressed as a % from 00% to 0%: when the battery charge is too low the device should be charged up. The measuring station also functions effectively when charging, hence it can even be used when connected to the battery charger. During the charging phase, pressing the Battery button displays the BATTERY CHARGE indication. A Light Menu Battery Cod. 3000 IP 44 Code 3000 A 55 B 96 C 9 Mass (kg) 0,0

Browsing menus and device configuration The device is equipped with three buttons: Menu Battery ON/OFF Use the menu button to browse items in the main menu, whilst pressing the Battery button will open sub-menus. To exit the menu and go back to measurement mode, use the Battery button. Press the ON/OFF button to exit, to return to the previous menu or measurement mode. The menu is structured as illustrated below. MENU UNIT MENU VERSION CALEFFI S.p.A. I 00 SW 0/0 HW 0/0 Reset EXIT When browsing menus, inactive headings are shown with a minus sign ( - ) whilst active headings have a cursor ( > ). Take the following unit of measurement for instance, i.e. l/min : UNIT OF MEASUREMENT Battery - l/h Menu > l/min Menu - GPM UNIT > l/h - l/min - GPM EXIT MENU LIQUID LIQUID > Water - 30% glycol - 50% glycol EXIT SPECIFICATION SUMMARY series Ball shut-off valve fitted for integrated flow rate measuring sensor with Vortex effect. Brass body. Upper cap in composite material. Female connections with trapezoidal thread captive nut 4 p.,5 mm and fitting for polyethylene pipe Ø 5, Ø 3, Ø 40. Maximum working pressure 6 bar. Maximum system test pressure 0 bar. Working temperature range -0 40 C. Ambient temperature range -0 60 C. Medium water, saline solutions and glycol solutions. Maximum percentage of glycol 50%. Code 00/3 Insulation for shut-off valves. For size valves Ø 5, Ø 3 (00), Ø 40 (003). Material closed cell expanded PE-X. Thickness 0 mm. Density inner part 30 kg/m 3, outer part 80 kg/m 3. Thermal conductivity (DIN 56) at 0 C 0,038 W/(m K), at 40 C 0,045 W/(m K). Coefficient of resistance to water vapour (DIN 565) >300. Working temperature range 0 00 C. Reaction to fire (DIN 40) class B. Code 00 Flow rate integrated measuring sensor with Vortex effect. Composite material body. Fitted to be attached solely to series shut-off valve. Maximum working pressure 6 bar. Working temperature range -0 60 C. Ambient temperature range -0 60 C. Medium water, glycol solutions and saline solutions. Maximum percentage of glycol 50%. Code 3000 Flow rate electronic measuring station to connect Vortex effect sensor. Complete with case, electric supply unit, control lever, measuring sensor with Vortex effect, connection cable, clip and lock. Rechargeable NiMh 9 V battery. Electric supply 30 V 50 Hz. Maximum power output of electric supply unit 6 W. Flow rate scale 300 400 l/h. Accuracy of flow rate reading with Vortex sensor ±0%. Protection class IP 44. We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice. Caleffi S.p.A. S.R. 9 n. 5 800 Fontaneto d Agogna (NO) Italy Tel. +39 03 849 Fax +39 03 86373 info@caleffi.com www.caleffi.com Copyright 03 Caleffi