k VS DN (mm) Connections ( C) (m 3 /h)

Similar documents
Differential pressure controller (PN 16, 25, 40) AFP(-9) / VFG 2(1) return and flow mounting, adjustable setting

Flow controller (PN 16, 25, 40) AFQ / VFQ 2(1) - return and flow mounting

Differential pressure relief controller (PN 16, 25, 40) AFPA / VFG 2(1)

Pressure relief controller AFA / VFG 2(1) (PN 16, 25, 40)

Flow Control and Differential Pressure Controller AFPQ / VFQ 2(21) - Installation in return line AFPQ 4 / VFQ 2(21) - Installation in flow line

Flow controller (PN 25) AVQ - return and flow mounting

Flow controller (PN 25) AVQ - return and flow mounting

Differential pressure controller AFP / VFG 2 (VFG 21)

Pressure reduction controller AFD / VFG 2, VFG 21, VFGS 2

Pressure reduction controller AFD / VFG 2, VFG 21, VFGS 2

Differential pressure controller AFP / VFG 2 (VFG 21)

Differential pressure relief controller AFPA / VFG 2 (VFG 21)

Differential pressure controller AFP / VFG 2 (VFG 21)

Flow controller with integrated control valve (PN 16) AHQM return and flow mounting

Pressure reduction controllers (PN 25) AVDS - for steam AVD - for water

Pressure relief controller AVA (PN 25)

AVQMT. AVQT controller can be combined with AVT or STM thermostatic actuators.

Data sheet Pressure independent control valve with integrated flow limiter AVQM (PN 16) - return and flow mounting

Flow controller with integrated control valve (PN 16) AVQM - return and flow mounting

Differential pressure controller with flow limitation and with integrated control valve (PN 16) AHPBM-F flow mounting, fixed setting

Flow controller with integrated control valve (PN 16) AHQM - return and flow mounting

Pressure independent control valve with integrated flow limiter AVQM (PN 16) - return and flow mounting

Two- and three way valves VFG.. / VFGS 2 / VFU.. for self-acting thermostats and electrical actuators

Pressure relief controller for oil V22D28 (PN 16, 25)

Temperature controller for heating (PN 25) AVT / VG - external thread AVT / VGF - flange

2 - way valve (NO), pressure relieved (PN 25) VG - external thread VGF - flange

Temperature controller (PN 25) AVT / VG - external thread AVT / VGF - flange

Temperature controller AVT with safety temperature monitor STM/VG(F) (PN25)

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

Seated valves (PN 16) VF 2-2-way valve, flange VF 3-3-way valve, flange

Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange

Temperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25)

Seated valves (PN 16) VRB 2 2-way valve, internal and external thread VRB 3 3-way valve, internal and external thread

Flow-compensated temperature controller AVTQ DN 15

ZONE CONTROLE / 2-WAY

Seated valves (PN 16) VRB 2 2-way valve, internal and external thread VRB 3 3-way valve, internal and external thread

Seated valves (PN 16) VRG 2 2-way valve, external thread VRG 3 3-way valve, external thread

DA 50. Differential pressure controllers Adjustable set-point

Seated valves VF 2, VL 2-2-way VF 3, VL 3-3-way

Butterfly valve with electrical actuator VFY-WA

Butterfly valve with electrical actuator VFY-WA

Pressure independent balancing and control valve

Your Personal Catalog Temperature Controllers All our know-how - is now yours

Thermostatic actuator RAVI - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16)

Static Balancing Valve

Pressure independent balancing and control valve For ON/OFF control

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Pressure independent balancing and control valve AB-QM DN

Automatic balancing valves ASV-PV DN (3rd gen.)

2, 3 and 4 - way valves VZL

Self-operated Pressure Regulators Type Universal Pressure Reducing Valve

Series 240 Pneumatic On-off Valve Type 3351

Series 240 Type 3351 Pneumatic On/off Valve

Combined automatic balancing valve AB-PM valve DN 10-32, PN 16

Series 02: DN40 and DN50 Series 01: DN Three-port slipper valves PN6

Typetested versions With Type 3213 Globe Valve, unbalanced. With Type 3214 Globe Valve, balanced

Series 240 Electric Control Valve Type 3241/3274 Globe Valve Type 3241 Electric Control Valve Type 3244/3274 Three-way Valve Type 3244

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Pressure relief controller V22 D28

Series 46 Self-operated Regulators Differential Pressure and Flow Limiters Type 46-5 Type 46-6

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Pressure independent balancing and control valve AB-QM DN

ANSI version. The valve closes when the differential pressure rises

Combined automatic balancing valve AB-PM valve DN 15-25, PN 16

Maintenance-free metallic seat shut-off globe valves

Valve Series V2001 Three-way Valve Type 3323

Combined Self-operated Regulators Regulators for Differential Pressure, Flow Rate and Temperature

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

Self-operated Temperature Regulators Temperature Regulator Type 1u

HERZ-Motorised flow controler

Pressure reducing valve Pressure reducing valve in straightway form DN

3-port seat valves PN16 with flanged connection

Maintenance-free metallic seat shut-off globe valves

ARI-STEVI 423 / 463 (DN ) Control valve - 3-way-form (mixing/diverting valve) (optional with screwed seat ring)

Excess pressure regulator Excess pressure regulator, straight through DN

ARI-STEVI 423 / 463 Pneumatic actuator ARI-DP 34-34T. Electric actuator ARI-PREMIO 5-25 kn ARI-PREMIO-Plus 2G 5-25 kn

Pneumatic Butterfly Valve Type 3335 / AT

Technote. Frese YDF-2F & YDF-20F - differential pressure control valve. Application. Benefits. Features.

Self-operated Temperature Regulators Type 1u Temperature Regulator

SELF-ACTUATING DIFFERENTIAL PRESSURE AND FLOW REGULATORS TYPE ZSN91; 92

Series 42 Self-operated Regulators. Type RS Check Valve (backflow protection)

ARI-STEVI 450 / 451 (DN15-150) Control valve - 3-way-form (mixing/diverting valve) (optional with screwed seat ring)

Control valves with pneumatic actuators up to 350 C PN

Data Sheet T EN

Pre-Fabricated Flushing Bypass Assembly for Plant Applications Hero Plant DN15-150

High capacity valve body, type RA-G

Butterfly valves PN6, PN10, PN16

Pressure Reducing Valve Type 2114/2415

ARI-STEVI 450 / 451 (DN15-150) Control valve - 3-way-form (mixing/diverting valve) (optional with screwed seat ring)

ARI-STEVI 450 / 451 Pneumatic actuator ARI-DP 32-34T. Electric actuator ARI-PREMIO 2,2-25 kn ARI-PREMIO-Plus 2G 2,2-25 kn

Butterfly valves PN 16

3-port valves vxf42..

2-port ball valves with flanged connection, PN25

STAF, STAF-SG. Balancing valves PN 16 and PN 25 DN

Fan-coil valves Series

Type 1a Globe Control Valve

VALFONTA PRESSURE REGULATOR WITHOUT AUXILIARY ENERGY EXCESS PRESSURE VALVE (PRESSURE RELIEF VALVE) MODEL S1 MAIN CHARACTERISTICS

Pressure Independent Control Valve AB QM, ½ thru 2 2½ thru 4 5 thru 10 Valve Size

3-port seat valves PN6 with flanged connection

2-way and 3-way globe valves

Transcription:

Data sheet Differential pressure and flow controller (PN 16, 25, 40) AFPQ / VFQ 2( - return mounting, adjustable setting AFPQ 4 / VFQ 2( - flow mounting, adjustable setting Description The controller has a control valve with adjustable flow restrictor, an actuator with two control diaphragms and spring for differential pressure setting. Differential pressure control and flow control are independent. Further on two valve versions are available: VFQ 2 with metallic sealing cone VFQ 21 with soft sealing cone (on special request) The controller is a self-acting differential pressure and flow controller primarily for use in district heating systems. The controller closes on rising differential pressure or when set max. flow is exceeded. Main data: DN 15-250 k VS 4.0-400 m 3 /h Flow range: 0.1-250 m 3 /h PN 16, 25, 40 Setting range: 0.1-0.7 bar / 0.15-1.5 bar Flow restrictor p b : 0.2 bar or 0.5 bar Temperature: Circulation water / glycolic water up to 30 %: 2 150/200 C Connections: Flange Ordering Example 1: Differential pressure and flow controller; return mounting; DN 15; k VS 4.0; PN 16; metallic sealing; setting range 0.1-0.7 bar; flow restrictor p b 0.2 bar; T max 150 C; flange; 1 VFQ 2 DN 15 valve Code no: 065B2654 1 AFPQ actuator Code no: 003G1029 1 AFPQ DN 15 impulse tubes Code no: 003G1365 1 Impulse tube set AF Code no: 003G1391 Products will be delivered separatly. VFQ 2 Valves (metallic sealing cone) Picture DN (mm) k VS (m 3 /h) 15 4.0 Connections T max ( C) Code No. T max Code No. PN 16 ( C) PN 25 PN 40 065B2654 065B2667 065B2677 20 6.3 065B2655 065B2668 065B2678 25 8.0 065B2656 065B2669 065B2679 32 16 065B2657 065B2670 065B2680 40 20 065B2658 065B2671 065B2681 150 200 50 32 065B2659 065B2672 065B2682 65 50 Flanges acc. to EN 1092-1 065B2660 065B2673 065B2683 80 80 065B2661 065B2674 065B2684 100 125 065B2662 065B2675 065B2685 125 160 065B2663 065B2676 065B2686 150 280 065B2664 065B2687 200 320 150 065B2758 150 065B2688 250 400 065B2759 065B2689 At temperatures above 150 C only with seal pots (see Accessories) Impulse tubes AFPQ Impulse tube set AF Danfoss 2018.05 VD.CA.A6.02 1

Ordering (continuous) Example 2: Differential pressure and flow controller; return mounting; DN 15; k VS 4.0; PN 25; metallic sealing; setting range 0.1-0.7 bar; flow restrictor p b 0.2 bar; T max 200 C; flange; 1 VFQ 2 DN 15 valve Code no: 065B2667 1 AFPQ actuator Code no: 003G1029 1 AFPQ DN 15 impulse tubes Code no: 003G1365 1 Impulse tube set AF Code no: 003G1391 1 Seal pot V1 Code no: 003G1392 Products will be delivered separatly. Seal pot V1 Impulse tubes AFPQ Impulse tube set AF Example 3: Differential pressure and flow controller; flow mounting; DN 15; k VS 4.0; PN 25; metallic sealing; setting range 0.1-0.7 bar; flow restrictor p b 0.2 bar; T max 200 C; flange; 1 VFQ 2 DN 15 valve Code no: 065B2667 1 AFPQ actuator Code no: 00G1033 4 Impulse tube set AF Code no: 003G1391 3 Seal pot V1 Code no: 003G1392 Products will be delivered separatly. Impulse tube set AF Seal pot V1 Impulse tube set AF AFPQ / AFPQ 4 Actuators Picture Accessories p setting range (bar) 0.1-0.7 0.15-1.5 Flow restrictor p b (bar) 0.2 Picture Type designation For controller Impulse tubes 3) (Stainless steel) AFPQ AFPQ 4 Nominal pressure (PN) AFPQ (return) 003G1029 Code No. AFPQ 4 (flow) 003G1033 0.5 003G1030 003G1034 40 0.2 003G1031 003G1035 0.5 003G1032 003G1036 DN (mm) 15 20 25 32 PN Code No. 003G1365 003G1367 40 003G1369 50 16, 25, 40 003G1370 65 80 003G1371 100 003G1373 125 003G1374 150 003G1375 200 250 15 20 25 32 16 003G1416 40 003G1376 16 003G1417 40 003G1405 003G1378 003G1380 40 003G1382 50 16, 25, 40 003G1383 65 80 003G1384 100 003G1386 125 003G1387 150 003G1388 200 250 16 003G1418 40 003G1389 16 003G1419 40 003G1406 Picture Type designation Description Ordering number Code No. port B port A 4) Impulse tube set AF Seal pot V1 Compression fitting 2) Combination piece KF3 Combination piece KF2 1 Copper tube Ø10 1 1500 mm 1 compression fitting for imp. tube connection to pipe (G 1/4) 2 socket Capacity 1 liter; with compression fittings for imp. tube Ø10 For impulse tube Ø10 connections to controller For combination with pressure actuators. Electrical actuator connected on side (port B) only for ON/OFF function For combination with thermostat - side connection to port B 003G1391 AFPQ 1 AFPQ 4 3 G 1/4 G 11/4 / 2 G 11/4 003G1392 003G1468 003G1397 003G1398 Shut off valve Throttle valve For impulse tube Ø10 003G1401 065B2909 Seal pot has to be used on impulse tubes always when T max 150 C 2) Consist of a nipple, compression ring and nut 3) With combination piece KF2 or KF3 use 2 003G1391 at PN 16 and T<150 C. Otherwise impulse tubes on special request. 4) Port A - for connection of any type of actuator 2 Danfoss 2018.05 VD.CA.A6.02

Ordering (continuous) Service kits Picture Type designation For valve Valve insert VFQ 2 Stuffing cone (with EPDM O-rings) DN (mm) k VS (m 3 /h) Code No. 15 4.0 065B2796 20 6.3 065B2797 25 8 32 16 40 20 50 32 65 50 80 80 100 125 125 160 065B2798 065B2799 065B2800 065B2801 150 280 065B2964 250 400 065B2965 003G1464 Technical data Valve Nominal diameter DN 15 20 25 32 40 50 65 80 100 125 150 200 250 k VS value of p controller Range of max. flow setting 4.0 6.3 8.0 16 20 32 50 80 125 160 280 320 400 from 0.1 0.2 0.2 0.4 0.6 0.8 3 4 6 8 12 15 18 p b = 0.2 bar to m 3 /h 2 3 4 7 11 16 28 40 63 80 125 150 180 p b = 0.5 bar from 0.2 0.3 0.3 0.5 0.8 1.2 4 6 9 12 18 22 25 to 3 4.5 6 10 16 24 40 58 90 120 180 220 250 Cavitation factor z 0.6 0.6 0.6 0.55 0.55 0.5 0.5 0.45 0.4 0.35 0.3 0.2 0.2 Leakage acc. to standard IEC 534 (% of k VS ) VFQ 2 0.03 0.05 VFQ 21 0.01 Nominal pressure PN 16, 25, 40 Min. differential pressure for max flow 2) Max. differential pressure p b = 0.2 0.5 0.4 0.5 0.4 0.5 0.4 p b = 0.5 0.8 0.7 0.8 0.7 0.8 0.7 bar PN 16 16 15 12 10 PN 25, 40 20 Media Circulation water / glycolic water up to 30 % Media ph Min. 7, max. 10 Media temperature Connections Materials Valve body VFQ 2 2 150/2 200 3) C 2 150 VFQ 21 2 150 PN 16 PN 25 Flange Grey cast iron EN-GJL-250 (GG-25) Ductile iron EN-GJS-400(GGG-40.3) PN 40 Cast steel GP240GH (GS-C 25) Valve seat Stainless steel, mat. No. 1.4021 Stainless steel, mat. No. 1.4313 Valve cone Stainless steel, mat. No. 1.4404 Sealing VFQ 2 VFQ 21 Metal EPDM Stainless steel, mat. No. 1.4021 Pressure relieve system Bellows (Stainless steel, mat. No. 1.457 Diaphragm (EPDM) p b differential pressure over flow restrictor 2) Q For flows smaller than Q max -> pmin pb k VS 3) at temperatures above 150 C only with seal pots (see Accessories) 2 VD.CA.A6.02 Danfoss 2018.05 3

Technical data (continuous) Actuator Type AFPQ, AFPQ 4 Actuator size cm 2 250 Nominal pressure PN 40 Flow restrictor diff. pressure p b Diff. pressure setting ranges and spring colours Materials Actuator housing Control diaphragm bar 0.2 / 0.5 0.1-0.7 0.15-1.5 yellow Steel, mat. No.1.0338, zinc plated EPDM (Rolling; fibre enforced) red Application principles Return mounting Direct-connected heating system Indirectly connected heating system Flow mounting Direct-connected heating system Indirectly connected heating system 4 Danfoss 2018.05 VD.CA.A6.02

Combinations Example: Differential pressure, flow and temperature controller, return mounting; DN 15; k VS 4.0; PN 16; metallic sealing; setting range 0.1-0.7 bar; flow restrictor p b 0.2 bar; T max 150 C; flange; 1 VFQ 2 DN 15 valve Code no: 065B2654 1 AFPQ actuator Code no: 003G1029 3 Impulse tube set AF Code no: 003G1391 1 AFT06 thermostat Code no: 065-4390 1 Combination piece KF2 Code no: 003G1398 Products will be delievered separatelly. Note: For AFT 06 thermostat data see relevant data sheet AFT 06 / KF2 / AFPQ / VFQ2 Differential pressure, flow and temperature controller, return mounting AFT 06 / KF2 / AFPQ 4 / VFQ2 Differential pressure, flow and temperature controller, flow mounting Installation positions DN 15-80 T max 120 C The controllers can be installed in any position. DN 15-80 T max > 120 C; DN 100-250 The controllers can be installed in horizontal pipes only, with a pressure actuator oriented downwards. DN 15-80 T max 120 C DN 15-80 T max > 120 C; DN 100-250 VD.CA.A6.02 Danfoss 2018.05 5

Pressure temperature diagram Working area is below P-T line and it ends at Tmax for each valve PN 16 EN-GJL-250 (GG-25) Maximum allowed operating pressure as a function of media temperature (according to EN 1092-2) PN 25 EN-GJS-400 (GGG-40.3) Maximum allowed operating pressure as a function of media temperature (according to EN 1092-2) PN 40 EN-GP-240-GH (GS-C 25) Maximum allowed operating pressure as a function of media temperature (according to EN 1092-6 Danfoss 2018.05 VD.CA.A6.02

Sizing Directly connected heating system Example 1 Motorised control valve (MCV) for mixing circuit in direct-connected heating system requires differential pressure of 0.3 bar (30 kpa) and flow less than 1.900 l/h. Given data: Q max = 1.9 m 3 /h (1.900 l/h) p min = 0.9 bar (90 kpa) p circuit = 0.1 bar (10 kpa) p MCV = 0.3 bar (30 kpa) selected 2) p b = 0.2 bar (20 kpa) Remark: p circuit corresponds to the required pump pressure in the heating circuit and is not to be considered when sizing the AFPQ(4). 2) p b is differential pressure over flow restrictor. The differential pressure set value is: p set value = p MCV p set value = 0.3 bar (30 kpa) The total pressure loss across the controller is: p AFPQ = p min p MCV = 0.9 0.3 p AFPQ = 0.6 bar (60 kpa) Possible pipe pressure losses in tubes, shut-off fittings, heatmeters, etc. are not included. k v value is calculated according to formula: Qmax 1,9 k v p p 0,6 0,2 AFPQ k v = 3.0 m 3 /h b Solution: The example selects AFPQ 4 DN 15, k VS value 4.0, with differential pressure setting range 0.1-0.7 bar, flow setting range 0.1-2.0 m 3 /h. Q max Δp min AFPQ Δp circuit Δp b Δp AFPQ Δp MCV AFPQ 4 Q max Δp min Δp circuit Δp b Δp AFPQ Δp MCV VD.CA.A6.02 Danfoss 2018.05 7

Sizing (continuous) Indirectly connected heating system Example 2 Motorised control valve (MCV) for indirectly connected heating system requires differential pressure of 0.3 (30 kpa) bar and flow less than 1.800 l/h. Given data: Q max = 1.8 m 3 /h (1.800 l/h) p min = 1.0 bar (100 kpa) p exchanger = 0.05 bar (5 kpa) p MCV = 0.3 bar (30 kpa) selected p b = 0.2 bar (20 kpa) Remark: p b is differential pressure over flow restrictor The differential pressure set value is: p set value = p exchanger + p MCV p set value = 0.05 + 0.3 p set value = 0.35 bar (35 kpa) The total pressure loss across the controller is: p AFPQ = p min p exchanger p MCV p AFPQ = 1.0 0.05 0.3 p AFPQ = 0.65 bar (65 kpa) Possible pipe pressure losses in tubes, shut-off fittings, heatmeters, etc. are not included. k v value is calculated according to formula: Qmax 1,8 kv p p 0,65 0,2 AFPQ k v = 2.7 m 3 /h b Solution: The example selects AFPQ 4 DN 15, k VS value 4.0, with differential pressure setting range 0.1-0.7 bar, flow setting range 0.1-2.0 m 3 /h. Q max Δp min AFPQ Δpexchanger Δp b Δp AFPQ Δp MCV AFPQ 4 Q max Δp min Δpexchanger Δp b ΔpAFPQ Δp MCV 8 Danfoss 2018.05 VD.CA.A6.02

Design 1. Valve body 2. Cover 3. Adjustable flow restrictor 4. Valve seat 5. Valve insert 6. Pressure relieved valve cone 7. Valve stem 8. Bellows for pressure relief of valve cone 9. Diaphragm for pressure relief of valve cone 10. Actuator 11. Control diaphragm for flow control 12. Control diaphragm for diff. pressure control 13. Excess pressure safety valve 14. Built-in spring for flow control 15. Setting spring for diff. pressure control 16. Adjuster for diff. pressure setting, prepared for sealing 17. Stuffing cone 18. Union nut 19. Impulse tube 20. Compression fitting for impulse tube 21. Upper casing of diaphragm 22. Lower casing of diaphragm 23. Valve body extension 24. Shut off valve for water filling 25. Closing plug 12 20 20 19 10 3 1 4 6 7 5 8 2 17 18 21 14 11 13 22 15 16 AFPQ VFQ 2(, DN 15-125 19 20 10 AFPQ 4 VFQ 2(, DN 15-125 3 1 4 6 7 5 8 2 17 18 21 14 11 13 12 22 15 16 2 9 VFQ 2( DN 150-250, T max 150 C 25 23 9 24 2 VFQ 2 DN 150-250, T max 200 C Function Flow volume causes pressure drop across the adjustable flow restrictor. Resulting pressures are being transferred through the impulse tubes to the actuator chambers and act on control diaphragm for flow control. The flow restrictor diff. pressure is controlled and limited by means of built-in spring for flow control. Control valve closes on rising differential pressure and opens on falling differential pressure to control max flow. Pressure changes from flow and return pipes are being transferred through the impulse tubes to the actuator chambers and act on control diaphragm for diff. pressure control. The diff. pressure is controlled by means of setting spring for diff. pressure control. Control valve closes on rising differential pressure and opens on falling differential pressure to maintain constant differential pressure. Controller is equipped with two excess pressure safety valves, which protect control diaphragms for flow and diff. pressure control from too high differential pressure. Setting Flow setting Flow setting is being done by the adjustment of the flow restrictor position. The adjustment can be performed on the basis of flow adjustment diagram (see relevant instructions) and/or by the means of heat meter. Differential pressure setting Differential pressure setting is being done by the adjustment of the setting spring for diff. pressure control. The adjustment can be done by means of adjuster for diff. pressure setting and pressure indicators. VD.CA.A6.02 Danfoss 2018.05 9

Dimensions L L H B B 2 VFQ DN 15-125 L A ø60 ø89 H 1 B3 120 H SW 22 78 110 Shut off valve Ø10 40 B H B 2 B 1 VFQ DN 150-250 VFQ DN 150-250 with valve body extension up to 200 C VFQ 2, VFQ 21 Valves DN 15 20 25 32 40 50 65 80 100 125 150 200 250 L 130 150 160 180 200 230 290 310 350 400 480 600 730 B 213 213 239 239 241 241 276 276 381 381 326 354 401 mm B 2 124 124 135 135 152 152 164 164 194 194 269 332 355 H 337 337 374 374 393 393 440 440 575 575 595 686 756 Weight B 1 PN 16 / 25 28.5 31 61 71 120 193 337 kg 8 9 10.5 12.5 15.5 18.5 PN 40 31 34 63 72 147 264 347 620 852 1199 B 3 mm 269 332 356 H 1 889 1184 1555 Weight (valve with body extension) PN 16 / 25 160 314 489 kg PN 40 187 350 526 AFPQ, AFPQ 4 Actuators Actuator type AFPQ / AFPQ 4 Ø A 257 mm H for xs = 0.1-0.7 / 0.15-1.5 520/540 Weight kg 34 240 Seal pot V1 70 Comb. piece KF2, KF3 SW19 G1/4 Compression fitting 10 Danfoss 2018.05 VD.CA.A6.02

VD.CA.A6.02 Danfoss 2018.05 11

12 Danfoss DHS-SRMT/SI 2018.05 VD.CA.A6.02