G83/2 Engineering Recommendation

Similar documents
Solar Grid tied inverter. Power-One Italy S.p.A. Via S. Giorgio 642, Terranuova Bracciolini (AR) - Italy. P acr [W] P acmax [W]

Harmonic current emissions as EN Harmonic Test Value in Amps % of fund Limit value in Amps

Technical Requirements for Renewable Energy Power System

SolarMax S series (United Kingdom) Maximising solar plant yields can be so easy.

Jiangsu Zeversolar New Energy CO.LTD Building 9 No.198, Xiangyang Road, Suzhou, PEOPLE'S RE- PUBLIC OF CHINA

Certificate of Conformity self-generation unit

Certificate of Conformity self-generation unit

Certificate of Conformity self-generation unit

Certificate of Conformity self-generation unit

SA Power Networks Commissioning Witnessing Checklist

TEST REPORT DIN V VDE V

GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS

Smart connections. Certificates. PIKO-Inverter

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

BANGALORE ELECTRICITY SUPPLY COMPANY LIMITED

TEST REPORT DIN V VDE V

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Enquiry Form (Non-Registered Generator With Capacity less than 5 MW)

Development of Power Conditioner with a Lithium Ion Battery

AS/NZS AS/NZS

Standards, Procedures and Policies for Grid Connection

APPLICATION ELECTRICITY SERVICES. APPLICATION FOR THE CONNECTION OF SMALL SCALE EMBEDDED GENERATION Page 1

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM

Large Embedded Generation User Guide A

GUIDELINES FOR OPERATING, METERING AND PROTECTIVE RELAYING FOR. NET METERED SYSTEMS UP TO 50 kw AND BELOW 750 VOLTS

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Compliance of Solar PV Installation with the New Renewables SA Grid Code Jimmy Goulding, Electrical Technologist, Aurecon, South Africa

Time Electronics DC Multifunction Voltage/Current/Resistance Calibrator. Technical Manual

Jemena Electricity Networks (Vic) Ltd

Enquiry Form for Micro and Small Generators 5MW and Less

NRS 097-series / Grid Code Discussion:

WP2 - CFD Private Network Meter Commissioning, Proving and Calibration Tests

C08-00A. Model: C08-00A. Product Data Sheet 8mm Linear Resonant Actuator - 3mm Type. Ordering Information. Key Features. Datasheet Versions

Power conversion systems for energy storage. Engineering that stores

UL-EU CERTIFICATE EN :2006/A1:2010, EN :2006/A2:2013, EN :2006. Certificate No. UL-EU Page 1/6 Date of Issue

UTILITY ASPECTS OF GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

GEatom306KHF-5U Three-phase Grid-Tied Battery Inverter. Version 1.1. Global Mainstream Dynamic Energy Technology Ltd. 1

RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY

Guidelines for connection of generators:

PVES Series User Manual User Manual Shenzhen Pvinergy Technologies Co., Ltd

Requirements on Minimum Energy Performance Standard and Energy Efficiency Rating Labelling and Inspection of Air Compressors (draft)

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Guidelines for the Design of Residential and Community Level Storage Systems Combined with Photovoltaics (PV)

TANZANIA BUREAU OF STANDARDS

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management

DEEP SEA ELECTRONICS PLC

REQUIREMENTS FOR GRID INTERCONNECTION OF RENEWABLE GENERATION SYSTEMS

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER

Connecting your home or small business generation

Elmdene International Ltd

PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION

CHECK LIST FOR REGISTRATION FORM

Copyright 2003 Advanced Power Technologies, Inc.

Micro Embedded Generating Units (0-30 kva)

Connecting your business diesel generation

DEEP SEA ELECTRONICS PLC

INVERTER APPROVAL FOR INSTALLATION IN ISRAEL

702 AUTOMATIC START MODULE OPERATING INSTRUCTIONS

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

PQstorI One stop solution for energy storage and power quality

WIND ENERGY DENMARK

I t n e t l e l l i l g i e g n e t n So S l o a l r a Ch C a h r a g r e g Co C n o t n r t o r l o l l e l r U e s r e s Man an al

DT33B/C/D OPERATOR S MANUAL LIMITED WARRANTY AND LIMITATION OF LIABILITY

Technical specifications

Distributed Generation Interconnection Policy

On and Off Grid Interactive Features AC Coupling

Advanced Small Cell with XP Technology

Installation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies

Installation and user manual. 5SC 500i 5SC 750i 5SC 1000i 5SC 1500i ENGLISH. Copyright 2013 EATON All rights reserved.

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Electric Vehicle Charging Safety Guidelines Part 1: Safety Fundamentals Edition DRAFT

Power Systems Trainer

RULES & REGULATIONS FOR RENEWABLE GENERATION SYSTEMS 2. SUMMARY OF APPLICATION AND INTERCONNECTION PROCESS

Session 3 - Mitigating economic repercussions of fluctuating voltage and consumption peaks

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor Installation Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

500 / 630 / 720 / 760 / 800 / 850 / 900

Testing procedure for the evaluation of grid compliance of power generating units according to the requirements of the Indian Grid Code

Form C Renewable Energy Micro-Generation Connection Application Distribution System

Output Current Input Current Reflected Ripple. VDC VDC ma ma(typ.) ma(typ.) ma(typ.) VDC μf %

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

Maxwell s Highest Power and Energy Cell

Technical Requirements for Export Limiting Schemes

Use of Microgrids and DERs for black start and islanding operation

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances

Delta Products VFD CP2000 Bypass Control Packages.

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

Model: Product Data Sheet Pico Vibe. 3mm Vibration Motor - 8mm Type. Key Features. Ordering Information. Datasheet Versions

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.

The 4HR-UPS 220V ac output is provided via a Pure Sine Wave inverter, allowing it to be backed up by 2x 12V standby batteries.

2-Color Display High-Precision Digital Pressure Switch

SINGLE VOLTAGE EXTERNAL POWER SUPPLY TEST REPORT

Impact Analysis of Off-board Charger to Power Quality

Ningbo Inyan Solar Technology Co.,Ltd

Transcription:

G83/2 Engineering Recommendation Certificate Number: TR002007 001 Type Approval and manufacturer/supplier declaration of compliance with the requirements of Engineering Recommendation G83/2. Type reference number Generating Unit technology System supplier name Address PVI4000TL Photovoltaic Grid Tied Inverter Trannergy Co., Ltd. No. 188 Weiwu Rd, Shanghai 201802, China Tel 0086 021 38953908 Tel 0086 021 38953908 E:mail xujm@trannergy.com E:mail xujm@trannergy.com Connection Option 3.65 kw single phase, single, split or three phase system Maximum rated kw three phase capacity, use separate sheet if more than one connection option. kw two phases in three phase system kw two phases split phase system manufacturer/supplier declaration. I certify on behalf of the company named above as a manufacturer/supplier of Small Scale Embedded Generators, that all products manufactured/supplied by the company with the above Type referencee number will be manufactured and tested to ensure that they perform as stated in this Type Verification Test Report, prior to shipment to site and that no site modifications are required to ensure that the product meets all the requirements of G83/2. Signed On behalf of Trannergy Co., Ltd. Note that testing can be done by the manufacturer of an individual component, by an external test house, or by the supplier of the complete system, or any combination of them as appropriate. Where parts of the testing are carried out by persons or organisations other than the supplier then the supplier shall keep copies of all test records and resultss supplied to them to verify that the testing has been carried out by people with sufficient technical competency to carry out the tests.

Power Quality. Harmonics. The requirement is specified in section 5.4.1, test procedure in Annex A or B 1.4.1 rating per phase (rpp) 3.65 kw NV=MV*3.68/rpp Harmonic At 45-55% of rated Normalised Value Value (MV) in (NV) in 100% of rated Value (MV) in Normalised Value (NV) in Limit in BS EN 61000-3-2 in Higher limit for odd harmonics 21 and above 2 0.053 0.053 0.066 0.066 1.080 3 0.076 0.076 0.064 0.064 2.300 4 0.021 0.021 0.007 0.007 0.430 5 0.139 0.140 0.077 0.078 1.140 6 0.007 0.007 0.007 0.007 0.300 7 0.141 0.142 0.029 0.029 0.770 8 0.007 0.007 0.012 0.012 0.230 9 0.069 0.069 0.059 0.060 0.400 10 0.006 0.006 0.010 0.010 0.184 11 0.039 0.039 0.087 0.088 0.330 12 0.008 0.008 0.022 0.022 0.153 13 0.057 0.057 0.044 0.044 0.210 14 0.007 0.007 0.023 0.023 0.131 15 0.100 0.101 0.038 0.038 0.150 16 0.007 0.007 0.015 0.016 0.115 17 0.126 0.127 0.044 0.044 0.132 18 0.010 0.010 0.008 0.008 0.102 19 0.115 0.115 0.074 0.075 0.118 20 0.015 0.015 0.014 0.014 0.092 21 0.102 0.103 0.103 0.104 0.107 0.160 22 0.015 0.015 0.013 0.013 0.084 23 0.081 0.082 0.018 0.018 0.098 0.147 24 0.010 0.010 0.010 0.011 0.077 25 0.024 0.024 0.036 0.036 0.090 0.135 26 0.013 0.013 0.019 0.020 0.071 27 0.024 0.024 0.050 0.051 0.083 0.124 28 0.011 0.011 0.016 0.016 0.066 29 0.020 0.020 0.042 0.043 0.078 0.117 30 0.007 0.007 0.023 0.023 0.061 31 0.019 0.019 0.023 0.024 0.073 0.109 32 0.008 0.008 0.004 0.004 0.058 33 0.018 0.018 0.011 0.011 0.068 0.102 34 0.006 0.006 0.010 0.010 0.054 35 0.020 0.020 0.034 0.035 0.064 0.096 36 0.008 0.008 0.006 0.006 0.051 37 0.025 0.026 0.023 0.023 0.061 0.091 38 0.006 0.006 0.005 0.006 0.048 39 0.035 0.035 0.033 0.033 0.058 0.087 40 0.010 0.010 0.005 0.005 0.046 Note the higher limits for odd harmonics 21 and above are only allowable under certain conditions, if these higher limits are utilised please state the exemption used as detailed in part 6.2.3.4 of BS EN 61000-3-2 in the box below.

Power Quality. Voltage fluctuations and Flicker. The requirement is specified in section 5.4.2, test procedure in Annex A or B 1.4.3 Starting Stopping Running d max d c d (t) d max d c d (t) P st P lt 2 hours Values Normalised to standard impedance and 3.68kW for multiple units Limits set under BS EN 61000-3-2 0.38 0.28 0.32 1.65 0.28 0.32 0.225 0.185 0.38 0.28 0.32 1.65 0.28 0.32 0.225 0.185 4% 3.3% 3.3% 4% 3.3% 3.3% 1.0 0.65 500ms 500ms Test start date 2014.12.08 Test end date 2014.12.08 Test location Floor 2, Building 2, No. 188, weiwu Road, jiading District, Shanghai Power quality. DC injection. The requirement is specified in section 5.5, test procedure in Annex A or B 1.4.4 Test power 10% 55% 100% level Recorded value 5.5mA 7.6mA 9.8mA as % of 0.03% 0.05% 0.06% rated AC current Limit 0.25% 0.25% 0.25% Power Quality. Power factor. The requirement is specified in section 5.6, test procedure in Annex A or B 1.4.2 216.2V 230V 253V at three voltage levels and at full. Voltage to be maintained 0.995 0.997 0.996 within ±1.5% of the stated level during value the test. Limit >0.95 >0.95 >0.95 Protection. tests The requirement is specified in section 5.3.1, test procedure in Annex A or B 1.3.3 Function Setting Trip test tests Time Time /time Confirm no trip U/F stage 1 47.5Hz 20s 47.49 Hz 18S 47.7Hz 25s

U/F stage 2 47Hz 0.5s 46.99 Hz 0.4S 47.2Hz 19.98s 46.8Hz O/F stage 1 51.5Hz 90s 51.51 Hz 88S 51.3Hz 95s O/F stage 2 52Hz 0.5s 52.01 Hz 0.4S 51.8Hz 89.98s 52.2Hz Protection. Voltage tests The requirement is specified in section 5.3.1, test procedure in Annex A or B 1.3.2 Function Setting Trip test tests Voltage Time Voltage Time Voltage Confirm no trip /time U/V stage 1 200.1V 2.5s 200.1V 2.4S 204.1V 3.5s U/V stage 2 184V 0.5s 184.0V 0.4S 188V 2.48s 180V O/V stage 1 262.2V 1.0s 262.2V 0.9S 258.2V 2.0s O/V stage 2 273.7V 0.5s 273.7V 0.4S 269.7V 0.98s 277.7V Note for Voltage tests the Voltage required to trip is the setting ±3.45V. The time can be measured at a larger deviation than the minimum required to operate the protection. The tests need to be carried out at the setting ±4V and for the relevant times as shown in the table above to ensure that the protection will not trip in error. Protection. Loss of Mains test. The requirement is specified in section 5.3.2, test procedure in Annex A or B 1.3.4 To be carried out at three power levels with a tolerance of plus or minus 5% in Test Power levels. Test Power 10% 55% 100% 10% 55% 100% Balancing load on islanded network Trip time. Limit is 0.5 seconds 0.380S 0.365S 0.420S 0.395S 0.340S 0.405S Protection. change, Stability test The requirement is specified in section 5.3.3, test procedure in Annex A or B 1.3.6 Start Change End Confirm no trip Positive Vector Shift 49.5Hz +9 degrees

Negative Vector Shift 50.5Hz - 9 degrees Positive drift 49.5Hz +0.19Hz/sec 51.5Hz Negative drift 50.5Hz -0.19Hz/sec 47.5Hz Protection. Re-connection timer. The requirement is specified in section 5.3.4, test procedure in Annex A or B 1.3.5 Test should prove that the reconnection sequence starts after a minimum of 20 seconds for restoration of voltage and frequency to within the stage 1 settings of table 1. Time setting Checks on no reconnection when voltage or frequency is brought to just outside stage 1 limits of table 1. 30 32 At 266.2V At 196.1V At 47.4Hz At 51.6Hz Confirmation that the does not re-connect. No-reconnect Fault level contribution. The requirement is specified in section 5.7, test procedure in Annex A or B 1.4.6 For a directly coupled For a Inverter Parameter Symbol Value Time Volts after fault Peak Short Circuit current i p - 20ms 33.5 0.56 Initial Value of aperiodic current Initial symmetrical shortcircuit current* Decaying (aperiodic) component of short circuit current* Reactance/Resistance Ratio of source* A - 100ms 32.8 0.38 I k - 250ms 32.5 0.25 i DC - 500ms 31.6 0.16 X / R Time to trip 0.085S In seconds