Powers Controls TT 184 Temperature Transmitters

Similar documents
POWERS CONTROL RC 195 Multiple Input Receiver- Controller

Powers TM Controls RL 243 SW Switching Relay

Powers Controls RL 147 Positioning Relay

Distributed By: M&M Control Service, Inc PRODUCT PRODUCT CODE RESOURCE DOCUMENTS PAGE #

POWERS TM CONTROLS LC Pneumatic Damper Actuator

TK-6024, TK-6124, TK-8024, TK-8124

Powers Controls Powermite Two-Way Flared Valves Normally Open/Normally Closed

Powers TM Controls VP 656 Powermite Three-way Mixing Valves (Flared Type)

Powers TM Controls SW 141 Differential Static Airflow Switches

Powers Controls Powertop Two-Way Valves Normally Open

Powers TM Controls SW 134 Pressure Electric Switch (Adjustable Differential)

POWERS TM CONTROLS SW 786 Selector Switch

Flowrite VF 599 Series Two-Way Valves 2-1/2 to 6-inch Flanged Iron Body

Flowrite TM AP 599 Series 8-inch Pneumatic Valve Actuator

Flowrite 599 Series Two-Way Valves, 1/2 to 2- inch Bronze Body, ANSI 250

Flowrite AP 599 Series

Powers TM Controls Three-way Electro-pneumatic (EP) Valve Model 2

Flowrite 599 Series High Pressure Close-Off 2-Way Valves, 2-1/2 to 6-Inch, Flanged Iron Body, ANSI Classes 125 & 250

Flowrite VF 599 Series Two-Way Valves 2-1/2 to 6-inch Flanged Iron Body

599 Series Zone Valve Bodies:

Flowrite 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

Flowrite 599 Series Two-Way Valves 1/2 to 2-inch Bronze Body

Flowrite 599 Series Two-Way Valves, 1/2 to 2- inch Bronze Body, ANSI 250

Pneumatic Controls. Pneumatic Controls Sections

Flowrite 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

Flowrite VF 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

Flowrite 599 Series. Technical Bulletin. 1/2 to 2-Inch Valve (2-Way & 3-Way) and Actuator Assembly Selection. Document No.

POWERS Controls No. 4 Pneumatic Damper Actuator

VE VVG Series Electronic Two-way Valves Normally Closed

Powers Controls No. 6 Pneumatic Damper Actuator

Powermite 599 MT Series Terminal Unit Valve and Actuator Assembly Selection

Powers Controls 656 Powermite Valve with 3-inch Top Rebuilding

Rebuild/Repack Kits for Flowrite VF 599 Series 2-1/2 to 6-inch Valves

Powermite 599 Series MT Series Terminal Unit Three-way Valves

Powers Controls No. 6 Damper Actuators Tandem Mounting

Powermite 599 Series MT Series Terminal Unit Two-way Valves

Powers Controls No. 4 Pneumatic Damper Actuator

Powermite 599 MT Series Terminal Unit Valve and Actuator Assembly Selection

Flowrite VF 599 Series Two-Way Valves 2-1/2 to 6-inch Flanged Iron Body

POWERS Controls. Technical Instructions Document No P25 AP December 3, No. 6 Pneumatic Damper Actuator.

Fisher 2506 and 2516 Receiver Controllers

Powers Controls Maximum Thrust Ratings of Pneumatic Damper Actuators

* T Temperature-Indicating Dial (Must be field set and calibrated to an actual thermometer)

Packing Replacement Kit for Flowrite VF 599 Series Valves

599 Series Zone Valve Bodies:

599 Series 6-Way Ball Valves

599 Series 2-Way Ball Valves

Accessories/Kits Ball Valve Bracket Kit (includes bracket, mounting screws, shaft and handle)

TEMPERATURE REGULATORS W91/W94 Series

Powers TM Controls RL 243 SW Switching Relay

Foxboro Dew Point Measurement System Model 2761 Mechanical DEWCEL Element Model 2781 Electrical DEWCEL Element

Pressure Independent Control Series

599 Series Ball Valve and Actuator Assemblies Selection

599 Series Ball Valve and Actuator Assemblies Selection

TKS-5001, TKS , TKS-6001, TKS-7001

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

W91/W94 Series TEMPERATURE REGULATORS. Self-Operated Temperature Regulators. Design & Operation W91 Non-Indicating W94 Dial Thermometer

SCC Inc. FLMTR Series. Installation Instructions Document No. LV February 21, KT-BMK-PLC Gas Flow Meter Kits for Flow Totalization

599 Series 2-Way Ball Valves

Pressure Independent Control Series

Distributed By: M&M Control Service, Inc Product Product Code Technical Instructions Page #

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

SAX Electronic Valve Actuator

STYLE B THERMOSTATIC TEMPERATURE REGULATOR

Laboratory Exhaust Air Terminal

Powermite 599 MT Series SQS Electronic Valve Actuator, 24 Vac, Floating Control (3-position)

SKP Series SKP15 U.. Gas Valve Actuator with Safety Shutoff Function

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Floating Control

Ball Valve Bracket Kit

Differential pressure switch for monitoring air pressure in HVAC systems.

Powermite 599 Series MZ Series SSB Electronic Valve Actuator 24 Vac Proportional Control

2211 Series. Application. Features. One-Pipe Pneumatic Room Thermostats General Instructions SPECIFICATIONS

L3 Pneumatic Level Controller

STYLE J COMBINATION PRESSURE AND TEMPERATURE REGULATOR

599 Series 2-Way Ball Valves

Self-Operating Temperature Regulators

Temperature Indicating Controller

Toroidal Conductivity Sensor

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

599 Series 2-Way Ball Valves

Fisher L3 Pneumatic Level Controller

Laboratory Room Single Duct Supply Air Terminal

SECTION AIR INTAKE SYSTEM

Rosemount TM 222 Toroidal Flow-Through Conductivity Sensor. Instruction Manual LIQ-MAN-222 Rev.D June 2017

SAX Electronic Valve Actuator

Powermite 599 Series MZ Series SSB Electronic Valve Actuator 24 Vac Floating Control

Auxiliary Equipment. Table of Contents. Auxiliary Equipment H-1. Product Product Code Technical Instructions Page #

Powers TM Controls EA 338 Electronic Actuator

Room Temperature Sensors Series to 20 ma

Model 40 Temperature Bulbs And Connections

SPANS AND RANGES. Lower Range Limits 150 in. H 2 O ( 38 kpa) 800 in. H 2 O ( 200 kpa)

Temperature Regulators

TECHNICAL INSTRUCTIONS

Operation and Maintenance Instructions Manual BOOSTER. Volume amplifier

2 1 /2" Glycerin-Filled Dual Scale Vacuum Gauges

Process Industry. Diaphragm Seal Solutions

SED2 Variable Frequency Drives

Technical Instructions Flowrite 599 Series SKD6xU Electronic Valve Actuators 24 Vac Proportional Control Description Features Application

Laboratory Room Controller

SAV Electronic Valve Actuator

Transcription:

Powers Controls Document No. 155-077P25 TT 184-1 Room Transmitter Remote Bulb Average Bulb Rigid Bulb Description The are direct acting, one-pipe instruments that sense temperature and transmit a proportional pneumatic signal. Normally, this signal is transmitted to a remotely located receiver gauge and/or receiver-controller. The receiver gauge would be calibrated to read directly in temperature. Features Rapid response to temperature changes over their full range Application Product Numbers See Table 1. lnternal feedback for excellent linearity and accuracy Variety of sensing elements and temperature ranges The temperature transmitters are ideal for applications requiring indication with a receiver gauge and/or control with a receiver-controller. Specifications Operating Action Output air pressure Ambient temperature range lnput (supply) air pressure: Restrictor size Calibration Pressure Maximum Thermal system: Room Rigid bulb Remote bulb Air consumption Direct acting 3 to 15 psi (21 to 103 kpa) 40 to 120 F (4.4 to 49 C) 40 scim (11 ml/s) 22 ± 1.0 psig (152 ± 6.9 kpa) 30 psig (207 kpa) Bimetal Rod and tube Liquid filled 35 scim (10 ml/s)

Specifications, Physical Mounting: Room Wall terminal Rigid bulb Mounting flange Remote bulb Mounting flange or well bracket mounting kit Averaging bulb Mounting flange Air connection 1/8-inch NPT Cover finish: Room Desert beige Rigid, averaging and remote bulb Gray Well See Table 2 Table 1. Product Numbers. Description Bulb & Capillary Product Number Rigid Bulb Transmitter Averaging Transmitter Remote Bulb Transmitter Remote Bulb Transmitter Room Transmitter (with 180-443A wall plate and 192-256 cover) 1/4-inch 9-inch (6.4 mm 229 mm) bulb 3/32-inch 20 feet (2.4 mm 6.1 m) averaging bulb 12-inch (0.305 m) capillary 1/4-inch 4-inch (6.4 mm 102 mm) bulb, 3 feet (0.92 m) capillary 1/4-inch 4-inch (6.4 mm 102 mm) bulb, 3 feet (0.92m) armored capillary Range (3-15 psig) (21-103 kpa) Max. Bulb Temperature 184-0001 35 to 135 F (1.7 to 57.2 C) 195 F (91 C) 184-0002 50 to 100 F (10 to 37.8 C) 130 F (54 C) 184-0003 80 to 240 F (27 to 116 C) 240 F (116 C) 184-0028 0 to 100 F (-18 to 37.8 C) 160 F (71 C) 184-0004 35 to 135 F (1.7 to 57.2 C) 184-0048 0 to 100 F (-18 to 37.8 C) 184-0005 - 40 to 120 F (-40 to 48.9 C) 184-0018 50 to 100 F (10 to 37.8 C) 184-0014 80 to 240 F (27 to 116 C) 184-0036 0 to 100 F (-18 to 37.9 C) 184-0015 -10 to 65 F (-23 to 18 C) 184-0034 35 to 135 F (1.7 to 57.2 C) 184-0006 - 40 to 120 F (-40 to 48.9 C) 275 F (135 C) 184-0340 50 to 100 F (10 to 37.8 ) Product Number Material Maximum Temperature F ( C) Table 2. Well Specifications. Max. Static Pressure psi (kpa) Max. Shock Pressure psi (kpa) Max. Fluid Velocity ft./sec. (m/s) Max. Steam Velocity ft./sec (m/s) 184-118 347 St. Steel 400 (204) 650 (4478) 1000 (6890) 25 (7.62) 84 (25.6) 184-119 Copper 265 (129) 250 (1722) 400 (2756) 10 (3.05) 84 (25.6) Page 2

Accessories Well bracket mounting kit 184-105 Packing nut 141-333 Restrictors for remote air supply 40 scim (11 ml/s) See (TB 167) (155-213P25) Outdoor bulb shield 929-043 Remote bulb holder kit 808-517 See TB 179 (155-217P25) for details Wall plate kit (room) 180-443A Operation The transmitter is provided with a restricted (40 scim) supply of air. Assume a rise in temperature at the transmitter sensing element. The free end of the bimetal, the rod and tube, or the liquid-filled element moves downward. This increases the load on the throttling pin (or throttling ball) and moves it closer to the nozzle. Pressure builds up in the chamber below the nozzle until the force of the increased air pressure against the bottom of the throttling pin exactly balances the downward force of the free end of the sensing element. Figure 1. Operation of the Room Transmitter. Figure 2. Operation of the Remote Bulb. Page 3

Operation, Figure 3. Operation of the Rigid Bulb. Installation Temperature transmitters may be mounted in any position on a vertical surface. Room Transmitters Installation may be made inside or outside of ducts and near fans, compressors, ducts, and air conditioning equipment. Transmitters, generally, are not affected by light vibration. Room transmitter mounting is shown in Figure 4. The dimensions of the room transmitter are shown in Figure 15. Use the wall plate kit provided with the room transmitter for any surface. See 1 TB 145 (5-210P25) for additional installation information. Figure 4. Mounting the Room Transmitter. Page 4

Installation, Rigid Bulb Rigid bulb transmitter mounting is shown in Figure 5. The transmitter is secured to the flange by a set screw. The dimensions of the rigid bulb transmitter are shown in Figure 14. When installing rigid bulb temperature transmitters on insulated ducts, the insulation must not cover any portion of the bulb (Figure 11). Incorrect installation of the rigid bulb can create a 16% of span error (for example, 8 F error using the 50 to 100 F transmitter). NOTE: If it is not possible to properly install a rigid bulb transmitter, then a remote bulb transmitter must be used. Figure 5. Rigid Bulb Mounting. Remote Bulb The remote bulb transmitter mounting is shown in Figure 6. Secure the transmitter to the flange by tightening the set screw. The well mounting of the remote bulb transmitter is shown in Figure 7. The set screw on the well secures the transmitter to the mounting plate. Dimensions for the remote bulb transmitter are shown in Figure 14. Page 5

Installation, Figure 6. Remote Bulb Mounting. Figure 7. Remote Bulb Mounting in a Well. Page 6

Installation, Figure 8. Outdoor Bulb Shield. S RESTRICTOR 40 SCIM GAUGE TRANSMITTER TR0065R1 CONTROLLER Figure 9. Typical Connections. Page 7

Components Table 3. Room Transmitter Parts (See Figure 10). Item Part No. Part Name No. Req'd. Material 1 Nozzle 1 Brass 2 Guard 1 Brass 3 Ball & stem assembly 1 Stainless steel 4 Bimetal & spring assembly 1 5 Mounting screw 2 Brass 6 182-159 Cover screw 2 Stainless steel 7 833-009 Seal screw 1 Bronze Figure 10. Room Transmitter. Figure 11. Installation on Insulated Ducts. Page 8

Installation, Table 4. Rigid and Remote Bulb Parts (See Figures 12 and 13). Item Part No. Part Name No. Req'd Material 1 Adjustment plate & spring assembly 1 Stainless steel 2 Preload spring 1 Music wire 3 Feedback ball seat 1 Brass 4 Ball 1 Stainless steel 5 Rigid bulb assembly 1 6 184-129 Filter 1 Foam 7 O-ring 1 Buna N 9 Capsule nest 1 Stainless steel 10 Compensator hub 1 Brass 11 Bimetal compensator 1 Bimetal 12 Thermal system, averaging bulb 1 Copper Thermal system, short bulb 1 Copper Thermal system, short bulb arm. cap. 1 Copper Figure 12. Rigid Bulb. Figure 13. Remote Bulb Page 9

Calibration Because of variations in lengths of pneumatic tubing, airflow through restrictors, ambient temperatures, etc., there will be small errors between actual temperature at sensing element and gauge indication. Adjusting the pointer on the receiver gauge to agree with the temperature at the sensing element will result in greater accuracy. Additional suggestions are given in the Table 5. The only way to determine if the temperature transmitter is out of calibration (either span adjust or zero adjust) is with an accurate two-temperature bath and an accurate pressure gauge. Span adjustment or zero adjustment cannot be made in the field because of the equipment and time required. Preventive Maintenance 1. Check yearly to see that temperature at sensing element agrees with temperature at gauge. See Calibration. 2. Periodically, clean dust from the transmitter body using a soft hairbrush. 3. Temperature transmitters do not require lubrication. Troubleshooting Table 5. Troubleshooting Chart. Complaint Check Probable Cause Corrective Action Low temperature indication High temperature indication Restrictor Receiver gauge temperature indication vs. temperature at sensing element Plugged restrictors Wrong size restrictor Receiver gauge out of calibration Clean and replace if clogged Replace restrictor Adjust receiver gauge Fittings and tubing Leak in transmitter line As necessary Filters Dirty Filter Replace filter Supply pressure Low supply pressure As necessary Receiver gauge temperature indication vs. temperature at sensing element Restrictor used Receiver gauge out of calibration More than one restrictor used. Both internal (in receivercontroller) restrictor and external restrictor installed Adjust receiver gauge Remove all but one restricted air supply Defective gasket on receivercontroller restrictor Wrong size restrictor Replace restrictor Replace restrictor Page 10

Dimensions Dimensions in Inches (Millimeters) Figure 14. Dimensions of the Rigid Bulb and Remote Bulb Transmitters. (Bulb Not Shown. See Table 1). Figure 15. Dimensions of the Room Transmitter. Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Powers is a registered trademark of Other product or company names mentioned herein may be the trademarks of their respective owners. 2005 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 U.S.A. Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor@siemens.com Document No. 155-077P25 Country of Origin: US Page 11