Rack Mount Series UL Listed CCTV Power Supplies Installation Guide Models Include: R615DC8UL R615DC8ULCB - 6-15VDC @ 4 amp. - 6-15VDC @ 4 amp. - Eight (8) Fuse Protected - Eight (8) PTC Protected R615DC416UL R615DC416ULCB - 6-15VDC @ 4 amp. - 6-15VDC @ 4 amp. - Sixteen (16) Fuse Protected - Sixteen (16) PTC Protected R615DC616UL R615DC616ULCB - 6-15VDC @ 6 amp. - 6-15VDC @ 6 amp. - Sixteen (16) Fuse Protected - Sixteen (16) PTC Protected Rev. 031804
Overview: These Altronix Rack Mount CCTV Power Supplies provide 6-15VDC distributed via eight (8) or sixteen (16) fuse or PTC protected outputs for powering CCTV Cameras, heaters and other video accessories. Altronix Model Number R615DCUL Rack Mount Configuration Reference Chart: Total Output Current (Power) Output Voltage R615DC8UL 4 amp 6-15VDC 8 x - x 3.5 amp.9 amp R615DC8ULCB 4 amp 6-15VDC 8 x x - 2.5 amp.9 amp R615DC416UL 4 amp 6-15VDC 16 x - x 3.5 amp.9 amp R615DC416ULCB 4 amp 6-15VDC 16 x x - 2.5 amp.9 amp R615DC616UL 6 amp 6-15VDC 16 - - x 3.5 amp 1.5 amp R615DC616ULCB 6 amp 6-15VDC 16 x x - 2.5 amp 1.5 amp UL Listed for Commercial CCTV Equipment (UL2044). CUL Listed - CSA Standard C22.2 No.1-98, Audio, Video and Similar Equipment. Eight (8) or sixteen (16) individual power LED indicators Power switch w/built-in circuit breaker. Filtered and electronically regulated outputs. Spare fuses included. Unit maintains camera synchronization. Short circuit and thermal overload protection. Number of Ouputs Class 2 Rated Power Limited Specifications: Caution: This installation should be made by qualified service personnel and should conform to all local codes and the National Electrical Code. Installation Instructions: 1. Unit is factory set at 12VDC. To adjust the output voltage remove the top cover to access trimpot on the power supply board (Fig. 1B, pg. 3). 2. Mount unit in desired rack location (Space unit at least 3 from any video monitors). 3. Set power switch on back of unit to the OFF position (Fig. 1E, pg. 3). 4. Plug power cord into grounded 115VAC 50/60 Hz receptacle (Fig. 1D, pg. 3). 5. Set power switch to the ON (RESET) position and measure output voltage before connecting devices (Fig. 1E, pg. 3). This helps avoid potential damage. CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output voltage. 6. Set power switch on back of unit to the OFF position (Fig. 1E, pg. 3). 7. Connect devices to removable terminal blocks marked [1P & 1N through 8P & 8N] or [1P & 1N through 16P & 16N], where applicable (Fig. 1C, pg. 3). When wiring is completed on terminal blocks they can be locked down by tightening screw flanges. All terminals with common suffix (P) 1P, 2P... are the same polarity (positive). All terminals with common suffix (N) 1N, 2N... are the same polarity (negative). 8. Upon completion of wiring, set power switch on back of unit to the ON (RESET) position (Fig. 1E, pg. 3). 9. Green power LEDs on faceplate will illuminate when DC output power is present. When an output is in a trouble condition (blown fuse or tripped PTC) the corresponding LED will not be illuminated (Fig. 1, pg. 3). a. Blown fuse (R615DC416UL, R615DC616UL & R615DC8UL) - Set power switch on back of unit to the - 2 - PTC Protected Fuse Protected Output Current (max per output) 115VAC 50/60Hz Input Current Removable terminal blocks w/locking screw flange. 2U rack mount chassis for use in standard EIA 19 rack. Removable faceplate and sliding rear section for easy access. Ease of installation saves time and eliminates costly labor. Rack Dimensions: 3.25 H x 19.125 W x 8.5 D
BROOKLYN, NY 11220 MADE IN USA OFF position (Fig. 1E, pg. 3). Remove front faceplate to access fuses. Replace with fuses rated @ 3.5A/250VA (Altronix model # Fuse1). b. Tripped PTC (R615DC416ULCB, R615DC616ULCB & R615DC8ULCB) - To reset PTC, set power switch on back of unit to the OFF position (Remove overloaded circuit condition prior to reset). After approximately 30 secs. set power switch to the ON (RESET) position (Fig. 1E, pg. 3). 10. Power switch with built-in circuit breaker: OFF position - Switch not Illuminated. not powered. ON (RESET) position - Switch illuminated. powered. Circuit breaker tripped - Switch not Illuminated. Power LEDs on faceplate are not illuminated. not powered. To reset circuit breaker set power switch to the ON (RESET) position (Fig. 1E, pg. 3). WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. For continued protection risk of fire, replace the fuses only with same type and rating (3.5 amp @ 250V). Fig. 1 Used on PTC Models Fig. 1A (Green Wire Earth GND) PTC1 + AC -- + DC -- ALTRONIX CORP. BKLYN, NY 11220 MADE IN U.S.A. Power Supply Board P N XFMR XFMR Trimpot ALTRONIX CORP. Trimpot Fig. 1B Removable Terminal Block Strain Relief Line Cord Power Switch Fig. 1C Fig. 1D Fig. 1E The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the products enclosure that may be of sufficient magnitude to constitute an electric shock. The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance. CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel. - 3 -
3.25 H x 19.125 W x 8.5 D Rack Mechanical Drawing and Dimensions: View from back 3.125" BACK Eight (8) terminal blocks for eight (8) output models. 17.625" 8.5" BOTTOM View from front FACEPLATE Eight (8) for eight (8) output models. 19.125".75" Altronix is not responsible for any typographical errors. Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIR615DCUL Series F16D MEMBER - 4 -
BarcodesInc 200 West Monroe Street Chicago, Illinois 60606 Phone: 1-800-351-9962 Fax: 1-312-212-1800 www.barcodesinc.com About BarcodesInc BRANDS Who We Are BarcodesInc is North America's leading provider of p We Owe Our Success To You Why Choose BarcodesInc? Dedicated Account Our Account Managers will not compromise when it comes to providing you top-notch service. Your Account Manager is the primary point of contact for your business and makes it a priority to get to know you, your company and all your needs. Highly-Trained Technical Support Our technical staff has the broadest knowledge and every significant certification in the industry. One of our friendly experts is always available to suggest products and solutions for any situation. Incredible Value Our purchasing power means big savings for you. Whatever your project, our team will work hard to deliver a solution that fits your budget. Largest Inventory in the Industry and Same-Day Shipping Whatever your barcoding, mobile computing, or printing needs, we will fill your order and ship it the same Premier Access to Top Manufacturers BarcodesInc maintains strong strategic partnerships with the leading manufacturers in barcoding, mobile computing, printing and RFID. Responsive Customer Service Every phone call and email is responded to promptly, completely and accurately by our customer service Easy Returns Damaged, defective or incorrectly ordered goods may be returned without hassle. AND MORE BarcodesInc 200 West Monroe Street, Chicago, IL 60606 T: 1-800-351-9962 F: 1-312-212-1800 www.barcodesinc.com