GV Standard 3 Wall Box Operation and Maintenance Manual

Similar documents
GV Standard Skyglide Operation and Maintenance Manual

GV Standard Sliding Over Roof Operation and Maintenance Manual

GV Standard Three Wall Box Operation and Maintenance Manual

GV Standard Pyramid Operation and Maintenance Manual

GV Chain Actuated VisionVent Patent GB

GV Standard Electric Pyramid

GV Standard Skydoor Installation Instruction Manual

SECEUROGLIDE ROLLER GARAGE DOORS, SECEUROSHIELD, SECEUROSCREEN & SECEUROVISION ROLLER SHUTTERS CONTENTS

Product Maintenance Guide

Tyre Pressure Monitoring System

Multi-colour LED Status Light - using it as a diagnostic tool:

Dedicated PIR Light Controller c/w RF remote control for LEDPRO Floodlights

Installation & Service Manual

Cleaning & Maintenance. For Aluminium Products

User Manual GRX- 950 and GRX- 950 Li

MP V 8A Electronic Smart Charger. Instruction and Information Manual

Installation and Service Manual M² Sync Room Slideout System without Room Lock Connectors on Control Box

40 V LITHIUM-ION BATTERY ATTACH YOUR RECEIPT HERE AB13786C 1. kobalttools.com ITEM # /

Battery Charger JCB-FCH20LI2

TIX402 EOS Installation and Operating Guide

Get Cleaning... User Guide Vax Careline: (UK) (ROI) Cordless Handheld. H90-LF Series. vax.co.uk

Ultra 5.0 Manufactured By Hanil Science Industrial Co., Ltd. In Korea

OPERATION AND MAINTENANCE MANUAL

Model S-777NA USER MANUAL. Please ensure this manual is read and understood before using the scooter.

LED Twister II. User manual UK Version 1.0

EN Instruction Manual

QuickBoost Instruction Manual

12 amp RMS Battery Charger

Tri-Spark Ignition System Installation Triple Cylinder TRI-0001

RAAS Troubleshooting Guide. Confirm that the power switch to the unit is in the on position.

Pan and Tilt Head CDD2416-T

Battery Charger JCB-FCH12Li

C15C C15C. Page 1 of 20

Model S888NR & Model S889NR USER MANUAL. Please ensure this manual is read and understood before using the scooter.

Installation. Aerada 1200 Series CS Faucet S Battery-Operated Capacitive Sensing Gooseneck Faucet IMPORTANT

MR5501 MR SAFE Adjustable Height Patient Trolley

Battery Charger JCB- SCH20LI.2

NCSA 20plus Service Manual

Lastolite Lastolite Lumen8 F200 Lumen8 F400 Stored Energy Guide Number (m/100iso) Recycling Time (100%) Flash Duration Flash Power

APT14 Automatic Pump Trap Installation and Maintenance Instructions

Features Technical Parameters

DEFOGGER SYSTEM PARTS LOCATION

PSU1 Power Supply Unit

Installation and Set Up Instructions

Car Battery Charger Instructions for Use

OWNER'S MANUAL WARNING DANGER. Propane cylinders sold separately. The propane cylinder must be disconnected when this firebowl is not use.

AC / 65 W M PLEASE READ BEFORE OPERATING THIS EQUIPMENT.

7 Handle Tubes. 10 Charging Jack 11 LED Indicator 12 ON/OFF button

MAC FAUCETS. FA400 Wall Mount Sensor

Operators Guide: RoboSign Stop/Go Traffic Control System

Installation and Service Manual M² Sync Room Slideout System without Room Lock Connectors on Control Box

Installation Instructions

Zonestar Installation Manual

Power Beam 20MCP Searchlight with 12 LED Area Light and Vehicle Jump Starter. Instruction Manual

Search by illustration

(K),(M)430TB/G Up to 36 kv

82V LITHIUM-ION BATTERY CHARGER GC 400

Back-Up Sensor System

CGD8800X CGD8800X220 Combustible Gas Detector

RECHARGEABLE PORTABLE EVAPORATIVE COOLER

READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

Model Number: CM-046. QUATTRO Handset Installation guide and user information. Ref: CM-046 UK-Rev.C.

HDE 500-A22. English. Printed: Doc-Nr: PUB / / 000 / 03

PRODUCT MANUAL 46ST (V.5.0) 46ST FS (V.5.0.F) 50ST (V.2.0) 50ST FS (V.2.0.F) RON-WPM ST/46STFS/50ST/50STFS-Rev.3

Use and Care Guide. Part # SC SV-OS-BZ SC SV-OS-W Model #

Oreck Magnesium Series Service Manual. The Oreck Manufacturing Company

Skippa Mobility Scooter Owner Manual

3KVA DUAL VOLTAGE GENERATOR MODEL NO: PG3800DV

WARNING. This product uses High Brightness LEDs. Direct viewing of the SMD LEDs at close range should be avoided. Keep product away from children.

INSTRUCTIONS FOR USE

Operators Guide: RoboSign Stop/Go Traffic Control System

6000DC Single 12V Motor Wireless Controller Kits With Extra Options

TL4076 Top 5 Tips Get to know your TL4076

General Information. Note : The aftertreatment DOC is integrated into the inlet of the exhaust aftertreatment system. WARNING

GLM SERIES CONTROL Users Manual Rev:

Operating Instructions For The X-Seal Manual Thermal Sealer

20V Lithium-Ion Battery Pack

WIRELESS TRI-JACK WIRELESS REMOTE KIT COMPONENTS LITERATURE NUMBER REV. C WARNING EXPLOSION WARNING PERSONAL INJURY & PROPERTY DAMAGE

15Amp Intelligent Battery Charger Suitable for SLA, Gel, Maintenance Free, AGM, Deep Cycle batteries

Thunder Power Tarp Kit Operation Guide

ALTERNATOR - BOSCH 35/75-AMP & 40/90-AMP

Electric Hi Lo Screen lift Trolley Mount 8960

PRODUCT MANUAL 52ST (V.4.0) 52ST FS (V.4.0.F) RON-WPM ST/52STFS-Rev.3

Application Guide for MasterSeal Sealants MasterSeal NP 430 MasterSeal CR 195

Aspen Lift Part Number Spectrum Lane ~ Missoula MT ~

WARNING: Read these instructions before using the machine GENERATOR MODEL NO: IG3500F PART NO: OPERATION & MAINTENANCE INSTRUCTIONS

Product Data Sheet : LIGHTHAWK 6 CELL

Installation Guide The RSi brief overview:

2 Ton - 50 Ton Bottle Jack

V3700UK OWNER S GUIDE.

PORTABLE ASPEN. Part Number 42643

Product Manual Manuel du Produit Manual del Producto

REMOTE CARAVAN MOVER Installation guide and user information. e-go /10/01/rev 3

MB V 3-IN-1 JUMP STARTER WITH SPIRAL WOUND BATTERY

Sectional And Tilting Door Opener

TIF8800X. Combustible Gas Detector. an spx brand. Owner s Manual. 99 Washington Street Melrose, MA Phone Toll Free

KWIKEE DOOR SWITCH STEP ACTIVATION INSTALLATION GUIDE ( )

These instructions are to be left with the user

Zip FlushMaster Solo Water Saver Urinal Flushing System Keeps Urinals Clean & Reduces Water Wastage

ALTERNATOR - CHRYSLER 40/90-AMP & 50/120 AMP

Transcription:

GV Standard 3 Wall Box Operation and Maintenance Manual Technical experts in the design, manufacture and supply of precision engineered, architectural rooflights for residential and commercial buildings.

TWB-O&M V2.0 19/10/2018 Page 2 of 8 GV Standard 3-Wall Box Rooflight Operation and Maintenance Manual Contents Section Description Page Contents & Introduction 2 Controls and Operation 3 Manual Override 4 Troubleshooting 5 Standard Glass Specification and Breakage Instruction 6 General Maintenance and Safety 7 Cleaning the 3 Wall Box 7 COSHH and Safe Disposal 8 Warranty Information 8 Introduction Thank you for purchasing a GV Standard 3-Wall Box (figure 1). We hope that it gives you many years of service. Should you have any queries beyond this manual, please do not hesitate to contact Glazing Vision. Figure 1 3 Wall Box

TWB-O&M V2.0 19/10/2018 Page 3 of 8 Controls and Operation Control switch The standard operation is via the supplied wall switch (figure 2) and can be operated using two different methods as explained below: Status light Figure 2 Control switch 1. One touch operation Press and release the control switch in either the up or down (open/closed) direction as required. The product will open or close fully. Press the control again to stop the product if you want it partially open or closed. 2. Press & hold operation Press and hold the control switch until the product has reached the position you want. When you release the switch the product will stop in that position. If you continue to press the switch the product will stop when it becomes either fully open or closed. Status light The status light (LED) will illuminate green if the product is working normally or intermittent green when closing due to rain. If the status light displays another colour please refer to the troubleshooting section. Remote Control (Optional): The remote control unit (figure 3) functions in the same way as the control switch allowing the rooflight to be opened and closed from a short distance away. The remote control is powered by one long life A23 12V battery. The battery cover plate is found on the rear of the remote and can be accessed by pushing down and sliding the rear cover to one side. Figure 3 Remote control Building management (Optional): The 3-Wall box can be connected to a building management system. Please contact Glazing Vision Ltd for further details if required. Rain sensor (optional): The rain sensor (figure 4) automatically closes the rooflight when it rains. If moisture is detected on the rain sensor when rooflight is opened, a special built in heater activates for 60 seconds to evaporate standing water. If after 60 seconds water is still detected, the rooflight will close. This feature enables the rooflight to differentiate between rain and standing water / morning dew. Figure 4 Rain sensor

TWB-O&M V2.0 19/10/2018 Page 4 of 8 Manual Override The 3-Wall box is equipped with a manual override function. This is an emergency fail safe should the unit not open or close for any reason. The override hole is located internally on the treadplate approximately 250mm from the centre of the rooflight (figure 5). Figure 5 Manual override location To override the electric mechanism, insert a 6mm Allen key (supplied with the rooflight) through the hole and engage with the corresponding hexagonal feature on the override. Rotate the Allen key in a clockwise direction to disengage the motor. To engage the motor, rotate the Allen key in an anti-clockwise direction. If you have trouble rotating the Allen key fully, gently rock the sliding section back and forth to engage/disengage the drive. If a solenoid bolt is fitted, this will also need to be disengaged before the door can be opened. This can be done simply by unscrewing the solenoid bolt from the framework, taking care to not disrupt the cables. When fully disengaged, the rooflight will be able to be pushed by hand to open or close it, however it will not be secure.

TWB-O&M V2.0 19/10/2018 Page 5 of 8 Troubleshooting The 3-Wall Box control board monitors the operation of the rooflight. If a fault is detected, the board will stop the rooflight to prevent possible damage. Fault and standard conditions are indicated by the status light on the control switch (figure 2). The table below shows the various status light displays and their meanings. Although the rooflight will still operate following detection of a fault please observe the status displayed and attempt to resolve the issue with the suggested action. Avoid operating rooflight if fault persists. In this case, contact Glazing Vision for further assistance. Status light shown: Continuous Green Intermittent Green Continuous Red Intermittent Red Continuous Blue Intermittent Blue Continuous Yellow Meaning: Lit whilst the rooflight is in motion under the control of the operate switch or remote control with no faults present. If the rooflight is one-touch opened or closed LED will remain lit until motion stops. Flashes whilst the rooflight is in motion but not under control of the operate switch or remote control. Flashing will stop when motion stops. (i.e. whilst controlled by rain sensor) Lit whilst the battery is at low level (regardless of whether mains is present or not). The control system will ignore requests to open from sealed state. Rooflight will close but not open. Lit whilst the rooflight is in motion and no mains is present. To tell you there is a power failure and the batteries are not being charged. Rooflight will open and close for a limited number of operations. Indicates a seal timeout, opening timeout or closing timeout condition. LED remains lit, if mains is present, until control switch is pressed. Indicates an over-current or undercurrent condition. Flashes, if mains is present, until control switch is pressed. Indicates that a safety device is active, preventing rooflight operation. If a fault occurs please refer to the table below. Some faults with the unit may be easily corrected without the need for a site engineer, however if you are unsure, please contact Glazing Vision Ltd. Status Light Shown Possible Cause Action Continuous Green No action required (No Fault) Intermittent Green (No Fault) No action required Continuous Red (Low Battery) Intermittent Red (Mains supply absent) Continuous Blue (Sealing Fault) Batteries are at low level, possibly coming to the end of their service life. No mains electricity is getting to the rooflight. Is there a mechanical obstruction preventing the sliding frame from moving? Is the sliding frame frozen to the base? Has the rooflight been left inactive for a long period (a month or longer)? Check that the mains electrical supply is switched on and connected to the rooflight. Leave rooflight for 24 hours then check status again. If fault persists, contact Glazing Vision. Reconnect mains electrical supply to rooflight. If possible, look at the mechanisms and remove any obvious obstructions. Attempt to open the rooflight once ice has melted. A sealing fault is likely after a long period of inactivity. If fault persists, contact Glazing Vision.

TWB-O&M V2.0 19/10/2018 Page 6 of 8 Intermittent Blue (Over-current) 3 Wall Box opens or closes for no apparent reason. Is there a mechanical obstruction preventing the sliding frame from moving? This should only occur if a rain sensor or building management system is fitted. Remove any obstruction preventing movement and try again. If fault persists contact Glazing Vision. When either of these devices activates your rooflight the status LED will flash green. This is not a fault condition. Standard Glass Specification and Breakage Instructions Glass Specification The standard glass used within the 3 Wall Box comprises a 6mm toughened outer pane, a 16mm argon filled silicone sealed cavity and a 6mm soft coat Low E coated toughened inner pane. However, various options are available at time of order. If specific data is required for the glazing please contact Glazing Vision for a glass data sheet for the specification installed within your product. Breakage Instructions Should the double glazed unit break for any reason, due to the unique method of bonding the glass unit into the frame, new framework may need to be supplied. Glass breakage is not covered in the product warranty unless the breakage is a direct result of Glazing Vision Limited or its product failing. In the event of the glass being damaged please contact Glazing Vision for assistance.

TWB-O&M V2.0 19/10/2018 Page 7 of 8 General Maintenance & Safety To keep the 3 Wall Box in good working order there are a few basic points that should be observed: Do not place anything on the lid or cause obstruction to the lid of the 3 Wall Box when opening the unit as this may cause damage to the unit s mechanisms. Do not walk or sit on the unit. Make sure fingers and other obstructions are clear of the rooflight before closing the unit (although there is a circuit board overload cut out, damage/injury may be caused). Do not allow unauthorised persons (e.g. children) to operate the rooflight as this may lead to injury or damage to the product. It is recommended that a general inspection is carried out on the unit wherever possible at least once every 6 months. Glazing Vision, if required, can offer a service / maintenance contract. Please contact our office for further details. Keep the frame clear of general dirt and debris particularly around the opening mechanism. Do not use any abrasives or aggressive cleaners on the painted framework or glass of the unit as this may affect the finishes. Cleaning the 3 Wall Box Due to the 3-Wall boxes unique bonding method and the built in pitch, there should be no water ponding on the glass when installed correctly. Any standard glass-cleaning product can be used to clean the glass unit. However take care not to use abrasive materials or cleaners as this may affect the unit and its finish. The framework of the unit can be cleaned using warm soapy water with a soft lint free cloth.

TWB-O&M V2.0 19/10/2018 Page 8 of 8 COSHH and Safe Disposal The battery and control electronics are the only hazardous materials used in the construction of the 3-Wall box. Wherever possible when disposing of the 3-wall box recycle as much as possible and dispose of the batteries correctly. Do not burn any plastic materials. The following materials are used throughout the 3-wall box: Framework Aluminium sheets and angles EPDM rubber gaskets Polyester powder coated finish PVC foam tape Stainless steel fixings Polyethylene backing rod Upvc solid bar Toughened glass panes Low modulus silicone Aluminium spacer bar Polypropylene brush strip Hardwood insulation Closed cell PIR foam insulation Mechanisms and control Stainless steel fixings Printed circuit board Stainless steel bearings SPST rocker switch Magnetic reed switches (various) Copper wiring Standard insulated spade terminals Electric motor (various) Stainless steel push switch (access) Product Warranty A warranty document will be provided with the product. If this is misplaced it can be found at www.glazingvision.co.uk/resources/warranties/.