K35 HeatBloC with 3-temperature mixing valve

Similar documents
Installation and Operation Instructions K38 HeatBloC - DN 32

Installation and Operation Instructions HeatBloC K31 - DN 25

Installation and Operation Instructions K31 HeatBloC - DN 50

Installation and Commissioning Instructions High Temperature Zone Module F31-1" (DN 25)

Catalogue

Product range Solex Technical data and dimensioning. 5 Years

Pump Stations for Heating Circuits

Catalogue Smart system technology for modern heating, solar thermal systems & domestic hot water technology.

Catalogue Solar stations DN 20. Solar thermal solutions. Valid for the UK

HERZ-Motorised flow controler

Pump group DN 25 SA, SMTC, SMT. Mounting and operating instruction

Pump group DN 32 SA, SMT. Mounting and operating instruction

HERZ PUMPFIX HERZ PUMPFIX. Datasheet 1 45XX XX, Issue Table of contents. Page 1. General information about HERZ PUMPFIX pump groups...

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/14 GB

CALEFFI. Motorised temperature regulating unit for heating and air conditioning systems WYP UPM series 01254/17 GB

CALEFFI. Manifolds in composite specifically designed for radiant panel systems. 670 series 01126/05 GB. Function

COMPONENTS FOR SOLAR THERMAL SYSTEMS

DISTRIBUTION GROUP WITH THERMOSTATIC REGULATION. Upper connections G1 F Without fittings Fittings with running connection* Without pump

Preassembled manifolds with flow meter, series CPRFL

Floor heating manifold with automatic flow control

CALEFFI. Composite manifolds specifically designed for radiant panel systems. 670 series 01126/18 GB. replaces dp 01126/11 GB.

Installation and Operating Manual for Tank and Equipment Cleaning Nozzles Series 5TM

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/18 GB. replaces 01260/14 GB

HERZ 7217 V. Integral Fixed Orifice Control Valve HERZ 7217 V. Data sheet 7217 V, Issue Size in mm. STRÖMAX Fig No DN L Lm Rp H SW kv kvs

EN Operating manual. Motorised zone valve. Three-way, 22 mm & 28 mm 3PV2, 3PV8 & VRMH3

Zone manifold DN 25, DN 32, DN 50. Mounting and operating instructions

COMPONENTS FOR SOLAR THERMAL SYSTEMS

Dynacon. Floor Heating Manifolds Floor heating manifold with automatic flow control

OPERATION AND INSTALLATION

Operating Instructions Flexdip CYA112

SBS Manual for the specialised craftsman. Filling and flushing station. Connection Operation. en Manual

Lowara Ecocirc Vario (EV)

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions

BA 46 BA 46-ASME BA 47 BA 47-ASME BAE BAE ASME BAE BAE ASME

Operating instructions ErgoPack 600 E

FCU Floor Control Unit

M-8100EP. Installation Guide ENGINEERED PLASTIC MANIFOLD SERIES. Introduction. A. Assemble Manifold Components

Operating manual. ba55321de LRD Conductivity measuring cell to be installed in pipelines. ba55321de01 12/00

Exchange of rollers from the XTS-Mover

Stud Gun Automatic Stud Gun EP-8, EP-9, EP-10

Pressure relief valve

HKV 1 1/4 in. Brass Manifold Product instructions. Construction Automotive Industry

Valves, controls + systems Stations for the connection heat generator/heating circuit

V5032. Kombi-2-plus Manual double regulating balancing valve. Product specification sheet

ON SAFEGUARD S ON SAFEGUARD M

Operating Instructions Ball Valves

Overview of types. Characterised control valves, 3-way, with internal thread For closed cold and warm water systems

THERMOSETTER Recirculation thermal balancing valve

Operating instructions - Translation of the original -

CALEFFI. Pre-assembled distribution manifolds for radiant panel systems. series 663 & /05 NA. Function

dynacon floor heating manifold with automatic flow control

3 & 4-Way Rotary Valves

M Installation Guide. PRECISION Manifold Series. Introduction. A. Assemble Manifold Components

TBM Series 3-Way Ball Valve

SOLAR THERMAL EQUIPMENT

CALEFFI. Direct supply unit for heating systems. 165 series 01237/17 GB. replaces dp 01237/15 GB. Function

PRO-BALANCE 1 1/4 IN. BRASS MANIFOLD. Product Instructions

T2 Wall Hung Radiator & UFH Manifolds

The valves can be controlled electronically by thermal actuators or act as self-acting units by means of remote temperature adjusters.

Installation and Operating Instructions Magnetic Vibrator MR 1

RESOL SBS 1000 * * Connection Operation

Manifold Isolation Valves

DN [ ] DN [ ] Functional data Media Cold and hot water, water with glycol up to max. 50% vol.

CEGA SYSTEMS BY GREGGERSEN

HERZ-Connect 4 / Compact Connect 4 & Commissioning Centres

HST -LS Interlocking device (Translation of Original Manual)

LK Manifold Shunt VS 2-2,5

CALEFFI. Pre-assembled distribution manifolds for. heating and air-conditioning systems. 663 series 01065/18 GB. replaces dp 01065/06 GB.

CALEFFI. Modulating temperature regulating unit with distribution kit for primary circuit. 171 series 01153/15 GB. replaces 01153/07 GB

underfloor heating PRODUCTS FOR UNDERFLOOR HEATING

KLINGER Piston Valves KVN DN PN 16 I/III with valve ring KX-GT Modul

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

CETOP POSITION PAPER PP 07

OPERATING INSTRUCTIONS

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Product range. Technical specifications. Characteristic components

Inazuma Installation and Operating Instructions INAZUMA HD PRO UV-C. High-Performence Duo UVC Lamp

TECHNICAL INSTRUCTIONS

4017 M HERZ Dimensions in mm

The information in this instruction manual is subject to modifications without prior notice and is the exclusive property of Zorzini.

Product Catalog Evacuated tube collectors CPC OEM CPC w OEM

EASY!Force trigger gun, rotary knob, spray lance, PowerControl spray lance Service Manual

Operating Instructions

Zone manifold DN 25, DN 32, DN 50. Mounting and Operating Instructionsi

Technical Instructions

Products for underfloor heating

Instructions for Fitting, Operating and Maintenance

Components for central heating

Drive Unit e-drive1. Installation instructions 04/2014. English translation of the original German installation instructions

SOLAR THERMAL Forced circulation solar thermal system with selective flat plate collectors SELECTIVE SLIM

SOLAR AEROLINE. fast simple reliable. The perfect connection technology for solar hot water

CALEFFI. Pre-assembled distribution manifold for radiant panel systems S1 series 01144/11 GB. Replaces 01144/07 GB.

savings flexibility recyclable LIGHTNESS FULL FLOW MECHANICAL STRENGTH IMPROVE CONTROL TECHNICAL BROCHURE aesthetic performance CHANGE

Repair Manual Ford DPS6 Gearbox. INA GearBOX

Valves, controls + systems Valves and controls for solar installations Regusol-180

MANIFOLDS & WATER TEMPERATURE CONTROL

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Important Product range Technical specifications

PRODUCTS FOR HEATING AND TAP WATER SYSTEMS. Product Catalogue

Installation, Operation, and Maintenance Manual

Operating Instructions

SonoSensor 30 Ultrasonic flow meter for heating and cooling applications

Transcription:

PAW GmbH & Co. KG Böcklerstr. 11, D-31789 Hameln, Germany Phone: +49-5151-9856-0, Fax: +49-5151-9856-98 E-mail: info@paw.eu, Web: www.paw.eu Installation and Operation Instructions K35 HeatBloC with 3-temperature mixing valve 2012/10 9936092x-mub-en V07 1

1 General information Contents 1 General information... 3 1.1 Scope of these instructions... 3 1.2 Designated use... 3 2 Safety instructions... 4 3 Product description... 5 3.1 Equipment... 5 3.2 Function... 6 3.2.1 3-temperature mixing valve [specialist]... 7 3.2.2 Change of the flow line [specialist]... 8 3.2.3 Check valve and non return valve [specialist]... 11 3.3 Optional equipment: actuator [specialist]... 12 4 Assembly and installation [specialist]... 13 4.1 Accessories: compression fitting (not included in delivery)... 13 4.2 Assembly of the HeatBloC... 14 5 Scope of delivery [specialist]... 16 6 Technical data... 17 6.1 Pressure drop and pump characteristics... 18 Item no. 9936092x-mub-en Version V07 Issued 2012/10 Translation of the original instructions We reserve the right to make technical changes without notice! Printed in Germany Copyright by PAW GmbH & Co. KG PAW GmbH & Co. KG Böcklerstr. 11 31789 Hameln, Germany 2 9936092x-mub-en V07 2012/10

1 General information 1 General information 1.1 Scope of these instructions These instructions describe the installation, commissioning and operation of the K35 HeatBloC with 3-way mixing valve. For other components of the heating system such as pumps, controllers or distribution manifolds, please observe the instructions of the corresponding manufacturer. The chapters called [specialist] are intended for specialists only. 1.2 Designated use The HeatBloC may only be used in hydronic heating closed-loop systems taking into consideration the technical limit values indicated in these instructions. The HeatBloC must not be used in domestic water applications. Improper usage excludes any liability claims. Only use PAW accessories with the HeatBloC. The wrapping materials are made of recyclable materials and can be disposed of with recyclable materials. 2012/10 9936092x-mub-en V07 3

2 Safety instructions 2 Safety instructions The installation and commissioning as well as the connection of electrical components require technical knowledge commensurate with a recognised vocational qualification as a fitter for plumbing, heating and air conditioning technology, or a profession requiring a comparable level of knowledge [specialist]. The following must be observed during installation and commissioning: relevant local and national regulations accident prevention regulations of the professional association instructions and safety instructions mentioned in this manual CAUTION Personal injury and damage to property! The HeatBloC must only be used in hydronic heating closed-loop systems filled with heating water according to VDI 2035 / Ö-Norm H 5195-1. The HeatBloC must not be used in domestic water applications. NOTICE Material damage due to mineral oils! Mineral oil products cause lasting damage to seals made of EPDM, whereby the sealant properties are lost. We do not assume liability nor provide warranty for damage to property resulting from sealants damaged in this way. It is imperative to avoid that EPDM gets in contact with substances containing mineral oils. Use a lubricant based on silicone or polyalkylene and free of mineral oils such as Unisilikon L250L and Syntheso Glep 1 of the Klüber company or a silicone spray. 4 9936092x-mub-en V07 2012/10

3 Product description 3 Product description The K35 HeatBloC is a preassembled fitting group for hydronic heating closed-loop systems. The HeatBloC is designed such that it can be directly mounted onto a mounting plate with thread connections or onto a distribution manifold. The distance between the pipe axis and the wall must be at least 10 cm, as the connection C-3 is on the back side of the mixing valve. 3.1 Equipment A-1 Flow to the consumer circuit A-2 Full metal thermometer with immersion sleeve integrated in the ball valve (flow) B C Heating pump 3-temperature mixing valve C-1 High-temperature flow from the buffer tank C-2 Return to the buffer tank C-3 additional connection on the back side of the mixing valve, for supply of the low-temperature flow C-4 Non return valve, can be opened D-1 Check valve, can be opened D E Return pipe Design insulation with optimised function F-2 Full metal thermometer with immersion sleeve integrated in the ball valve (return) F-1 Return from the consumer circuit Rear view of the mixing valve with flow on the right 2012/10 9936092x-mub-en V07 5

3 Product description 3.2 Function K35-3-temperature mixing valve with additional connection for a second flow temperature The 3-temperature mixing valve is used in combination with a buffer tank, which can be heated by either a solar thermal installation, a solid fuel boiler or a conventional boiler. If the consumer only needs a low temperature level, such as radiant panel heating systems, the 3-T mixing valve first takes the the flow water from the intermediate part of the storage tank. When the temperature in this part is no longer sufficient, the hot water from the upper part of the tank is used. By using two parts of the storage tank for two different flow temperatures, the energy from the buffer tank can be used more efficiently. The return temperatures are low and the stratification in the tank is maintained. Applications: Heating systems with buffer tank and solar heating support Control of radiant floor or wall heating Assembly with radiator circuit 6 9936092x-mub-en V07 2012/10

3 Product description 3.2.1 3-temperature mixing valve [specialist] The 3-temperature mixing valve driven by an electric motor adjusts the flow temperature of the consumer circuit to the desired value in combination with a flow sensor and the controller. The 3-temperature mixing valve is equipped with a second flow connection (C-3) on the back side. This connection allows to take water with a low flow temperature from the intermediate part of the tank (for example a buffer tank). Rear view of the mixing valve with flow on the right Position 0-5: Position 5: The flow temperature is attained by mixing return water and water from the intermediate part of the tank 100% supply from the intermediate part of the tank Front view of the mixing valve with flow on the right Position 5-10: The flow temperature is attained by mixing water from the intermediate part and the upper part of the tank 2012/10 9936092x-mub-en V07 7

3 Product description 3.2.2 Change of the flow line [specialist] Dismounting the mixing valve 1. Take off the thermometer handles (A-2, F-2) and remove the insulating front shell. 2. Take the HeatBloC out of the insulating back shell. 3. Dismount the mixing valve (C). Conversion of the mixing valve 1. Unscrew the screw (1). 2. Take the rotary knob (2) off the rod of the cock. 3. Unscrew the screw (3). 4. Take off the cover plate (4). 5. Unscrew the two screws (5). 6. Remove the front plate (6). 7. Extract the sealing bush (7) and the valve cock (8) from the mixing valve body. 8. Unscrew the screws (10) on the back side of the mixing valve and take off the cover (9). 9. Pull the sealing plug (11) to the front using pliers. Remove the flow-reducing plate (12) by pushing from front to back. 8 9936092x-mub-en V07 2012/10

3 Product description 10. Turn the body of the mixing valve by 180. 11. Mount the flow-reducing plate (12) on the back side and the sealing plug (11) on the front. Assembly position for mixing valve with flow on the left 12. Mount the cover (9) on the back side of the mixing valve. The letters on the cover indicate the correct assembly position: flow on the left: L points upwards flow on the right: R points upwards 13. Fix the cover (9) using the screws (10). 14. Insert the sealing bush (7) and the valve cock (8) into the channel of the mixing valve. 15. Fix the front cover (6) with the screws (5). Assembly position for mixing valve with flow on the right Flow Flow Mixing valve with flow on the right Mixing valve with flow on the left 16. Turn the cover plate (4) such that the designation PAW is at the bottom and the scale is located as can be seen in the figure above. 17. Fix the cover plate (4) with the screws (3). 18. Put the rotary knob (2) onto the cock rod. 19. Fix the rotary knob (2) to the cock (8) with the screw (1). 2012/10 9936092x-mub-en V07 9

3 Product description Modification and commissioning of the heating circuit 1. Interchange the return pipe (D) and the flow pipe and the pump (B). Consider the flow direction of the pump! Turn the pump head such that the terminal head is directed to the top or to the centre of the HeatBloC. 2. Dismount and interchange the ball valves. 3. Mount the HeatBloC and connect it to the installation. 4. Check all union nuts before commissioning and firmly tighten them if necessary. 5. Mount the insulation after the pressure test. Mount the thermometer handles (A-2, F-2). 10 9936092x-mub-en V07 2012/10

3 Product description 3.2.3 Check valve and non return valve [specialist] The HeatBloC is equipped with a check valve (D-1, opening pressure 200 mm wc) in the return pipe and a non return valve (C-4, opening pressure 50 mm wc) in the mixing valve return. They can be opened manually. Operation During operation, both marks must point to "Z" (closed). The check valve and the non return valve are closed. Flow only in the direction of the arrow. Filling, emptying, bleeding For filling, emptying and bleeding the mark must be directed to "A". The check valve and the non return valve are open. Flow in both directions. 2012/10 9936092x-mub-en V07 11

3 Product description 3.3 Optional equipment: actuator [specialist] The PAW actuator for weather-compensated control is available as an accessory. For mixing valves with flow on the left, the scale must be turned by 180. for mixing valves with flow on the right for mixing valves with flow on the left Assembly of the actuator for mixing valves with flow on the right: 1. Turn the rotary knob of the mixing valve to position 0. 2. Set the actuator to manual mode by turning the selector switch. 3. Turn the rotary lever of the actuator to the left to the position shown in the figure. 4. Put the actuator onto the rotary knob of the mixing valve and the two stop bolts. 5. Set the actuator to automatic mode. Stop bolt 12 9936092x-mub-en V07 2012/10

4 Assembly and installation [specialist] 4 Assembly and installation [specialist] The K35 HeatBloC must be either installed on a set of wall bracket and mounting plate or a modular distribution manifold. The wall bracket and the mounting plate (item no. 3422SET) or the distribution manifold are not included in delivery. The distance between the pipe axis and the wall must be at least 10 cm, as the connection C-3 is on the back side of the mixing valve. NOTICE Damage to property! The location of installation must be dry, load-carrying, frost-proof and protected against ultraviolet radiation to prevent material damage to the installation. 4.1 Accessories: compression fitting (not included in delivery) The connection to the heating installation can be carried out fast, pressure-proof and without soldering when you use the optionally available compression fittings. 1. Push the union nut 2 and the cutting ring 3 onto the copper pipe 1. The pipe must protrude at least 3 mm from the cutting ring in order to ensure the force transmission and the sealing. 2. Insert the support sleeve 4 into the copper pipe. 3. Insert the copper pipe with the plugged-on individual parts (2, 3 and 4) all the way into the housing of the compression fitting 5. 4. First screw the union nut 2 manually. Not included in the scope of delivery! 5. Tighten the union nut 2 by rotating one full turn. Secure the housing of the compression fitting 5 against distort in order to avoid damaging the sealing ring. 2012/10 9936092x-mub-en V07 13

4 Assembly and installation [specialist] 4.2 Assembly of the HeatBloC 1. Mount the wall bracket with mounting plate. Flange (top view) 2. Take off the thermometer handles and remove the insulating front shell of the HeatBloC. 3 2 1 Nut 3. Unscrew the nuts on the lower connections of the HeatBloC and take out the sealing rings. 4. Flip the two nuts over the flanges. Flange (side view) 5. Insert the sealing rings into the nuts. Sealing ring 6. Put the HeatBloC onto the two nuts. 7. Tighten the nuts. Take care that the nuts do not get jammed and that the sealing rings do not slip. 14 9936092x-mub-en V07 2012/10

4 Assembly and installation [specialist] 8. Connect the HeatBloC to the installation. The connections to the installation must be stress-free. 1 - flow from the upper part of the storage tank 2 - return to the storage tank 3 - flow from the intermediate part of the storage tank (connection on the back of the mixing valve) 4 - return from the consumer 5 - flow to the consumer 9. Connect the pump. 10. Carry out the pressure test and check all thread connections. 11. Mount the insulating front shell and the thermometer handles. 2012/10 9936092x-mub-en V07 15

5 Scope of delivery [specialist] 5 Scope of delivery [specialist] NOTICE Complaints and requests/orders of spare parts will only be processed with information on the serial number! The serial number can be found on the return pipe of the heating circuit. Item no. E1236046 Equipment Pump Wilo-Yonos PARA RS 25/6-RKA E1239625 Pump Wilo-Stratos PICO 25/1-6 E121390 Pump Grundfos Alpha2 L 25-60 E121391 Pump Grundfos Alpha2 25-60 G705001 Actuator SR5 37013 Sealing set for mixing valve 3422SET 36092KS2 36092KS3 Wall bracket set (wall bracket and mounting plate) Pipe set for connecting the connections on the back of the mixing valves of two K35 HeatBloCs (for example for assembly on a PAW distribution manifold). Pipe set for connecting the connections on the back of the mixing valves of three or more K35 HeatBloCs 16 9936092x-mub-en V07 2012/10

6 Technical data 6 Technical data K35 DN 25 (1") Dimensions Centre distance (1) 125 mm Width insulation (2) 250 mm Height insulation (3) 396 mm Installation length (4) 345 mm Connections Upper connections (A-1, F-1) 1" internal thread Lower connections (C-1, C-2) 1½" external thread Connection on the back (C-3) 1" external thread Technical data Opening pressure check valve (D-1) 200 mm wc, can be opened Opening pressure non return valve (C-4) 50 mm wc, can be opened Materials Valves and fittings Brass Gaskets EPDM / NBR Insulation EPP 2012/10 9936092x-mub-en V07 17

6 Technical data K35 DN 25 (1") Hydraulics Maximum pressure 8 bars Maximum temperature 110 C 6.1 Pressure drop and pump characteristics Pressure [m wc] Pressure [kpa] Flow rate [l/h] (1) 100% return, Kvs value = 4.1 (2) 100% low-temperature flow, Kvs value = 4.35 (3) 100% high-temperature flow, Kvs value = 4.65 18 9936092x-mub-en V07 2012/10

2012/10 9936092x-mub-en V07 19

PAW GmbH & Co. KG Böcklerstraße 11 D-31789 Hameln, Germany www.paw.eu Phone: +49 (0) 5151 9856-0 Fax: +49 (0) 5151 985698 9936092x-mub-en V07 2012/10