ISO 9001 REGISTERED HTDM SERIES HTDM0600BR

Similar documents
Direct Gas-Fired Heating

ICEMINI & Vertical MTI Units

MODEL IFG INDIRECT FIRED MAKE-UP AIR HEATER

TGIF-3. Indirect Fired Heating Systems. Technical Guide for: IF Indoor Installations. IFW Outdoor Installations. Applied Air. Keeps You.

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

Complete HVAC Capability

BELT DRIVEN CENTRIFUGAL ROOFTOP FILTERED SUPPLY FAN

Climas y Proyectos Leyco, S.A. de C.V.

WAC Air Curtains Technical Guide

Centrifugal Filtered Supply Roof Blowers

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499]

Quantity Model Length (in.) Width (in.) Height (in.) Volume (CFM) SP (in. wg) 1 Air Curtain Supply (ASP)

I.C.E. DIRECT FIRED MAKE-UP AIR UNITS

Warm. DFC Direct Fired Gas Heating System. Applied Air. Keeps You. Technical Guide for: Outdoor Mounted Units To 100,000 CFM And 14M BTUH

TYPICAL SPECIFICATION: Critical Process Roof Top Unit 7/14/15

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Comfortable. Cooling/Heating Comfort Systems. Applied Air. Keeps You. Technical Guide for: IFL TGIFL-4

FILTERED SUPPLY CENTRIFUGAL Belt Drive

SECTION DUST COLLECTOR

The Industrial Choice. Model SCDD Direct Drive. Model SCBD Belt Driven SQUARE INLINE FANS. Direct Drive & Belt Driven Model SCDD / SCBD

.3 Section Vibration Isolation and Seismic Control..2 ANSI/AMCA 210/ASHRAE 51 Laboratory Methods of Testing Fans for Rating.

forward curved inline duct blowers

FD68 BURNERS SELECTION GUIDE & ENGINEERING SPECS

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators

Filtered Kitchen Supply Packaged Ventilator

Bulletin BCF 103 DESIGN 10A BACKWARD INCLINED WHEELS

SECTION AXIAL HVAC FANS

Direct Gas-Fired Make-up Air Heaters

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL

TECHNICAL GUIDE DESCRIPTION MODELS: D4HH 024 THRU 180 HORIZONTAL FEATURES SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW

MODEL LUBK (Belt Drive) UPBLAST PROPELLER ROOF EXHAUSTERS

Warm. SDR Direct Fired Gas Heating System. Sterling. Keeps You. Technical Guide for: Outdoor or Indoor Mounted Units To 16,000 CFM And 1.

VERTICAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT

FS Fan-Coil Units Hi-Rise, Vertical

AIR ZONE INTERNATIONAL MIXED-FLOW AIR COLUMN UNIT

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING


DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS

HORIZONTAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT

ERV ENERGY RECOVERY VENTILATOR 60 HZ. Indoor / Outdoor 500 to 10,000 cfm Capacity ERV I - D - D - P - 1 MODEL NUMBER IDENTIFICATION

SECTION CENTRIFUGAL HVAC FANS

TURNING AIR INTO SOLUTIONS. LOW PROFILE UPBLAST PROPELLER ROOF VENTILATORS. LUD/LUB (Standard) LUBMO (Motor Out of Airstream) LUBSH (UL Smoke & Heat)

SINGLE PACKAGE AIR CONDITIONING WATER COOLED

RAV Sales Guide FAN COIL UNITS HI-RISE, VERTICAL

The Industrial Choice. Model BD40C UPBLAST AXIAL ROOF VENTILATORS. Macheta Airfoil Design. Model BD40C

AIR-AIR ENERGY CONSERVATION MODULE

BVX SERIES VERTICAL DIRECT EXPANSION BLOWER COIL UNITS

Tubular Centrifugal Fans

A Division of Nailor International Inc. ECONOMY AIR HANDLERS

"SPOAU" DEDICATED 100% OUTSIDE AIR UNITS Self Contained Single Package or Split System Units

UTILITY BLOWERS. Models: BIUB / BIUBR / BIUBSH BAUB / DFC / FCUB. The Industrial Choice.

The Industrial Choice. Model BSHD Direct Drive LOW PROFILE HOODED PROPELLER ROOF VENTILATORS. Models BSHD / BSHB

CH5000 Heat Recovery Ventilator

FILTERED AIR SUPPLY FANS. Direct Drive & Belt Driven Models FSR / FSWD / FSWB / FF. Model FSWB Wall Mounted. Model FSR Roof Mounted

SQUARE INLINE CENTRIFUGAL FANS

Industry best 5 year fan housing warranty, 1 year motor warranty

S/T Ratio. Input BTU/h

Direct Fire Heated Make-Up Air Unit

TVS/R FAN COIL UNITS HI-RISE, VERTICAL

TURNING AIR INTO SOLUTIONS. UTILITY SETS DCV BCV BCVR BCVSH BAV DDF FCV

TU-WAY ROOF VENTILATORS

ZEPHYR CABINET. Single & Twin Unit Cabinet Fans. Moving Your Way BULLETIN ZC15 TABLE OF CONTENTS

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS

The Premium Quality Fan Coil Units for Horizontal Application Hydronic or Electric Heat

Twin City Fan & Blower

ROOF TOP SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING

CENTAXIAL TUBULAR CENTRIFUGAL FANS. BIA Airfoil Blade Design Direct Drive & Belt Driven Model CBD / CDD (Class I, II & III) Model CBD Belt Driven

SPUN ALUMINUM POWER ROOF AND WALL VENTILATORS

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

Twin City Fan & Blower

TURNING AIR INTO SOLUTIONS. DIRECT DRIVE EXHAUST & SUPPLY PANEL FANS. Model TCPE

R6GP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6, 7½ and 10 Ton Packaged Gas/Electric Units, with R-410A WARRANTY

XeteX, Inc. All Rights Reserved.

Warm. SDFI Direct Fired Gas Heating System. Sterling. Keeps You. Technical Guide for: Indoor Mounted Units To 64,000 CFM And 9M BTUH

Submittal 30 [762] 36 [914] 40 [1016] 50 [1270] 60 [1524] 70 [1778]

FN Fan-Coil Units High-Performance, Horizontal

NON PRESSURIZED, GALVANIZED PREP ROOM Model #ENCG C-PREP

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

A. NU2035 HRV Specifications NU2035

Industry best 5 year fan housing warranty, 1 year motor warranty

INLINE CENTRIFUGAL DUCT FANS Direct and Belt Driven Models ZIDK and ZIBK

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

INDIRECT FIRED FURNACE PARTS

PGMD Series 10 SEER. International Comfort Products 651 Heil Quaker Avenue Lewisburg, Tn Part No

SECTION HVAC POWER VENTILATORS

Tube Axial Inline Fans

UPBLAST AXIAL ROOF VENTILATORS

TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS

Warm. Air Turnover Systems. Applied Air. Keeps You. Technical Guide for: IFP IFS CAT IFA IFJ TGATS-4. Standard Gas Heat Air Turnover

Tube Axial Fan Page Specifications & Dimension Data Performance Data

Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges

LIST PRICES WAC AIR CURTAINS

SECTION AIR TERMINAL UNITS

Twin City Fan & Blower

BULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven

University of Delaware

an ISO 9001 Company Bulletin BCPF 100 NEW Design 70 PLUG FANS CHICAGO BLOWER CORPORATION GLENDALE HEIGHTS, ILLINOIS USA

MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN

Power Flame Incorporated

Transcription:

ISO 9001 REGISTERED HTDM SERIES C R R HTDM0600BR

TABLE OF CONTENTS Page 1. Standard and Optional Features 2. Efficiencies and Weight Specifications 3. Amperage Specifications & Static Pressure Losses Due to Accessories 4. HTDM High Turndown Indirect Fired Performance Specifications 5. Air Turnover Performance Specifications & Filter Specifications 6. Dimensional Drawings 6. Horizontal Configuration with Louvered Inlet 7. Horizontal Configuration with Louvered Inlet and Mixbox 8. Horizontal Configuration with Louvered Inlet, Mixbox and DX Coil 9. Horizontal Configuration with Louvered Inlet, DX Coil and Horizontal Discharge 10... Horizontal Configuration with Louvered Inlet, DX Coil and Down Discharge 11... Horizontal Configuration with Louvered Inlet, Mixbox, DX Coil and Horizontal Discharge 12... Horizontal Configuration with Louvered Inlet, Mixbox, DX Coil and Down Discharge 13... Horizontal Configuration with Louvered Inlet, Mixbox and High Efficiency Filters 14... Horizontal Configuration with Louvered Inlet, Mixbox, High Efficiency Filters and Horizontal Discharge 15... Horizontal Configuration with Louvered Inlet, Mixbox, High Efficiency Filters and Down Discharge 16... HTDM 200 Horizontal Configuration with Louvered Inlet and Mixbox with Relief 17... Horizontal Configuration with Louvered Inlet and Mixbox with Relief 18... HTDM 200 Horizontal Configuration with Louvered Inlet, Mixbox with Relief and DX Coil 19... Horizontal Configuration with Louvered Inlet, Mixbox with Relief and DX Coil 20... Horizontal Configuration with Louvered Inlet, Mixbox with Relief and Return Air Blower 21... Vertical Configuration with Louvered Inlet 22... Vertical Configuration with Louvered Inlet and Mixbox 23... Vertical Configuration with Louvered Inlet and DX Coil 24... Vertical Configuration with Louvered Inlet and High Efficiency Filters 25... Vertical Configuration with Louvered Inlet and Mixbox with Relief 26... Vertical Configuration with Louvered Inlet, Mixbox with Relief and Return Air Blower 27... Vertical Air Turnover with Propeller Fan and Screened Plenum 28... Vertical Air Turnover with Propeller Fan, Screened Plenum and High Velocity Discharge Head 29... Perimeter Roof Curbs 34 Control Panels 36 HTDM Specification

STANDARD FEATURES ASSURANCE - ETL listed - Factory wired, piped, and test fired CABINET - Welded structural or formed channel base frame primed with rust inhibitor - Heavy gauge colorbond steel casing with rust-resistant gray enamel paint finish - One inch thick 1.5# density neoprene coated fiberglass. The insulation is glued and pinned, solid liner in the burner section - Lifting lugs BLOWER/MOTOR - AMCA rated forward curve DWDI centrifugal blower - Polished steel shaft with rust inhibitor - Maximum operating speed less than 75% of first critical speed - Standard heavy-duty industrial bearings used on unit with blower sizes 20x20 and larger. - Sealed cartridge bearings provided on units with blower sizes 18x18 and smaller. - ODP motor, 1800 RPM, T frame, 1.15 service factor mounted on adjustable base - Drives designed for 150% motor brake horsepower - Adjustable V-belt drives used up to and including 5 HP; fixed drives on 7.5 HP and larger HEAT EXCHANGER/MANIFOLD - Stainless steel primary and secondary heat exchanger and cast iron gas manifold - Intermittent pilot assembly with spark igniter and ignition transformer - Solid state flame monitoring system - Burner observation port - Choice of temperature control systems - Manifold pressure for natural gas 7-14 W.C. or 1-5 psig - Manifold pressure for propane 11 W.C. - Manifold includes: pilot regulator, gas valve and shutoff valve, safety shutoff valve, pressure regulator or combination modulating and pressure regulating valve, modulating gas valve, main test fire valve, manifold pressure taps. CONTROLS ENCLOSURE - Electronic flame safeguard relay manual reset - High and low airflow pressure switches - Manual reset high limit - Factory wired control panel with numbered terminal strip - Motor starter with overloads - Control circuit transformer, 120 volt - Control panel service switch - Circuit breaker - Terminal connections for exhaust interlock - Nationally recognized components, service parts. OPTIONAL FEATURES 80/20 MIX BOX Allows the recirculation of air to occur. This will provide a cost effective way of space heating. Includes V-bank filter rack WEATHERHOUSING Control and manifold enclosure FILTER SECTION V-bank filter section with side access suitable for 2" filters. WINTER FILTER SECTION Located on the discharge side of burner. FILTERS 2" thick permanent, pleated and throwaway filters; high efficiency filte rs, various efficiency bag filters and HEPA filters complete with filter gauge and/or indicating light. MOTORIZED INLET & DISCHARGE DAMPER Parallel blade damper with a two-position spring return actuator and end switch. ROOF CURB Prefabricated galvanized roof curb 16" or 24" high; full perimeter available on most units. BLOWERS Backward inclined, air foil, and plug fans For special fan performance, contact the factory DX PLENUM Coil located in vertical or horizontal airflow complete with drain pan when applicable. - Auto low limit freeze pr otection control with bypa ss timer - 10 point electronic circui t analyzer with signal lights - Exhaust Interlock Relay - Proof of Closure Valve - Inlet Air Controller (burn er economizer) - Ultra violet flame supervision - Audible alarm - Null pressure switch - Firestat COIL PLENUMS Heating coils- steam, hot water, and glycol Cooling coils- chilled water, DX coil EVAPORATIVE COOLERS Industrial and commercial HINGED ACCESS DOORS Optional on filter section, motor section and weatherhousing. Comes with #140 ventlock handles, #310 ventlock handles upgrade available MUSHROOM HOOD Complete with internal screen for debris LOUVERED INLET Standard on all units. Manufactured by ICE and sized for a maximum velocity of 500 FPM to ensure moisture does not enter the unit. 4 WAY DISCHARGE HEAD The adjustable 4 way discharge head provides 4 equal quantities of air in the conditioned space HORIZONTAL DISCHARGE HEAD 180 deg. vertical and horizontal adjustment with 360 deg. of free rotation INTERNAL VIBRATION ISOLATION Blower and motor isolated on separate frame with R.I.S. or spring c/w ca nvas connector EXTERNAL VIBRATION ISOLATION Floor mounted or suspended isolation ADDITIONAL OPTIONS - Purge timer - Delay exhaust start - 115 volt GFI service rece ptacle - Marine service light with 100 watt bulb, guard, a nd lighted switch - High density insulation - 2" thick and 4" thick ins ulation - Motor and bearings out of airstream - Internal liners- 22 gauge solid or perforated SERVICE PLATFORM Provides access to controls and gas train MOTORS TEFC and high-efficiency, meeting EEE and CSA standards and 2-speed DISCONNECT SWITCH Weatherproof enclosure; non-fused or fused FM GAS TRAIN Meets Factory Mutual (FM) requirements IRI GAS TRAIN Meets Industrial Risk Insurers requirements HIGH GAS PRESSURE REGULATOR Required on natural gas with pressure in excess of 14" W.C and LP applications in excess of 11 "W.C. HIGH/LOW GAS PRESSURE SWITCHES Manual reset, gas pressure safety switches which lock out the burner in the event of gas pressure malfunction. CONTROL PANELS NEMA4 or 12 custom, unit mounted or remote enclosures Explosion proof panels - JIC wiring - Extended grease lines - Belt guards - Checker plate floor - Walk-in service corridors - Corrosion resistant two-step ac rylic finish - Special coatings - Special construction: al uminum, stainless steel, heavier gauges 1

Efficiencies & Turndowns MODEL HTDM EFFICIENCY TURNDOWNS 200 85% 23:1 400 82% 35:1 600 82% 34:1 1000 80% 50:1 Weights (in Pounds) Horizontal Units HTDM 200 HTDM 400 HTDM 600 HTDM 1000 HTDM 1400 Basic Unit: B lower, Filter S ection 1100 1710 2240 3480 4250 & Heat E xchanger (p. 6) c/w Return A ir 1190 1845 2460 3920 4630 Mixbox (p.7) c/w Mixbox & 1355 2110 2675 4195 4915 DX Coil Section (p. 8) c/w Mixbox & 1430 2230 2950 4615 5070 High Eff. Filter Sec tion(p. 13) c/w Mixbox 1360 2205 2915 5070 6040 with Relief (p. 16 & 17) c/w M ixbox wi th Relief 1475 2570 3445 6665 8265 and Return Air Blower (p. 20) Vertic al Units HTDM 200 HTDM 400 HTDM 600 HTDM 1000 HTDM 1400 Basic Unit: B lower, Filter S ection 1105 1790 2400 3540 4410 & Heat E xchanger (p. 21) c/w Return A ir 1260 1860 2440 3865 4770 Mixbox (p. 22) c/w Mixbox & 1335 2030 2665 4225 5250 DX Coil Section (p.23) c/w Mixbox & 1340 1825 2495 3795 4680 High Eff. Filter Sec tion (p.24) c/w Mixbox 1165 2360 2975 4980 6120 with Relief (p. 25) c/w M ixbox wi th Relief 1740 2540 3460 6535 8090 and Return Air Blower (p. 26) COMPONENTS HTDM 200 HTDM 400 HTDM 600 HTDM 1000 HTDM 1400 Coil Plenum 400 630 765 1075 1275 Horizontal Dis charge Coil Plenum 450 700 850 1295 1520 Down Discharge High Eff. Filter Sec tion 300 420 490 730 835 Horizontal Dis charge High Eff. Filter Sec tion 350 490 570 875 990 Down Discharge Louvered Inlet 60 110 130 230 260 Notes: - All units include the louvered inlet weight. If no hood is required, subtract the hood weight. - For additional components, add the component weight to the basic unit weight. 2

Amperage Specifications Motor Running Motor Amperage Voltage/Phase/Cycles HP 115/1/60 230/1/60 208/3/60 230/3/60 416/3/60 460/3/60 575/3/60 1/4 5.60 2.80 NA NA NA NA NA 1/3 5.80 2.90 NA NA NA NA NA 1/2 8.40 4.20 2.20 2.00 1.10 1.00 0.80 3/4 12.00 6.00 3.00 2.50 1.50 1.38 1.10 1 16.00 8.00 3.10 3.25 1.80 1.63 1.30 1 1/2 20.00 10.00 5.25 4.75 2.60 2.38 1.90 2 24.00 12.00 6.60 6.00 3.30 3.00 2.40 3 34.00 17.00 9.60 8.75 4.80 4.38 3.50 5 56.00 28.00 15.10 13.75 7.60 6.88 5.50 7 1/2 80.00 40.00 24.00 21.75 12.00 10.88 8.70 10 100.00 50.00 28.90 26.25 14.50 13.13 10.50 15 NA NA 44.20 40.00 22.10 20.00 16.00 20 NA NA 58.00 52.50 29.00 26.25 21.00 25 NA NA 74.50 67.50 37.30 33.75 27.00 30 NA NA 85.60 77.50 42.80 38.75 31.00 40 NA NA 115.90 105.00 58.00 52.50 42.00 50 NA NA 146.30 132.50 73.00 66.25 53.00 60 NA NA 165.60 150.00 82.80 75.00 60.00 75 NA NA 204.40 185.00 102.10 92.50 74.00 100 NA NA 270.50 245.00 135.20 122.50 98.00 Notes: - To calculate the inrush amp draw: running motor amperage x 2.5 - To calculate the full load amps (fla): 1.25 x largest motor draw + additional motor draw at face value - If you require specific control amperages, please contact the factory Static Pressure Drop(s) Due To Accessories Accessories Note: - Accessory static pressure drops are calculated at maximum CFM loads Static Pressure Drop (in inches water) Flat and V-Bank Filter Secti on 0.4 Louvered Inlet Hood 0.1 Evaporative Cooler (Commercial) 0.3 Evaporative Cooler (Industri al) 0.4 Inlet Damper 0.1 DX Plenum and Coil 0.6 80/20 Mixbox w/ Filters 0.7 Horizontal Discharge Head 0.5 3

HTDM Performance Specifications Input/ Air Temp. 0.25" W.C. 0.5" W.C. 0.75" W.C. 1.0" W.C. 1.5" W.C 2.0" W.C. Gas Output Capacity Rise Blower BHP Blower BHP Blower BHP Blower BHP Blower BHP Blower BHP Conn. (MBH) (CFM) (degf) Inches 1431 110 9x9 0.32 9x7 0.44 9x7 0.52 9x7 0.60 9x7 0.75 CF - 1574 100 9x9 0.38 9x7 0.53 9x7 0.61 9x7 0.69 9x7 0.86 CF - 1749 90 9x9 0.46 9x9 0.57 9x9 0.67 9x7 0.84 9x7 1.01 9x7 1.23 200/170 1968 80 12x9 0.43 9x9 0.74 9x9 0.86 9x9 0.98 9x7 1.27 9x7 1.52 1 2249 70 12x9 0.61 12x9 0.72 9x9 1.16 9x9 1.30 10x8 1.46 10x8 1.75 2623 60 12x9 0.87 12x9 1.00 12x9 1.13 9x9 1.74 10x8 1.91 10x8 2.27 3148 50 12x9 1.30 12x9 1.47 12x9 1.63 12x9 1.80 12x9 2.06 9x9 3.34 Input/ Air Temp. 0.25" W.C. 0.5" W.C. 0.75" W.C. 1.0" W.C. 1.5" W.C 2.0" W.C. Gas Output Capacity Rise Blower BHP Blower BHP Blower BHP Blower BHP Blower BHP Blower BHP Conn. (MBH) (CFM) (degf) Inches 2761 110 12x9 0.79 12x9 0.93 12x9 1.08 12x9 1.23 12x9 1.51 9x9 2.48 3037 100 12x12 0.85 12x12 1.01 12x12 1.18 12x9 1.35 12x9 1.80 12x9 2.10 3374 90 12x12 1.09 12x12 1.27 12x12 1.45 12x12 1.63 12x12 2.01 12x9 2.53 400/328 3796 80 15x15 0.98 12x12 1.63 12x12 1.82 12x12 2.03 12x12 2.44 12x12 2.87 1 4339 70 15x15 1.31 15x15 1.53 12x12 2.42 12x12 2.65 12x12 3.11 12x12 3.59 5062 60 15x15 1.85 15x15 2.09 15x15 2.35 15x15 2.60 12x12 4.20 12x12 4.74 6074 50 18x18 2.56 18x18 2.08 15x15 3.57 15x15 3.84 15x15 4.48 15x15 5.11 Input/ Air Temp. 0.25" W.C. 0.5" W.C. 0.75" W.C. 1.0" W.C. 1.5" W.C 2.0" W.C. Gas Output Capacity Rise Blower BHP Blower BHP Blower BHP Blower BHP Blower BHP Blower BHP Conn. (MBH) (CFM) (degf) Inches 4141 110 12x12 1.78 12x12 1.96 12x12 2.14 12x12 2.34 12x12 2.80 12x12 3.26 4556 100 15x15 1.33 15x15 1.55 15x15 1.78 15x15 2.02 15x15 2.51 12x12 3.03 5062 90 18x18 1.40 15x15 1.96 15x15 2.21 15x15 2.47 15x15 3.00 15x15 3.55 600/492 5694 80 18x18 1.79 15x15 2.54 15x15 2.81 15x15 3.10 15x15 3.68 15x15 4.28 1 6508 70 18x18 2.40 18x18 2.77 18x18 3.79 18x18 3.51 18x18 4.28 18x18 5.06 7593 60 18x18 3.42 18x18 3.84 18x18 4.27 18x18 4.70 18x18 5.57 18x18 6.46 9111 50 20x20 4.00 20x20 4.48 20x20 4.97 20x20 5.49 20x20 6.58 18x18 9.13 Input/ Air Temp. 0.25" W.C. 0.5" W.C. 0.75" W.C. 1.0" W.C. 1.5" W.C 2.0" W.C. Gas Output Capacity Rise Blower BHP Blower BHP Blower BHP Blower BHP Blower BHP Blower BHP Conn. (MBH) (CFM) (degf) Inches 6734 110 18x18 2.34 18x18 2.71 18x18 3.09 18x18 3.47 18x18 4.24 18x18 5.04 7407 100 20x20 2.07 18x18 3.28 18x18 3.69 18x18 4.10 18x18 4.94 18x18 5.79 8230 90 20x20 2.61 18x18 4.16 18x18 4.59 18x18 5.04 18x18 5.96 18x18 6.90 1000/800 9259 80 20x20 3.48 20x20 3.94 20x20 4.41 20x20 4.91 20x20 4.95 20x20 7.07 1 1/4 10582 70 20x20 4.56 20x20 5.06 20x20 5.58 20x20 6.11 20x20 7.22 20x20 8.40 12346 60 22x22 5.63 20x20 7.13 20x20 7.72 20x20 8.31 20x20 9.53 20x20 10.81 14815 50 22x22 8.60 22x22 9.40 22x22 10.13 22x22 10.88 22x22 12.42 22x22 14.04 Input/ Air Temp. 0.25" W.C. 0.5" W.C. 0.75" W.C. 1.0" W.C. 1.5" W.C 2.0" W.C. Gas Output Capacity Rise Blower BHP Blower BHP Blower BHP Blower BHP Blower BHP Blower BHP Conn. (MBH) (CFM) (degf) Inches 10101 110 22x22 3.10 20x20 4.08 20x20 4.56 20x20 5.06 20x20 6.11 20x20 7.22 2-15x15 3.35 2-15x15 3.82 2-15x15 4.31 2-15x15 4.83 2-15x15 5.88 2-15x15 6.97 11111 100 22x22 3.85 20x20 5.06 20x20 5.58 20x20 6.11 20x20 7.23 20x20 8.40 2-18x18 3.34 2-15x15 4.71 2-15x15 5.24 2-15x15 5.79 2-15x15 6.92 2-15x15 8.09 12346 90 22x22 4.96 22x22 5.55 20x20 7.06 20x20 7.65 20x20 8.84 20x20 10.09 2-18x18 4.20 2-18x18 4.89 2-15x15 6.58 2-15x15 7.18 2-15x15 8.41 2-15x15 9.67 1500/1200 13889 80 25x25 4.44 22x22 7.24 22x22 7.91 22x22 8.60 22x22 10.03 22x22 11.55 1 1/4 2-18x18 5.43 2-18x18 6.20 2-18x18 6.97 2-18x18 7.76 2-18x18 9.36 2-18x18 11.00 15873 70 25x25 6.07 25x25 6.84 22x22 10.78 22x22 11.54 22x22 13.12 22x22 14.76 2-18x18 7.47 2-18x18 8.34 2-18x18 9.22 2-18x18 10.10 2-18x18 11.90 2-18x18 13.73 18519 60 25x25 8.70 25x25 9.58 25x25 10.47 25x25 11.40 25x25 13.33 25x25 15.37 2-20x20 7.69 2-20x20 8.63 2-20x20 9.62 2-20x20 10.64 2-20x20 12.78 2-18x18 17.98 22222 50 27x27 11.21 27x27 12.18 27x27 13.17 27x27 14.21 27x27 16.42 27x27 18.83 2-20x20 12.23 2-20x20 13.32 2-20x20 14.45 2-20x20 15.61 2-20x20 18.02 2-20x20 20.56 Notes: - All static values include the blower, burner and casing Consult Factory for: - Higher air capacities or special applications - Accessory static values must be added to obtain the total static (see pg. 3) - Performance data on higher statics than listed - Brake horsepower does not include drive losses - Performance data at elevations other than sea level - A V-bank filter section is required on HTDM 1000 and 1500 with a temperature rise of less than 70 F 4

Air Turnover Performance Specifications Fan HP Gas Conn. S ize Fan Fan w/o w/ w/ Filter Heat Output Burner 7-14" 1-5 Stack Model SCFM Qty. Dia. Filters Filters & Cooling MBH HP W.C. psi Size in. 200 5,000-8,000 1 30 1.5 2 3 164 1/3 1" 1" 6 8,000-10,000 1 30 2 3 3 164 1/3 1" 1" 6 10,000-15,000 1 36 3 3 5 328 1/3 1" 1" 8 400 15,000-18,000 1 36 3 5 7.5 328 1/3 1" 1" 8 18,000-20,000 1 36 5 5 10 328 1/3 1" 1" 8 600 17,750-28,000 1 48 5 7.5 10 510 1/3 1" 1" 8 28,000-31,000 1 48 7.5 7.5 10 510 1/3 1" 1" 8 25,000-34,000 1 54 5 5 7.5 820 1/3 1-1/4" 1-1/4" 10 1000 34,000-44,000 1 54 7.5 10 15 820 1/3 1-1/4" 1-1/4" 10 44,000-50,000 1 54 15 15 20 820 1/3 1-1/4" 1-1/4" 10 35,000-44,000 1 60 5 7.5 10 1120 3/4 1-1/4" 1-1/4" 12 1500 44,000-54,000 1 60 10 15 15 1120 3/4 1-1/4" 1-1/4" 12 54,000-69,000 1 60 20 20 20 1120 3/4 1-1/4" 1-1/4" 12 Standard Filter Section Summary Horizontal Units Vertical Units Model Quantity - Total Filter Maximum Quantity - Total Filter Maximum Size Free Area Air Flow Size Free Area Air Flow Inches ft 2 CFM Inches ft 2 CFM HTDM 200 2-16 x 25 x 2 5.56 2,780 2-20 x 20 x 2 5.56 2,780 400 4-16 x 25 x 2 11.1 5,550 4-16 x 25 x 2 11.1 5,550 600 3-16 x 20 x 2 15.0 7,500 4-16 x 25 x 2 15.6 7,780 3-20 x 20 x 2 2-16 x 20 x 2 1000 4-20 x 25 x 2 25 12,500 8-20 x 20 x 2 22.2 11,100 4-20 x 20 x 2 1500 12-16 x 25 x 2 33.3 16,650 12-16 x 25 x 2 33.3 16,650 General Filter Performance Notes: - The standard filter section may contain one of the three types: Replacable: 2 inch fiberglass media with an average efficiency of 20% at 500 fpm. Throwaway: 2 inch pleated media with an average efficiency of 30% at 500 fpm. Permanent: 2 inch media with layers of slit and expanded aluminum. The media efficiency averages 20% at 500 fpm. The media can be cleaned using a stream of water. Note: - The static pressure drop through the filters is approximately 0.4" W.C. (clean) and approximately 0.8" W.C. (dirty). - The maximum airflow is calculated so the velocity across the filters never exceeds 500 fpm. - A V-bank filter section is required on HTDM 1000 and 1500 with a temperature rise of less than 70 F 5

V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w FLAT FILTER AND LOUVERED INLET 6

V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w FLAT FILTER, MIX BOX AND LOUVERED INLET 7

D V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. 8 HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w FLAT FILTER, COIL, MIX BOX AND LOUVERED INLET

V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w FLAT FILTER, HORIZ. DISCH. COIL PLENUM AND LOUVERED INLET 9

V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. 10 HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w FLAT FILTER, BTM. DISCH. COIL PLENUM AND LOUVERED INLET

V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. 11 HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w MIX BOX, FLAT FILTER, HORIZ. DISCH. COIL PLENUM AND LOUVERED INLET

4 1 2 V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. 12 HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w MIX BOX, FLAT FILTER, BTM. DISCH. COIL PLENUM AND LOUVERED INLET

V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w MIX BOX, HI-EFFICIENCY FILTER AND LOUVERED INLET 13

V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. 14 HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w MIX BOX FLAT FILTER, HI-EFFICIENCY FILTER PLENUM AND LOUVERED INLET

V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. 15 HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w MIX BOX, FLAT FILTER, HI-EFFICIENCY FILTER PLENUM AND LOUVERED INLET

MIX BOX w/ RELIEF/FILTER/BLOWER SECTION HEAT EXCHANGER SECTION 10 Ø6 22 1 2 22 1 2 FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. 16 HTDM 200 HORIZONTAL CONFIGURATION GRAVITY VENTED c/w MIX BOX w/ RELIEF, FLAT FILTER AND LOUVERED INLET

O N Z D 4 1 2 Z Q N M V Z FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. 17 HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w MIX BOX w/ RELIEF, FLAT FILTER AND LOUVERED INLET

6 FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. 18 HTDM 200 HORIZONTAL CONFIGURATION GRAVITY VENTED c/w MIX BOX w/ RELIEF, COIL, FLAT FILTER AND LOUVERED INLET

S 24 Q M V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w MIX BOX w/ RELIEF, COIL, FLAT FILTER AND LOUVERED INLET 19

N D Q V FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE. 20 HTDM SERIES HORIZONTAL CONFIGURATION GRAVITY VENTED c/w MIX BOX w/ RELIEF, RETURN BLOWER SECTION, FLAT FILTER AND LOUVERED INLET

X S 4 2 Y D K 9 Z F W E L P 25 V H G N E C A B U J M Q HTDM SERIES VERTICAL CONFIGURATION UPFLOW GRAVITY VENTED c/w FILTER AND LOUVERED INLET I 21

S Y D 4 1 2 D K X 4 2 9 Z F W E L P 25 V H G N E C A B U J Q M HTDM SERIES VERTICAL CONFIGURATION UPFLOW GRAVITY VENTED c/w MIX BOX, FILTER AND LOUVERED INLET I 22

COIL R Y D K S X 4 9 2 Z F W E L P 25 v H G N E C A B U J M Q HTDM SERIES VERTICAL CONFIGURATION UPFLOW GRAVITY VENTED c/w FILTER,COIL AND LOUVERED INLET I 23

HI-EFFICIENCY FILTER S Y D K X 4 Z 2 9 F W E L P 25 V H G N E C A B U J Q M HTDM SERIES VERTICAL CONFIGURATION UPFLOW GRAVITY VENTED c/w HI-EFFICIENCY FILTER, AND LOUVERED INLET I 24

R1 T2 K S1 4 1 2 E G I E Q H Z S1 R2 9 F U V O X E C P1 4 2 A B HTDM SERIES VERTICAL CONFIGURATION UPFLOW GRAVITY VENTED c/w FILTER, MIX BOX w/ RELIEF AND LOUVERED INLET 25

R1 T2 K 4 1 2 E E G S1 I Q H Z S1 R2 9 F U V O X E C P1 4 2 A B Y2 26 HTDM SERIES VERTICAL CONFIGURATION UPFLOW GRAVITY VENTED c/w FILTER, MIX BOX w/ RELIEF, RETURN BLOWER SECTION AND LOUVERED INLET

B C F G E A D B 1 3 4 D 1 3 4 B+3 1 2 C+3 1 2 HTDM SERIES VERTICAL TURNOVER c/w PROP FAN AND SCREENED PLENUM 27

B C H B 32 C G F J A E D B 1 3 4 1 3 4 C B+3 1 2 C+3 1 2 HTDM SERIES VERTICAL TURNOVER UNIT c/w PROP FAN, SCREENED INLET AND HIGH VELOCITY DISCHARGE HEAD 28

1 4 1 2 3 4 DUCT SUPPORT ANGLE CURB ENDS CURB SIDES CENTER CURB BRACING 2 WOODEN NAILER 3 1/4X1/2 NC BOLTS SUPPLIED FOR EACH CORNER C/W LOCKWASHERS AND NUTS CORNER BOLTING ASSEMBLY DETAIL #2 UNIT BASE FRAME FLASHING (BY OTHERS) ROOFING PAPER (BY OTHERS) NEOPRENE GASKET OR CAULKING (BY OTHERS) WOODEN NAILER INSULATION (BY OTHERS) 3 CANT STRIP (BY OTHERS) 4 BLOWER BURNER SECTION ONLY ROOF CURB CROSS SECTION DETAIL AA COIL PLENUM BTM. DISCHARGE 1/4X1/2 NC BOLTS SUPPLIED FOR EACH CORNER c/w LOCKWASHERS AND BOLTS CENTER BRACING BOLTING ASSEMBLY DETAIL #1 WOODEN NAILER 1. FIELD ASSEMBLED BY OTHERS. 2. ENSURE THAT THE 16 INCH CURB HEIGHT IS IN COMPLIANCE WITH LOCAL CODES. 3. ON UNITS OVER 108" IN LENGTH, THE CURB WILL HAVE 2 PIECE CONSTRUCTION & CENTER BRACING ITEM #4 ADDED AT SPLICE. 4. CONTRACTORS DUCTING MUST BE FLUSH WITH ROOF CURB TO ALLOW FOR PROPER MATING BETWEEN BUILDING DUCT AND UNIT. HTDM SERIES PERIMETER ROOF CURB 29

1 4 1 2 DUCT SUPPORT ANGLE CURB ENDS 2 WOODEN NAILER 3 UNIT 3 4 CURB SIDES CENTER CURB BRACING 1/4X1/2 NC BOLTS SUPPLIED FOR EACH CORNER C/W LOCKWASHERS AND NUTS BASE FRAME FLASHING (BY OTHERS) ROOFING PAPER (BY OTHERS) NEOPRENE GASKET OR CAULKING (BY OTHERS) WOODEN NAILER INSULATION (BY OTHERS) CANT STRIP (BY OTHERS) CORNER BOLTING ASSEMBLY DETAIL #2 ROOF CURB CROSS SECTION DETAIL AA COIL PLENUM HORIZ. DISCHARGE RIGAFLO FILTER HORIZ. DISCHARGE 3 4 1. FIELD ASSEMBLED BY OTHERS. 2. ENSURE THAT THE 16 INCH CURB HEIGHT IS IN COMPLIANCE WITH LOCAL CODES. 3. ON UNITS OVER 108" IN LENGTH, THE CURB WILL HAVE 2 PIECE CONSTRUCTION & CENTER BRACING ITEM #4 ADDED AT SPLICE. 4. CONTRACTORS DUCTING MUST BE FLUSH WITH ROOF CURB TO ALLOW FOR PROPER MATING BETWEEN BUILDING DUCT AND UNIT. 1/4X1/2 NC BOLTS SUPPLIED FOR EACH CORNER c/w LOCKWASHERS AND BOLTS CENTER BRACING BOLTING ASSEMBLY DETAIL #1 WOODEN NAILER HTDM SERIES PERIMETER ROOF CURB 30

1 3 4 E 2 B 1 2 3 4 DUCT SUPPORT ANGLE CURB ENDS CURB SIDES CENTER CURB BRACING A/2 2 WOODEN NAILER 3 1/4X1/2 NC BOLTS SUPPLIED FOR EACH CORNER C/W LOCKWASHERS AND NUTS CORNER BOLTING ASSEMBLY DETAIL #2 UNIT 3 BASE FRAME FLASHING (BY OTHERS) ROOFING PAPER (BY OTHERS) NEOPRENE GASKET OR CAULKING (BY OTHERS) WOODEN NAILER INSULATION (BY OTHERS) CANT STRIP (BY OTHERS) ROOF CURB CROSS SECTION DETAIL AA 4 WOODEN NAILER 1/4X1/2 NC BOLTS SUPPLIED FOR EACH CORNER c/w LOCKWASHERS AND BOLTS MIX BOX/BLOWER SECTION MIX BOX/COIL SECTION MIX BOX/RIGAFLO SECTION CENTER BRACING BOLTING ASSEMBLY DETAIL #1 1. FIELD ASSEMBLED BY OTHERS. 2. ENSURE THAT THE 16 INCH CURB HEIGHT IS IN COMPLIANCE WITH LOCAL CODES. 3. ON UNITS OVER 108" IN LENGTH, THE CURB WILL HAVE 2 PIECE CONSTRUCTION & CENTER BRACING ITEM #4 ADDED AT SPLICE. 4. CONTRACTORS DUCTING MUST BE FLUSH WITH ROOF CURB TO ALLOW FOR PROPER MATING BETWEEN BUILDING DUCT AND UNIT. HTDM SERIES PERIMETER ROOF CURB 31

B 2 WOODEN NAILER 3 UNIT 1 2 3 4 DUCT SUPPORT ANGLE CURB ENDS CURB SIDES CENTER CURB BRACING 1/4X1/2 NC BOLTS SUPPLIED FOR EACH CORNER C/W LOCKWASHERS AND NUTS BASE FRAME FLASHING (BY OTHERS) ROOFING PAPER (BY OTHERS) NEOPRENE GASKET OR CAULKING (BY OTHERS) WOODEN NAILER INSULATION (BY OTHERS) CANT STRIP (BY OTHERS) CORNER BOLTING ASSEMBLY DETAIL #2 ROOF CURB CROSS SECTION DETAIL AA 3 4 1. FIELD ASSEMBLED BY OTHERS. 2. ENSURE THAT THE 16 INCH CURB HEIGHT IS IN COMPLIANCE WITH LOCAL CODES. 3. ON UNITS OVER 108" IN LENGTH, THE CURB WILL HAVE 2 PIECE CONSTRUCTION & CENTER BRACING ITEM #4 ADDED AT SPLICE. 4. CONTRACTORS DUCTING MUST BE FLUSH WITH ROOF CURB TO ALLOW FOR PROPER MATING BETWEEN BUILDING DUCT AND UNIT. 1/4X1/2 NC BOLTS SUPPLIED FOR EACH CORNER c/w LOCKWASHERS AND BOLTS CENTER BRACING BOLTING ASSEMBLY DETAIL #1 WOODEN NAILER HTDM SERIES PERIMETER ROOF CURB FOR COIL PLENUM (DOWN. DISCH.) AND RIGAFLO PLENUM (DOWN. DISCH.) 32

1 3 4 E 2 B 1 2 3 4 DUCT SUPPORT ANGLE CURB ENDS CURB SIDES CENTER CURB BRACING A/2 2 WOODEN NAILER 3 1/4X1/2 NC BOLTS SUPPLIED FOR EACH CORNER C/W LOCKWASHERS AND NUTS CORNER BOLTING ASSEMBLY DETAIL #2 UNIT BASE FRAME FLASHING (BY OTHERS) ROOFING PAPER (BY OTHERS) NEOPRENE GASKET OR CAULKING (BY OTHERS) WOODEN NAILER INSULATION (BY OTHERS) CANT STRIP (BY OTHERS) 4 3 WOODEN NAILER ROOF CURB CROSS SECTION DETAIL AA 1/4X1/2 NC BOLTS SUPPLIED FOR EACH CORNER c/w LOCKWASHERS AND BOLTS MIX BOX w/ RELIEF BLOWER SECTION MIX BOX w/ RELIEF R/A BLOWER SECTION MIX BOX w/ RELIEF AND COIL SECTION CENTER BRACING BOLTING ASSEMBLY DETAIL #1 1. FIELD ASSEMBLED BY OTHERS. 2. ENSURE THAT THE 16 INCH CURB HEIGHT IS IN COMPLIANCE WITH LOCAL CODES. 3. ON UNITS OVER 108" IN LENGTH, THE CURB WILL HAVE 2 PIECE CONSTRUCTION & CENTER BRACING ITEM #4 ADDED AT SPLICE. 4. CONTRACTORS DUCTING MUST BE FLUSH WITH ROOF CURB TO ALLOW FOR PROPER MATING BETWEEN BUILDING DUCT AND UNIT. HTDM SERIES PERIMETER ROOF CURB 33

HTDM SPECIFICATION TYPE AND DESCRIPTION Furnish an I.C.E HTDM Model indirect fired self-contained make-up air unit in accordance with the following specifications. The unit shall be ETL and CETL certified. The heater shall be designed to ensure a minimum efficiency of 80% at full firing rate. The power burner has a turndown capacity between 23:1 and 60:1. The heat exchanger and blower shall be constructed so they can easily be disassembled and reassembled in the field if necessary. The unit shall be equipped to operate from a single point power connection. The heater shall be flame tested before shipment and the manufacturer shall keep a detailed flame test report on file. Factory testing shall be confirmed with a combustion analyzer and flow meter. The heater shall be shipped completely factory assembled and wired including all prepiped manifold components and fuses, ready for immediate power and fuel connections. CASING The unit exterior casing shall be heavy gauge G90 rated bonderized steel. Unit roofs shall feature standing seam construction. The entire unit casing shall be insulated with 1-in. thick 1.5-lb. (2-in. thick 1.5-lb.) fiberglass insulation with hard neoprene backing in a sandwich wall fashion (22-gauge solid liner). The unit exterior shall be finished with industrial enamel (catalyzed epoxy) paint. An integral welded iron channel frame shall support the unit casing. Formed sheet metal bases are unacceptable. The structural iron frame shall be sandblasted, primed and finished with industrial enamel (catalyzed epoxy) paint. BLOWER/MOTOR SECTION The fan section and motor assembly shall be constructed in accordance with the requirements of the Air Moving and Conditioning Association (AMCA). The assembly shall be designed to house the fan(s), bearings, motor, and v-belts, which shall be selected for at least 50% above the rated motor capacity. The fan(s) and motor shall be mounted on a welded unitary base made of angle iron frame. The frame shall be sandblasted, primed and finished with industrial enamel (catalyzed epoxy) paint. The unitary base shall be provided with seismic spring vibration isolation. The blower section shall have a hinged access door with Ventlock handles to allow easy maintenance of filters and belts. The NEMA T-Frame motor shall be mounted on an adjustable base located within the fan section. The blower shall be a forward curve DWDI centrifugal blower. The blower wheel shall be statically and dynamically balanced, and mounted on a turned, ground and polished shaft with rigid bearing supports. The shaft shall be designed with a maximum operating speed not exceeding 75% of the first critical speed. The bearings shall be split taper lock ball bearing type L20 minimum life of 100,000 hours (L10 200 khr). Fan performance shall be based on tests conducted in accordance with AMCA Standard Test Code for Air moving Devices. (All fans shall have sharply rising pressure characteristic extending throughout the operating range and continuing to rise well beyond the efficiency peak to assure quiet and stable operation under all conditions. Horsepower characteristics shall be truly non-overloading and shall reach a peak in the normal selection area.) Fan manufacturer shall provide sound power ratings in the eight octave bands, which shall be based on AMCA Standard 300-67, test, setup number one. Sound power ratings shall be referenced 10-12 watts. A factory dynamic balance shall be made on all fans after their assembly. An IRD or PMC analyzer shall be used to measure velocity, and the final reading shall not exceed 0.1 inches per second. The exact level of vibration shall be recorded on the fan as proof of the final dynamic balance at the factory. HEAT EXCHANGER The heat exchanger shall be of two-pass design, made up of at least 16-gauge stainless steel drum and tubes. The primary and secondary heat transfer surfaces shall be constructed of Type 409 series stainless steel, with internal stainless steel high efficiency enhancing baffles. The stainless steel tubes shall be continuously welded into the secondary front and rear header tube sheets to ensure an airtight seal. Units shall be provided with multiple condensate drains. The heat exchanger section shall have an internal radiation shield to maintain a jacket loss of less than 2% of rated output. All heat transfer surfaces, including headers and the front collector box, shall be inside the casing and in the airstream. The construction of the heat exchanger shall permit free, unrestricted lateral, vertical, and peripheral expansion during the heating and cooling cycle without damage or strain to any parts. The burner shall be constructed with at least 14-gauge stainless steel and with the air baffles being made up of 430 stainless steel to ensure high durability and life of the burner. The burner assembly shall be a blow through positive pressure type with an intermittent pilot ignition system. Flame supervision shall be with a solid state programmed flame relay complete with flame rod. The unit s burner motor and modulating gas valve must be electronically controlled to guarantee, to the customer, a highly efficient unit at all times and applications. The unit efficiency shall be a minimum of 80% through the entire operating range and shall be independently tested and verified by ETL. The main and pilot 36

HTDM SPECIFICATION manifolds shall be completely factory pre-piped to the burner. This assembly must be factory wired and include the following minimum components: main and pilot manual shut-off valves, main and pilot regulators, main and pilot automatic shut-off valves and adequate union and test ports for unconstrained service. All indoor units can be vented using type B vent without a draft hood on all models in Canada. In the United States, indoor units can be vented using type B vent without a draft hood on models 200, 400 and 600 and with a diverter on models 1000 and 1400 to assure safety and guarantee that all combustible gases leave the unit. There must also be a means of collecting and disposal of condensate formed in the flue gas by means of a 409 stainless steel flue box with drain and heat exchanger drain. Drains shall be made of copper (stainless steel) tubing. CONTROLS Units must be controlled electronically to achieve a turndown of at least 23:1 and to guarantee the heat exchanger efficiencies of at least 80%. Unit controller must be a true proportional integral (PI) controller to maintain the turndown and unit efficiencies. The controller must be able to electronically adjust the burner blower and modulating gas valve to maintain ideal combustion levels. The controller shall monitor the amount of combustion air available to guarantee proper emission standards. Unit control will consist of a highly accurate feedback control system. Corrective action in this system is taken only when the balance has been upset due to a change in the disturbance variable. Any other control that does not behave in this manner is unacceptable. An amplitude decay ratio of one quarter is essential to the stability. Sine wave pattern cycling is unacceptable. Control must be achieved with a PI control algorithm. The ICECON1 controller analyzes the process calculates a control error from the measured values. The control error will vary from positive to negative depending on whether the value of the controlled variable is greater than or less than the set point. Continuous cycling of the burner or blower is unacceptable. The proportional control in the ICECON1 controller will provide an output signal in proportion to the size of the control error. The longer the control error is present, the more the controller output will change. If the control error persists, the output will continue to ramp in the correct direction, until the control error is eliminated. The ICECON1 modulation controller is compatible with the following external inputs: Discharge air sensor. Discharge air sensor with space override thermostat. Discharge air sensor with remote temperature selector and space override thermostat. Discharge air sensor with high and low temperature remote temperature selector and space reset thermostat. 0-10 volt dc signal from building management system. 4-20 ma signal from building management system. ELECTRICAL CONTROL EQUIPMENT Electrical assembly and components shall be in strict accordance with the latest provisions and requirements of the Nation Electric Code. Control cabinet shall be designed and constructed to ETL specifications. A safety disconnect switch shall be mounted on the unit. The controls shall be located in a weatherproof cabinet. Provisions for service padlocking shall be provided. The following items shall be located within the cabinet: fuses, starters, control relays, timing and holding relays, resistors and numbered terminal strips. All components shall be labeled and cross-referenced to control and field wiring diagrams. The control circuit shall be 110V, single phase. Wiring shall be neatly run in "PANDUIT" wiring duct. Low and/or line voltage thermostats shall be furnished shipped loose for installation by others. Unit shall be equipped with automatic low limit freeze protection with bypass timer. Unit will feature a convenience outlet with separate disconnect, circuit breaker protection and supply transformer. DAMPERS & FILTER SECTION The dampers are to be galvanized steel (aluminum airfoil low leak) type (with seals). The dampers shall be equipped with 2- position (modulating) actuators. The filters shall be 2" pleated throwaway type with minimum of 85% arrestance and 30% dust. Filter access shall be through a latched and gasketed access doors located on both sides of the unit. (Final filters shall be 8 or 12 inch high efficiency cartridge filters.) REMOTE CONTROL PANELS Remote NEMA 1(12) locking control panel shall be equipped with summer/of/winter switch and blower on, burner on, flame failure and loaded filter lights. (A remote adjustment potentiometer shall control damper positioning.) (An LCD display shall provide system temperature and set points.) 37