Service Procedure D01A

Similar documents
DigiTemp. Digital Thermometer

TECHNICAL NOTE #4 Revised May 24, BOGART ENGINEERING Two Bar Road, Boulder Creek, CA (831)

1984 Jeep CJ7. IGNITION SYSTEM - SOLID STATE' 'Distributors & Ignition Systems MOTORCRAFT SOLID STATE IGNITION (SSI)

Online Service Center for Monaco Coach

TOTALFLOW Technical Bulletin 59 Lead Acid Battery Inspection and Maintenance Procedures

Harris IRT Enterprises Digital Resistance Tester Model XP

TEST CHART. Voltage Supply

Section 55 Chapter 6

U tube viscometer. Kinematic viscosity bath RASAYAN

Chrysler Electronic Ignition System

Maintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C

5 Volt Engine Pressure Sensor Supply Circuit - Test

2000 F-150 Workshop Manual

STANDARD AND GROUND SWITCHED APPLICATIONS

SERVICE MANUAL FOR ANALOG CONTROLLER MODELS

MODEL No s: PP3, PP3K

MINOTOUR SERVICE MANUAL

Third Generation NITE Phoenix

DIAGNOSIS AND TESTING Procedure revision date: 06/21/2000

Battery Control Center - Diesel

2006 F-150/Mark LT Workshop Manual

2003 Explorer Sport/Sport-Trac Workshop Manual. 7. Disconnect the vacuum harness connector. Remove the nut.

SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator.

Binary Switch Retrofit for Century Class and Argosy Vehicles 83-71

IDEAL INDUSTRIES INC. TECHNICAL MANUAL - SUPPLEMENT MODEL

Technical Information and Diagnostic Guide

TurfDefender Electronic Leak Detector Kit Reelmaster 5000, 6000 and 5010 Series Traction Units

A/C SYSTEM SPECIFICATIONS

OFI MODEL 60 ATMOSPHERIC CONSISTOMETER INSTRUCTIONAL MANUAL

NUMBER: 1 DDEC VI 07 S.M. REF.: Listed in Table 1 ENGINE: Series 60 DATE: February 2007

C802/C802D/C802TD/C820 Alternators Troubleshooting Guide

Thermocouple Thermometer Models

Thermistor Thermometer MODEL NO

Technical Service BULLETIN

1995 Aerostar/Ranger/Explorer

Additions, Revisions, or Updates

TECHNICAL PAPER 1002 FT. WORTH, TEXAS REPORT X ORDER

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi

ALTERNATOR REQUESTED INFORMATION. Vehicles With Dual Generator [ Engine Mount - LH ] 2007 Ford Pickup 6.0L Eng F350 Super Duty

Open Center Compact Valve Custom Installation Guide Rev A

1. SPECIFICATION Typ. HPS EPS Capacity 120 A 140 A. 76/140 A at 1,800/6,500 rpm. 70/120 A at 1,800/6,500 rpm. Normal output.

INSTALLING NON-CARBONATED DRINK KIT ON THE VISTA POST-MIX CARBONATED DISPENSER

COLORADO DEPARTMENT OF LABOR AND EMPLOYMENT DIVISION OF OIL AND PUBLIC SAFETY STATISTICAL INVENTORY RECONCILIATION (SIR) GUIDANCE DOCUMENT

Occupant Classification Sensor

INSTRUCTION MANUAL YOKOHAMA QUICK CHARGER WITH LCD DISPLAY. Safety

PHscan10S Pocket ph Tester Instruction Manual

with lcd display 12-42v

SECTION 1E ENGINE ELECTRICAL

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values


COMPONENT LOCATION INDEX

EBP Sensor (Exhaust Back Pressure)

Barnant Company (Type J) (Type K) (Type T)

A/C-HEATER SYSTEM - AUTOMATIC

Unit 5 Troubleshooting

UNIVERSAL GAUGE WIRE HARNESS

Removing and installing dash panel insert

Using the PST-2000 with Peterbilt Trucks. Document Number B

It is normal for the A/C compressor to turn off under certain conditions, such as low idle, high engine coolant temperature, or hard acceleration.

Alliance Towel Dispensing System. Operation Manual

G - TESTS W/CODES - 2.2L

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units

PAGE Both power cords must be connected & powered to operate the E-TES SD 120 volt unit.

Northwest RV Supply Manual Compliments of Printed From TROUBLESHOOTING

ACCESSORY KIT INSTALLATION INSTRUCTIONS

2001 Focus Workshop Manual

# : SMU - Revised DTC P0341 Camshaft Position (CMP) Sensor Performance - (Feb 20, 2002)

SECTION Anti-Lock Brake System (ABS) and Stability Control

Tige Troubleshooting (Electronic Throttle Engines)

SAFETY PRECAUTIONS AND WARNINGS...

5 Volt Sensor Supply Circuit - Test

DTC P0300-P0308. Diagnostic Instructions. DTC Descriptors. Circuit/System Description. Conditions for Running the DTC

1. (a) If a large power generating station is operating with steam at 16,000 kpa and 500 and exhausting to a condenser at, 37.6 mm mercury absolute;

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

1. SPECIFICATION

Additions, Revisions, or Updates

Title: M.I.L. ON DTC P3191, P3190, AND/OR P0A0F Models:

System III Wiring Information 54-12

Tachometer, Ametek Electronic 54.21

Troubleshooting Guide for N1225-1/N1237-1/N Alternators

1994 Aerostar/Ranger/Explorer

F - BASIC TESTING Infiniti G20 INTRODUCTION PRELIMINARY INSPECTION & ADJUSTMENTS VISUAL INSPECTION MECHANICAL INSPECTION

Side marker lamps from the factory. General information

Maintenance of the Electronic ( EPC ) Pressure Controllers on SRI GCs

AIRSTREAM - BATTERY CONTROL CENTER - Diesel

Parts List. Self-Contained Cubelet. Models AM-50BAE AM-50BAE-DS AM-50BAE-AD AM-50BAE-ADDS. hoshizakiamerica.com

MasterCraft Troubleshooting (Electronic Throttle Engines)

CAUTION: CAREFULLY READ INSTRUCTIONS BEFORE PROCEEDING

Repair content for 2005 GMC W4500 Forward

International VT 275 Engine Program II: Hard Start/No Start & Performance Diagnostics

SECTION 4A HYDRAULIC BRAKES

SERVICE MANUAL. Kysor Instrumentation Troubleshooting Guide

SBW and SBW2 Troubleshooting Guide AES-286 ECN REV REVISION RECORD DATE ENGINEER

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2015 CLOVER SYSTEMS All Rights Reserved

Advanced Troubleshooting Guide Snorkel V Battery Charger Rev 0 3JAN07

2005 Hyundai Truck Santa Fe V6-3.5L

C.E. Niehoff & Co. N1601, N1602, N1603, and N1604 Alternator Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

Wiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents.

WE INCREASE UPTIME AND EFFICIENCY IN THE REFRIGERATION INDUSTRY

MANUAL. Single charger

Transcription:

Service Procedure D01A 0Title: RETURN AIR, DISCHARGE AIR, COIL, AND AMBIENT TEMPERATURE SENSOR TEST Where Used: All units equipped with μp-vi Microprocessors and Revision 40xx Software. Purpose: This procedure must be used to confirm the proper operation of the return air, discharge air, coil and/or ambient sensors. STEP ACTION RESULTS COMMENTS NOTE: Polarity must be considered when connecting temperature sensors. If the sensors are connected backwards, the display will show four dashes (----). Consult the schematic diagram or wiring diagram for the correct connections. 1 Turn the unit off. 2 Disconnect the appropriate sensor at the plug next to the sensor. 3 Turn the unit on. The Standard Display will appear. P41OD01A - 19 July 1999 D01A - Page 1

Service Procedure D01A 4 Select the appropriate sensor by pressing the Select key. 5 Using a high quality digital multimeter, check the voltage at the sensor plug on the plug half that is still connected to the microprocessor. 6 If the voltage measured in Step 5 above is incorrect, recheck the voltage at the same circuits on the sensor connector on the back of the microprocessor. 7 If a bad microprocessor is indicated, check with Microprocessor Tester as shown in Service Procedure A01A. 8 If the microprocessor and harness appear to be OK, but the return air or discharge air sensor is still suspected of reading incorrectly, check the sensor grade calibration using Service Procedure A15A and with an ice water bath as shown in. The display for the disconnected sensor should show [----]. The voltage must be from 4.90 to 5.10 volts DC. The voltage must be from 4.90 to 5.10 volts DC. If all sensors show [----] without being disconnected, the microprocessor is probably defective. Test it using Service Procedure A01A. If the voltage is correct, replace the sensor. If the voltage is correct at Step 6 and incorrect at Step 5, the problem is in the wiring. If the voltage is incorrect in both Steps 5 and 6, the problem is in the microprocessor. Substitute or replace sensor if needed. Return air and discharge air sensors must be replaced with graded sensors and calibrated as shown in Service Procedure A15A. Coil and ambient sensors are ungraded sensors and do not require calibration. P41OD01A - 19 July 1999 D01A - Page 2

0Title: CHECKING SENSOR CALIBRATION WITH AN ICE WATER BATH Where Used: All units equipped with μp-vi Microprocessors and Revision 40xx Software. Purpose: This procedure must be used when it is necessary to confirm sensor calibration of the return air or discharge air sensors. NOTE: To be effective, an ice water bath must be constructed as shown in this procedure. Using a bag or cup of ice instead of an insulated container and/or failing to stir the bath during the test will result in erroneous readings. STEP ACTION RESULTS COMMENTS NOTE: Polarity must be considered when connecting temperature sensors. If the sensors are connected backwards, the display will show four dashes (----). Consult the schematic diagram or wiring diagram for the correct connections. Preparing the Ice Water Bath 1 Obtain a clean, well insulated container with a capacity of at least one quart. NOTE: To be effective, an ice water bath must be constructed as shown in this procedure. Using a bag or cup of ice instead of an insulated container and/or failing to stir the bath during the test will result in false readings. P41OD02A - 19 July 1997 D02A - Page 1

2 Clean the insulated container. NOTE: Contamination of the container with antifreeze or other substances will result in false readings. 3 Completely fill the insulated container with crushed ice. 4 Add cold water to the top of the ice in the insulated container. 5 Allow the container to stabilize for at least 15 minutes. Stir the contents of the container briskly several times during this period. 6 Remove the sensors to be tested as required to immerse them in the ice water bath. The graded return air and discharge air sensors are the only sensors requiring ice water calibration. Testing the Return Air Sensor 7 Be certain the unit display is showing the Standard Display. 8 After the bath has stabilized for 15 minutes, insert the return air sensor completely into the ice and water mixture. Stir the bath briskly. 9 Allow the sensor to remain in the bath for at least 5 minutes. Stir the bath briskly several times. 10 Stir the bath briskly and observe the Standard Display. The display must show setpoint ± 0.4 F (0 C ± 0.2 C). P41OD02A - 19 July 1997 D02A - Page 2

11 If the display is not within the required range, recheck the return air sensor calibration as shown in Service Procedure A15A. 12 If the sensor is still not within the required range as shown it must be replaced. Testing the Discharge Air Sensor 13 Be certain the unit display is showing the Standard Display. 14 After the bath has stabilized for 15 minutes, insert the discharge air sensor completely into the ice and water mixture. Stir the bath briskly. 15 Allow the sensor to remain in the bath for at least 5 minutes. Stir the bath briskly several times. 16 Press the Select key to select [DIS.A] and press the Enter key to lock the display. 17 Stir the bath briskly and observe the display. 18 If the display is not within the required range, recheck the discharge air sensor calibration as shown in Service Procedure A15A. The display must show setpoint ± 0.6 F (0 C ± 0.3 C). The display must show [DIS.A] ± 0.6 F (0 C ± 0.3 C). P41OD02A - 19 July 1997 D02A - Page 3

19 If the sensor is still not within the required range as shown it must be replaced. Re-install Sensors 20 Re-install sensors in the appropriate locations. Be certain the return and discharge sensors are not interchanged. 21 Secure sensor harnesses and replace any cable ties as required. The display must show [DIS.A] ± 0.6 F (0 C ± 0.3 C). Be certain the return air and discharge air sensors are not interchanged. If they are interchanged the unit will fail the pretrip. P41OD02A - 19 July 1997 D02A - Page 4

Service Procedure D03A 0Title: PRESSURE SENSOR TEST Where Used: All μp-vi Microprocessors. Purpose: This procedure can be used to confirm the proper operation of the suction or discharge pressure transducer. STEP ACTION RESULTS COMMENTS 1 Turn the unit on. 2 Select the pressure transducer by pressing the Gauge key to show [SUC.P] or [HED.P]. The display should show the pressure reading for the sensor. If the sensor reading is obviously incorrect or the display shows [----], proceed as shown below. If all sensors show [----] without being disconnected, the microprocessor may be defective, a sensor lead may be shorted to chassis ground. Confirm incorrect reading with refrigeration gauges as necessary. 3 Turn the unit off. 4 Disconnect the suction or discharge pressure transducer at the transducer plug. 5 Turn the unit on. 6 Using a high quality digital multimeter, check the voltage at The voltage between wires HSPP and HSPN must be from If the microprocessor fails the test it must be replaced. the transducer plug on the plug half that is still connected to the microprocessor. 4.90 to 5.10 volts DC. If the voltage is not present, check the microprocessor using Service Procedure A01A. 7 If the microprocessor passes the test, check the continuity of harness wire HSPP, HSPN, DPI and/or SPI from the microprocessor to the sensor using Service Procedure H04A. The wires run from the microprocessor sensor connector J17 to the transducers. See the wiring diagram for details. If the voltage in step 6 checks good and continuity exists to the microprocessor on the HSPP, HSPN, DPI and/or SPI wires, replace the transducer. P41OD03A - 19 January 2000 D03A - Page 1