Technical Information Omnigrad TST90, TET90

Similar documents
RTD Insert for Temperature Sensor omniset- TPR100

Technical Information Omnigrad T TR24

Technical Information Omnigrad S TR66, TC66

Omnigrad M TR10. Technical Information. Modular RTD assembly thermowell and neck tube, thread

Omnigrad M TR11. Technical Information. Modular RTD assembly protection tube, thread

Technical Information Omnigrad S TR88, TC88

Technical Information Omnigrad M TR12, TC12

Technical Information Omnigrad S TR66, TC66

itherm TS111 Technical Information Insert for installation in thermometers

Thermowell for temperature sensors omnigrad M TW 11

Omnigrad M TR12. Technical Information. Modular RTD assembly protection tube and compression fitting

RTD Temperature Sensor omnigrad T -TR 470

Technical Information Omnigrad M TR15, TC15

Thermowell for temperature sensors omnigrad M TW 13

Omnigrad T TR24. Technical Information. Modular RTD assembly threaded or weld-in compression fitting

Omnigrad M TR10. Technical Information. Modular RTD assembly protection tube and neck tube, thread

Technical Information Omnigrad M TR13, TC13

Omnigrad S TR61, TC61

Technical Information itherm TT411

RTD Temperature Sensor omnigrad M- TR 11

Omnigrad S TC88. Technical Information. Modular TC assembly Extension neck and threaded connection for installation in an existing thermowell

RTD Temperature Sensor omnigrad M TR 15

Technical Information itherm TT411

RTD Temperature Sensor omnigrad M- TR 13

Omnigrad TA20, TA21. Technical Information. Temperature Measuring Technology Terminal heads for mounting on thermowells of resistance thermometers

Omnigrad S -TC65. Technical Information

Thermocouple insert for Temperatur Sensor omniset- TPC 100

Thermocouple Thermometer omnigrad M -TC 12

Soliswitch FTE20. Technical Information. Point level switch for granular solids

RTD TH11 and TH12. Technical Information

Process resistance thermometer Model TR12-B, for additional thermowell Model TR12-M, basis module

Thermocouple Thermometer omnigrad S -TC 15

RTD Temperature Sensor omnigrad M TR 47, TR 48

ENGLISH Datasheet Platinum Resistance Pt100 4 wire class B Resistance Thermometer with Compact KNS Head

RTD Assembly TH15. Compact Instructions. KA195R/24/ae/

Threaded resistance thermometer Model TR10-C, with fabricated thermowell model TW35

Flanged resistance thermometer Model TR10-F, with fabricated thermowell model TW40

Article on Sheath materials, Thermowells, Fittings, and Terminations

Resistance thermometer For sanitary applications Model TR22-B, for orbital welding

Resistance thermometer with digital indicator Model TR75, battery operation

Cable resistance thermometer Model TR40

Electromagnetic Flow Monitor magphant

Resistance thermometer Model TR10-L, Ex d, for additional thermowell

Thermocouple For additional thermowell, flameproof enclosure (Ex d) Model TC10-L

Threaded Resistance Thermometers Model TR10-C, with Fabricated Thermowell Model TW35

Resistance thermometer For additional thermowell, flameproof enclosure (Ex d) Model TR10-L

Direct immersion resistance thermometer

Optidew Vision Optical Dew-Point Meter

Resistance thermometer with digital display Model TR75, battery operation

Cable resistance thermometer Model TR40

SITRANS F M. Flow sensor MAG 1100 F 3/59

Explosion proof RTD assembly T15

Flow Measurement SITRANS F M

Resistance thermometer Model TR10-E, for additional thermowell

Thermocouple with spring-loaded tip Model TC55

Flow Measurement SITRANS F M. Flow sensor MAG 1100 F 4/57

Miniature resistance thermometer For sanitary applications Model TR21-A, with flange connection

Platinum-chip Temperature Sensors in SMD Design Type According to DIN EN 60751

SPT- I / U PRESSURE TRANSMITTER for general applications

Thermocouple Model TC10-H without thermowell

Temperature sensors. and accessories for heat and cooling measurement points. Applications. Benefits. Features

Mineral Insulated Resistance Thermometers (RTD)

SPRING LOADED RESISTANCE THERMOMETER CONFIGURATIONS

Integrated temperature test and calibration bench Model CBS-SC4000

DIRECT IMMERSION RESISTANCE THERMOMETER CONFIGURATIONS

JUMO dtrans p20. Process pressure transmitter. Type Brief description. Key features. Block diagram

Resistance thermometer Without thermowell Model TR10-H

Level Probes multicap T DC 12 TA multicap T DC 11/16/21/26 TAN/TAS

HUMIDITY / TEMPERATURE TRANSMITTER

Level Limit Switch liquiphant FTL 360 / FTL 361

SITRANS P measuring instruments for pressure

Flow Measurement SITRANS F M

Measuring insert for process resistance thermometer

Rod probe 11375Z. Technical Information. Conductive level limit detection Partially insulated rod probe for use in conductive liquids

Spring loaded resistance thermometer

Thread Mounted Resistance Thermometers Model TR201, with Fabricated Thermowell

Threaded resistance thermometer With perforated thermowell model TW35 Model TR10-J

Portable pressure calibrator, Wally Box III Model CPH7600

MWD. Industrial Temperature Assemblies RTD. Meassuring range ºC. Pt100 sensor class A, class B, class 1/3, class 1/10, or Cryogenic.

Cable thermocouple Model TC40

Electromagnetic Flow Monitor magphant

Resistance Thermometers Model TR217, with Spring-Loaded Probe Tip

JUMO Dtrans T100 Screw-in RTD Temperature Probe with/without Transmitter

Thermowell For sanitary applications Model TW61, for orbital welding

Thermowell For sanitary applications Model TW61, for orbital welding

Cable resistance thermometer Model TR40

Soliphant T FTM260. Technical Information. Level limit switch Cost-effective vibration limit switch for fine-grained solids

Level Limit Switch liquiphant FTL 365 / FTL 366

Duct thermometer Model TF40

Pipe surface resistance thermometer, for clamping Model TR57-M, miniature design

Thermocouple Model TC10-E, for additional thermowell

Screw-in thermometer with connection lead Model TF37

Temperature Sensor without thread

Technical Information Cleanfit Control CYC25

DM01. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

Thermowell For sanitary applications Model TW61, for orbital welding

Tubeskin thermocouple assembly Model TC59-V

Resistance Thermometers Model TR602, for Flat Surfaces Model TR603, for Pipe Surfaces

DL 01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05

Metal-Protected Measuring Inserts

Transcription:

TI01109T/09/EN/02.13 71214205 Products Solutions Services Technical Information Resistance thermometer and insert for thermal energy measurement High-precision measurement of temperature differences with matched sensor pairs Application Universally usable for thermal energy measurements Measuring range: 200 to 600 C ( 328 to 1 112 F) Sensors in matched pairs within the range: 0 to 120 C (±0.05 K) 40 to 0 C (±0.1 K) Protection class: up to IP68 Your benefits Fast replaceability of the insert High degree of insert compatibility and design as per DIN 43772 Fast response time with reduced tip

Function and system design Measuring principle Resistance thermometer (RTD) These resistance thermometers use a Pt100 temperature sensor according to IEC 60751. The temperature sensor is a temperature-sensitive platinum resistor with a resistance of 100 Ω at 0 C (32 F) and a temperature coefficient α = 0.003851 C -1. There are generally two different kinds of platinum resistance thermometers: Wire wound (WW): Here, a double coil of fine, high-purity platinum wire is located in a ceramic support. This is then sealed top and bottom with a ceramic protective layer. Such resistance thermometers not only facilitate very reproducible measurements but also offer good long-term stability of the resistance/temperature characteristic within temperature ranges up to 600 C (1 112 F). This type of sensor is relatively large in size and it is comparatively sensitive to vibrations. Thin film platinum resistance thermometers (TF): A very thin, ultrapure platinum layer, approx. 1 μm thick, is vaporized in a vacuum on a ceramic substrate and then structured photolithographically. The platinum conductor paths formed in this way create the measuring resistance. Additional covering and passivation layers are applied and reliably protect the thin platinum layer from contamination and oxidation, even at high temperatures. The primary advantages of thin film temperature sensors over wire wound versions are their smaller sizes and better vibration resistance. A relatively low principle-based deviation of the resistance/ temperature characteristic from the standard characteristic of IEC 60751 can frequently be observed among TF sensors at high temperatures. As a result, the tight limit values of tolerance category A as per IEC 60751 can only be observed with TF sensors at temperatures up to approx. 300 C (572 F). For this reason, thin-film sensors are generally only used for temperature measurements in ranges below 400 C (932 F). Measuring system 2 1 3 2 1 Application example 1 EngyCal - The TU meter is used to measure the heat and cold in systems with liquid heat transfer fluids. It is easy to install and read. Thanks to its verified long-term stability and high-precision measurements, the device helps optimize processes and control costs in the process. More information on this can be found in the Technical Information ( 13). 2 Mounted thermometers TST90 3 Flow meter A0019685 2

Design 1 2 3 IL IL 4 L 9 (0.35) 2 Design 1 Insert with mounted ceramic connection socket (example with 6 mm (0.24 in)) 2 Insert with mounted ceramic connection socket (example with 3 mm (0.12 in)) 3 Thermometer with terminal head 4 Tapered tip IL Total length of insert L Thermometer immersion length A0019601 Measurement range RTD: 200 to 600 C ( 328 to 1 112 F) Sensors in matched pairs within the range: 0 to 120 C (±0.05 K) 40 to 0 C (±0.1 K) 3

Performance characteristics Sensor technology, measurement range Sensor type Pt100 (TF) Tolerance Measurement range Connection type ±0.05 K 0 to 120 C (32 to 248 F) 2- or 4-wire Matched sensor pairs ±0.1 K 40 to 0 C ( 40 to 32 F) 4-wire Process pressure The pressure values to which the actual thermowell can be subjected at the various temperatures and maximum permitted flow velocity are illustrated by the figure below. Occasionally, the pressure loading capacity of the process connection can be considerably lower. The maximum allowable process pressure for a specific thermometer is derived from the lower pressure value of the thermowell and process connection. P (PSI) P (bar) P (PSI) P (bar) 5000 350 5000 350 4300 3600 300 250 A 4300 3600 300 250 2900 200 2900 200 2100 150 2100 150 1400 700 100 50 Pmax. 1400 700 100 50 Pmax. 0 0 150 200 250 300 350 400 L (mm) 0 L (mm) 0 150 200 250 300 350 400 L (in) 6 8 10 12 14 16 L (in) 6 8 10 12 14 16 3 Maximum permitted process pressure for tube diameter, limited to 75 bar (1088 psi) by the threaded process connection A0019753 A L P Pmax. Medium water at T = 50 C (122 F) Medium superheated steam at T = 400 C (752 F) Immersion length Process pressure Maximum permitted process pressure, limited by the process connection Thermowell diameter 9 x 1 mm (0.35 in) 4

Permitted flow velocity depending on the immersion length The highest flow velocity tolerated by the thermometer diminishes with increasing immersion length exposed to the stream of the fluid. In addition it is dependent on the diameter of the thermometer tip, on the kind of measuring medium, on the process temperature and on the process pressure. The following figures exemplify the maximum permitted flow velocities in water and superheated steam at a process pressure of 5 MPa (50 bar). v (ft/s) 145 130 115 100 80 65 50 30 15 v (m/s) 45 40 35 30 25 20 15 10 5 0 0 50 L (mm) 2 L (in) A 100 200 300 400 500 4 8 12 16 20 v (ft/s) v (m/s) 295 90 260 230 200 165 130 100 65 80 70 60 50 40 30 20 30 10 0 0 50 L (mm) L (in) 2 100 200 300 400 500 4 8 12 16 20 4 Maximum flow velocity A0019755 A L v Medium water at T = 50 C (122 F) Medium superheated steam at T = 400 C (752 F) Immersion length Flow velocity Thermowell diameter 9 x 1 mm (0.35 in) Shock and vibration resistance The Endress+Hauser inserts exceed the IEC 60751 requirements stating a shock and vibration resistance of 3 g within a range of 10 to 500 Hz. 5

Accuracy RTD resistance thermometer as per IEC 60751 Class Max. tolerances ( C) Temperature range Characteristics RTD max. error type TF - range: 50 to +500 C Cl. AA, former 1/3 Cl. ± (0.1 + 0.0017 t 1) ) 0 to +150 C 3.0 2.5 Max. deviation ( C) Cl. A ± (0.15 + 0.002 t 1) ) Cl. ± (0.3 + 0.005 t 1) ) RTD maximum error type WW - range: 196 to +600 C Cl. AA, former 1/3 Cl. ± (0.1 + 0.0017 t 1) ) Cl. A ± (0.15 + 0.002 t 1) ) Cl. ± (0.3 + 0.005 t 1) ) 30 to +300 C 50 to +500 C 50 to +250 C 100 to +450 C 196 to +600 C 2.0 1.5 1.0 A 0.5 AA -200-100 0 100 200 300 400 500 600 C AA - 0.5 A - 1.0-1.5-2.0-2.5-3.0 Max. deviation ( C) A0008588-EN 1) t = absolute value C In order to obtain the maximum tolerances in F, the results in C must be multiplied by a factor of 1.8. Response time Calculated at an ambient temperature of approx. 23 C by immersing in running water (0.4 m/s flow rate, 10 K excess temperature): Type t (x) Straight tip Reduced tip Resistance thermometer (measuring probe Pt100, TF/ WW) t 50 18 s 11 s t 90 55 s 37 s Insert TET90 t 50 2.5 s 2 s t 90 5.5 s 5 s Insulation resistance Self heating Insulation resistance according to IEC 60751 > 100 MΩ at 25 C between terminals and sheath material measured with a minimum test voltage of 100 V DC. RTD elements are passive resistances that are measured using an external current. This measurement current causes a self-heating effect in the RTD element itself which in turn creates an additional measurement error. In addition to the measurement current, the size of the measurement error is also affected by the temperature conductivity and flow velocity of the process. This selfheating error is negligible when an Endress+Hauser itemp temperature transmitter (very small measurement current) is connected. 6

Calibration Endress+Hauser provides comparison temperature calibration from 80 to +600 C ( 110 to +1 112 F) based on the International Temperature Scale (ITS90). Calibrations are traceable to national and international standards. The calibration certificate is referenced to the serial number of the thermometer. Only the insert is calibrated. Insert: Ø6 mm (0.24 in) and 3 mm (0.12 in) Minimum insertion length of insert in mm (in) Temperature range without head transmitter with head transmitter 80 to 40 C ( 110 to 40 F) 200 (7.87) 40 to 0 C ( 40 to 32 F) 160 (6.3) 0 to 250 C (32 to 480 F) 120 (4.72) 150 (5.91) 250 to 550 C (480 to 1 020 F) 300 (11.81) 550 to 650 C (1 020 to 1202 F) 400 (15.75) Material Extension neck and thermowell The temperatures for continuous operation specified in the following table are only intended as reference values for use of the various materials in air and without any significant compressive load. The maximum operation temperatures are reduced considerably in some cases where abnormal conditions such as high mechanical load occur or in aggressive media. Material name Short form Recommended max. temperature for continuous use in air Properties AISI 316Ti/ 1.4571 X6CrNiMoTi17-12-2 700 C (1292 F) 1) Properties comparable to AISI316L Addition of titanium means increased resistance to intergranular corrosion even after welding road range of uses in the chemical, petrochemical and oil industries as well as in coal chemistry Can only be polished to a limited extent, titanium streaks can form 1) Can be used to a limited extent up to 800 C (1472 F) for low compressive loads and in non-corrosive media. Please contact your Endress+Hauser sales team for further information. 7

53 (2.1) 79 (3.11) Components Terminal heads All terminal heads have an internal shape and size in accordance with DIN EN 50446, flat face and a thermometer connection of M24x1.5, G1/2" or 1/2" NPT thread. All dimensions in mm (in). The cable glands in the diagrams correspond to M20x1.5 connections. Specifications without head transmitter installed. For ambient temperatures with head transmitter installed, see "Operating conditions" section. TA30A 68.5 (2.7) 15.5 (0.6) 28 (1.1) 78 (3.1) 107.5 (4.23) A0009820 Specification Available with one or two cable entries Protection class: IP66/68 (NEMA Type 4x encl.) Temperature: 50 to +150 C ( 58 to +302 F) without cable gland Material: aluminum, polyester powder coated Seals: silicone Threaded cable entry: G ½", ½" NPT and M20x1.5; Protection armature connection: M24x1.5 Head color: blue, RAL 5012 Cap color: gray, RAL 7035 Weight: 330 g (11.64 oz) Ground terminal, internal and external 3-A marked TA30D 110 (4.3) 15.5 (0.6) 28 (1.1) 78 (3.1) 107.5 (4.23) A0009822 Specification Available with one or two cable entries Protection class: IP66/68 (NEMA Type 4x encl.) Temperature: 50 to +150 C ( 58 to +302 F) without cable gland Material: aluminum, polyester powder coated Seals: silicone Threaded cable entry: G ½", ½" NPT and M20x1.5 Protection armature connection: M24x1.5 Two head transmitters can be mounted. In the standard version, one transmitter is mounted in the terminal head cover and an additional terminal block is installed directly on the insert. Head color: blue, RAL 5012 Cap color: gray, RAL 7035 Weight: 390 g (13.75 oz) Ground terminal, internal and external 3-A marked TA20R Specification 28 (1.1) 81 (3.2) 54 (2.13) Protection class: IP66/67 Max. temperature: 100 C (212 F) Material: SS 316L (1.4404) stainless steel Cable entry: 1/2" NPT, M20x1.5 or plug M12x1 PA Head and cap color: stainless steel Weight: 550 g (19.4 oz) LAS-free 3-A marked 55 (2.17) A0008667 8

Maximum ambient temperatures for cable glands Type Cable gland ½" NPT, M20x1.5 (non Ex) Temperature range 40 to +100 C ( 40 to +212 F) Design All dimensions in mm (in) 1 2 3 42 (1.65) 33 (1.3) 42 (1.65) 33 (1.3) E 10 (0.4) M4 10 (0.4) SW/AF 27 TL G½" IL 4 L X ID A0019711 5 Dimensions 1 Complete thermometer with terminal head 2 Insert with terminal block mounted (example with 6 mm (0.24 in)) 3 Insert with terminal block mounted (example with 3 mm (0.12 in)) 4 Tapered tip E Extension neck length ID Insert diameter IL Insertion length = E + L + 10 mm (0.4 in) L Immersion length SW/AF Width across flats TL Thread length 15 mm (0.6 in) X Thermowell diameter 9

Tip shape S 9 (0.35) 9 (0.35) T 1-2.5 (0.04-0.1) 40 (1.6) 20 (0.8) ~3.5 (0.14) 3 (0.12) 7 (0.28) 6.6 (0.26) 6 Available tip shapes (straight or tapered). Maximum surface roughness Ra 0.8 μm (31.5 μin) A0019712 Pos. No. Tip shape, L = immersion length Insert Outer diameter D S Straight 6 mm (0.24 in) 9 mm (0.35 in) T Tapered, L 90 mm (3.54 in) 3 mm (0.12 in) 9 mm (0.35 in) Spare parts The thermowell is available as spare part TW10 (refer to Technical Information in the chapter "Documentation"). The gasket M21-G½", copper is available as spare part (material no. 60001328). The paired RTD inserts are available as spare part TET90 (refer to Technical Information in the chapter "Documentation"). If inserts are required as spare parts refer to the following equation: Insertion length IL = E + L + 10 mm (0.4 in) Wiring Wiring diagram for RTD Type of sensor connection Terminal block mounted 1 x Pt 100 red red 1 x Pt 100 red white white white 4 wires 2 wires A0019723-EN 10

Installation conditions Orientation No restrictions. Installation instructions A C L L D 7 Installation examples A - In pipes with a small cross section the sensor tip should reach or extend slightly past the center line of the pipe (= L). C - D Tilted installation. A0008603 The immersion length of the thermometer influences the accuracy. If the immersion length is too small then errors in the measurement are caused by heat conduction via the process connection and the container wall. If installing into a pipe then the immersion length should be half of the pipe diameter, if possible (see A and ). A further solution could be an angled (tilted) installation (see C and D). When determining the immersion length all thermometer parameters and the process to be measured must be taken into account (e.g. flow velocity, process pressure). Installation possibilities: Pipes, tanks or other plant components Recommended minimum immersion length: 80 to 100 mm (3.15 to 3.94 in) The immersion length should correspond to at least 8 times of the thermowell diameter. Example: Thermowell diameter 12 mm (0.47 in) x 8 = 96 mm (3.8 in). A standard immersion length of 120 mm (4.72 in) is recommended Certificates and approvals CE Mark Other standards and guidelines PED approval Test on thermowell The device meets the legal requirements of the EC directives if applicable. Endress+Hauser confirms that the device has been successfully tested by applying the CE mark. IEC 60529: Degree of protection of housing (IP code) IEC 61010-1: Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures IEC 60751: Industrial platinum resistance thermometers DIN 43772: Thermowells DIN EN 50446: Terminal heads IEC 61326-1: Electromagnetic compatibility (EMC requirements) The thermometer complies with paragraph 3.3 of the Pressure Equipment Directive 97/23/CE and is not marked separately. Thermowell pressure tests are carried out in accordance with the specifications in DIN 43772. With regard to thermowells with tapered or reduced tips that do not comply with this standard, these are tested using the pressure of corresponding straight thermowells. Sensors for use in hazardous areas 11

are also always subjected to a comparative pressure during the tests. Tests according to other specifications can be carried out on request. The liquid penetration test verifies that there are no cracks in the welded seams of the thermowell. Test report and calibration The "Factory calibration" is carried out according to an internal procedure in a laboratory of Endress +Hauser accredited by the European Accreditation Organization (EA) according to ISO/IEC 17025. A calibration which is performed according to EA guidelines (SIT/Accredia or DKD/DAkks calibration) may be requested separately. The calibration is performed on the replaceable insert of the thermometer. In the case of thermometers without a replaceable insert, the entire thermometer - from the process connection to the tip of the thermometer - is calibrated. Ordering information Detailed ordering information is available from the following sources: In the Product Configurator on the Endress+Hauser website: www.endress.com Select country Instruments Select device Product page function: Configure this product From your Endress+Hauser Sales Center: www.endress.com/worldwide Product Configurator - the tool for individual product configuration Up-to-the-minute configuration data Depending on the device: Direct input of measuring point-specific information such as measuring range or operating language Automatic verification of exclusion criteria Automatic creation of the order code and its breakdown in PDF or Excel output format Ability to order directly in the Endress+Hauser Online Shop Accessories Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com. Service-specific accessories Accessories Description Applicator Konfigurator +temperature Software for selecting and sizing Endress+Hauser measuring devices: Calculation of all the necessary data for identifying the optimum measuring device: e.g. pressure loss, accuracy or process connections. Graphic illustration of the calculation results Administration, documentation and access to all project-related data and parameters over the entire life cycle of a project. Applicator is available: Via the Internet: https://wapps.endress.com/applicator On CD-ROM for local PC installation. Software for selecting and configuring the product depending on the measuring task, supported by graphics. Includes a comprehensive knowledge database and calculation tools: For temperature competence Quick and easy design and sizing of temperature measuring points Ideal measuring point design and sizing to suit the processes and needs of a wide range of industries The Konfigurator is available: On request from your Endress+Hauser sales office on a CD-ROM for local PC installation. 12

W@M FieldCare Life cycle management for your plant W@M supports you with a wide range of software applications over the entire process: from planning and procurement, to the installation, commissioning and operation of the measuring devices. All the relevant device information, such as the device status, spare parts and device-specific documentation, is available for every device over the entire life cycle. The application already contains the data of your Endress+Hauser device. Endress +Hauser also takes care of maintaining and updating the data records. W@M is available: Via the Internet: www.endress.com/lifecyclemanagement On CD-ROM for local PC installation. FDT-based plant asset management tool from Endress+Hauser. It can configure all smart field units in your system and helps you manage them. y using the status information, it is also a simple but effective way of checking their status and condition. For details, see Operating Instructions A00027S and A00059S Documentation Technical Information: EngyCal RH33 Custody transfer TU meter (TI00151K/09/en) Thermowell for temperature sensors Omnigrad M TW10 (TI261T/02/en) 13